You are on page 1of 16

bulk storage of

acetic acid
contents

1. INTRODUCTION 2

2. COMMERCIAL ASPECTS OF BULK STORAGE 2

3. TECHNICAL ASPECTS OF BULK STORAGE 3

4. LOCATION OF STORAGE TANKS 3

5. TANKER DISCHARGE 3

6. DESIGN AND CONSTRUCTION OF TANKS 4

7. LEVEL MEASUREMENT 4

8. PIPEWORK 5

9. VALVES 6

10. PUMPS 6

11. HEATING FACILITIES 6

12. PRE-COMMISSIONING 7

13. ACID DILUTION 7

14. LABELLING AND SAFETY PRECAUTIONS 8

15. PRODUCT TRAINING 8

16. OPERATING PROCEDURES 9

17. FURTHER TECHNICAL LITERATURE 9

Appendix 1 Key Safety and Environmental Data of Acetic Acid 10


Appendix 2 Typical Weights and Dimensions of Fully Laden Road Tankers 10
Appendix 3 Diagram of Typical Above Ground Storage Installation 11
Appendix 4 Diagram of Typical Above Ground Fixed Roof Storage Installation 12
Appendix 5 Diagram of Typical Under Ground Storage Installation 13
Appendix 6 Suitable Fittings for Tank Inlet Connections 14
Appendix 7 Suitable Materials for Seals, Gaskets and Hoses 14

1
bulk storage of acetic acid

1. INTRODUCTION of the bulk installation will depend upon its size and
the rate at which the acetic acid is used.
1.1 This technical booklet has been produced for
the guidance of customers who are interested in 2.2 Acetic acid is available in bulk from BP in four

installing bulk storage facilities for acetic acid. It grades as follows: Chemically Pure Acetic Acid,
describes in general terms the requirements for a 99.5% Technical, 80% Pure, and 80% Technical.
suitable installation. 2.3 When small quantities of aqueous acetic acid

1.2 Our experience has shown that the design and are required, it is usual to buy the appropriate dilute
construction of each bulk storage installation grade, which is more convenient for handling.
requires individual consideration, because of the However, where large quantities are used,
nature of the site, the users specific requirements consideration should be given to the purchase of full
and the impact on any existing facilities in the strength acid in bulk which can be diluted to the
vicinity. BP offers a Technical Advisory Service, free required strength following receipt. The initial capital
of charge, to customers who wish to make use of it. outlay is higher, because of the additional
We consider that our Technical Advisory Service is requirement to provide mixing equipment, but this is
most useful to a customer when discussions are offset by the saving resulting from the lower
held at the earliest possible stage and certainly purchase cost of the acid.
before the design of the unit has been finalised. Our 2.4 Bulk deliveries of BP’s acetic acid are normally
local Sales Representative will be pleased to make made by road tankers. Customers should carefully
the necessary arrangements. consider the optimum storage capacity for the
1.3 The storage and handling of corrosive and installation, bearing in mind delivery load sizes as
flammable liquids is subject to legislative controls in well as current and estimated future usage.
many countries. Customers are recommended to Adequate capacity should be provided to allow a
obtain and make themselves familiar with any delivery to be taken well before the previous supply
relevant regulations and keep abreast of new is exhausted and also to hold sufficient stock to return to contents
regulations, as and when these apply. Information meet contingencies.
contained in this booklet is not intended to replace
any legal requirements which may be applicable to 3. TECHNICAL ASPECTS OF BULK
the storage and handling of acetic acid in particular STORAGE
circumstances. It is recommended however, that the
3.1 Acetic acid is a corrosive and flammable and
guidance outlined in this technical booklet is
thus certain precautions are necessary if it is to be
followed, provided that it does not conflict with any
stored and handled safely. This can be achieved by
specific legal obligations.
ensuring that the storage and handling facilities are
1.4 A Material Safety Data Sheet has been issued correctly designed and constructed and that safe
describing the health, safety and environmental operating procedures are followed.
properties of acetic acid, identifying the potential
3.2 Information on the design, construction and
hazards and giving advice on handling precautions
location of storage installations for acetic acid
and emergency procedures. This must be consulted
contained in this booklet is applicable only if the
and fully understood before handling, storage or use.
temperature of the liquid remains below 30°C. At
Key safety and environmental data are listed in
higher temperatures, different materials of
Appendix 1.
construction may be required.

2. COMMERCIAL ASPECTS OF BULK 3.3 The following aspects need to be considered for
STORAGE the safe and efficient receipt and storage of acetic
acid:
2.1 Although acetic acid can be supplied in
packages, for example nominal 210 litre drums, it is • Location of storage tanks
often more convenient for the customer to receive • Tanker discharge
bulk supplies. Bulk storage is more compact than
storage in drums and therefore releases space and • Design and construction of tanks
handling equipment for other duties. Stock control is • Level measurement
also made easier and deliveries can be received less
frequently. There may be cost savings from reduced • Pipework

handling. The time taken to recover the capital cost • Valves

2
• Pumps small spillages and to minimise the surface area of
any spillage.
• Heating facilities
4.8 The floor of the bund should be sloped to
• Pre-commissioning
prevent minor spillages remaining below any tank.
• Acid dilution Provision should be made for the removal or
drainage of surface water from the area within the
• Labelling and safety precautions
bund. Surface water should preferably be pumped
• Product training out of bunds. If bund drains are used they should
be provided with valves outside the bund walls,
• Operating procedures
with procedures in force to ensure these valves
3.4 These aspects are considered in detail in the remain closed, and preferably locked, except when
following sections. drainings are being removed.

4. LOCATION OF STORAGE TANKS 5. TANKER DISCHARGE

4.1 The arrangement and any grouping of tanks 5.1 The provision of vehicle access needs to be
requires careful consideration. It is important to taken into account when selecting the site for the
consider access not only for normal operations but storage installation. The following aspects need to
also for emergency evacuation. be considered:
4.2 The design of the tank farm should take a) a clear, safe access for the vehicle with
account of the likely consequences of any sufficient room to manoeuvre to and from the
accidental spillage or fire. Products which react discharge point (this must allow the vehicle to
chemically with acetic acid should be kept in totally be driven forward from the unloading point in
segregated storage. an emergency rather than being reversed),
4.3 Storage at ground level and in the open air is b) the width, corners, type of surface and load-
preferable because in the unlikely event that a leak bearing capacities of the approach road,
occurs, it is more likely to be detected.
c) headroom under any overhead gantries, return to contents
Examination, modifications and repairs are also
easier and corrosion can be more readily identified d) any bridge or other restrictions.
and controlled. An exception to an outside
5.2 Typical weights of fully laden vehicles with
installation is where a small tank for glacial acetic
dimensions and turning circle are shown in
acid can be conveniently installed in a building
Appendix 2.
which is already heated thus removing the need for
heating and insulating the tank. 5.3 A trial run with an empty tanker may be
appropriate if the access is doubtful.
4.4 Storage tanks should not be located:
The unloading point should be located facing the
a) on the roof of a building,
tanker’s outlet connection to avoid the need to run
b) in an elevated position, flexible hoses under or to the rear of the tanker
when discharging. Ideally, only one short length of
c) on top of each other,
flexible hose should be used for the discharge
4.5 Storage tanks should be discharged by pump. operation.
Horizontal tanks should be positioned just high
5.4 Vehicles must not stand on a road or path used
enough above ground level to provide clearance for
by the public while being discharged and must be at
convenient operation and maintenance of valves.
least 6 metres from a right of way. It is preferable if
4.6 All tanks should be surrounded by a bund wall. the immediate area surrounding the discharge point
The required capacity of the bund may be subject to is closed to all except those directly concerned with
local regulations. It should be equivalent to at least the operation while tanker discharge is being carried
110% of the capacity of the largest tank within the out.
bund. The walls and floor of the bund should be
5.5 It is good practice to provide an earthing point
impervious to liquid and designed to withstand a full
near the discharge point for connection to the
hydrostatic head. Bund walls should not be higher
earthing point on the road tanker.
than 1.5 metres in order to ensure adequate natural
ventilation of the bunded areas, ready access for 5.6 The rate at which the discharge takes place is
fire fighting and a good means of escape. normally about 600 litres per minute whether by the
vehicle’s pump or compressor. This depends to
4.7 Intermediate lower bund walls are
recommended to divide tanks into groups to contain

3
some degree on the configuration of the pipework to 7. LEVEL MEASUREMENT
the storage tank. When the customer’s own pump is
to be used, a similar rate should be planned. 7.1 Every tank should be provided with a suitable
means of determining the volume of the contents. A
5.7 Road tankers are fully insulated to prevent acetic contents indicator is preferred to manual dipping.
acid freezing in cold weather.
The following types of contents indicator may be
5.8 During the road tanker discharge operation acid used:
vapour will normally be displaced from the storage
tank vent. If the presence of acid vapour in the a) Gauge glass
discharge area is unacceptable, the installation of a Gauge glasses of the reflex type may be used with
system to return the vapour to the road tanker can 80% acid.
be considered. Further details can be obtained from
BP’s Technical Advisory Service. They should be suitably protected on all sides
against shock damage and fitted with top and
bottom isolating cocks. They are not suitable for
6. DESIGN AND CONSTRUCTION OF
glacial acid because of the difficulty of preventing
TANKS
freezing in the gauge glass.
6.1 The storage tank must be of adequate strength b) Hydrostatic gauge
and capacity for the proposed duty.
Hydrostatic gauges provide a level measurement
The tank and its supports should be designed and system requiring no external power source or
constructed in accordance with an appropriate adjustment. They are simple but robust in
recognised standard of good engineering practice. construction and require little maintenance. All metal
The choice of construction material for storage tanks parts of these instruments should be fabricated in
depends upon the grade of acid, and also on cost. stainless steel of a suitable grade.

6.2 Tanks constructed from the following materials c) Pneumacator


are suitable for storing 80% acetic acid. This is a simple type of level indicator which is
a) Stainless steel grades 304, 316 and 321 relatively cheap but effective. Care should be taken
return to contents
that all parts of the system are compatible with
b) High density polyethylene (HDPE) acetic acid. All metal parts of these instruments
c) Polypropylene (PP) should be fabricated in stainless steel of a suitable
grade.
d) Glass reinforced plastic (GRP) with either a
HDPE or PP lining d) Ultrasonic and radar level indicators

e) Rubber lined carbon steel. For higher accuracy in level measurement, ultrasonic
and radar level indicators are available for use with
Increase in temperature can affect the mechanical
acetic acid. Care should be taken to ensure that they
properties of some plastics and care should be taken
are intrinsically safe to BASEEFA (British Approvals
to avoid overheating the tank contents.
Service for Electrical Equipment in Flammable
6.3 Stainless steel of ASTM 316 or 321 grade or Atmospheres) standard SFA 3012 for Zone ‘O’ with
equivalent is suitable for the storage of all grades of certified ‘Ex’ head units and probes, or to an
acetic acid. equivalent standard.

6.4 Aluminium of minimum 99.5% purity is suitable 7.2 Where manual dipping is necessary the
for the storage of glacial acetic acid, but any dilution following precautions should be applied:
of the acid should not be allowed as this will
a) the tank should be fitted with a dip tube
accelerate corrosion of the tank. The temperature
extending down close to the bottom of the tank,
control of the acid must be more precise when
with a wear pad welded to the tank bottom
aluminium is used rather than stainless steel, since
beneath the dip tube.
above 30°C the corrosion rate increases sharply, with
the formation of aluminium acetate. b) the top of the dip tube should have a vapour
tight cap which should always be in position
6.5 The materials of construction described above
except when gauging is actually taking place.
are only suitable for acetic acid as delivered. Where
any process material is recycled to the storage tank, c) dip roads should be substantially smaller in
trace quantities of impurities may cause or diameter than the dip tube to reduce any
accelerate corrosion. Corrosion tests should be inaccuracy in measurement. Wooden or
carried out using the recycle material. stainless steel dip rods can be used.

d) dipping should never take place through open


manholes.

4
7.3 It is recommended that each tank should be far removed as possible from the inlet line. To
fitted with a high level alarm, the measuring element prevent possible damage to the tank, the vent line
of which should be independent from level indicator. should not be smaller in diameter than either the
An alarm operated from a float switch is suitable for inlet or the discharge lines.
this purpose.
It is good practice to connect the vent line to a
scrubbing system. However, if no such system is
8. PIPEWORK available, it is recommended that the tank vent is
extended down into the tank bund to within 200mm
8.1 The general layout of pipelines directly
of the floor, to prevent injury to personnel from
connected to the tank is shown in Appendices 3, 4
windborne droplets of acetic acid at the end of the
and 5. These should normally be of the same
discharge. Free circulation of air around this vent is
material as the tank, except for plastic tanks, which
essential to disperse vapours, particularly while that
should have the inlet pipeline fabricated from a
tank is being filled. A vacuum break should be
suitable grade of stainless steel.
provided on this vent line. This may be in the form
8.2 The tanker hose connecting point (inlet of a tun dish, or be a small hole (6mm) drilled in the
connection) should be provided with a suitable fitting vent line above the level of the bund wall.
to connect to the delivery hose. Suitable fittings are
8.6 In order to reduce vapour emissions to the
described in Appendix 6. The inlet connection should
atmosphere it is possible that legislation will in
be positioned as near as possible to where the
future require that bulk deliveries of acetic acid are
vehicle will stand during discharge, and should be
made using a vapour return system or a tank with a
protected from accidental damage. The inlet
vent scrubber. A typical vapour return system is
connection should be located at a convenient height,
shown in outline in Appendices 3 and 4. Vapours
i.e., not more than 1 metre above ground level,
displaced from the storage tank during delivery
facing outwards, for hose coupling. The inlet line
would be transferred to the vapour space of the
should be fitted with an isolation valve as close as
delivering tanker.
possible to the inlet connection. When a number of
different products are stored, each inlet connection 8.7 Wherever possible, continuously welded
should be clearly marked with the name of the pipework should be used. However, where pipework
return to contents
product to which it relates. An inlet line of 80mm may have to be disconnected for maintenance or
nominal bore is a suitable size for transferring acetic inspection, flanged joints should be fitted. Flanges
acid from the road tanker to the tank. The line conforming to the American National Standards
should enter the top of the tank. The inlet should be Institute (ANSI) 150lb and PTFE envelope gaskets
sloped towards the tank as shown in Appendix 3. A are recommended. Other suitable gasket materials
drain cock should be fitted at the lowest point in the are shown in Appendix 7. Graphitised jointing paste
inlet line so that the line can be drained at the should not be used with stainless steel.
completion of tanker discharge. Space for a small
8.8 A vapour tight manhole should be provided on
receptacle (20 litres capacity) should be left under
all tanks to allow for internal inspection and cleaning.
this drain cock.
8.9 An earthing point should be fitted on tanks
8.3 A tank discharge line should be provided which
containing pure acetic acid, and this should be
should be a minimum of 50mm nominal bore. The
connected to a good earth. The resistance to earth
discharge line is usually taken through the bottom or
at any point of the installation should be less than 10
the side of the tank to an isolating valve.
ohms. This also applies to the tanker earthing point
This isolating valve should be located as close as which preferably should be connected to the same
possible to the tank. In all cases, discharge should earth, or if independent should have minimal
be by pump. The pump and controls should be sited resistance between this and the tank-pipework
outside the bund. system. It is good practice to fit an earthing point on
tanks containing 80% acetic acid.
8.4 If the tank discharge line is not located at the
lowest point of the tank, a facility should be provided 8.10 The pipework system should be designed such
for draining the tank. A 25mm nominal bore branch that liquid cannot be trapped between closed valves
fitted at the lowest point of the tank is suggested. without some form of pressure relieving device. This
The branch should be fitted with a suitable isolating applies especially to heated pipework (see section
valve and blanked off when not in use. 11).
8.5 A vent line needs to be provided, leading from 8.11 Joints in pipework should not be located over
the vapour space at the top of the tank, for the doorways, windows or close to possible sources of
dispersion of vapour. This vent line should be ignition.
connected to the highest point of the tank and be as
8.12Pipework should be routed to minimise the
possibility of accidental damage.

5
9. VALVES Temperature control

9.1 Stainless steel ball or gate valves with PTFE 11.3 If heating is provided, thermostatic temperature

seats are recommended for use with acetic acid and control is strongly recommended to ensure that the
are suitable for all applications. temperature of the acetic acid does not exceed
30°C. At higher temperatures the rate of corrosion
9.2 Plug or diaphragm valves can also be used with of stainless steel by acetic acid increases and
acetic acid. However, diaphragm valves should not flammable mixtures of air and acetic acid are
be used on the bottom outlets of tanks. possible. The fitting of low and high temperature
9.3 PVC or polypropylene ball valves can be used alarms is recommended.
for 80% acetic acid. 11.4 Thermostatic control also ensures economy in
the usage of the heating medium and minimises
10. PUMPS vent loses. The temperature sensing element for the
tank should be installed in a 40 mm nominal bore
10.1 Pumps should be located outside tank bunds,
pocket at the side of the tank and which extends
on an impervious base, in an open space, and not in
towards the bottom of the tank at a point remote
walled or confined spaces.
from the heating element. The thermometer pocket
10.2 Pumps for 99.5% acetic acid should be should be of stainless steel, filled with oil. If heating
fabricated from a suitable grade of stainless steel, is by hot water or steam and instrument air is
i.e. ASTM 316. Polypropylene may be used for 80% available, a simple pneumatic temperature indicating
acetic acid. controller will be adequate. If instrument air is not
available a direct-acting controller must be used, and
10.3 Self-priming centrifugal pumps should be used
a direct reading temperature indicator should be
wherever possible. Mechanical seals with PTFE
installed.
wedges (Crane Type 109 or equivalent) are
recommended for this duty but these seals must 11.5 With electric heating, a simple on/off
not be run dry. If packed glands are used, braided thermostatic control switch will be adequate.
PTFE should be used. If metering or other
Heating of the storage tank
reciprocating pumps are used, PTFE packing is
return to contents
preferred. Glandless centrifugal pumps with 11.6 For glacial grades, the storage installation
magnetic coupling may also be used. should be designed to maintain the tank contents at
a temperature of 25°C ± 5°C. If the tank is installed
10.4 Arrangements should be made to collect any
inside a building, provided the ambient temperature
leakage from glands. Connections at the pump
is not allowed to fall below 20°C, no additional
should be flanged to ANSI 150lb. Threaded joints
means of heating is required. Precautions will still
must not be used.
have to be taken to avoid freezing of the inlet and
10.5 When glacial acetic acid is being handled, it is vent pipes if these pass outside the building.
normal practice to drain a pump after use and to
11.7 If the tank is installed outside, an internal
close the isolating valves until it is required again.
stainless steel (ASTM 316L) heating coil is
10.6 If pumps can be remotely controlled, a stop recommended. This may be heated by either hot
button should be provided both at the pump, and at water or low pressure steam. Electric heating pads
the delivery point. can be used but these should be designed so that
overheating of the surface of the tank does not
10.7 Suitable materials for use as seals and hoses
occur.
are shown in Appendix 7.
11.8 In all cases where storage tanks are heated,

11. HEATING FACILITIES they must also be effectively insulated.

Heating of pipework
Introduction
11.9 The ratio of heating surface to liquid volume is
11.1 In most situations it is necessary to take
much higher in pipework than in the storage tank.
precautions, such as the provision of heating and/or
This means that acid in a pipe is much more
insulation, to prevent glacial grades of acetic acid
susceptible to overheating, if heat is applied, or to
from freezing in tanks and pipelines. These grades
freezing if the insulation is faulty. In view of this,
freeze at temperatures between 14°C and 16°C.
some system of thermostatically controlled heating
11.2 For 80% grades, the need for precautions to on the pipework is recommended. Care must be
be taken to prevent freezing of the acid will depend taken to avoid high surface temperatures, as these
upon the location of the tank and local ambient might cause an increased rate of corrosion and
temperature conditions. 80% grades of acetic acid
freeze at -7°C. Consequently, in many cases special
precautions are unnecessary.

6
consequent contamination of the acid. 12. PRE-COMMISSIONING
11.10 Pipelines may be heated electrically or by hot 12.1 When the bulk installation is completed it is
water. Electric heating tapes wrapped around the normal practice flush the whole system through
pipe or electric heating elements running along the with water to remove any debris. When this is done
underside of the pipe may be used. When hot water it is advisable to:
is available, a 15mm nominal bore mild steel trace
line can be run directly below the acid line. The a) fit fine wire mesh strainers at the inlets of
tracing is supported by the acid line but small pumps and meters to prevent them being
spacing pads prevent direct contact. Maintenance is damaged by solids,
simplified if the trace line is jointed adjacent to the b) use water with a low chloride content i.e. below
acid line joints. For pipelines in continuous service 30ppm, to avoid any possibility of chloride
automatic control must be used to avoid corrosion of the stainless steel.
overheating.
12.2 Where a stainless steel tank is to be used, and
For occasional duties, such as the inlet line, steam the iron content of the product is important, it is
heating may be used. The installation should be advisable to condition the tank before use, to
similar to hot water heating, with steam traps at all remove iron. BP will be pleased to advise on
low points. The line should be drained after use and suitable conditioning procedures.
the heating properly shut off. To ensure complete
drainage the slope of the line should be increased to
13. ACID DILUTION
1 in 50.
Introduction
It is most important that the vent line is fully trace
heated and insulated to avoid blockage by 13.1 Reference to price schedules will show
crystallised acetic acid vapour during cold weather. whether it is economic to buy glacial acid and dilute
it with water down to the required strength. There
Heating of pumps
are no major process difficulties and personnel soon
11.11 Steam/water-jacketed pumps can be obtained become accustomed to the method of dilution and
but are not usually necessary. It is normally sufficient its control.
return to contents
protection if the pump is sited inside a warm building
Water quality
or if the heating element or tracing line is continued
around the base of the pump. 13.2 All town water contain soluble salts, although
some waters are of a better, or softer, quality than
Heating of valves
others.
11.12 Steam/water-jacketed valves are expensive
13.3 The quality of the diluted acid depends upon
and not readily available. It is normally adequate to
the quality of the water used. For this reason, it is
continue the heating element or tracing line close to
recommended that for high grade 80% acetic acid
the valve body.
demineralised water or distillate is used as diluent.
Thermal insulation of tanks and lines Filtered steam condensate may be used only if it
11.13 Heated tanks, pumps and pipelines should be
has not been in contact with mild steel equipment.
insulated to prevent heat losses and reduce heating However, not all customers require such a high
costs. In addition, if the installation is sited outdoors, grade product. In such cases, ordinary towns water
the insulation must be weatherproofed. may be used as diluent. However, it should be noted
that contaminants, e.g. chloride, can cause
11.14 Preformed types of insulation are increased corrosion in subsequent processing.
recommended. Preformed slabs or mattresses may
be used with tanks, and preformed sections of Dilution equipment
adequate bore for the pipelines plus heating devices. 13.4 The dilution is normally carried out in the bulk
All flanges, valve bodies and pumps should be storage tank. The tank should be sized, therefore, to
insulated. contain the required delivery of acetic acid, plus the
11.15 For tanks and pipework in stainless steel,
dilution water, plus any residue of diluted acid which
chloride-free insulation must be used or corrosion had not been utilised. Acid and water are intimately
will result. mixed using either a top entry agitator or a jet mixer
nozzle and pump. Jet mixing is normally the more
convenient method. It is favoured by the basic
geometry of a storage tank and the cost can be less,
particularly as a pump is usually required for other
purposes.

7
13.5 Jet mixing is simply the circulation of acid from where W is the amount of water to be added in
the tank into a pump and back into the tank through litres and M is the amount of 99.5% acid in tonnes.
an inclined nozzle at the tank base. The jet of liquid
For different strengths the following equation may
from the nozzle produces the stirring action in the
be used:
tank.
W = M x (X - 80) x 125.24
13.6 The nozzle design is critical, depending on the
10
geometry of the tank and the pump rating. Our
Technical Advisory Service engineers will, on where X is the initial concentration of acetic acid,
request, advise on a jet mixing system for the mass per cent, W is the amount of water to be
proposed duty. added in litres and M is the amount of acid in
tonnes. Thus, for X = 99% m/m
The nozzle should not be used until there is about
1.5 metres of liquid above it. Mixing time is so short W = 1 x (99 - 80) x 125.24 litres per tonne
that this is not at all a serious disadvantage. The 10
tank should not be filled through the nozzle. = 19 x 125.24
10
The inlet delivery line should be heat traced and
= 238.0 litres per tonne
insulated.

Demineralised water 14. LABELLING AND SAFETY


13.7 Where demineralised water is used for the PRECAUTIONS
dilution of acid, a tank should be installed for the
14.1 The words:
storage of the treated water. The economics of
water treatment are such that it is cheaper to install ACETIC ACID – CORROSIVE TO SKIN
a small capacity demineralising unit feeding over a
should be painted on all acetic acid bulk tanks.
prolonged period of time into a water storage tank
Emergency instructions, in case of splashing, should
rather than a large capacity unit feeding into the acid
be shown at the main places of work. An adequate
tank over a short period. Alternatively, the acid tank
number of eye baths or wash bottles containing
can be filled slowly with water if not required
water (for use until a source of running water can be return to contents
continuously.
used) should be kept in the working area. Buckets of
13.8 Demineralising equipment is supplied by sodium bicarbonate may also be kept in the working
manufacturers specialising in this field and their area for skin use only.
advice should be sought regarding the most suitable
14.2 In addition, safety showers with a quick acting
unit for a specific application.
valve, adequately protected against frost, or a water
13.9 Demineralised water is corrosive to some bath should be installed on site. There should be an
materials. Equipment such as the treated water adequate supply of water for hosing down the area
storage tank should be of corrosion resistant in the event of an acid spillage.
material. Stainless steel, ebonite-lined carbon steel,
14.3 Buildings in which acetic acid is stored or
polyethylene or polypropylene may be used.
handled should be well ventilated.
Method of dilution
15. PRODUCT TRAINING
13.10 It is recommended that initially up to 80% of
the water required for dilution is added before the All personnel associated with the handling of acetic
acid delivery. After the delivery, the tank can be jet acid should be fully trained to enable them to
mixed and the contents sampled. Measurement of understand:
the relative density of the liquid and its assay will
give the quantity of acid in the tank. a) the nature of the potential hazards associated
with the handling of acetic acid,
It is a simple matter to calculate the additional water
and to add the quantity required accurately. The tank b) the appropriate storage and handling
is again jet mixed and the assay checked. As the precautions including personal protection
operator becomes more skilful in the technique of measures,
dilution, the initial charge of water may be increased c) the appropriate action to be taken in the event
to say 90%. of an emergency.
Calculation of dilution

13.11 For the dilution of 99.5% by mass acetic acid


to 80% by mass:

W = 244.1 M

8
16. OPERATING PROCEDURES closed. The drain cock adjacent to the inlet
valve should then be opened carefully, to allow
Written operating instructions should be available for any product remaining in the inlet pipe to drain
the receipt of acetic acid, and operating personnel into a receptacle. Next, the hose should be
should be fully trained in their implementation. The drained through the inlet valve and drain cock
instructions should take account of the specific into a receptacle (5 to 10 litres of drainings may
hazards, and ensure the correct operation of be expected). It is the customer’s responsibility
equipment in both normal and emergency situations. to provide adequate facilities for disposal of
Key points of a typical discharge operation for bulk these hose drainings.
road tankers are:
h) the delivery hose should be thoroughly washed
a) the customer's representative must ensure that through with water.
there is sufficient ullage available in the
receiving tank to accept the nominated delivery. i) all equipment must be properly stowed before
the road tanker is given authorisation to depart
b) prior to discharge, all appropriate safety from the discharge point.
equipment must be checked and suitably
positioned. j) finally, the quantity in the tank should be
checked against the amount expected. Dipping
c) only those personnel directly concerned with the tank or removal of a sample for testing
the discharge operation should be in the area, should not take place until at least 30 seconds
with appropriate protective clothing being worn. after completion of discharge. This is to allow
d) a customer’s representative must identify the for the relaxation of any electro-static charge
discharging point to be used, and the earthing which may have been generated in the transfer.
point, and must supervise all connections to the
vehicle. 17. FURTHER TECHNICAL LITERATURE

e) the road tanker should be connected to the 17.1 Further technical literature on acetic acid is
earthing point before the delivery hose is available from BP as follows:
connected. This earth must be maintained
throughout the operation and not be broken a) BP Acetic Acid Product Specification and return to contents
until after the hose is disconnected, on Physical Properties.
completion of product transfer. b) Material Safety Data Sheet, giving health, safety
f) during discharge, regular checks should be and environmental data.
carried out to ensure that the load is being Copies of Material Safety Data Sheets are normally
received into the appropriate storage tank. The supplied automatically by our Sales Offices. Further
customer's representative must remain in copies are available either by direct request to the
attendance throughout the discharge operation. Sales Office or by asking our local sales
g) on completion of discharge, the pump (if used) representative to arrange for copies from the Sales
should be stopped and the valves in the pipeline Office.

9
APPENDIX 1 KEY SAFETY AND ENVIRONMENTAL DATA OF ACETIC ACID

Flash point (closed cup) Acetic acid chemically pure 39°C

Acetic acid 80% pure 65°C

Autoignition temperature 463°C

Freezing points Acetic acid chemically pure 16.6°C

Acetic acid 80% pure -7.0°C

Flammable limits in air lower 4.0% volume

upper 19.9% volume

Acetic acid is readily biodegradable in both fresh and salt water. It is slightly toxic to aquatic species,
i.e. TLm96 10-100 ppm, but is unlikely to bio-accumulate.

APPENDIX 2 TYPICAL WEIGHTS AND DIMENSIONS OF FULLY LADEN ROAD TANKERS

Nett weight 22 – 25 tonnes


return to contents
Gross weight 38 – 44 tonnes

Overall length 13.5 – 15.5 metres

Overall height 4 metres

Overall width 2.5 metres

Turning circle 14 – 17 metres

Actual values will depend upon the vehicle design and construction regulations currently in force in the country
concerned.

10
Shower located adjacent
1 Max bund height 1.5m to storage installation
2 Tank heating will be required for glacial grades of acetic acid incorporating quick acting Water hose for
valve and eye-bath washing down

Intake point for 65mm


APPENDIX 3

road tanker delivery intake Town's water supply


valve 38mm vapour return
2½" BSP male
inlet connection (where fitted)

Pressure/vacuum
valve Vent
Slope to scrubber
protective 80mm inlet line tank (alternate
750 mm cap and design)
approx. chain 25mm
drain
valve
600mm manhole 80mm minimum
with bolted cover vent pipe

Water
Tank contents to LI LAH
be clearly
marked on tank

11
Products to be Fixed access
clearly marked ladder
at delivery point
Pipes to be
Single short length 1 m min 1m sealed in
of flexible hose min bund wall
TI

Slope

Tank 50mm ball


earthing valve To pump

50mm Tank insulation


drain (glacial grades)
branch 50 mm
Slope delivery line
DIAGRAM OF TYPICAL ABOVE GROUND STORAGE INSTALLATION

Tanker earthing with 2m long common Tank supports


Bund wall Sump steel or concrete Impervious base Bund wall
bulldog clip copper earthing rod
return to contents
1 Max bund height 1.5m
2 Min bund wall to tank 1m
3 Tank heating will be required for glacial grades of acetic acid

pressure/
APPENDIX 4

Intake point for


road tanker delivery vacuum
valve
65mm 600mm manhole fitted with
2½ inch BSP intake hinged emergency relief
hatch 50mm dip pipe
male valve with screwed cap
Handrails local to stairs
Fixed access
LI stairs

750mm protective 25mm


INSTALLATION

approx. cap and drain


chain valve
150mm min Vent
38mm vapour
return (where scrubber
fitted) LAH
Tank contents to Water
be clearly marked
on tank

12
Product to be
clearly marked at TI
Single short lengths delivery point
Tank insulation Pipes to be
of flexible hose
(glacial grades) sealed in
Mixing nozzle bund wall

Non-return Manhole
Tank
valve Pump recycle
earthing Wear
\` plate

Slope
To pump
80mm inlet line
Slope
DIAGRAM OF TYPICAL ABOVE GROUND FIXED ROOF STORAGE

Tanker earthing with


Bund wall Sump 50mm Common earth system Impervious base Bund wall Sample point
bulldog clip
drain
return to contents
Note: Tank recirculation system not shown Flame arrestor
80mm fill and dip pipe
APPENDIX 5

fitted with lockable cap


38mm vapour 80mm minimum vent pipe to safe
Single short lengths location (to be fitted with a
return (where
of flexible hose pressure relief system if a vapour
fitted)
return system is used)

Inlet connection for


LI
Product and vapour
road tanker delivery return, where fitted, to be
clearly marked at delivery
To pump
point

50mm suction line

Tanker earthing

13
lead with bulldog
clip

Tank and pipes below ground to be


2m long common protected against external corrosion
copper earthing rod

Sealed to keep out


water
Pit back filled with dry
Tank earthing
sand

Tank supports
Wear plate
steel or concrete

Reinforced
DIAGRAM OF TYPICAL UNDER GROUND STORAGE INSTALLATION

concrete
return to contents
APPENDIX 6 SUITABLE FITTINGS FOR TANK INLET CONNECTIONS

UK: 2.5 inch BSP parallel threaded male connection

France: symmetric coupling NF-E 29.572, 80 mm nominal


diameter (type ‘Guillemin’ or equivalent)

Germany: quick coupling DIN 28450, 3 inch male connection

APPENDIX 7 SUITABLE MATERIALS FOR SEALS, GASKETS AND HOSES

Seals Ethylene propylene rubber (EPDM)

‘Kalrez’

Butyl rubber

PTFE encapsulated

Gaskets PTFE envelope

EPDM
return to contents
Butyl rubber

Hoses Polyethylene

Polypropylene

Stainless steel (316)

EPDM

Butyl rubber

PTFE

14
For further information

BP
Logistics Technical & Safety Unit
Building A
Chertsey Road
Sunbury-on-Thames
Middlesex
TW16 7LL
UK

www.bpchemicals.com

EXCLUSION OF LIABILITY BP accepts no liability whatsoever (except as otherwise expressly


Information contained in this publication is accurate to the best of the provided by law) arising out of the use of information supplied, the
knowledge of BP p.l.c. application or processing of the products described herein, the use of
other materials in lieu of BP materials in conjunction with such other
Any information or advice obtained from BP otherwise than by means of
materials.
this publication and whether relating to BP materials or other materials, is
also given in good faith. However, it remains at all times, the responsibility Published by BP p.l.c.
of the customer to ensure that BP materials are suitable for the particular © BP p.l.c.
purpose intended. February 2002

Insofar as materials not manufactured or supplied by BP are used in bp, and the Helios mark are trade marks of BP p.l.c.
conjunction with or instead of BP materials, the customer should ensure Designed by LTD Design Consultants
that he has received from the manufacturer or supplier all the technical Printed by Clement & Foster
data and other information relating to such materials.
20–8b/2001/1000GB

You might also like