You are on page 1of 1

TO MDP

LP
GENERAL ELECTRICAL NOTES
COMPUTATION OF LOADS
1. ALL ELECTRICAL WORKS SHALL BE DONE IN ACCORDANCE
AMPERES ACB WITH THE RULES AND REGULATIONS WITH THE LATEST EDITION
CIRCUIT WIRE CONDUIT OF THE PHILIPPINE ELECTRICAL CODE, BUILDING CODE AND
NO. LOAD DESCRIPTION 2-14mm², THHN WIRE +
SIZE SIZE 1-14mm² GROUND WIRE EXISTING APPLICABLE ORDINANCES OF THE LOCAL
VOLTS VA AB CA BC ABC POLE RATING IN 35mmØ RSC
GOVERNMENT AND WITH THE REQUIREMENTS OF THE LOCAL
POWER COMPANY.
1 7 LIGHTING OUTLET 220 700 3.18 2 15 2.0 mm² THHN 20mm uPVC LP
2 5 LIGHTING OUTLET 220 500 2.27 2 15 2.0 mm² THHN 20mm uPVC 60 AMP 2. ALL WIRING SHALL BE INSTALLED IN STANDARD ELECTRICAL
uPVC CONDUIT, RUN EMBEDDED INSIDE THE HOLLOW BLOCKS
15 A 15 A
3 6 LIGHTING OUTLET 220 600 2.73 2 15 2.0 mm² THHN 20mm uPVC AND CONCRETE STRUCTURES, SLABS, COLUMNS, WALLS,
L.O. 1 2 L.O.
15A 15 A PARTITIONS, AND OR / RUN CONCEALED BETWEEN DOUBLE WALL
15 2.0 mm² THHN 20mm uPVC L.O. 3 4 L.O. WOODEN PARTITIONS AND INSIDE THE CEILING SPACES, WHERE
4 7 LIGHTING OUTLET 220 700 3.18 2
15 A 15 A THE USE OF CONCEALED OR EMBEDDED CONDUIT WIRING IS
2.0 mm² THHN 20mm uPVC L.O 5 6 L.O INPRACTICABLE METAL MOULDING WIRING MAYBE USED.
5 8 LIGHTING OUTLET 220 800 3.64 2 15 15 A 15 A
L.O 7 8 L.O
6 6 LIGHTING OUTLET 220 600 2.73 2 15 2.0 mm² THHN 20mm uPVC 15 A 15 A
3. UNLESS OTHERWISE INDICATED ON THE PLANS THE MINIMUM
L.O. 9 10 L.O. SIZE OF CONDUIT AND WIRE TO BE USED SHALL BE 20mm
30A 30 A
7 6 LIGHTING OUTLET 220 600 2.73 2 15 2.0 mm² THHN 20mm uPVC DIAMETER AND 2.0mm² TW RESPECTIVELY.
ACU 11 12 ACU
30 A 30 A
8 6LIGHTING OUTLET 220 600 2.73 2 15 2.0 mm² THHN 20mm uPVC ACU 13 14 ACU 4. WHEREVER REQUIRED AND NECESSARY PULL BOXES AND
30 A 30 A
JUNCTION BOXES OF PROPER SIZES SHALL BE INSTALLED AT A
9 8 LIGHTING OUTLET 220 800 3.64 2 15 2.0 mm² THHN 20mm uPVC ACU 15 16 C.O CONVENIENT AND INSCONSPICIOUS LOCATIONS ALTHOUGH
30 A 30 A
SPARE 17 18 SPARE SUCH BOXES ARE NOT SHOWN ON THE PLANS NOR MENTIONED
10 5 LIGHTING OUTLET 220 500 2.27 2 15 2.0 mm² THHN 20mm uPVC ON THE SPECIFICATIONS.

11 ACU 220 3000 13.64 2 30 3.5 mm² THHN 25mm uPVC 5. ALL ELECTRICAL WORKS SHALL BE DONE UNDER THE DIRECT
14 mm² GROUND WIRE
AND IMMEDIATE SUPERVISION OF A DULY LICENSED ELECTRICAL
12 ACU 220 3000 13.64 2 30 3.5 mm² THHN 25mm uPVC CONNECTED GROUND ROD ENGINEER OR MASTER ELECTRICIAN.

13 220 3000 13.64 2 30 3.5 mm² THHN 25mm uPVC RISER DIAGRAM
ACU

14 ACU 220 3000 13.64 2 30 3.5 mm² THHN 25mm uPVC

15 ACU 220 3000 13.64 2 30 3.5 mm² THHN 25mm uPVC

16 8 CONVENIENCE OUTLET 220 1600 7.27 2 30 3.5 mm² THHN 25mm uPVC

TOTAL 23 000 104.55

COMPUTATION:
IT = 23 000 = 104.55 AMP
220

USE: 60AT, 220V, 1ɸ, 60H2

USE: 2-14mm², THHN WIRE + 1-14mm²


GROUND WIRE IN 35mmØ RSC

PROPOSED:
AR. ARVIN KEITH NAÑO 2
AS SHOWN E
ARCHITECT UAP MULTI-PURPOSE HALL
2
THIS DRAWING AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF THE ARCHITECT. IT IS UNLAWFUL FOR
ANY PERSON TO COPY OR RECOPY WITHOUT SPECIFIC PERMISSION FROM THE OFFICE. (RA 9266)