Single DTMlibrary V2.44.00

Document V1.00.00

DTM Release Notes


Single DTMlibrary V2.44.00
HART, PROFIBUS, FOUNDATION fieldbus, Modbus,
EtherNet/IP, PROFINET, IPC, PCP, CDI

Endress+Hauser Process Solutions AG


Christoph Merian-Ring 12
CH-4153 Reinach/BL
Switzerland

Date 2016-07-04 Page 1 of 21


Release Notes
Single DTMlibrary V2.44.00

Document V1.00.00

Contents

1. General ................................................................................................................. 3
2. Revision History ................................................................................................... 3
3. Installation ........................................................................................................... 4
4. FDT Version .......................................................................................................... 5
5. Frame Applications............................................................................................... 5
6. Operation Advice .................................................................................................. 5
6.1. The connected device does not match to the associated DTM ..................................................... 5
6.2. Bus scan (FieldCare) ...................................................................................................................... 5
6.3. Bus settings for PROFIBUS P+F SK1 .............................................................................................. 6
7. Troubleshooting ................................................................................................... 7
7.1. Gathering necessary information .................................................................................................. 7
7.1.1. General ................................................................................................................................. 7
7.1.2. HART .................................................................................................................................... 7
7.1.3. PROFIBUS ............................................................................................................................. 7
7.1.4. Service Flow (ISS) ................................................................................................................. 7
7.1.5. Service “Phanten” (PCP) ....................................................................................................... 7
7.1.6. Service CDI ............................................................................................................................ 7
7.2. Known issues and limitations ........................................................................................................ 7
7.2.1. Installation – issue with Chinese operating systems............................................................ 7
7.2.2. Installation – issue with third party frames ......................................................................... 8
7.2.3. Installation – problems with the DTM library with Windows XP ......................................... 8
7.2.4. Installation – problems after uninstallation ........................................................................ 8
7.2.5. Uninstallation – best practice............................................................................................... 8
7.2.6. Computer lock and screen saver ........................................................................................... 8
7.2.7. Communication errors during download to device .............................................................. 8
7.2.8. Resetting a device ................................................................................................................ 8
7.2.9. Usage of the help functionality ............................................................................................ 8
7.2.10. Offline Parameterization ...................................................................................................... 8
7.2.11. Additional Functions -> Linearization.................................................................................. 9
7.2.12. Additional Functions -> HistoROM ...................................................................................... 9
7.2.13. Additional Functions -> Envelope Curve .............................................................................. 9
7.2.14. Additional Functions -> Create Documentation ................................................................... 9
7.2.15. Additional Functions -> Concentration ................................................................................ 9
7.2.16. FDT-Print & FDT-Up/Download ........................................................................................... 9
7.2.17. Upload functionality for FOUNDATION fieldbus ................................................................ 10
8. Device Configuration .......................................................................................... 10
8.1. HART ........................................................................................................................................... 10
8.2. PROFIBUS .................................................................................................................................... 12
8.3. FOUNDATION fieldbus ................................................................................................................ 13
8.4. Service CDI ................................................................................................................................... 13
8.5. DeviceCare ................................................................................................................................... 14
8.6. Diagnostic Module ...................................................................................................................... 14
9. Supported Devices .............................................................................................. 20
9.1. HART, PROFIBUS, FOUNDATION fieldbus, Modbus.................................................................... 20
9.2. Basic DTM FOUNDATION fieldbus .............................................................................................. 20
9.3. Service Flow (ISS DTM Library) ................................................................................................... 21
9.4. Service „Phanten“ (PCP DTM Library) ......................................................................................... 21
9.5. Service (CDI DTM Library) ........................................................................................................... 21

Date 2016-07-04 Page 2 of 21


Release Notes
Single DTMlibrary V2.44.00

Document V1.00.00

1. General
These release notes describe general information concerning the installation of DTMs, their
compatibility with FDT Frame applications, and known issues and workarounds.
Details on platform compatibility can be found in the folder "Technical Information" on the
FieldCare DVD.
Information to identify DTMs can be found within this document, as well as device
configuration and device specific specialties.

2. Revision History

Product- Improvements /Changes


Version
V2.44.00  New HART, PROFIBUS, EtherNet/IP, CDI Geräte and bugfixing
V2.43.00  New HART, PROFIBUS, CDI devices and bugfixing
V2.42.00  New HART, PROFIBUS, FOUNDATION fieldbus, CDI devices and
bugfixing
V2.41.00  New HART, PROFIBUS, FOUNDATION fieldbus, EtherNet/IP, CDI,
IPC, ISS devices and bugfixing
V2.40.00  New HART, PROFIBUS, FOUNDATION fieldbus, Modbus, CDI, ISS
devices and bugfixing
V2.39.00  New HART, PROFIBUS, FOUNDATION fieldbus, CDI, IPC, ISS, PCP
devices and bugfixing
V2.38.00  New HART, PROFIBUS, FOUNDATION fieldbus, CDI, IPC, ISS devices
and bugfixing
V2.37.00  New HART, PROFIBUS, FOUNDATION fieldbus, CDI, IPC, ISS devices
and bugfixing

Date 2016-07-04 Page 3 of 21


Release Notes
Single DTMlibrary V2.44.00

Document V1.00.00

3. Installation
This installation contains the following DTM setup(s):
 DTM library 2.44.00
- HART DTM library
- FOUNDATION DTM library
- PROFIBUS DTM library
- Modbus DTM library
- EtherNet/IP DTM library
- CDI DTM library
- PCP DTM library
- IPC DTM library
 BasicDTM FOUNDATION fieldbus 2.43.00
 Flow (ISS) DTM library 3.27.00

The Setup of the Single DTM library contains above listed DTM libraries. During
installation this new setup enables the ability to select measuring methods,
protocols and single/multiple device DTMs. The following screenshot shows as an
example this selection of the setup:

Date 2016-07-04 Page 4 of 21


Release Notes
Single DTMlibrary V2.44.00

Document V1.00.00

4. FDT Version
The DTMs are compatible to interface specification FDT 1.2 including addendum.

5. Frame Applications
The DTMs are released for:
 FieldCare V2.11.zz
 DeviceCare V1.02.zz
 PACTware V5.0 (1)
 Yokogawa PRM R3.30 (1)
 Honeywell FDM R450 (1)

(1) does not apply for Service libraries

If these DTMs are used in combination with a different (not listed) frame application,
then Endress+Hauser cannot guarantee for their correct function.
If the DTMs need to be integrated in third party frame applications, please contact
Endress+Hauser.

6. Operation Advice

6.1. The connected device does not match to the associated DTM
When connecting online to the device the following message occurs:

Please cross check the supported software version in the DTM catalog with the version of
the device. Without the matching DTM it is not possible to connect to the device.

6.2. Bus scan (FieldCare)


A bus scan achieves level 1 in most circumstances, which means that the device can be
exactly matched to a DTM.
Devices that run in profile mode currently only achieve a scanning level of 3.
Currently the devices are identified by the PROFIBUS IDENT number (GSD e.g. 0x15xx
hex). Verify the device’s software revision in the DTM catalog before accepting the
assignment. If the device is not identified a placeholder DTM will be assigned.
Profile 3 devices are supporting a minimum of two operating modes (e.g. Cerabar S):
0x1501hex (manufacturer specific mode) (Level 2) recognized
0x9700hex (profile mode with one AI) (Level 3) not recognized

Date 2016-07-04 Page 5 of 21


Release Notes
Single DTMlibrary V2.44.00

Document V1.00.00

Please check in the following dialog which device from which manufacturer could not be
identified (refer to the column Device type):

In the above shown dialogue you can manually assign a device by means of right clicking
and selecting it from the context menu.

6.3. Bus settings for PROFIBUS P+F SK1


We recommend setting the following parameters for the SK1 in the ComDTM:

Date 2016-07-04 Page 6 of 21


Release Notes
Single DTMlibrary V2.44.00

Document V1.00.00

7. Troubleshooting
If any problems with Endress+Hauser DTMs are encountered, please gather the
following information before contacting your local Endress+Hauser representative or
service.

7.1. Gathering necessary information

7.1.1. General
Please gather the following:
 Name of the frame application and it’s version; for this refer to the about box
 WINDOWS version and its service pack.
In addition, please select the about box for the device from the context menu (by right
clicking on the device in the network view <Additional functions><About …>) and then
proceed with the next chapter according to the communication protocol.

7.1.2. HART
Determine the identification code in the field “Version:” of the Aboutbox, e.g.
“H/000017/0007/07020S/01045500-01040055-01040055”.

7.1.3. PROFIBUS
Determine the identification code in the field “Version:” of the Aboutbox, e.g.
“P/000017/5421/0101S/1.5.37/1.5.37006”.

7.1.4. Service Flow (ISS)


Determine the identification code in the field “Version:” of the Aboutbox.

7.1.5. Service “Phanten” (PCP)


Determine the identification code in the field “Version:” of the Aboutbox.

7.1.6. Service CDI


Determine the identification code in the field “Version:” of the Aboutbox.

7.2. Known issues and limitations

7.2.1. Installation – issue with Chinese operating systems


Even after a successful installation of the Profibus DTM Library, there are no DTM’s
available. At the moment there is no workaround. Please contact your local
Endress+Hauser helpdesk.

Date 2016-07-04 Page 7 of 21


Release Notes
Single DTMlibrary V2.44.00

Document V1.00.00

7.2.2. Installation – issue with third party frames


Using third party Frames, it may be the case that a .net Framework Version 3.5 is not
installed. However, for the use of some DTM’s it is necessary to have the above
mentioned .net framework installed. While executing the DTM’s Modules, problems may
occur due to the missing .net Framework Version 3.5.

7.2.3. Installation – problems with the DTM library with Windows XP


By installing the DTM library setup under Windows XP an error occurs if there is not a
FOUNDATION fieldbus Communications DTM installed. In this case, the FOUNDATION
fieldbus Communications DTM has to be installed first and the DTM library Setup should
be executed again.

7.2.4. Installation – problems after uninstallation


In the case of a reinstallation after performed uninstallation ends in error, the Computer
has to be restarted before executing reinstallation.

7.2.5. Uninstallation – best practice


To uninstall the DTM library use control panel “Programs and Features”.

7.2.6. Computer lock and screen saver


To prevent FieldCare from freezing after using Computer lock or Screen Saver, switch off
the automatic activation through Windows Display Properties.

7.2.7. Communication errors during download to device


Currently it cannot be automatically checked if the device is locked or not. Check the
“Lock/Unlock” menu before downloading or accessing the device.
The locking/security code is device specific. Therefore refer to the Operating Manual of
the corresponding device.

7.2.8. Resetting a device


After reset some devices need a few seconds to re-establish communication. In this case,
the DTM window will open again automatically. If the reconnection is not established,
disconnect (menu <Device Operation><Go offline>) and re-connect (menu <Device
Operation><Go online>) the device again.

7.2.9. Usage of the help functionality


For Windows 7 it is possible that the Help Link will not show the correct target of the
Web Page (the device-viewer). The following URL should be used in these cases:
http://www.products.endress.com/eh/home.nsf/systemcontentview/index.html#products/device-viewer

7.2.10. Offline Parameterization


On changing a unit parameter it may occur that parameters (values) which do not
depend on this specific unit parameter will be recalculated.

Date 2016-07-04 Page 8 of 21


Release Notes
Single DTMlibrary V2.44.00

Document V1.00.00

After changing a unit parameter you should validate all editable parameters depending
on any unit parameter.

7.2.11. Additional Functions -> Linearization


The “distance unit” may be invalid if the Linearization is opened before switching the
DTM Online. To solve this problem, switch the DTM Online and open the Linearization.

7.2.12. Additional Functions -> HistoROM


If there are neither diagram values nor time stamp values shown on the x-axis, you can
reset the zoom range via the context menu of the diagram to enable these values again.

7.2.13. Additional Functions -> Envelope Curve


1. If the distance unit has been changed and is not set to meters, the curves are
sometimes not displayed correctly. If it happens it will be quite evident (e.g.
measured range is 7 mm). In this case, close all open modules, go offline, reopen
the envelope curve module and go online again. This procedure forces a refresh of
all parameters and the curve will be displayed correctly.
2. In context with switch Online/Offline it is possible that the “Read” button
becomes deactivated. Reopen the window Envelope Curve to reactive it.
3. When using special signs in the Device DTM tag (e.g. “-,+“), it may appear that
the tag is not shown correctly in module envelope curve.
4. If 'Hardware Lock' is active on the device (dip switch) it is still possible to read
envelope curves but there is no way to zoom or to save this curve because almost
every user control is locked. Deactivate the 'Hardware Lock' on the device to be
able to use the envelope curve editor in a suitable way.

7.2.14. Additional Functions -> Create Documentation


In case that there are several opened Envelope Curves, the current curve will be printed
out.
The tank geometry of the linearization is not part of the printout.
The device state could be wrong in the diagnosis overview page. The state shown in the
corresponding device menus is always correct.

7.2.15. Additional Functions -> Concentration


The temperature must be in column 1 for calculations based on fluid properties with
negative temperatures and the input format set to matrix.

7.2.16. FDT-Print & FDT-Up/Download


Opening another window (function e.g Extended HistoROM) while a FDT-Print or a FDT-
Up/Download is running might freeze the frame application.
This UseCase is not possible in FieldCare (by design).

Date 2016-07-04 Page 9 of 21


Release Notes
Single DTMlibrary V2.44.00

Document V1.00.00

7.2.17. Upload functionality for FOUNDATION fieldbus


The “Upload” function may take up to 20 minutes depending on the complexity of the
device. To reduce the upload time it is necessary to close the view of the online
parameterization.

8. Device Configuration
For the following devices there are special remarks for their configuration.

8.1. HART
Cerabar/Deltabar For the Devices version 7.x the device version is to be set Offline
with the parameter “INSTR.&SOFTW.NO” (menu “Service”).
The following hints apply for the DTMs version V01.00 and
V02.00:
By switching the Operating Mode or the Unit, the operator has to
ensure that the dataset is still consistent. Advice: by changing
these parameters exclusively Online and performing an Upload to
DTM, the parameter set is automatically adjusted by the device
according to the specific sensor type.
Version 2.00.xx/2.10.xx: you can switch between complete and
reduced parameter set using the menu “Mode Selection”.
Following hint applies to the Deltabar M PMD55: After a reset
please use the refresh button to get all the default values.
Liquisys / Smartec If a device of either of these families hasn’t been operated for 15
minutes or a reset has been performed, the device is automatically
locked. To be able to operate these devices, first enter the unlock
code within the start page. Locked parameters are marked with a
red symbol when an edit is attempted.
The Chemoclean functionality is only operable by the local display.
Liquisys M PH If the operating mode is changed to offline and the offline view is
locked, the new operating mode is transmitted still to the device.
Liquiline M CM42 When using the simulation in the DTM, the device correctly
recognizes this and indicates “SIMU” in the display. The status
signal in the DTM header indicates “OK”, this is wrong. It should
state “Function Check”. This scenario only occurs in the Honeywell
Experion frame using devices with the firmware V20.05.00,
V10.07.00 and below. Actual firmware versions work as intended.
Promag / Promass Writing of lower case letters or special characters for the variable
„TAG“is allowed in principle while operating the device locally.
However, this is not a recommended practice.

Date 2016-07-04 Page 10 of 21


Release Notes
Single DTMlibrary V2.44.00

Document V1.00.00

Lower case letters and special characters are not supported by


remote operation via Frame application.
If a “timeout” occurs during Up/Download, repeat the procedure.
Promag 23 The private Code is editable when the device is locked.
Levelflex M Int FMP4x
If FieldCare Language is not German or English the unit US/Gal
might not work properly.
With Asian languages, missing translations are displayed as “???”
in Module Envelope Curve. In this case, switch FieldCare language
to English.
Levelflex FMP5x Red exclamation marks can occur while configuring the offline
parameterization after adding the DTM to the project tree. To
prevent this perform an initial upload. After that, the problem will
not occur anymore even after reopening the frame application
(e.g. FieldCare).
Under rare circumstances it is possible that a OneClickPrint job
never ends on its own. In this case press the Cancel button and
restart the print job.
In 'Save/Restore' Module, An upload must be performed before
completely writing back with an upload file (*.deh) in. This is due
to the fact that in the initial state of the DTM - after scanning or
manually added - only a certain part will be written to the device.
Levelflex FMP5x Dev.Rev.3
It is not possible to activate SIL-locking via the DTM as the SIL-
sequence of the DTM does not work properly.
Activate the SIL-locking through the device display.

Micropilot M FMR2xx
Above Firmware version 5.00 both devices FMR2xx and FMR25x
are operable through following device type: “Micropilot M /
FMR25x / V5.xx”.
Tank Gauging Radar NMR8x Dev.Rev.2
After reading the histoROM data, the values will not be shown
correctly if the PC clock is not synchronous with the Device clock.

Date 2016-07-04 Page 11 of 21


Release Notes
Single DTMlibrary V2.44.00

Document V1.00.00

TMT 82 The device type “iTEMP / TMT82 / HART / V1.01.xx / Dev.Rev.


02” is not part of the DTM library, please download the Single
DTM from www.endress.com
TMT 162 Resetting the “Configuration Changed Flag” does not work via the
button in the “Diagnosis” window.
This can be reset in menu Diagnosis during online configuration.
TMT 182/ TMT 122 The simultaneous visualisation of the windows “Observe”, “Trend”
and “Diagnosis” may cause communication errors due to
insufficient resources within the device.
General While configuring a device via the PC software because of data
consistency reasons you must not concurrently configure it from
the device's operating panel.

8.2. PROFIBUS
Cerabar/Deltabar The following hints apply for the DTM version V03.00.10:
Both serial number and order code are written to the device during
a “Save/Restore” action.
Levelflex FMP5x To prevent freezing on closing DTM function like Envelope Curve,
please wait until opening/instantiating has finished completely.
Red exclamation marks can occur while configuring the offline
parameterization after adding the DTM to the project tree. To
prevent this perform an initial upload. After that, the problem will
not occur anymore even after reopening the frame application
(e.g. FieldCare).
Under rare circumstances it is possible that a OneClickPrint job
never ends on its own. In this case press the Cancel button and
restart the print job.
Liquiline M pH The following features from the device V10.03.00 are not
operable with the DTM: PCP Process Check System, SCC Sensor
Check System, Pfaudler Electrode (analog) / measuring probe.
Prowirl 77 There is a problem using the coupler Pepperl+Fuchs SK1 (release
1998 1PA.2).
Solution:
- change the coupler to SK1 1PA.93 (release 1999 or newer), SK2
or SIEMENS DP/PA Coupler
- or turn off and turn on the device
- and configure in dialog Offline Parameterization Static update to
1 (off)

Date 2016-07-04 Page 12 of 21


Release Notes
Single DTMlibrary V2.44.00

Document V1.00.00

- and use the recommended settings from P+F.


After having reset the device, the DTM cannot access the
parameters of the device correctly. Communication errors are
produced and can be avoided by turning the device off and on.
Promag 3x Refer Prowirl 77.
Promass 6x Refer Prowirl 77. Offline configuration and Upload/Download are
not available. The error message using the Upload/Download
Buttons is noncritical.
V3.00.xx: The 3 last AI Blocks have been disabled and are not
shown.
Prosonic Flow 9x After having switched the Ident Number selector offline, the
function "download to device" will be interrupted as the device
performs a reset. Please Go Offline, Go Online again and call the
function "download to device" again.
Promass / Promag After having switched the Ident Number selector offline, the
function "download to device" will be interrupted as the device
performs a reset.
Prosonic FMU 86x The device type (860, 861, 862 or 867) is to be set properly
Offline with the parameter “Device type” (menu Service and
Simulation).
General When configuring in AI block, there may be error messages if the
limit values are not entered by starting with the lowest value and
proceeding towards the highest value.

8.3. FOUNDATION fieldbus


Prowirl 72/73 The Diagnostic module “NE107” needs devices configured in one of
the listed languages to work properly.
English, German, French, Italian, Spanish, Portuguese
iTemp TMT85 It is possible, that the following problem occurs in third party
frames: While executing an Upload or a Print, other functions of the
DTM are not deactivated and therefore can be accessed. This may
lead to error messages. To avoid this behavior, restrain from using
any other functions while uploading or printing.

8.4. Service CDI


CM442 The functionality Scan and Up/Download are not supported for
this device.
It is currently not possible to parameterize the Device with the
DTM in Windows 7

Date 2016-07-04 Page 13 of 21


Release Notes
Single DTMlibrary V2.44.00

Document V1.00.00

8.5. DeviceCare
Licenses With the DTMs Promass 84, Promass 2-wire and Prosonic Flow B-
200 occurs a license error, while trying to connect in DeviceCare.
Prosonic S Restoring the Data, after using the Save functionality does not work
for the Prosonic S DTM. An error occurs.
Disconnect While connecting a DTM after disconnection of another DTM, the
newly connected DTM will be shown as the previously disconnected
DTM.
Devicetag A modified device tag will not be shown correctly after using the
save functionality. The old device tag is still displayed. The same
behavior occurs with the device report functionality.

8.6. Diagnostic Module


Following device types support NE107 diagnostic categories (F, M, C, S) and provide
extended information about cause and remedy. This function is available from the main
page of Online Parameter Editor and under Additional Functions -> Diagnostic.

HART
Cerabar S / PMx 7x / V02.10.xx
Cerabar S / PMx 7x / HART / FW 2.20.zz / Dev.Rev. 22
Deltabar S / xMD 7x / V02.10.xx
Deltabar S / xMD 7x / HART / FW 2.20.zz / Dev.Rev. 22
Deltabar / FMD 7x / V1.00.xx
Deltapilot S / FMB 70 / V02.10.xx
Deltapilot S / FMB 70 / HART / FW 2.20.zz / Dev.Rev. 22
Gammapilot M / FMG 60 / V02.xx
iTEMP / TMT82 / HART / FW 1.00.zz
iTEMP / TMT82 / HART / V1.01.xx / Dev.Rev. 02
iTEMP / TMT162 / HART / V1.03.05
iTEMP / TMT142 / HART / V1.03.05
iTEMP / TMT82 / HART / FW 1.01.zz / Dev.Rev. 2
Gammapilot M / FMG 60 / HART / FW 1.04.zz / Dev.Rev. 3
Levelflex / FMP 5x / HART / FW 1.01.zz / Dev.Rev. 2
Liquicap M / FMI 5x / 1.03.xx
Liquiline M / CM44x / FW 1.02.zz / Dev.Rev. 1 (*)

Date 2016-07-04 Page 14 of 21


Release Notes
Single DTMlibrary V2.44.00

Document V1.00.00

HART
Liquiline M Cci / CM 42 / V13.05.xx (*)
Liquiline M DO / CM 42 / V20.03.xx (*)
Liquiline pHORP / CM 42 / HART / FW 2.01.zz / Dev.Rev. 01
Liquiline Cond / CM 42 / HART / FW 2.01.zz / Dev.Rev. 01
Liquiline Oxygen / CM 42 / HART / FW 2.01.zz / Dev.Rev. 01
Liquiline M pH-ORP / CM 42 / V10.05.xx (*)
Liquiport / CSPxx / HART / FW 01.02.zz / Dev.Rev.1 (*)
Liquistation / CSFxx / HART / FW 01.02.zz / Dev.Rev.1 (*)
Levelflex / FMP 5x / HART / FW 1.02.zz / Dev.Rev. 03
Levelflex / FMP5x / HART / FW 1.30.zz / Dev.Rev. 04
Micropilot M / FMR 25x / V5.xx
Micropilot M / FMR 2xx / V4.xx
Micropilot / FMR5x / HART / FW 1.00.zz / Dev.Rev. 1
Micropilot / FMR5x / HART / FW 1.01.zz / Dev.Rev. 2
Micropilot / FMR5x / HART / FW 1.02.zz / Dev.Rev. 03
Micropilot / FMR6x / HART / FW 1.00.zz / Dev.Rev. 01
Micropilot / FMR20 / HART / FW 1.00.zz / Dev.Rev. 01
Micropilot S / FMR 53x / V3.00
Micropilot S / FMR 540 / V01.01.xx
Multicap / FEC 12 / V1.0 … 1.2
Prosonic Flow / B200 / HART / FW 1.00.zz / Dev.Rev. 1
Prosonic Flow / B200 / HART / FW 1.01.zz / Dev.Rev. 2
Prosonic Flow B 200 / 9B2B / HART / FW 1.02.zz / Dev.Rev. 03
Prosonic M / FMU 4x / V4.xx
Prosonic S / FMU 90 / V2.01.xx
Promag / 53 / HART / FW 2.07.zz / Dev.Rev. 09
Promag 100 / 5x1Bxx / HART / FW 1.00.zz / Dev.Rev. 1
Promag 200 / 5x2Bxx / HART / FW 1.00.zz / Dev.Rev. 1
Promag 200 / 5x2B / HART / FW 1.01.zz / Dev.Rev. 02
Promag 400 / 5x4Bxx / HART / FW 1.00.zz / Dev.Rev. 1

Date 2016-07-04 Page 15 of 21


Release Notes
Single DTMlibrary V2.44.00

Document V1.00.00

HART
Promass / 83 / HART / V3.07.xx / Dev.Rev. 0A
Promass 100 / 8x1Bxx / HART / FW 1.00.zz / Dev.Rev. 1
Promass 100 / 8x1Bxx / HART / FW 1.01.zz / Dev.Rev. 2
Promass 200 / 8x2B / HART / FW 1.02.zz / Dev.Rev. 3
Promass 200 / 8x2B / HART / FW 1.03.zz / Dev.Rev. 4
Promass 300 500 / 8x3x 8x5x / HART / FW 1.00.zz / Dev.Rev. 01
Promag 400 / 5x4Bxx / HART / FW 1.01.zz / Dev.Rev. 2
Promag 400 / 5x4Cxx / HART / FW 1.04.zz / Dev.Rev. 5
Promag 400 / 5x4Cxx / HART / FW 1.05.zz / Dev.Rev. 6
Promag 300 500 / 5x3x 5x5x / HART / FW 1.00.zz / Dev.Rev. 01
Prowirl 200 / 7x2Bxx / HART / FW 1.00.zz / Dev.Rev. 1
Prowirl 200 / 7x2B / HART / FW 1.01.zz / Dev.Rev. 02
Prowirl 200 / 7x2B / HART / FW 1.02.zz / Dev.Rev. 03
Proservo / NMS8x / HART / FW 1.02.zz / Dev.Rev. 02
Tank Side Monitor / NRF8x / HART / FW 1.02.zz / Dev.Rev. 02
Tank Gauging Radar / NMR8x / HART / FW 1.02.zz / Dev.Rev. 02
Waterpilot 2x / FMX 21 / V1.00.xx

PROFIBUS
Cerabar S / PMx 7x / PA / V4.00.xx
Cerabar S / PMx 7x / PA / FW 4.01.zz / Dev.Rev. 3
Deltabar S / xMD 7x / PA / V4.00.xx
Deltabar S / xMD 7x / PA / FW 4.01.zz / Dev.Rev. 3
Deltapilot S / FMB70 / PA / V4.00.xx
Deltapilot S / FMB70 / PA / FW 4.01.zz / Dev.Rev. 3
Gammapilot M / FMG 60 / PA / V1.02.xx
iTemp / TMT84 / PA / V1.0
Levelflex M / FMP 4x / PA / V4.xx
Levelflex / FMP 5x / PA / FW 1.00.zz / Dev.Rev. 1
Levelflex / FMP5x / PA / FW 1.01.zz / Dev.Rev. 02

Date 2016-07-04 Page 16 of 21


Release Notes
Single DTMlibrary V2.44.00

Document V1.00.00

PROFIBUS
Liquiline M Cci / CM 42 / PA / V13.05.xx (*)
Liquiline M Cci / CM 42 / PA / FW V13.07.zz
Liquiline M DO / CM 42 / PA / V20.03.xx (*)
Liquiline M DO / CM 42 / PA / FW V20.05.zz
Liquiline Cond / PA / FW 2.01.zz / Dev.Rev. 01
Liquiline / CA80xx / DP / FW 1.06.zz / Dev.Rev. 04
Liquiline Oxygen / PA / FW 2.01.zz / Dev.Rev. 01
Liquiline M / CM44x /DP / FW 1.03.zz / Dev.Rev. 1
Liquiline M / CM44x /DP / FW 1.04.zz / Dev.Rev. 2
Liquiline M / CM44x /DP / FW 1.05.zz / Dev.Rev. 2
Liquistation / CSFxx / DP / FW 01.03.zz / Dev.Rev.1
Liquistation / CSFxx / DP / FW 01.04.zz / Dev.Rev.2
Liquistation / CSFxx / DP / FW 01.05.zz / Dev.Rev.2
Liquistation / CSFxx / DP / FW 1.06.zz / Dev.Rev. 04
Liquiline M pH-ORP / CM 42 / PA / V10.05.xx (*)
Liquiline M pH-ORP / CM 42 / PA / FW V10.07.zz
Liquiline pHORP / PA / FW 2.01.zz / Dev.Rev. 01
Liquiphant M/S / FTL 5x/7x / PA / V1.3
Micropilot / FMR5x / PA / FW 1.00.zz / Dev.Rev. 1
Micropilot / FMR5x / PA / FW 1.01.zz / Dev.Rev. 02
Micropilot M / FMR 25x / PA / V5.xx
Micropilot M / FMR 2xx / PA / V4.xx
Multicap / FEC 14 / V1.0
Promag / 50 / PA / V3.06.xx
Promag / 53 / DP / V3.06.xx
Promag / 53 / PA / V3.06.xx
Promag / 55 / DP / V3.06.xx
Promag / 55 / PA / V3.06.xx
Promag 100 / 5x1B / DP / FW 1.00.zz
Promag 100 / 5x1B / DP / FW 1.01.zz / Dev.Rev. 02

Date 2016-07-04 Page 17 of 21


Release Notes
Single DTMlibrary V2.44.00

Document V1.00.00

PROFIBUS
Promag 200 / 5x2B / PA / FW 1.00.zz / Dev.Rev. 01
Promag 400 / 7x1B / DP / FW 1.00.zz
Promag 400 / 5x4C / DP / FW 1.01.zz / Dev.Rev. 02
Promass / 80 / PA / V3.06.xx
Promass / 83 / DP / V3.06.xx
Promass / 83 / PA / V3.06.xx
Promass 100 / 8x1B / DP / FW 1.00.zz
Promass 100 / 8x1B / DP / FW 1.01.zz / Dev.Rev. 2
Promass 200 / 8x2Bxx / PA / FW 1.00.zz / Dev.Rev. 1
Prosonic Flow / 92 / PA / V1.00.xx
Prosonic Flow / 93 / DP / V3.06.xx
Prosonic Flow / 93 / PA / V3.06.xx
Prosonic M / FMU4x / PA / V4.xx
Prosonic S / FMU 90 / DP / V2.01.xx
Prosonic S / FMU 95 / DP / V1.01.xx
Prowirl / 72 / PA / V1.03.00
Prowirl / 73 / PA / V1.03.00
Prowirl 200 / 7x2Bxx / PA / FW 1.00.zz
Prowirl 200 / 7x2Bxx / PA / FW 1.01.00 / Dev.Rev. 02
t-mass / 65 / DP / V3.06.xx
t-mass / 65 / PA / V3.06.xx

FOUNDATION fieldbus
Cerabar M / PMx5x / FF / FW 1.00.zz / Dev.Rev. 1
Cerabar S / PMx7x / FF / V3.00.xx / DevRev6
Cerabar S / PMx7x / FF / FW 4.00.zz / Dev.Rev. 7
Deltabar M / PMD5x / FF / FW 1.00.zz / Dev.Rev. 1
Deltabar S / PMx7x / FF / V3.00.xx / DevRev6
Deltabar S / xMD 7x / FF / FW 4.00.zz / Dev.Rev. 7
Deltapilot M / FMB5x / FF / FW 1.00.zz / Dev.Rev. 1

Date 2016-07-04 Page 18 of 21


Release Notes
Single DTMlibrary V2.44.00

Document V1.00.00

FOUNDATION fieldbus
Deltapilot S / FMB70 / FF / V3.00.xx / DevRev6
Deltapilot S / FMB 70 / FF / FW 4.00.zz / Dev.Rev. 7
iTEMP / TMT162 / FF / FW 1.00.zz / Dev.Rev. 2
iTEMP / TMT162 / FF / V1.00.xx / DevRev1
iTEMP / TMT162 / FF / V2.00.xx / Dev.Rev. 03
iTEMP / TMT85 / FF / V1.00.xx / DevRev1
iTEMP / TMT85 / FF / FW 2.00.zz / Dev.Rev. 2
Levelflex / FMP 5x / FF / FW 1.00.zz / Dev.Rev. 1
Levelflex / FMP5x / FF / FW 1.01.zz / Dev.Rev. 02
Levelflex M / FMP4x / FF / V4.xx / DevRev4
Liquiline_pHORP / Rev 2
Liquiline_Cond / Rev 2
Liquiline_Oxygen / Rev 1
Micropilot M / FMR2xx / FF / FW 1.04.zz / Dev.Rev. 4
Micropilot M / FMR2xx / FF / FW 1.04.zz / Dev.Rev. 5
Micropilot / FMR5x / FF / FW 1.00.zz / Dev.Rev. 1
Micropilot / FMR5x / FF / FW 1.01.zz / Dev.Rev. 02
Promag / 53/55 / FF / V2.00.xx / DevRev3
Promag / 53/55 / FF / V3.00.xx / DevRev4
Promag / 53/55 / FF / V4.00.xx / DevRev5
Promag 200 / 5x2B / FF / FW 1.00.zz / Dev.Rev. 01
Promass / 83 / FF / V2.00.xx / DevRev3
Promass / 83 / FF / V3.00.xx / DevRev4
Promass / 83 / FF / V4.00.xx / DevRev5
Promass 200 / 8x2B / FF / FW 1.00.zz / Dev.Rev. 01
Prosonic Flow / 92 / FF / V1.00.xx / DevRev1
Prosonic Flow / 93 / FF / V4.00.xx / DevRev4
Prowirl / 72 / FF / V1.00.xx … V1.01.xx / DevRev1
Prowirl / 73 / FF / V1.00.xx … V1.01.xx / DevRev1
Prowirl 200 / 7x2B / FF / FW 1.00.zz / Dev.Rev. 01

Date 2016-07-04 Page 19 of 21


Release Notes
Single DTMlibrary V2.44.00

Document V1.00.00

FOUNDATION fieldbus
t-mass / 65 / FF / FW 3.00.zz / Dev.Rev. 1
t-mass / 65 / FF / FW 4.00.zz / Dev.Rev. 2

Modbus
Dosimag / 5BH / MR4 / FW 3.00.zz / Dev.Rev. 01
Dosimass / 8BE / MR4 / FW 3.00.zz
Promass 100 / 8x1B / MR4 / FW 1.03.zz / Dev.Rev. 03
Promag 100 / 5x1B / MR4 / FW 1.01.zz / Dev.Rev. 02

EtherNet/IP
Promag 100 / 5x1B / ETH / FW 1.01.zz / Dev.Rev. 02
Promass 100 / 8x1B / ETH / FW 1.02.zz

PNIO-CDIE
Promag 100 / 5x1B / PNIO-CDIE / FW 1.00.zz / Dev.Rev. 1
Promass 100 / 8x1B / PNIO-CDIE / FW 1.00.zz / Dev.Rev. 1

(*) For these Device-Types the instrument health status from the function « Diagnosis »
could show a false category after closing/reopening the DTM window. In this case it is
necessary to disconnect/reconnect the device.

9. Supported Devices

9.1. HART, PROFIBUS, FOUNDATION fieldbus, Modbus


See device list.

9.2. Basic DTM FOUNDATION fieldbus


Additionally to the devices contained in the FOUNDATION fieldbus DTM Library, the
following device types can be operated Online with the use of the “Basic DTM
FOUNDATION fieldbus” library:

See device list.

Date 2016-07-04 Page 20 of 21


Release Notes
Single DTMlibrary V2.44.00

Document V1.00.00

9.3. Service Flow (ISS DTM Library)


See device list.

9.4. Service „Phanten“ (PCP DTM Library)


See device list.

9.5. Service (CDI DTM Library)


See device list.

Date 2016-07-04 Page 21 of 21