Item
Description Status
No
1. Is the building / area inspected adequately heated? Yes N/A No
(Note: Maintain minimum temperature of 4.4°C)
2. What is the type of sprinkler head installed? Standard response
Quick-response
Upright
Pendent
Sidewall
Extended coverage
ESFR
3. Are system valves and gauges accessible for operation, inspection, Yes N/A No
tests and maintenance?
4. Check the following information for each type of sprinkler head
inspected –
a. Manufacturer name Yes N/A No
b. K-factor (orifice size) or orifice shape Yes N/A No
c. Pressure rating Yes N/A No
d. Thermal sensitivity Yes N/A No
e. Glass bulb color Yes N/A No
5. Are all sprinklers installed throughout a compartment of same Yes N/A No
temperature rating?
6. Check if any sprinkler head shows sign of – (Provide photographic
evidence)
Leakage Yes N/A No
Corrosion Yes N/A No
Physical Damage Yes N/A No
Loss of fluid in the glass bulb heat responsive element Yes N/A No
Painting Yes N/A No
Loaded with dust, dirt, and grease. Yes N/A No
7. Are sprinklers installed in the correct orientation they are designed Yes N/A No
for?
8. Check if sprinklers are installed above suspended ceilings? Identify
Yes N/A No
the concealed spaces not provided with sprinklers.
9. Check if a minimum clearance of 457mm is available below the Yes N/A No
sprinkler deflector of all sprinkler heads installed in the area being
inspected.
10. Check if any sprinklers are located in the close proximity of stocks, Yes N/A No
furnishings, equipment or architectural features?
15. Are pipes and fittings in good condition and free of mechanical Yes N/A No
damage, leakage, and corrosion?
16. Check if sprinkler piping is subjected to any external load by Yes N/A No
materials either resting on the pipe or hung from the pipe?
17. Check if any cabling is wrapped around the sprinkler piping? Yes N/A No
18. Check if the hanger rods are properly attached from the ceiling Yes N/A No
Anchor?
19. Check if the hangers are not damaged or lose? Yes N/A No
20. What is the type of sprinkler head installed? Standard response
Quick-response
Upright
Pendent
Sidewall
Extended coverage
ESFR
37. Check that water control valves and flow switches are electronically Yes N/A No
monitored with the main fire alarm control panel
38. Check that the drains discharge outside or to a drain connection Yes N/A No
capable of handling the flow of drain.
39. Check that the pressure gauge is not installed on the drain side of the Yes N/A No
riser.
Figure below shows an unacceptable installation of pressure gauge
Comments: