6th International Conference on Large Power

Transformers- Modern Trends

Benefits of SFRA - Case Studies

B B Ahir
Gujarat Energy Transmission Corporation Limited

1
Outline
 Condition Monitoring in GETCO

 Why SFRA ?

 Case study (1):SFRA - How it helped to find a fault in winding

 Case study (2): SFRA - How it helped to find a fault in core

 Case study (3): SFRA - How it helped to find a fault in core

 Conclusion

2
Condition Monitoring in GETCO
Transformer
Technology / Tool Online Offline
Insulation Resistance and Polarisation Index √
Routine Low Voltage tests √
Capacitance & Tan δ measurements √ √
(Bushing)

Infrared Thermograph √
Measurement of Moisture in Oil √ √
DGA √ √
SFRA √
Acoustic Partial Discharge √
Measurement moisture content in active parts of Transformer √
3
Why SFRA ?
 To assess mechanical integrity of a transformer

 To detect core displacement and winding deformation


due to :
 Large electromagnetic forces from fault current
 Transformer transportation and relocation
 Winding shrinkage causing release of clamping structure

 To detect broken or loosened clamping structure

 Hoop Buckling

 Shorted turns and open winding

4
Case study (1):

Location : 220 kV Kapadwanj S/s


Rating : 220/66kV, 100 MVA
Date : 22.01.2012

OSR relay operated due to LV side Isolator support insulator flash over

Initially SFRA along with Low Voltage Test and DGA


5
Case study (1):
LV MAGNETIC BALANCE ( Post fault – Abnormal )
APPLIED Tap 1 Tap 17
VOLTAGE r-n y-n b-n r-n y-n b-n
r–n 255 V 255 0 0 255 0 0
y–n 251 V 174 251 74 175 251 68
b–n 256 V 27 225 256 24 226 256

DGA Results ( Post Tripping )


H2 O2 N2 CH4 C2H2 C2H4 C2H6 CO CO2

119 3657 14212 11 36 27 1 169 570


Nature of incipient fault Major Key Minor Key
Gas Gas
Arcing C2H2 , H2 CH4, C2H4

Low voltage magnetic balance test found abnormal in R phase and DGA indicates arcing
Case study (1):
HV – N at Tap No.1 ( Post fault - Abnormal)

500Hz to 2MHz with +/- 3


dB: Tap and Main winding

HV R
Phase

HV R phase shifted -3dB with reference to other phase in main and tap winding portion

7
Case study (1):
LV – N at Tap No.17 ( Post fault - Abnormal)

500Hz to 2MHz with +/- 3


dB: Tap and Main winding

20Hz – 10KHz – Core


deformation/open ckt./
LV R
Shorted turns / residual
Phase magnetism

LV R phase shifted widely with reference to other phase in main and tap winding portion.
It seems like open circuit. 8
Case study (1):
Analysis

 SFRA LV R phase found abnormal – defect in


tapped winding ( 500Hz to 2 MHz) and open
winding ( 5Hz to 100kHz ) with +/- 3 dB
variation.

 Problem reflected in low voltage magnetic


balance and DGA ( Arcing ) also.

 Based on above abnormal results, decided to


internal inspection of this transformer.

9
Case study (1): Internal Inspection
 LV R phase connecting leads of preselector switch of OLTC and its fixing
assembly burnt.

Burned connecting leads

 Burnt link and fixing assembly replaced


 Re-insulation of leads
 Drying process with oil filtration
 Take SFRA and other supporting test 10
Case study (1):
HV – N at Tap No.1 ( Normal – After rectification )

HV R
Phase

All phases are identical after rectification of problem


11
Case study (1):
LV – N at Tap No.17 ( Normal – After rectification)

LV R
Phase

All phases are identical after rectification of problem


12
Case study (1):

LV MAGNETIC BALANCE ( Normal – After rectification )

APPLIED Tap 1 Tap 17


VOLTAGE
r-n y-n b-n r-n y-n b-n

r–n 255 V 255 224 30 255 225 25

y–n 252 V 176 252 76 175 252 69

b–n 255 V 28 226 255 26 226 255

Low voltage test found normal after rectification


Case study (1):

Cause of failure

 The heavy fault current due to flash over of LV side


isolator support insulator caused R phase pre-selector
switch LV connection two nos. of leads between
position 3 & 12 to burn.

 SFRA plays a role as a supporting test to confirm the


fault with other test.

14
Case study (2):

Location : 220kV Khanpur Substation


Rating : 220/66kV , 100 MVA
Date : 21.04.08

High key gases in routine DGA test

Low voltage test - √ 15


Case study (2):
DGA Results ( on 22.12.07 , Normal )
H2 O2 N2 CH4 C2H2 C2H4 C2H6 CO CO2

7 3405 12150 21 Nil 48 15 34 292

DGA Results ( on 21.04.08 , Abnormal )


H2 O2 N2 CH4 C2H2 C2H4 C2H6 CO CO2

355 2988 13928 472 <1 538 214 57 1085

Nature of incipient fault Major Key Minor Key


Gas Gas

Thermal Fault - Over heated oil CH4, C2H4 C 2H 6 , H 2

DGA indicates thermal fault as per high key gases method

16
Case study (2): Low voltage Test

MAGNETIZING CURRENT ( Post fault - Normal)


CURRENT HV WINDING LV WINDING
MEASURED
R 3.2 mA 29.3 mA
Y 2.6 mA 26.3 mA
B 4.1 mA 35.2 mA

MAGNETIC BALANCE ( Post fault - Normal )


APPLIED
VOLTAGE R-N Y-N B-N r-n y-n b-n
R-N 255 V 255 193 56 87 65 18
Y-N 252 V 170 252 82 59 87 28
B-N 256 V 58 190 256 16 69 87

Low voltage test found normal after fault


Case study (2): Low voltage Test

SHORT CIRCUIT CURRENT ( Post fault - Normal )


CURRENT HV WINDING LV WINDING
MEASURED

R 3.54 A 10.38 A
Y 3.55 A 10.18 A
B 3.48 A 10.41 A

Low voltage test found normal after fault


Case study (2):
HV - N ( Post fault - Abnormal)

20Hz – 10KHz – Core


deformation/open ckt./
Shorted turns / residual
magnetism

HV B Phase

B phase curve differ in core area in compare with other two phases which shows core
related issue
19
Case study (2):
HV - N ( LV Shorted ) ( Post fault - Abnormal )

HV B Phase

LV short curve nullify effect of core, winding part seems identical and normal

20
Case study (2):
LV – N ( Post fault - Abnormal)

20Hz – 10KHz – Core


deformation/open ckt./
Shorted turns / residual
magnetism

LV B Phase

B phase curve differ in core dominated area, which shows problem in core area

21
Case study (2):
Analysis
 SFRA showed abnormality in the core.

 IR between core , frame and earth was measured.


Core to Frame : 2000MΩ
Frame to Earth : 8000MΩ
Core to Earth : 0.03MΩ

 As the Core to Earth insulation found quite low, internal


inspection carried out but nothing seen abnormal.

 Further investigation was done by inserting a GI wire


between core and bottom of the tank and along the core
nut found under the B phase core limb which was
touching core and bottom. 22
Case study (2): Schematic Diagram

23
Case study (2): Analysis

 After removing the nut, again IR between core , frame


and earth was measured.
Core to Frame : 2000MΩ
Frame to Earth : 8000MΩ
Core to Earth : 2000MΩ

 Normally core earthing provided on top of the tank. The


nut was providing another earthing and it caused thermal
fault due to circulating current between core and earth.

24
Case study (2):
HV - N ( Normal – After rectification)

After attending the problem all phase curves found identical

25
Case study (2):
HV - N ( LV Shorted ) ( Normal – After rectification )

After attending the problem all phase curves found identical


26
Case study (2):
LV – N ( Normal – After rectification)

After attending the problem all phase curves found identical

27
Case study (2):
Conclusion

 A metallic nut below the core at bottom of the tank was


found out with the help of SFRA which created parallel
path to earth and led to thermal fault.

 Such kind of unbelievable fault can be identified by


SFRA.

 In this case SFRA played a vital role as a supporting tool


with DGA to detect the faulty area and to reach up to the
root cause of the fault.

28
Case study (3):

Location : 66kV Chhala Substation


Rating : 66/11.55kV , 10 MVA
Date : 01.09.08

Tripped on differential relay due to failure of 66kV class


Y phase bushing with reflected of 11kV feeder
29
Case study (3): Low voltage Test

MAGNETIZING CURRENT ( Post fault - Abnormal )


CURRENT HV WINDING LV WINDING
MEASURED
R 1.8 mA 117.5 mA
Y 13.5 mA 133 mA
B 1.8 mA 135 mA

MAGNETIC BALANCE ( Post fault - Abnormal )


APPLIED
VOLTAGE R-Y Y-B B-R r-n y-n b-n
R–Y 433 V 433 388 176 41 37 16
Y–B 431 V 230 431 296 21 40 38
B-R 437 V 309 296 437 19 38 41

Low voltage test found abnormal after fault


30
Case study (3):
HV PH – PH ( Post fault - Abnormal )

20Hz – 10KHz – Core


deformation/open ckt./
Shorted turns / residual
magnetism

R-Y Y-B B-R

All three phases response are differ in core related area as mentioned frequency
31
Case study (3):
HV PH – PH ( LV Shorted ) ( Post fault – Normal )

In LV short condition core area nullify and winding area curves are identical in all
phases 32
Case study (3):
LV PH – N ( Post fault - Abnormal )

20Hz – 10KHz – Core


deformation/open ckt./
Shorted turns / residual
magnetism

R Y B

All three phases response are differ in core related area as mentioned frequency
33
Case study (2): Analysis

 SFRA and low voltage revealed problem inside core


area.

 Internal inspection carried out by removing top plate of


transformer.

 2 Nos. of bolts clamping the top channel with tank were


loose and top yoke channel got lifted upwards by about
25mm which caused a little core deformation.

34
Case study (2): Internal Inspection

Yoke
Bolt

Yoke
Channel

 After attending the problem, SFRA was taken. 35


Case study (3):
HV PH – PH ( Normal – After rectification )

All three phases response are identical in core dominated area after rectification of
fault 36
Case study (3):
HV PH – PH ( LV Shorted ) ( Normal – After rectification )

This response was identical from initially as problem was in core area after rectification
of fault 37
Case study (3):
LV PH – N ( Normal – After rectification )

All three phases response are identical now in core area after rectification of fault
38
Case study (3): Low voltage Test

MAGNETIZING CURRENT ( Normal – After rectification)

CURRENT HV WINDING LV WINDING


MEASURED
R 2.4 mA 56.2 mA
Y 1.9 mA 28.5 mA
B 2.2 mA 55.6 mA

MAGNETIC BALANCE ( Normal – After rectification)


APPLIED
VOLTAGE R-Y Y-B B-R r-n y-n b-n
R–Y 442 V 442 365 79 41 35 6
Y–B 450 V 256 450 189 23 42 17
B-R 445 V 44 396 445 4 37 41
Low voltage test found normal after rectification of fault 39
Case study (3):
Cause of Failure

 Heavy reflected fault caused axial and radial forces


exerted on transformer active part.

 Core structure got disturbed and it was reflected in SFRA


plot.

40
Conclusion
 SFRA responses clearly indicate faulty conditions of transformer and it
helped for root cause analysis.

 SFRA helps to detect fault by just compare with different phase with
different task without having a initial results of same transformer or
same design transformer.

 SFRA plays vital role as supporting test for final conclusion as its
deliver diversity of information in only one test.

 SFRA is very useful tool to detect heavy through fault current leads to
mechanical deformation of core or winding, internal connections and
contacts inside transformer.

 GETCO has adopted such diagnosis tool while fault as well as in


routine practice while shifting of transformer.