You are on page 1of 138

Instruction Manual

for Reciprocating Compressor

97.07
0171-488-EN

HPC 104S - 106S - 108S


99.09

Specifications
for
HPC 104S Ć 106S Ć 108S

The HPO-type reciprocating compressor can Some of these variants are discussed in this
be fitted with a range of equipment, depend- instruction manual, even if they are not fea-
ing on the function and requirements it is tured on your particular unit.
called on to meet. The variants featured on the unit are marked
with an ’x’ in the following diagram, with the
serial number stated below.

Compressor type

Serial number

Designation

Refrigerant R717 R410A

Capacity With standard start unloading


regulation
With total standard start unloading

Pinion drive
Oil pump drive
Chain drive
Solenoid valve in With solenoid valve
the compressor
water-cooling system Without solenoid valve

Vibration With vibration dampers


dampers
Without vibration dampers

0171-487-EN 1
Preface

The aim of this instruction manual is to this instruction manual to ensure reliable and
provide the operators with a thorough efficient operation of the plant as SABROE is
knowledge of the compressor and the unit, at unable to provide a guarantee against
the same time providing information about: damage occurring during the warranty period
where this is attributable to incorrect
S the function and maintenance of the
operation.
individual components;

S service schedules; To prevent accidents during dismantling and


S procedure for dismantling and assembly of compressors and components,
reassembling of the compressor. these should only be carried out by
authorized personnel.
The instruction manual also draws attention

96.06
to typical sources of errors which may occur
The contents of this instruction manual must
during operations. It states their cause and
not be copied or passed on to any
explains what should be done to rectify them.

0171-500-EN
unauthorized person without Sabroe’s
It is imperative that the operators familiarize permission.
themselves thoroughly with the contents of

In the space below you can enter the name and address of your local SABROE
REPRESENTATIVE :

SABROE REFRIGERATION A/S

P.O. Box 1810, DK–8270 Højbjerg Phone: +45 86 27 12 66


Chr. X’s Vej 201, Århus, Denmark Telefax: +45 86 27 44 74

2 0171-702-EN
Table of Contents

Specifications for HPC 104S - 106S - 108S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1


Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
First Aid for accidents with Ammonia . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
First Aid for accidents with HFC/HCFC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Protecting the environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Description of compressor - HPC 104S-106S-108S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Handling of the compressor, areas of application, safety equipment etc. . . . . . . . . . . . . . 14
Sound data for reciprocating and screw compressor units – all types of compressors . . 17
Vibration data for compressors - all types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Compressor data for reciprocating compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Operating limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
R717 - Operating limits, HPO 24-26-28, HPC 104S-106S-108S . . . . . . . . . . . . . . . . . . 24
General operating instructions for reciprocating compressors HPO - HPC . . . . . . . . . . . 25
Starting up compressor and plant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Stopping and starting-up compressor during a short period of standstill . . . . . . . . . . . 25
Stopping plant for brief periods (until 2-3 days) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Stopping plant for lengthy periods (more than 2-3 days) . . . . . . . . . . . . . . . . . . . . . . . . 26
Automatic plants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Pressure testing refrigeration plant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Pumping down refrigeration plant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Operating log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Servicing the reciprocating compressor HPO - HPC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Pressure drop test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Removing refrigerant from compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Lubricating oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Lubricating oil requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
General rules for use of lubricating oil in refrigeration compressors . . . . . . . . . . . . . . . 35
Instructions for choosing lubricating oil for refrigeration compressors . . . . . . . . . . . . . 35
Charging refrigeration compressor with lubricating oil . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Changing oil in refrigeration
compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Charging compressor with oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Assessing the oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Visual assessment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Analytical evaluation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
The analysis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Maintenance of reciprocating compressor HPC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
1. If the compressor is operational . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

0171-487-EN 3
2. If the compressor is inoperative . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Top covers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Mounting top and water covers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Discharge valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Cylinder lining with suction valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Connecting rod . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Piston . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Assembling and stripping down piston and connecting rod . . . . . . . . . . . . . . . . . . . . . . 49
Shaft seal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Crankshaft . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Compressor lubricating system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Oil pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Chain-driven oil pump with inverse direction of rotation . . . . . . . . . . . . . . . . . . . . . . . . . 57
Oil pressure valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
By-pass valve Pos. 24 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Oil filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Suction filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Stop valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Unloaded start and capacity regulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Description of unloader mechanism and capacity regulation . . . . . . . . . . . . . . . . . . . . . 64
Pilot solenoid valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Schematic outlines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Standard unloaded start and capacity regulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Regulating sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Totally unloaded start and capacity regulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Regulating sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Automatic capacity regulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Relief cylinder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Heating rods for heating the oil in reciprocating and screw compressors . . . . . . . . . . . . . 70
Stop valves pos. 23 and 42 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Monitoring cylinder lining insertion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
1. Checking clearance volume . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Adjustment is made as follows: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
2. Checking lifting reserve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Check lifting reserve: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Undersize Bearing Diameters for Crankshaft . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Sundry clearances and check dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Torque moments for screws and bolts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Refrigeration Plant Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Operational reliability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Pumping down the refrigeration plant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Dismantling plant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Tightness testing and pump-down of refrigeration plant . . . . . . . . . . . . . . . . . . . . . . . . . 80

4 0171-487-EN
Trouble-shooting on the Reciprocating Compressor Plant . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Remedying malfunctions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Selecting lubricating oil for SABROE compressors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Data sheet for listed Sabroe oils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
List of major oil companies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
Alignment of unit, AMR coupling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
Fitting and alignment of AMR-type coupling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
Boring of motor flange for AMR coupling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
Oil Separator OVUR for HPC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
Mode of operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
Checking oil return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
Choice of nozzle size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
Connections on SMC 104-106-108 Mk3, HPC 104S-106S-108S . . . . . . . . . . . . . . . . . . . . 150
Connections on TSMC 108 Mk3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
Water-cooling of reciprocating compressors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
Pressure loss in water cooling on SMC/TSMC/HPC compressors . . . . . . . . . . . . . . . . 154
Ordering Spare Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155
Spare parts sets for compressors and units HPO - HPC . . . . . . . . . . . . . . . . . . . . . . . . . . . 156
Compressor block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 156
Spare part set for Basic Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 156
List of parts for HPC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0662-002
Tools for compressor HPC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0662-004
Spare parts drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0662-000
Spare parts drawing (details) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0662-001
Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . order specific
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . order specific
Dimension drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . order specific
Hose diagram for water-cooling system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . order specific
Foundation drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . order specific
Placing the vibration dampers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . order specific

0171-487-EN 5
First Aid for accidents with Ammonia
(Chemical formula: NH3 - refrigerant no.: R717)

General Inhalation
Ammonia is not a cumulative poison. It has a 1. Move affected personnel into fresh air im-
distinctive, pungent odour that even at very mediately, and loosen clothing restricting
low, harmless concentrations is detectable by breathing.
most persons. Since ammonia is self-alarm-
ing, it serves at its own warning agent, so 2. Call a doctor/ambulance with oxygen
that no person will voluntarily remain in con- equipment immediately
centrations which are hazardous. Since am-
monia is lighter than air, adequate ventilation 3. Keep the patient still and warmly wrapped
is the best means of preventing an accu- in blankets.
mulation.
4. If mouth and throat are burnt (freeze or
Experience has shown that ammonia is ex-

96.01
acid burn), let the conscious patient drink
tremely hard to ignite and under normal water, taking small mouthfuls.
conditions is a very stable compound. Under
extremely high, though limited concentra- 5. If conscious and the mouth is not burnt,

0171-497-EN
tions, ammonia can form ignitable mixtures give hot, sweet tea or coffee (never feed
with air and oxygen, and should be treated an unconscious person).
with respect.
6. Oxygen may be administered, but only
Basic rules for first aid when authorized by a doctor.
1. Call a doctor immediately.
7. If breathing fails, apply artificial respira-
2. Be prepared: Keep an irrigation bottle tion.
available, containing a sterile isotonic
(0.9%) NaCl-solution (salt water).
Eye injuries from liquid splashes or
3. A shower bath or water tank should be concentrated vapour
available near all bulk installations with
ammonia. 1. Force the eyelids open and rinse eyes im-
mediately for at least 30 minutes with the
4. When applying first aid, the persons as- salt water solution just mentioned
sisting should be duly protected to avoid
further injury. 2. Call a doctor immediately.

6 0171-487-EN
Skin burns from liquid splashes or 2. Call a doctor immediately.
concentrated vapour
1. Wash immediately with large quantities of 3. After washing, apply wet compresses
water and continue for at least 15 minutes, (wetted with a sterile isotonic (0.9%)
removing contaminated clothing carefully NaCl-solution (salt water)) to affected
while washing. areas until medical advice is available.

No plant can ever be said to be too safe.


Safety is a way of life.

0171-487-EN 7
Protecting the environment

Increasing industrialisation threatens our en- concentrations of refrigerant vapours are in-
vironment. It is therefore absolutely impera- haled they attack the human nerve system.
tive that we protect nature against pollution.
When halogenated gasses come into contact
with open flame or hot surfaces (over approx.
To this end, many countries have passed le-
300°C) they decompose to produce poiso-
gislation in an effort to reduce pollution and
nous chemicals, which have a very pungent
preserve the environment. These laws apply
odour, warning you of their presence.
to all fields of industry, including refrigeration,
and must be complied with. In high concentrations, R717 causes respira-
tory problems, and when ammonia vapour
Be especially careful with the following sub- and air mix 15 to 28 vol. %, the combination
stances: is explosive and can be ignited by an electric

96.01
spark or open flame.
S refrigerants
Oil vapour in the ammonia vapour increases

0170-009-EN
S cooling media (brines etc)
this risk significantly as the point of ignition
S lubricating oils.
falls below that of the mixture ratio stated.
Refrigerants usually have a natural boiling
Usually the strong smell of ammonia will
point which lies a good deal below 0°C. This
give ample warning of its presence before
means that liquid refrigerants can be extre-
concentrations become dangerous.
mely harmful if they come into contact with
skin or eyes. The following table shows the values for refri-
gerant content in air, measured in volume %.
High concentrations of refrigerant vapours Certain countries may, however, have an offi-
are suffocating when they displace air; if high cial limit which differs from those stated.

Halogenated refrigerants Ammonia

HFC HCFC

R134a R404A R407C R410A R507 R22 R717

Unit

TWA
Time weighted ave- vol.% 0,1 0,1 0,1 0,1 0,1 0,1 0,005
rage during a week

Warning smell vol.% 0,2 0,002

8 0178-225-EN
Further comments on refrigerants: Halogenated refrigerants must never be
S If released to the atmosphere, haloge- mixed. Nor must R717 ever be mixed with
nated refrigerants of the type HCFC halogenated refrigerants.
(e.g. R22) may cause a depletion of the
ozone layer in the stratosphere. The Purging a refrigeration plant
ozone layer protects the earth from the If it is necessary to purge air from a refrige-
ultraviolet rays of the sun. Refrigerants of ration plant, make sure you observe the follo-
the types HFC and HCFC are greenhouse wing:
gases with contribute to an intensification
of the greenhouse effect. They must, S Refrigerants must not be released to the
therefore, never be released to the atmo- atmosphere.
sphere. Use a separate compressor to
draw the refrigerant into the plant con- S When purging an R717 plant, use an ap-
denser/receiver or into separate refriger- proved air purger. The purged air must
ant cylinders. pass through an open container of water
so that any R717 refrigerant remaining
S Most halogenated refrigerants are mis- can be absorbed. The water mixture must
cible with oil. Oil drained from a refrigera- be sent to an authorized incinerating plant.
tion plant will often contain significant
amounts of refrigerant. Therefore, reduce S Halogenated refrigerants can not be ab-
the pressure in the vessel or compressor sorbed by water. An approved air purger
as much as possible before draining the must be fitted to the plant. This must be
oil. checked regularly using a leak detector.

S Ammonia is easily absorbed by water:


At 15°C, 1 litre of water can
Cooling media
absorb approx. 0,5 kg liquid Salt solutions (brines) of calcium chloride
ammonia (or approx. 700 litres (CaCl2) or sodium chloride (NaCl) are often
ammonia vapour). used.

S Even small amounts of ammonia in water In recent years alcohol, glycol and halogena-
(2-5 mg per litre) are enough to wreak ted compounds have been used in the brine
havoc with marine life if allowed to pollute production.
waterways and lakes.
In general, all brines must be considered as
S As ammonia is alkaline it will damage
harmful to nature and must be used with
plant life if released to the atmosphere in
caution. Be very careful when charging or
large quantities.
purging a refrigeration plant.
Refrigerant evacuated from a refrigerant
plant shall be charged into refrigerant cylin- Never empty brines down a sewer or into
ders intended for this specific refrigerant. the environment.

If the refrigerant is not to be reused, return it The brine must be collected in suitable con-
to the supplier or to an authorized incinerat- tainers, clearly marked with the contents, and
ing plant. sent to an approved incinerating plant.

0178-225-EN 9
Lubricating oils – alkyl benzene-based synthetic oil

Refrigeration compressors are lubricated by – polyalphaolefine-based synthetic oil


one of the following oil types, depending on
the refrigerant, plant type and operating con- – glycol-based synthetic oil.
ditions. When you change the oil in the compressor
or drain oil from the refrigeration plant’s ves-
– mineral oil sels, always collect the used oil in containers
marked “waste oil” and send them to an ap-
– semi-synthetic oil proved incinerating plant.

Note
This instruction provides only general information. The owner of the refrigeration
plant is responsible for ensuring that all by-laws are complied with.

10 0178-225-EN
Description of compressor
HPC 104SĆ106SĆ108S
95.09
0171-489-EN

The HPC compressors have 100 mm diame-


ter pistons, as indicated by the first digit in
the type designation. The number of cylin- SABROE
ders in the compressor block is indicated by AARHUS DENMARK
the following two digits, where, for example, Type Refrigerant
HPC 108 is an 8-cylinder compressor. HPC Shop no Year
is a one-stage compressor which compres- Max. speed r.p.m.
ses the gas in a single stage.
Swept volume m3/h
Working pressure bar
The stroke is 80 mm. Test pressure bar

The type can be determined by the name- T0177093_2


plate, located on the end face of the com-
pressor, facing away from the coupling. Similarly, the nameplate indicates the com-
The following illustration shows a SABROE pressor’s serial number, which is also
nameplate. stamped into the compressor housing near
the suction chambers.
Whenever contacting SABROE about the
compressor, its serial number should be
stated.
The pistons operate in cylinder linings, which
are inserted in the frame with two cylinders
under each top cover. The suction valves, of
the ring-plate type, are mounted at the top of

0171-487-EN 11
the cylinder linings. The pressure valves form At the axle end, the crankshaft is fitted with a
the top of the cylinder linings and are kept in balanced slide-ring type seal consisting of a
position by a powerful safety spring. The cast iron ring with an O-ring which rotates
safety spring allows the discharge valve unit with the crankshaft, and a stationary
to rise, providing a greater throughflow aper- spring-loaded carbon ring.
ture in the event of liquid strokes in the cylin-
der. This prevents any overloading of the All compressors can be capacity-regulated
connecting rod bearings. by connecting or disconnecting the cylinders
The crankshaft is supported in slide bearings in pairs. The following diagram shows the
able to assimilate both radial and axial capacity stages at which the compressors
forces. The oil pressure for the bearings and can operate.
the capacity regulating system is supplied
from the gearwheel oil pump incorporated in Capacity regulation is controlled by means of
the compressor. solenoid valves mounted on the compressor.

25% 33% 50% 67% 75% 100%

HPC 104 x x
HPC 106 x x x
HPC 108 x x x x

12 0171-487-EN
Handling of the compressor, areas of application,
safety equipment etc.

Direction of rotation clearly marked with red paint. The weight of


In order to reduce the noise level from the the unit is stated on the package as well as in
electric motors these are often executed with the shipping documents.
specially shaped fan wings, thus determining During transportation and handling care
a particular direction of rotation. should be taken not to damage any of the
In case you yourself order a motor you components, pipe or wiring connections.
should take into consideration whether the Areas of application of the recipro-
motor is intended for direct coupling or for
cating compressors
belt drive of the compressor.
Compressor types:
The direction of rotation of the compressor BFO 3-4-5
for compressors CMO-TCMO and SMC- CMO-TCMO,
97.12

TSMC is indicated by an arrow cast into the SMC 100-TSMC 100 Mk3, S, L, E
compressor cover, near the shaft seal. SMC 180-TSMC 180,
On the BFO compressors the direction of HPO-HPC
0170-119-EN

rotation is not indicated by an arrow but is In view of preventing an unintended applica-


standard as illustrated by the following tion of the compressor, which could cause
sketch: injuries to the operating staff or lead to tech-
nical damage, the compressors may only be
applied for the following purposes:

The compressor may ONLY be used:


S As a refrigeration compressor with a num-
ber of revolutions and with operating limits
Seen towards shaft end
as indicated in this manual or according to
a written agreement with SABROE.
Handling of compressor and unit
S With the following refrigerants:
For lifting of the compressor the large models
R717 – R221 – R134a1 – R404A1 –
are equipped with a threaded hole for mount-
R410A1 – R5071 – R6001 – R600A1 –
ing of the lifting eye. As to the weight of the
R2901 – LPG1
compressor, see table on compressor data. 1) Exempted are the following compres-

Note: sors:
SMC-TSMC 100 E (only R717)
The compressor block alone may be lifted HPO and HPC (only R717 and R410A)
in the lifting eye. The same applies to the All other types of gas may only be
motor. used following a written approval from
SABROE.
The unit is lifted by catching the lifting eyes
welded onto the unit frame. These have been S As a heat pump:

0171-487-EN 13
– BFO 3-4-5 manual handle, to which there is free ac-
cess.
CMO - TCMO and SMC - TSMC may
be used with a max. discharge pressure S It must be able to stop any dangerous si-
of 25 bar. tuation, which may occur, as quickly as
possible without this leading to any further
– HPO – HPC may be used with a max.
danger.
discharge pressure of 40 bar.
S In an explosion-prone environment, pro- Combustion motors
vided the compressor is fitted with ap- If combustion motors are installed in rooms
proved explosion-proof equipment. containing refrigeration machinery or rooms
The compressor must NOT be used: where there are pipes and components con-
S For evacuating the refrigeration plant of air taining refrigerant, you must make sure that
and moisture, the combustion air for the motor is derived
from an area in which there is no refrigerant
S For putting the refrigeration plant under air
gas, in case of leakage.
pressure in view of a pressure testing,
S As an air compressor. Failure to do so will involve a risk of the lubri-
Emergency device cating oil from the combustion motor mixing
with the refrigerant; at worst, this may give
The compressor control system must be
rise to corrosion and damage the motor.
equipped with an emergency device.
In case the compressor is delivered with a Explosion-proof electrical execution
SABROE-control system this emergency de-
If the compressor is delivered in an explo-
vice is found as an integrated part of the con-
sion-proof electrical execution, this is stated
trol.
in the table on page 1 of this instruction
The emergency device must be executed in manual.
a way to make it stay in its stopped position,
following a stop instruction, until it is deliber- Likewise, the compressor will, besides the
ately set back again. It must not be possible SABROE name plate, be equipped with an
to block the emergency stop without a stop Ex-name plate like the one illustrated below.
instruction being released.
It should only be possible to set back the
emergency device by a deliberate act, and
this set back must not cause the compressor
to start operating. It should only make it pos-
sible to restart it.

Other demands to the emergency device:


S It must be possible to operate it by means
T2516273_0
of an easily recognizable and visible

14 0171-487-EN
The temperature of tangible surfaces close to the warning signs during operation
When a compressor is working, the surfaces are so hot that your skin may be burnt from 1
that are in contact with the warm discharge second’s touch or longer.
gas also get warm. However, the temperatu-
re depends on which refrigerants and under
which operating conditions the compressor
is working. Often, it exceeds 70°C which for
metal surfaces may cause your skin to be
burnt even at a light touch.

Consequently, the compressors will be equip-


ped with yellow warning signs informing
you that pipes, vessels and machine parts

0171-487-EN 15
Sound data for reciprocating and screw
compressor units - all types of compressors

In the following tables the noise data of the S SAB 81-83-85-87-89, SAB 128, Mk3,
compressors is stated in: SAB 163 Mk3, SAB 202, SAB 330, SV
and FV:
– A-weighted sound power level LW
Compressor block + IP23 special motor +
(Sound Power Level)
oil separator.
– A-weighted sound pressure level LP
S SAB 128 HR and SAB 163 HR:
(Sound Pressure level)
Compressor block at max. number of
The values for LW constitute an average of a revolutions + IP23 special motor + oil
large number of measurings on various units. separator
The measurings have been carried out in ac-
cordance with ISO 9614-2. S SAB 110:
Compressor block + IP23 standard motor
The values are further stated as average + oil separator

99.06
sound pressure in a free field above a re-
Dimensional tolerances are:
flecting plane at a distance of 1 meter from
a fictional frame around the unit. See fig. 1. ±3 dB for SAB, SV and FV screw com-

0170-114--EN
pressors
Normally, the immediate sound pressure
±5 dB for VMY screw compressors
lies between the LW and LP values and can
be calculated provided that the acoustic data As to the reciprocating compressors the
of the machine room is known. values are stated for the compressor block
only.
For screw compressors the average values
are indicated in the tables for the following The dimensional values are stated for 100%
components. capacity.

Fig. 1

Fictional frame

Dimensional plane

1 meter Reflecting plane


1 meter

16 0170-114-EN
Note the following, however: S the acoustics is another factor that can
change the sound level in a room. Please
S at part load or if the compressor works
note that the sound conditions of the site
with a wrongly set Vi the sound level can
have not been included in the stated
sometimes be a little higher than the one
dimensional values.
indicated in the tables.
S additional equipment such as heat ex- S by contacting SABROE you can have
changers, pipes, valves etc. as well as the sound data calculated for other operating
choice of a different motor type can in- conditions.
crease the noise level in the machine
room.
The tables have been divided into reciprocat-
S as already mentioned, the stated sound ing and screw compressors, respectively.
pressures are only average values above The reciprocating compressors are further
a fictional frame around the noise source. divided into one- and two-stage compressors
Thus, it is sometimes possible to measure as well as in a heat pump. In each table the
higher values in local areas than the ones operating conditions of the compressor dur-
stated – for inst. near the compressor and ing noise measuring have been stated, just
motor. as the refrigerant used has been mentioned.

0170-114-EN 17
RECIPROCATING COMPRESSORS Two-stage
One-stage Evaporating temperature = –35°C
Evaporating temperature = –15°C Condensing temperature = +35°C
Condensing temperature =+35°C Refrigerant = R22/R717
Refrigerant = R22/R717 Number of revolutions =1450 rpm.
Number of revolutions =1450 rpm.
Compressor block LW LP

Compressor block LW LP TCMO 28 81 66


TSMC 108 S 95 79
CMO 24 84 69
TSMC 116 S 97 81
CMO 26 86 71
TSMC 108 L 96 80
CMO 28 87 72
TSMC 116 L 98 82
SMC 104 S 95 79
TSMC 108 E 96 80
SMC 106 S 96 80
SMC 108 S 97 81 TSMC 116 E 98 82

SMC 112 S 99 82
SMC 116 S 100 83
Evaporating temperature = –35°C
Condensing temperature = +35°C
SMC 104 L 96 80
Refrigerant = R22/R717
SMC 106 L 97 81
Number of revolutions = 900 rpm.
SMC 108 L 98 82
SMC 112 L 100 83 Compressor block LW LP
SMC 116 L 101 84
TSMC 188 100 82
SMC 104 E 96 80
SMC 106 E 97 81
SMC 108 E 98 82 Heat pump
SMC 112 E 100 83 Evaporating temperature = +20°C
SMC 116 E 101 84 Condensing temperature = +70°C
Refrigerant = R22/R717
Number of revolutions =1450 rpm.
Evaporating temperature = –15°C
Condensing temperature = +35°C
Compressor block LW LP
Refrigerant = R22/R717
Number of revolutions = 900 rpm. HPO 24 91 76
HPO 26 93 78

Compressor block LW LP HPO 28 94 79


HPC 104 97 81
SMC 186 101 83 HPC 106 98 82
SMC 188 102 84 HPC 108 99 84

18 0170-114-EN
SCREW COMPRESSORS
Evaporating temperature = –15°C Evaporating temperature = –35°C
Condensing temperature = +35°C Condensing temperature = –5°C
Refrigerant = R22/R717 Refrigerant = R22/R717
Number of revolutions = 2950 rpm.
Number of revolutions = 2950 rpm.
*Number of revolutions = 6000 rpm.

Compressor block LW LP

SAB 110 SM 98 81 Compressor unit LW LP


SAB 110 SF 98 81
SAB 110 LM 98 81 SAB 163 BM 106 88
SAB 110 LF 98 81 SAB 163 BF 110 92
SAB 128 HM Mk2 102 84
SAB 128 HF Mk2 106 88
SAB 128 HM Mk3 101 84
SAB 128 HF Mk3 104 86 Evaporating temperature = –15°C
SAB 128 HR* 102 84 Condensing temperature =+35°C
SAB 163 HM Mk2 105 86 Refrigerant = R22/R717
SAB 163 HF Mk2 109 90 Number of revolutions = 2950 rpm.
SAB 163 HM Mk3 103 86
SAB 163 HF Mk3 106 87
SAB 163 HR* 103 85
SAB 202 SM 104 85
SAB 202 SF 105 86 Compressor block LW LP
SAB 202 LM 104 85
SAB 202 LF 105 86 VMY 347 H 97 82
VMY 447 H 100 85
SAB 330 S 106 87
SAB 330 L 106 87 VMY 536 H 104 88
SAB 330 E 106 87
SV 17 100 83
SV 19 101 84
Evaporating temperature = 0°C
FV 19* 101 86
Condensing temperature =+35°C
SV 24 103 85
FV 24* 104 86
Refrigerant = R22/R717
SV 26 103 85 Number of revolutions = 2950 rpm.
FV 26* 107 85
SAB 81 101 86
SAB 83 102 85 Compressor block LW LP
SAB 85 103 86
SAB 87 105 86 VMY 347 M 99 84
SAB 89 108 85 VMY 447 M 101 86
VMY 536 M 105 89
Min liquid pressure for liquid injection, suction
pressure bar (a) x 2+2 bar

0170-114-EN 19
Vibration data for compressors Ć all types

Vibration data for SABROE screw compres- sor unit can - under normal circumstances -
sors comply with the following norm: be classified in Class III or IV according to
ISO 2372 group C the following table from ISO 2372. Recip.
compressor units can be classified in class
Depending on the laying of the foundation
IV, likewise under normal conditions.
and the size of the motor a screw compres-

Vibration severity ranges and examples of their application to small machines (Class I) medium size ma-
chines (Class II), large machines (Class III) and turbo machines (Class IV)

Examples of quality judgement


Ranges of vibration severity for separate classes of machines

ms-velocity V (in mm/s)


Range Class I Class II Class III Class IV
at the range limits

95.06
0.28
0.28
0.45
0.45 A

0170-115-EN
0.71
0.71 A
1.12
1.8
1.12 B A
1.8 B A
2.8
2.8 C B
4.5
4.5 C B
7.1
7.1 D C
11.2
11.2 D C
18 18
28
D
28 D
45
45
71

SABROE screw compressor unit: – Motor and compressor have not been
Group C, class III or IV aligned as described in the Instruction
SABROE recip. compressor unit: Manual.
Group C, class IV. – For screw compressors, if the compres-
sor runs at a wrong Vi ratio.
Pay attention to the following, however:
– The pipe connections have been
S On placing the unit on the vibration executed in a way that makes them force
dampers delivered by SABROE pull or push powers on the compressor
(additional) the vibrations against the unit or they may transfer vibrations to the
foundation are reduced by: unit, caused by natural vibrations or con-
nected machinery.
– 85-95% for screw compressor units
– The vibrations dampers have not been
– 80 % for recip. compressor units
fitted or loaded correctly as indicated on
S However, a higher vibration level may oc- the foundation drawing delivered
cur if: together with the order.

20 0178-250-EN
Compressor data for reciprocating compressor
HPO 24Ć26Ć28, HPC 104SĆ106SĆ108S

Operating limits
SABROE prescribes some operating limits These limits for R717 as well as the main
within which the compressor and any addi- data for the compressor are shown in the fol-
tional equipment should operate. lowing table and diagram.

Compressor No. of Bore Stroke max/min Swept vol . Weight


type cyl. speed* (max. rpm) bare compr.
mm mm rpm m3/h kg
HPO 24 4 70 70 1500 97 340
HPO 26 6 70 70 1500 146 380
98.01

HPO 28 8 70 70 1500 194 410

HPC 104S 4 100 80 1500/1150 226 580


HPC 106S 6 100 80 1500/1150 339 675
HPC 108S 8 100 80 1500/1150 452 740
0171-490-EN

0171-487-EN 21
R410A
Operating limits
HPO 24-26-28
HPC 104S-106S-108S

TC ( °C)

60

50

40

30
Condensing temperature

20
2
10 1

–10

-20

-30

-40

-60 -50 -40 -30 -20 -10 0 10 20 30 40 50


Evaporating temperature TE ( ° C)

Type Area Direct. coupl. 0/min Cooling Remarks


max. min.
1
HPO 1500 1400 Vand
2 Min 50% capacity
1
HPC 1500 1150 Vand
2 Min 50% capacity

Water cooling
Top- and side covers are water-cooled
Oil-cooling is included in the system

22 0171-487-EN
TC
°F °C
R717
194 90
Operating limits
176 80 HPO 24-26-28
Condensing temperature

158 70 HPC 104S-106S-108S


140 60

122 50 1
2
104 40

86 30

68 20

50 10
T0177128_0/V6

–50 –40 –30 –20 –10 0 10 20 30 40 50 °C


TE
–58 –40 –22 –4 14 32 50 68 86 104 122 °F

Type Area Direct. coupl. Cooling Remarks


0/min
max. min.
1
HPO 1500 1400 Water
2 Min 50% capacity
1
HPC 1500 1150 Water
2 Min 50% capacity

Water cooling
Top- and side covers are water-cooled
Oil-cooling is included in the system

0171-487-EN 23
General operating instructions for
reciprocating compressors HPO Ć HPC

Starting up compressor and plant S Start compressor motor and check suction
and oil pressures.
S The heating rod in the crankcase should
be energized at least 6-8 hours before S Carefully continue opening suction stop
starting up the compressor in order to boil valve to its full open position.
any refrigerant out of the compressor oil.
S Open main valve in liquid line.
At the same time, the suction check valve
must be open. S If the oil in the crankcase foams, or knock-
ing noises are heard from the compressor
S Check oil level in crankcase. The oil level because droplets of liquid are being fed in
must always be visible in the oil sight with the suction gas, throttle suction stop
glass. valve immediately.
S The compressor is now operating.
S Check that the water cooling system for

97.02
Increase capacity stepwise, allowing the
compressor cooling functions.
compressor to adjust to new conditions

0171-491-EN
S Check correct setting of safety auto- before switching to next stage.
matics on compressor. Check carefully whether oil is foaming and
whether oil pressure is correct.
S Open discharge stop valve at compressor.
S Check whether oil return from oil separa-
tor is working. (Pay attention to any clog-
S Set capacity regulator to minimum.
ging of filter and nozzle.)
S In order to avoid excessive pressure re- The pipe should normally be warm.
duction in the compressor on start-up, the S Do not leave plant for first 15 minutes after
suction stop valve must be opened a few start-up and never before it has stabilized.
turns, as there is otherwise a risk of oil
foaming in the crankcase. Stopping and starting-up
compressor during a short
S Open all other stop valves except for the
main valve in the liquid line and by-pass period of standstill
possible valves serving other purposes. When stopping the compressor, its capacity
must be reduced to the lowest capacity stage
Note for a few minutes, before it stops.
If, during standstill, the oil separator is
During short periods of standstill, it is not
colder than the condenser, the valve in the
necessary to shut off the suction stop valve
oil return pipe must not be opened until
and the discharge stop valve but the heating
the oil separator has warmed up.
rod must be energized.
A time delay of 15 minutes has been built
into the UNISAB before the solenoid valve If the compressor is cooled by means of cool-
in the oil returns opens. ing water, the water flow must always be

24 0171-487-EN
stopped during periods of standstill. stop valves and close off stop valve in oil
This is normally done by means of a solenoid return.
valve in the water inlet line to the compres-
S Shut off condenser cooling.
sor. Connect the solenoid valve to the start/
stop relay of the compressor motor. S Cut off power supply to master and control
currents.
Compressor start-up must always take place
at the lowest capacity stage, after which ca- S Inspect receiver, condenser and pressure
pacity is increased stepwise at suitable inter- vessels as well as piping connections and
vals, in order to avoid that a sudden exces- apparatus for leakage.
sive pressure reduction in the evaporation
system causes liquid hammering in the com- Automatic plants
pressor and oil foaming in the crankcase S Refrigeration plant should normally be put
housing. into operation as described in the Start-up
section. Once started, switch over to auto-
Stopping plant for brief periods matic operation.
(until 2-3 days) S Special instructions for automatic plant in
S Shut off liquid supply to evaporators for a question should be followed to the letter.
few minutes before stopping the plant.
S The following should be checked daily,
S Stop compressor and shut off suction and even on automatic plants:
discharge stop valves. Close valve in oil – Correct oil charging,
return.
– Automatic oil return,
S Stop condenser cooling, pumps, fans and
– Correct oil pressure,
any compressor cooling.
– Suction and condenser pressure,
S Cut off power supply to both master and discharge pipe temperature,
control currents.
– Correct setting of safety automatics.

Stopping plant for lengthy periods


Pressure testing refrigeration plant
(more than 2-3 days)
Before charging the plant with refrigerant, it
S Shut off main valve in liquid pipe and must be pressure tested and pumped down.
pump-down evaporators. If necessary, ad-
just the UNISAB II Control to a lower suc- Pressure test the plant with one of the follow-
tion pressure during pump-down. ing:

S Dry air - pressurized cylinders containing


S Allow temperature in evaporators to rise,
dry atmospheric air may be used - but
then repeat pump-down.
never oxygen cylinders;
S When suction pressure has been reduced
S Air compressor for high pressure;
to slightly over atmospheric, stop com-
pressor. Shut off suction and discharge S Nitrogen.

0171-487-EN 25
maintain this pressure throughout the
Important
period.
The plant compressors must not be
used to pressurize the plant. During the tightness test, it is permitted to
enter the room and approach the plant.
Water or other fluids must not be used
for pressure testing. S By way of a second tightness test, ex-
amine all welds, flange joints etc. for leak-
If nitrogen is used, it is important to place a age by applying soapy water, while main-
reducing valve with a pressure gauge be- taining the 10 bar pressure.
tween the nitrogen cylinder and the plant. When pressure testing, compile a pressure
test report containing the following:
During pressure testing, it is important to en-
sure that pressure transducers and other S date of pressure testing,
control equipment are not exposed to the
testing pressure. The compressor stop S person carrying out the test,
valves must also be closed during pressure S comments.
testing, becurse the compressors are factory
tested.
Pumping down refrigeration plant
Plant safety valves must normally be blanked Following pressure testing, the refrigeration
off during pressure testing, as their opening plant must be pumped down in order to elimi-
pressure is lower than the testing pressure. nate atmospheric air and moisture.

Important The boiling point of a fluid is defined as the


temperature at which the steam pressure
During this pressure testing, no person
equals atmospheric pressure. For water, the
should be allowed to be present in
boiling point is 100°C. Lowering the pressure
rooms housing plant parts or in the vicin-
ity of the plant outside the rooms. also lowers the boiling point of the water.

The table sets out the boiling point of water


S The entire unit must be pressure tested in at very low pressures:
accordance with the local regulations for
pressure testing. Boiling point of At pressure
water °C mm HG
S If it is required that the compressor should
5 6.63
be pressure tested together with the unit
or with the plant, the testing pressure must 10 9.14
not exceed: 15 12.73
For reciprocating compressors HPC/HPO: 20 17.80
HP side: 40 bar
LP side: 22 bar For evacuation, use a vacuum pump which
bleeds the plant of air and steam.
S Afterwards, reduce pressure to 10 bar for
a period of 24 hours - as an initial tight- The vacuum pump must be able to lower the
ness test - as a tightly sealed plant will pressure to approx. 0.1 mm Hg (mercury col-

26 0171-487-EN
umn) and must be fitted with a gas ballast It is recommended to carry out pump-down
valve. This valve should be used wherever as follows:
possible to prevent water vapours condens-
S Pump-down to a pressure lower than 5
ing in the vacuum pump.
mm Hg.

Important S Blow dry air or nitrogen into system to a


pressure corresponding to atmospheric.
Never use the refrigeration compressor
Never use OXYGEN cylinders.
for pump-down of the plant.
S Repeat pump-down to reduce pressure to
less than 5 mm Hg.
For a satisfactorily performed pump-down,
the final pressure must be lower than 5 mm S Shut the vacuum pump off from refrigera-
Hg. Attention is drawn to the fact that there tion plant and check that the pressure
may be a risk of any water left in the refriger- does not rise for the next couple of hours.
ation plant freezing if ambient temperatures If the system still contains water, this will
are lower than 10°C. In such instances, it will evaporate and cause the pressure to rise,
be necessary to supply heat to the compo- thereby indicating unsatisfactory pump-
nent surroundings, as ice evaporates with down and necessitating a repetition of the
difficulty. procedure.

0171-487-EN 27
Operating log This operating log should be kept at regular
intervals, thus providing important informa-
In order to keep tabs on the operating state
tion about the cause of any undesired
of the refrigeration plant, it is recommended
changes in the operating state.
that an operating log be kept.

Observation Measuring point Measurement unit

Time Date and time


Suction pressure • UNISAB II Control °C or bar

Discharge pressure • UNISAB II Control °C or bar

Oil pressure • UNISAB IIControl bar

Oil temperature • UNISAB II Control °C

Suction gas temp. • UNISAB II Control °C

Discharge gas temp. • UNISAB II Control °C

Oil level in • Oil level sight glass Must be visible in oil


compressor in compressor sight glass

Recharding of oil on • See section on oil Number of litres


compressor charging

Compressor motor • Electrical panel Amps


consumption in amps.
• UNISAB II Control

At the same time, attention should be paid to the following:


(tick these off in the log, if you wish)
S Whether the compressor’s cooling system is functioning correctly,
S Whether any unusual noise is coming from the compressor,
S

28 0171-487-EN
Servicing the reciprocating compressor
HPO Ć HPC

In order to ensure problem-free operation, it S Immediately after stopping compressor,


is advisable to carry out regular servicing to read off pressure on discharge and suc-
the refrigeration plant. In this section, tion side of compressor.
SABROE indicates some periodic services
S Close discharge stop valve quickly and,
fixed on the basis of the number of operating
from moment of closure, time how long it
hours from the first start-up or after total ren-
takes for pressure to drop on high pres-
ovation of the compressor.
sure side of compressor. Normally, the
The compressor must always operate within pressure drop should not be more than
the speed recommended by SABROE. 3 bar over a period of 5 minutes or so.
See Description of compressor. Providing the
If the pressure falls more quickly, this is
compressor operates within the specified
due to internal leakage, which may occur:
pressures and temperatures and the pre-
99.05

scribed periodic services are performed, the S Where pressure valve ring plates are in
compressor will have a long and efficient ser- bad contact with their seats (Pos. 20C
vice life.
0171-492-EN

against Pos. 20A and 19H).


The following must therefore be checked S With defective seal Pos. 19T. (not HPO).
daily:
S With defective seal Pos. 19K.
Operating pressure,
Operating temperatures, S Because cylinder lining and top cover
Oil level and pressure, have been tightened without long mount-
Abnormal noise and vibrations. ing stopper having been fitted. Cylinder
lining is thus resting on rocker arms, Pos.
The actual operating conditions should be 15A. (not HPO).
entered in an operating log daily.
See the Operating log section. S On safety valve, because valve cone does
not fit tightly against seat, or outer
Pressure drop test O-ring Pos. 24B or inner O-ring Pos. 24C
is defective. (See Safety valve section.)
Using the pressure drop test, it is possible to
check the internal tightness of the compres- During pressure drop testing, pay attention to
sor from discharge to suction side. The pres- any piping connections to the discharge side
sure drop test is performed with the compres- of the compressor, which may have an influ-
sor at standstill, as described below: ence on the test result.

0178-225-EN 29
Removing refrigerant from Connect the purge valve Pos. 42 to a sealed,
compressor empty vessel which in turn is connected to an
open tank containing water.
Before the compressor can be dismantled,
the refrigerant must be removed from the The water will absorb the refrigerant, which
compressor, which can be done in the follow- can then be dispatched for proper destruc-
ing ways: tion. The moment the pressure is equalized,
the valve must be reclosed in order to pre-
1. Run compressor at lowest capacity stage
vent water being sucked back into the com-
and throttle suction stop valve slowly until
pressor.
completely closed.
Note
2. The compressor will then stop on the UNI-
The following instructions apply to the
SAB II Control; this can be adjusted to
compressor only. Servicing of the refrig-
stop compressor at a pressure lower than
eration plant is described in a separate
normal.
section. Service the compressor motor ac-
3. Close discharge stop valve and other pip- cording to your own instructions. For the
ing connections to compressor. various scheduled services, SABROE can
supply ready-made spare-part sets, which
it would be an advantage to have before
42
carrying out the scheduled service.

In the event that the compressor cannot op-


Water erate, start evacuation as described under pt.
3, and remember also to close the suction
stop valve.

30 0178-225-EN
Scheduled services

No. Operating Activity


hours

1.1 Remove filter bag in suction filter and discard.


Clean suction filter. Following major repair work or
1 50 in event of severe soiling of filter bag, it is recom-
mended that a new filter bag be fitted for another
period of 50 operating hours.

2.1 Check or change oil. When changing oil, change oil


filter cartridge, too. See following section:
Assessing the oil.
2.2 Clean suction filter.
2.3 Check that following function correctly:
Solenoid valves
Compressor cooling
2 200 Safety automatics
Heating rod
2.4 Retighten external piping connections.
2.5 Check oil return system from oil separator.
2.6 Retighten coupling.

3.1 Check or change oil. When changing oil, change


oil filter cartridge, too. See following section:
Assessing the oil.
3.2 Clean suction filter.
3.3 Check that following function correctly:
Solenoid valves
Compressor cooling
Safety automaitcs
Heating rod
3 5000 Oil return system from oil separator.
Valve seats
Cylinder linings
Pistons, gudgeon pins and gudgeon pin bearings
Piston and oil scraper rings
Suction and discharge valve ring plates
3.4 Finish off with a pressure drop test.

0178-225-EN 31
No. Operating Activity
hours

4.1 Check or change oil. When changing oil, change oil


filter cartridge, too. See following section: Assessing
the oil.
4.2 Clean suction filter.
4.3 Check following:
Solenoid valves
Water cooling system for any deposits and clogging
Safety automatics
Heating rod
Coupling and alignment
Oil return system from oil separator
4 10000
Valve seats
Cylinder linings
Pistons, gudgeon pins and gudgeon pin bearings
Piston and oil scraper rings
Relief mechanism
Seal for tightness

4.4 Change suction and discharge valve ring plates


4.5 Finish off with a pressure drop test.

5.1 Check following:


Valve seats
Cylinder linings
5 15000
Pistons, gudgeon pins and gudgeon pin bearings
Piston and oil scraper rings.
Suction and discharge valve ring plates.

32 0178-225-EN
No. Operating Activity
Hours

6.1 Change compressor oil,


Change oil filter cartridge,
Clean crankcase.
6.2 Clean suction filter.
6.3 Check following:
Solenoid valves
Water cooling system for any deposits and clogging
Safety automatics
6 20000 Heating rod
Coupling and alignment
Valve seats
Cylinder linings
Pistons, gudgeon pins and gudgeon pin bearings
Piston and oil scraper rings
Unloader mechanism
Seal for tightness
Oil pump and drive
Stop valves.
Main valve
6.4 Change:
Suction and discharge valve ring plates
Half section of bearings for connecting rod or
connecting rods (HPO)
6.5 Finish off with a pressure drop test.

7 25000 As for service no. 5


8 30000 As for service no. 4

9 35000 As for service no. 3

10 40000 Major overhaul; contact SABROE Refrigeration

Then repeat scheduled services from no. 3 inclusive.

0178-225-EN 33
Lubricating oil
Lubricating oil requirements used for a single, or at most, two top-ups.
Above all, the refrigerator oil must provide The oil containers must be kept carefully
satisfactory lubrication of the compressor, sealed. If all the oil in a container is not used
even at the relatively high temperatures oc- in one go, the container should be tightly
curring during compression. It must be inca- sealed and stored in a warm place to prevent
pable of coking at such high temperatures the absorption of moisture.
and must not precipitate solid constituents
Note
such as paraffin or wax at the lowest occur-
It is inadvisable to reuse oil which has
ring temperatures. The oil must not have any
been drawn from a compressor or plant.
corrosive effect, whether alone or mixed with
This oil will have absorbed moisture from
refrigerant. The oils recommended by SA-
the air and may cause operating prob-
BROE meet these conditions. See section on
lems. Always switch off the power to the
Choice of lubricating oils.
heating rod before drawing off the oil.

General rules for use of lubricating If, after reading the above, any doubt exists
oil in refrigeration compressors as to the type of oil which has been used on
your compressor, you are recommended to
S Only fresh, clean refrigeration machine oil
contact SABROE, rather than risk charging
may be charged. Oil tapped from the
with unsuitable oil.
evaporator system in an ammonia plant
must not be reused in the compressor.

S Use grade of oil originally prescribed for


Instructions for choosing
compressor. lubricating oil for refrigeration
compressors
S As far as possible, avoid mixing different
types of oil. Mixed oil is generally inferior The instructions in Choice of lubricating oils
to the two original oils. Mixing various offer more detailed guidelines for choosing
types of oil may give rise to formation of the lubricating oil best suited to each individ-
sludge, which will lodge in valves and fil- ual case on the basis of the anticipated oper-
ters. ating conditions.

S If necessary to switch to another brand of


oil, this must be done, at the same time as Charging refrigeration compressor
completely changing the oil in the com- with lubricating oil
pressor and tapping off all oil from the re-
Since all SABROE piston compressors are
frigeration plant.
supplied with a special oil charging valve on
S The refrigeration oil must be free of mois- the crankcase, refrigeration oil may be
ture, which may give rise to operating mal- topped up while the compressor is in opera-
functions and attacks of corrosion. tion.

The oil should therefore be purchased in con- For this purpose, use a manual oil pump or
tainers corresponding to the quantity to be adopt the following procedure:

34 0178-225-EN
Note throttling suction stop valve while com-
When charging for the first time, use the pressor is running at its lowest capacity
oil pump; it goes without saying that the stage. Alternatively, raise to slightly above
compressor must not be started unless atmospheric pressure by stopping com-
already charged with oil. pressor and closing suction stop valve.
Pressure in crankcase will then rise gradu-
S Reduce pressure in crankcase, e.g. by
ally.
throttling suction stop valve, until suction
pressure gauge shows pressure slightly S Oil in the crankcase can then be forced
below atmospheric. out through drain valve Pos. 23 when
S Fill pipe connected to oil charging valve compressor is at a standstill.
with refrigerator oil and insert free end of S Equalize pressure in compressor to atmo-
pipe down into a receptacle containing spheric through purge valve pos. 42. See
fresh refrigerator oil. section on Environmental protection.
S Open oil charging valve carefully, thereby
causing external air pressure to force oil S Dismantle side covers.
into crankcase. S Replace oil filter cartridge with a new one.
S Avoid getting air or other impurities
S Clean crankcase thoroughly, wiping with a
sucked into compressor.
clean, dry linen cloth (not cotton waste).
Note
In order to achieve pressure below atmo- S Reassemble side covers.
spheric, it will sometimes be necessary to
S Charge to correct level with fresh, clean
reset the low-pressure cut-out so that the
refrigeration oil according to SABROE’s oil
compressor can aspirate down to this
recommendations.
pressure. Remember to reset the pressure
cut-out to its normal setting after charging S Connect heating cartridge.
with oil.
S Connect vacuum pump to compressor and
When in operation, the compressor may be pump down to 5-7 mm Hg; close off con-
refilled with oil using the manual oil pump. nection.
After the plant has been started for the first
Then open suction stop valve a few turns,
time, you should for a while keep an extra
filling compressor with refrigerant gas. In
sharp eye on the oil level in the compressor.
the case of R717, it will suffice to blast the
compressor through by carefully opening
Changing oil in refrigeration suction stop valve while purge valve Pos.
compressor 42 is open. See section on Environmental
S Cut off power to heating rod. protection, however. When smelling R717,
close purge valve.
S Close compressor stop valves and valve
in oil return line from oil separator. S Open discharge stop valve and valve in oil
return line; compressor is then ready for
S Reduce pressure in compressor crank- start-up as described in section
case to slightly above atmospheric by General operating instructions.

0178-225-EN 35
Charging compressor with oil The oil level must always be visible in the
oil level sight glass. The below table illus-
Compressor Volume of oil
trates, how many litres of oil a drop in the
Type Size in crankcase
oil level of 10 mm is approximately equal
Litres
to.
3 1,5
BFO 4 4
5 5

HPO 24 14
CMO 26 16
TCMO 28 18
4 13

HPC 104 26
SMC 100 106 28
TSMC 100 108 30
Mk 3 112 47 T0177162_0

116 50

SMC 180 186 80


188 90 Compressor 10 millimeter
TSMC 180 difference in
type size oil levels equals
The volume of oil stated in the table is the HPO/ 24
CMO/ 26 ~1 litre of oil
amount which must always be present in the 28
TCMO
crankcase.
HPC/
104
As a rule, the compressor should be charged SMC / 106 ~2 litres of oil
TSMC 108
with oil after the plant is started for the first
time, as some of the oil – especially on an 100 112
S-L-E 116 ~6 litres of oil
HCFC installation – will be absorbed by the
refrigerant in the plant. SMC /
TSMC 186
188 ~6 litres of oil
The following determinants decide the total 180
volume of oil a refrigeration plant should con-
tain:
Assessing the oil
S type of refrigerant Refrigeration machine oil is a vital part of the
compressor, as it not only lubricates and
S refrigerant charge (volume)
cools the movable parts of the compressor, it
S size of plant also prevents abrasive particles from en-
tering the bearings.
S temperature range in which refrigeration
plant is to operate. An analysis of the oil can give important in-
formation on how the compressor is running.
The oil level must be checked with extreme We would, therefore, advise that the oil anal-
care, particularly when starting and charging yses be carried out at the intervals prescri-
with refrigerant. bed.

36 0178-225-EN
An oil sample must be drawn off while the cess pressure in the bottle with subsequent
compressor is in operation, which gives a risks of explosion. Never fill a bottle up com-
representative sample. Before taking the pletely. Do not send glass bottles through
sample, clean the drain valve and tap a little the postal service – use purpose-made plas-
oil off, to prevent any impurities which may tic bottles. Please see below.
have accumulated in the valve or the piping
from mixing with the sample. Analytical evaluation
Naturally, the oil sample can be analysed by
Visual assessment the oil company that supplies the oil.
If you pour the sample into a clean, transpar-
As a special offer to our customers
ent glass bottle or a test-tube and hold it up
SABROE has developed an analytical con-
to a clear light source, it will be easy to as-
cept, in cooperation with Mobil Oil, which
sess the quality. You can also compare the
is able to analyse all oil makes. This will
sample with the fresh oil of the same make
mean a uniform reporting of the results.
and grade.
The analysis allows the following to be deter-
An oil which you approve on the grounds of a
mined:
visual assessment must:
S Whether or not the oil is still usable, if nec-
S be clear and shiny essary after filtering.
S not contain any visible particles S Whether solid particles possibly present in
S feel viscous, smooth and greasy when a the oil originate from the bearings or other
drop is rubbed between two fingers. components exposed to wear and tear in
which case the compressor must be in-
If you don’t feel that you can approve the oil spected.
by visual assessment, charge with new oil or
S Each report will include the corresponding
send a sample to a laboratory for analysis.
measuring results from the previous 3 oil
If the oil sample is poured into a glass bottle, analyses. In this way you will be able to
this must not be hermetically sealed until all follow up on the state of both the oil and
the refrigerant in the oil sample has evapo- the compressor from one analysis to the
rated. Refrigerant in the oil may produce ex- next.

0178-225-EN 37
Procedure
S A form set with a plastic sampling bottle which the addresses of the laboratory in
and a dispatching envelope can be re- Holland are also mentioned.
quested from the local Sabroe Refrigera-
tion representation. The analysis
The following section states some average
S The oil sample must be drained from the values that can be applied in practice. How-
cleaned oil drain valve into the sample ever, you should be on the alert whenever
bottle. Screw the lid loosely on and let the the results of the analyses approach these
bottle stand for a few hours to enable re- values. In some cases the water content of
frigerant contained in the oil sample to 100 ppm in HCFC plants may be too much
evaporate before sending it to the labora- and thus lead to Cu–plating in the shaft seal.
tory. Similarly, a rise in the oil viscosity of max.
65% normally does not cause any operating
S Please follow the Sampling and Shipping problems as the refrigerant reduces the oil
Instructions enclosed in the form set in viscosity in the plant.

Limiting values
Sabroe Oil PAO 68 Sabroe Oil AP 68 Sabroe Oil A 100
Parameter Unit Method Target Target Target
Spec. Max. Min. Spec. Max. Min. Spec. Max. Min.
Viscosity @ 40°C cSt ASTM D 445 66 76 53 64 74 51 100 115 80
TAN *1) mg KOH/g ASTM D 664 0.03 0.2 – 0.01 0.2 – 0.05 0.2 –
SAN * 2) mg KOH/g ASTM D 665 – 0 – – 0 – – 0 –
Water ppm Karl Fisher – 100 – – 100 – – 100 –
Appearance – – report report report
Colour – ASTM D report report report
1500
Pentane Insolubles W% MM 490 – 0.05 – 0.05 – – 0.05 –
(5mm)
Oxidation abs/cm IR,1700-1720 – 5 – – 5 – – 5 –
/cm
Nitration abs/cm IR,1627-1637 – 5 – – 5 – – 5 –
/cm
Nitro Compounds abs/cm IR,1547-1557 – 0.5 – – 0.5 – – 0.5 –
/cm

Maximum values for metal content in the oil

Lead ppm ICP – 10 – – 10 – – 10 –


Copper ppm ICP – 10 – – 10 – – 10 –
Silicium ppm ICP – 25 – – 25 – – 25 –
Iron ppm ICP – 100 – – 100 – – 100 –
Chromium ppm ICP – 5 – – 5 – – 5 –
Aluminium ppm ICP – 10 – – 10 – – 10 –
Tin ppm ICP – 10 – – 10 – – 10 –

1): TAN (Total Acid Number) is only reported for non-ammonia- 2): SAN (Strong Acid Number) is only reported for non-ammo-
applications nia-applications

38 0178-225-EN
A report is drawn up for every sample re- through a 3 micron filter and back to the
ceived. This report indicates: unit. The system must be completely
closed, to prevent the oil being affected by
S Whether the oil can still be used – without moisture in the air.
taking any further action.
S Whether the oil is no longer fit for use.
S Whether the oil can be used after it has
been filtered through a very fine filter. The report will always be sent to the address
stated on the sample label included in the
If this is necessary, the oil must be form set. A copy will be sent to SABROE Re-
pumped directly from the compressor unit frigeration, so that we are in a position to ad-
vise you, if required.

0178-225-EN 39
Maintenance of reciprocating compressor
HPC

General Once the pressure is down to approx. 0.1


bar, stop the compressor and perform the
When the compressor requires maintenance,
following steps in the order specified:
it is important to follow the instructions given
below. In order to make sure that the com- S Close suction stop valve.
pressor is working correctly, the gauge mea-
S Cut off power to compressor motor.
surements and screw torques must be strictly
S Close discharge stop valve.
adhered to.
S Draw off last remains of refrigerant gas
Before opening the compressor, it is expedi- through purge valve Pos. 42.
ent to ensure that you have spares of those
S Having ensured that power to compressor
seals and gaskets to be stripped down or dis-
motor cannot be inadvertently connected,
mantled. An O-ring which has been exposed
compressor is ready for opening.
to oil and heat for any length of time may

98.05
have expanded so much as to prevent it from S Remove any fuses.
being refitted.

0171-493-EN
All gaskets used are resistant to oil, HFC/
2. If the compressor is inoperative
HCFC and ammonia. S Leave heating rod in crankcase connected
All O-rings are made of neoprene rubber. for a couple of hours before the compres-
sor is due to be opened in order to heat up
Pump-down oil. Warm oil does not contain as much
Before opening up the compressor for in- refrigerant.
spection, the pressure inside must be low- S Suction stop valve must be open while
ered to slightly above atmospheric. This can heating rod is connected.
be done in the following way, depending on
S Keep discharge stop valve closed.
whether the compressor is operational or de-
fective. S Close suction stop valve and disconnect
heating rod.

1. If the compressor is operational S Equalize pressure in compressor through


purge valve Pos. 42.
Run the compressor at minimum capacity at
normal operating temperature. S Once pressure has been equalized to at-
mospheric, compressor is ready for
UNISAB II Control must be adjusted to stop
opening. Remember to make sure that
the compressor at a suction pressure of 0.1
bar. power cannot be inadvertently connected,
thereby starting the motor.
Throttle the suction stop valve very slowly.
Keep an eye on the suction pressure gauge. S Remove any fuses.

40 0171-487-EN
Dismantling and assembly After dismantling the two bolts - unscrewing
them alternately - the top cover can be re-
The following sections describe the individual
moved.
components. When dismantling and assem-
bling, parts should generally be fitted in the
same position from which they were taken, Fitting top cover
and should therefore be marked as they are Before fitting the top cover, the long plug
removed. Further they should be thoroughly must be fitted into the relief cylinder. Check,
cleaned, checked and lubricated prior to be- in addition, that the gasket Pos. 2C is intact
ing reassembled. and, if necessary, check that the clearance
volume and lifting reserve have been ad-
justed as described later on in these instruc-
Top covers tions.

Dismantling top cover If the gasket Pos. 2C needs to be replaced at


Before dismantling the top cover, the relief all, the graphitized side must face the com-
mechanism must be deactivated; this is pressor frame. After placing the top cover
done by dismantling the short plug Pos. 12D loosely on top of the springs Pos. 21, it is
and mounting the long plug from the tool kit recommended that all screws be mounted by
instead. This moves the piston Pos. 12B to hand, as they will jointly guide the top cover
the opposite end of the relief cylinder. into position. Now tighten the top cover firmly
with the two screws mentioned above, then
Loosen and remove screws Pos. 2E, except with the remaining ones.
for the two screws shown on the drawing.
Finally, cross-tighten all the screws to the
prescribed torque in the following sequence:

7 1 3 5 9
11
15 13
16 14
12 10
8 4 2 6

These screws should be loosened approx. 1


mm, then checking that the cover lifts off the
gasket. If, to the contrary, it remains fastened
to the gasket, loosen it with a blow on the Once the top cover has been fitted, remove
side from a soft hammer while keeping the the long plug and insert the short plug. The
two screws fitted. This because of the pow- top covers must be mounted as shown in the
erful spring pressure beneath the top cover. following chart.

0171-487-EN 41
Mounting top and water covers

HPC 104S HPC 106S HPC 108S Control end

Shaft end
SABROE

Shaft end
SABROE Water covers
SABROE

Right top covers


SABROE
SABROE
SABROE
SABROE

Left top covers

SABROE SABROE SABROE SABROE

Side covers

T0177092_0

42 0171-487-EN
Discharge valve

21

20E
20F

20D
Pos. 20

20B 20A 20C 20G

As shown in the drawing, the function of the Identification:


discharge valve Pos. 20 is partly to allow the HPC compressors use discharge valves
compressed gas to pass from the compres- marked with 2 valves and stamped with HP
sion chamber of the cylinder to the discharge as shown on the drawing.
chamber beneath the top covers and partly to
create a seal from the discharge chamber to
Marked with
the cylinder. HP

Furthermore, the discharge valve acts as a


safety device in the event of liquid refrigerant
passing the valve together with the discharge
gas, also called liquid stroke. Such stroke
should normally not occur, as liquid cannot
Marked with
pass the valve as quickly as the compression
2 grooves
gas. This produces a violent increase in pres-
sure in the compression chamber.
Dismantling
In order to avoid pressure of such intensity S When the top cover has been removed,
as to damage the bearings in the compress- spring Pos. 21 and discharge valve Pos.
or, the discharge valve is retained in position 20 can be lifted out by hand.
by the safety spring Pos. 21, which allows it S Tighten discharge valve in a soft-jawed
to lift a little bit under the strain of increased vice, then dismantle two nuts Pos. 20E
pressure. together with spring guide Pos. 20F.

S Bolt Pos. 20D, discharge valve seat Pos.


Liquid strokes are heard as a distinct
20A and ring plate Pos. 20 can now be
hammering in the compressor; the cause
disassembled by hand.
must be found immediately and the mal-
function rectified. S Remove valve springs Pos. 20G by hand.

0171-487-EN 43
Assembling able intervals to replace the suction and dis-
Before assembling the discharge valve, you charge valve ring plates.
must make sure that the valve springs Pos.
20G are in good order and properly fitted in It is difficult to give altogether precise times
their apertures. for such replacements, as the durability of
the valve ring plates depends on the follow-
Assemble the discharge valve in reverse se-
ing factors:
quence to that described above. Note the fol-
lowing, however:
S If the compressor is exposed to liquid
S Tighten bottom nut Pos. 20E to torque of stroke or humid refrigerant gas, the ser-
10.2 Kpm ≅ 100 Nm. vice life is reduced.
If need be, exert counterpressure with 5
mm Allen key on bolt head. S Number of revolutions of the
compressor:
S Fit spring guide Pos. 20F and tighten top
Ved 900 o/min. er ventilringpladernes le-
nut to same torque: 10.2 Kpm ≅ 100 Nm.
vetid betydeligt længere end ved 1500
Testing the sealing tightness of the dis- o/min.
charge valve
This is done by means of the pressure drop S The compression ratio at which the
test as described elsewhere in this instruction compressor operates:
manual. At high compression ratios, the load on
valve ring plates and springs is appreci-
Service life of discharge and ably larger than at low compression ratios.
suction valves When the valve ring plates are changed,
In order to ensure that the compressor al- the valve springspos. 20 should also be
ways works perfectly, it is advisable at suit- replaced.

44 0171-487-EN
Cylinder lining with suction valve 19H and ring plate Pos. 19F to be removed
from the cylinder lining. The paper gasket
Marking of suction valve stop:
Pos. 19T can be expected to disintegrate
during dismantling and require replacement.

Mounting suction valve


Before reassembling the suction valve, you
must ensure that the valve springs Pos. 19G
are in good order and properly fitted in their
apertures.
Marked with
2 grooves
Perform the assembly in reverse sequence to
that described above. Note the following,
however:
T0177131_0 v3
S Change paper gasket pos. 19T.
The cylinder lining and suction valve form an S Before tautening screws 19N, ensure suc-
integral unit which can be dismantled by re- tion valve plate can be moved freely in its
moving the screws 19N. guide. Tighten screws Pos. 19N to torque
of 1.4 Kpm ≅ 14 Nm.
To access the cylinder lining or suction valve,
the top cover, spring Pos. 21, and pressure Inserting cylinder lining
valve Pos. 20 need to be disassembled. S Rotate crankshaft to position piston at top
dead centre.
Extracting cylinder lining
S Rotate crankshaft to position relevant pis- S Check that long plug from tool kit is
ton at top dead centre. screwed into relief cylinder; see Top cov-
ers section.
S Fit the two T-shape extractors Pos. 3 from
S Check that gasket Pos. 19K is in position
tool kit into threaded holes in guide ring
on frame.
Pos. 19J.
S Lubricate piston, piston rings and cylinder
S Carefully pull out cylinder lining with suc- face with clean refrigeration machine oil.
tion valve, checking that gasket Pos. 19K
remains in frame. S Rotate piston rings on piston so as to
stagger ring gaps at 120° to each other.
S Insert protective plate Pos. 5 (from tool kit) Press cylinder lining down over piston
between piston and frame so the piston carefully. The chamfering on the cylinder
can rest on it. This will enable piston and interior will catch the piston rings and
piston rings to slide onto the protective squeeze them to the diameter of the cylin-
plate without being damaged when the der. If possible, fit cylinder in same place
crankshaft is turned. from which it was taken.

Dismantling suction valve S Press cylinder lining down manually, and


Dismantling the screws Pos. 19N enables the with no rotary movements, until it makes
guide ring Pos. 19J, suction valve stop Pos. contact with gasket Pos. 19K.

0171-487-EN 45
S Check clearance volume, which is de- S Remove nuts pos. 17D, then take out the
scribed in section Control measurements lower part of the connecting rod by hand.
for insertion of new cylinder lining.
S Now take out piston and connecting rod
S Pressure valve Pos. 20 and safety head through the top cover opening of the
spring Pos. 21 can then be fitted. frame.
S Fit gasket pos. 2C, and top cover.
The connecting rod Pos. 17 is equipped with
S When the top cover is secured - see sec- independent bearings at both ends. The big
tion on Top covers - remove the long end is fitted with two bearing half bushes
threaded plug and screw in the short plug Pos. 17A, consisting of a half-cylindrical steel
after the aluminium gasket pos. 12E has plate internally coated with white metal.
been checked and found applicable. These bearing half bushes are secured in the
connecting rod, partly through their fit in the
Connecting rod connecting rod bore and partly by a spring
which fits into a milled groove in the connect-
The connecting rod pos. 17 is made of two
ing rod. The opposite end of the connecting
parts carefully adapted to each other.
rod is fitted with the gudgeon pin bearing
The two parts are held together by means of
Pos. 17B.
two bolts secured with lock nuts.
The bearing bushing Pos. 17B-1 is made of
Procedure for removing piston and con-
special bronze and is also used in R717
necting rod
compressors.
This section gives a brief description of the
individual tasks with refererence to the rele- If the bearings in the connecting rod are worn
vant section. so that the clearance is greater than that pre-
S Empty compressor of oil and refrigerant scribed in the table entitled Various clear-
and safeguard against unintended start- ances and adjustment measurements, they
up. must be replaced with new bearings. In this
connection, note that undersized half sec-
S Dismantle water hoses for top and side
tions of bearing can be supplied for use in
covers.
the crankshaft where the journals have been
S Dismantle top and side covers. ground to a corresponding undersize.
S Take out spring pos. 21, discharge valve See table in section on Diameters for under-
and cylinder liner. sized bearings.

46 0171-487-EN
Mounting of bearings position on crankshaft manually. Take care
Using a vice or hydraulic press, the bearing so that connecting rod bolts do not leave
bushing can be pressed out of or into the marks in crankshaft journals.
connecting rod.
S Position connecting rod interior through
Use soft jaws in the vice and use tools that
lateral opening on frame, and fit nuts.
do not damage any parts. Mount the bearing
bushing as shown in fig. 1 with the lubricating Note:
channels facing sideways. The two parts of the connecting rod are
numbered with the same number; this is
Fig. 1 only of importance when assembling.
Note:
Parts with different numbers must not be
Sleeve to be
fitted with lubri- assembled and it is important that the
cating ducts numbers are fitted in the same direction
positioned as as shown in Fig. 2.
shown on dra-
wing.
Fig. 2
Note:
T0177131_0 v2,a Stamped number on
the same side on as-
Fitting connecting rod sembly
Before fitting the connecting rod in the com-
pressor stand, piston and piston rings must
be fitted onto the connecting rod. See the fol- 916 916
lowing sections. In addition, the two connect-
ing rod bolts Pos. 17C must be fitted as
shown in the spare parts drawing. T0177131_0 v2,b

S Fit bearing bushes into both parts of con-


S Tighten nuts Pos. 17D alternately with in-
necting rod.
creasing torque and finish off with torque
S Introduce connecting rod down through wrench.
top cover opening in frame and guide into Torque: 4.4 Kpm ≅ 43 Nm.

0171-487-EN 47
Piston Assembling and stripping down
The piston is made of aluminium and fitted
piston and connecting rod
with two piston rings, nearest the piston top, Adopt the following procedure when assem-
and an oil scraper ring. bling piston and connecting rod:

S Fit one of the circlips rings pos. 18D into


bore for piston pin.
Fitting piston rings in piston
Before mounting the piston rings in the pis- S Heat the piston without piston pin to
ton, their fit in the cylinder lining should be approx. 70°C in oil or on a hot plate.
checked by measuring the ring gap. See sec- S Position connecting rod with inserted pis-
tion entitled Various clearances and adjust- ton pin bearing in the heated piston. The
ment measurements. piston pin can now be positioned without
the use of tools.
With your fingers or by means of a piston
S Fit the other circlip.
ring rod the piston rods can be extended ex-
actly so much that they can be pulled down Dismantling takes place in the reverse order.
over the piston to the groove. Start by fitting However, do not heat up the piston but press
oil scraper ring pos. 18C. out the piston pin by means of a punch.

48 0171-487-EN
Shaft seal

5,5 mm
8C
8H
2 mm
8A
8F

10F
10D
10E
10H
10J
10A
10G
10B
8G
8B

3126-176-R T0177131_0 V13

The purpose of the shaft seal is to create a It is recommended to exercise great care
tight seal along the crankshaft between the with the lapped slide surfaces. Even the
inside of the compressor and the atmo- slightest scratch or other damage to the slide
sphere. surfaces will result in leaks.

It comprises a slide ring Pos. 10E, manufac- The O-ring Pos. 10D creates a seal between
tured from special-purpose cast iron, which is the slide ring Pos. 10E and the crankshaft.
secured to the crankshaft by means of the TheO-ring Pos. 10G seals between the car-
locking ring Pos. 10H, tightening flange Pos. bon slide ring Pos. 10F and the shaft seal
10A and the four screws Pos. 10J with spring cover Pos. 8A.
washers Pos. 10K.

The carbon slide ring Pos. 10F is pressed When the shaft seal is operating, a tiny
against the flat-machined, lapped slide ring at amount of oil drifts out between the slide
the end of Pos. 10E by a series of springs faces to lubricate them. An oil throw ring Pos.
Pos. 10B, and the carbon slide ring is pre- 8F has therefore been fitted to prevent this oil
vented from rotating by means of the reten- migrating along the axle to the transmission
tion pin Pos. 8H. linkage.

The spring pressure, combined with the The thrower ejects the oil into the groove in
flat-lapped faces of the two slide rings, ensur- the shaft seal cover Pos. 8A and the oil is
es an optimal seal between the faces, either piped via the plastic hose to a plastic bottle
when rotating or stationary. positioned under the compressor.

0171-487-EN 49
1. Dismantling and stripping down and springs pos. 10B (see
shaft seal fig. 2) can now be dismantled.
1.1. Once the gas pressure in the compres-
sor has been eliminated and the motor Fig. 3
safeguarded against unintended 8G 10F 10G 8A 8C
start-up, dismantle coupling or V-belt
disk.
• •
Note:
On units featuring coupling, there is no
need to move the motor, as the coupling •
and the shaft seal can be taken out be- •

tween the two shaft ends. A


1.2. Dismantle shaft seal cover Pos. 8A by
alternately loosening bolts Pos. 8C so
as to displace shaft seal cover out-
wards without jiggling. This will avoid 1.5. Dismantle slide ring Pos. 10E by tur-
damage to internal parts of the shaft ning four Allen screws Pos. 10J a max.
seal. of 2-3 turns; the entire unit can then be
1.3. Once the spring force is equalized and taken out with the fingers or using two
the bolts removed, the shaft seal cover screwdrivers inserted into the external
can be taken off the shaft end by hand. groove on the slide ring Pos. 10E and
Take care so that no damage is done to moved in the direction of the arrow as
the carbon slide ring Pos. 10F which illustrated in fig. 4.
comes out with it.
1.4. The carbon slide ring Pos. 10F can be Fig. 4
extracted by dismounting circlip pos.
8G as follows:
Mount tool no. 2 as illustrated in fig. 3 10A

and tighten screw A so that the carbon


slide ring does not touch the locking
ring.

Take care not to tighten screw A too •


much as this could damage the car-
bon ring.

Circlip pos. 8G is now easily extracted


1.6. The O-ring Pos. 10D can now be remo-
by means of a screw driver without ved.
damaging the slide surface of the car-
bon slide ring. Assembling and mounting shaft seal
After thoroughly cleaning the crankshaft,
After removing tool no. 2, the carbon check that its sealing faces are smooth and
slide ring pos. 10F, O-ring pos. 10G free of scratches, blows and wear marks.

50 0171-487-EN
Then oil the crankshaft and the shaft seal 3.4. Gently pressing shaft seal cover and
components thoroughly with the same type of carbon ring in against slide ring 10E
oil as used in the compressor. without compressing springs 10B,
measure distance from gasket 8B to
2. Unit with slide ring, Pos. 10E sealing face of shaft seal cover.
2.1. Before fitting slide ring Pos. 10E, tigh- This distance must be about 3 mm.
ten screws Pos. 10J until there is ap- Make sure the hose branch 8D faces
prox. 2 mm spacing and parallelism be- down.
tween the two flanges. Check also that 3.5. Mount screws 8C and tighten evenly,
locking ring Pos. 10H is mounted as crosswise. This will avoid damaging
shown in the drawing and O-ring Pos. the carbon slide ring. Tighten screws
10D 8C to prescribed torque according to
table in instruction manual.
2.2. Position slide ring Pos. 10E on shaft
and ensure tightening flange makes 3.6. Mount oil throw ring pos. 8F, as shown
contact with shaft shoulder. in drawing.
3.7. After mounting coupling half, it must be
2.3. Crosswise, tighten screws Pos. 10J al-
possible to turn the crankshaft easily by
ternately with Allen wrench from tool
hand.
kit. The torque is specified in the in-
struction manual. Crankshaft
2.4. Check axial position of shaft seal by The crankshaft is made of heat-treated SG
measuring distance from frame sealing
cast iron with fine strength and glide proper-
face to slide face on Pos. 10E. This
ties. The bearing journals are superfinished
must measure approx. 5.5 mm, as
and oil channels are bored for all lubricating
shown in the drawing.
points.
3. Unit with shaft seal cover
Pos. 8A At the centre and end of the crankshaft, the
3.1. Mount O-ring Pos. 10G, and the ten oil channels are blanked off with 3 blind plugs
spiral springs 10B in shaft seal cover on the HPC compressor. On mounting the
Pos. 8A, then position carbon slide ring crankshaft, it should be checked that the
Pos. 10F carefully. Rotate carbon slide plugs are properly fitted and tightened.
ring so slot fits in over retention pin
By way of bores in the counterweights, the
Pos. 8H.
crankshaft is dynamically balanced with re-
3.2. With tool no. 2 fitted as shown fig. 3
gard to 1st and 2nd order forces.
press carbon slide ring pos. 10G
against springs pos. 10B after that the Dismantling crankshaft
locking ring pos. 8G kan now be fitted.
Dismantle the crankshaft through the pump
Observe closely that the carbon slide
end of the frame in the following way:
ring is not overloaded by misbalanced
pressure and that its slide face is not S Bleed compressor of oil and refrigerant
damaged. and safeguard against unintended
3.3. Give complete shaft seal cover an extra start-up.
oiling on slide face of carbon slide ring
and guide it in over shaft together with S Dismantle top and side covers.
gasket 8B. S Dismantle all cylinder linings.

0171-487-EN 51
S Extract all pistons and connecting rods. dersize of 0.5 mm can be supplied as
S Pull off coupling half. stated in the parts list.
S Dismantle shaft seal cover and shaft seal. The drawing for grinding the crankshaft to
S Dismantle piping connections to UNISAB. undersize can be requested from SABROE.
S Dismantle end cover, Pos. 4A. Note:
S Dismantle oil filter. After grinding the crankshaft, all lubrica-
S Dismantle oil pump drive and oil pump. ting channels must be thoroughly
cleaned with an approved cleansing fluid
S Rotate crankshaft to place connecting rod and blasted with compressed air. Remem-
journals on horizontal level. ber to refit the blind plugs.

S Dismantle bearing cover at pump end and S Check sealing face for O-ring seal, Pos.
support the crankshaft by means of a 10D, on shaft seal. The surface must be
board inserted through the side openings. bright and free of scratches and marks.
S The crankshaft can now be pulled out of
Refitting crankshaft
the frame but it must still be supported.
Refit the crankshaft in the reverse order to
Inspection that for dismantling. Note the following, how-
S Check bearing journals on connecting ever:
rods for wear and tear and, if necessary,
S After the crankshaft has been inserted into
measure diameter of journals.
the frame, mount main bearing cover
The maximum wear on the bearings is Pos. 5A using gasket Pos. 5D as a shim.
shown in the section Various clearances
S Check end play of crankshaft by pressing
and adjustment measurements.
shaft up against pressure bearing Pos. 6C
In most instances, the permissible play in and measure the clearance at the other
the bearing can be obtained by replacing bearing, by means of sensor blades.
the bearing half bushes.
The permissible end play is seen from the
The bearing journals on the main bearings section Various clearances and adjust-
are normally subject to very little wear, but ment measurements.
should be check measured during main
overhauls. End play adjustment is achieved by
means of the gasket Pos. 5D.
If wear and tear exceeds the play stated,
the crankshaft can normally be ground to The gasket can be supplied in the follow-
0.5 mm undersize. ing thicknesses, as per the spare-parts
list:
For the ground crankshaft, main bearings
and connecting rod bearings with an un- 0.25 mm 0.50 mm 0.75 mm 1.0 mm

52 0171-487-EN
Main bearings On mounting the bushings it is recommended
The main bearings pos. 5C and 6C are to secure them with Loctite 601.
mounted on the main bearing covers and
their purpose is to guide the crankshaft both
When a new bearing bushing pos. 6C at the
radially and axially.
shaft seal end is put into place in cover pos.
They consist of a steel bushing with collar.
The collar and the inside of the bushing are 6A the in- and outlets of the lubricating chan-
provided with a thin white metal coating. nels must be positioned in a four o’clock
The bushing can be pressed out and re- position as illustrated on fig. 1 below.
placed by new ones and need no further The bearing bushing pos. 5C is positioned
machining after mounting. with in- and outlets in a 12 o’clock position.

Fig. 1
Mounting of bearing bushing pos. 6C

12 o’clock

4 o’clock

Cover pos. 6A seen from the inside of the compressor T0177167_0

The bearing bushings can be delivered with See Spare Parts List.
crankshafts ground to undersize.

0171-487-EN 53
Compressor lubricating system

19D
15D
19B
15A
15B 12
13

22

11 38A

33A

33

33J/K

T0177131_0 V10

The oil pump sucks oil from the crankcase, anticlockwise rotation lowers the pressure.
through the filter element Pos. 33A, past the Excess oil is returned through a bored chan-
magnetic filter located inside the filter ele- nel to the crankcase.
ment. The pump forces the oil through an in-
From the shaft seal housing, the oil is distrib-
ternal pipe Pos. 38A and on to the shaft seal
uted as follows:
housing.
S Through the hollow-bored crankshaft to
The filter element Pos. 33A is a disposable
lubricate main and connecting rod bear-
filter which cannot be cleaned. See descrip-
ings. Lubrication of piston pin bearings is
tion of oil filter.
done by splash lubrication through a coun-
The shaft seal housing forms a distribution tersunk hole in the top of the connecting
chamber for the oil. The oil pressure in the rod.
seal shaft housing is adjusted by means of
S To the UNISAB II Control for oil pressure
the oil pressure regulating valve Pos. 22,
indication.
which is mounted on the shaft seal housing.
The regulating valve can be adjusted from S Through external oil pipes, on to the regu-
the outside by means of a screwdriver. lating cylinders Pos. 12 for unloaded start
Clockwise rotation increases the pressure; and capacity regulation.

54 0171-487-EN
Oil pump

11H
11Q
11R
11G
11J
11E
11C
11F
11U
11B
11A

The oil pump is a gearwheel pump driven by S Strip oil pump down by dismantling re-
the crankshaft via a pinion drive. maining free screws. Cover and pump
It is therefore important to ensure that the housing are interconnected by means of 2
direction of rotation of the crankshaft is as guide pins and sealed with a 0.2 mm pa-
indicated by the arrow on the bearing cover per gasket.
Pos. 6A.
If the crankshaft is to turn in the opposite di- Note:
rection of rotation, the oil pump can be fitted The oil pump normally has a very long
with a chain drive. See next section. service life. Therefore, it is not worthwhile
Dismantling the oil pump repairing it. Rather replace it with a new
one.
Having bled the compressor of oil and refri-
gerant and secured it against inadvertent
start-up, proceed as follows:
Mounting the oil pump
S Dismantle end cover Pos. 4A and side Before finally tightening the oil pump firmly to
covers Pos. 3. the bearing cover, the following adjustment
must be made to the gearwheel drive:
S Dismantle internal oil pipes and nipples
screwed into pump. The minimum play between the two teeth
when engaged must be 0.05-0.08 mm, as
S Dismantle nut Pos. 11J and extract gear-
measured with a feeler gauge. Repeat the
wheel.
measurement six times, turning the crank-
S When the four M6 screws securing the oil shaft 60° between each measurement, and
pump to the bearing cover have been re- adjust until the smallest play is measured to
moved, it can be taken out by hand. be as started above.

0171-487-EN 55
Chain-driven oil pump with inverse direction of rotation
If the HPC compressor is to run in the oppo- To this end, use a set of replacement parts,
site direction of rotation to that shown by the stores no. 3141-127. This set contains a
arrow on the bearing cover Pos. 6A, the chain, a chain wheel (springs for old shaft
gearwheel drive on the oil pump must be re- seals only) and a baffle for lubricating oil, as
placed with a chain drive. well as all screws needed.

5
3
1

6
7
8
4
2

1 Hub for the chain wheel 5 Endless chain


2 Hub for bottom chain wheel 6 Baffle for lubricating oil
3 Top chain wheel 7 Set screw M6 x 12
4 Bottom chain wheel 8 Spring washer for M6

Mounting instructions

The chain system can be mounted on all D92


HPC compressors:

S Dismantle the two gear wheels by remov-


ing screws pos. 11Q and nut pos. 11J (see
spare parts drawing). T0177085_0

Screw dimensions: M6 x 12 mm
S Mount the guide plate for lubricating oil as Thread depth: 5 mm
shown on drawing. Bore and screw-cut Drilling depth: 20 mm
the two M6 threaded holes, using the plate Core drill: 5 mm
as a gauge. The positioning must be such Secure screws with spring washers.
that it touches the inner diameter of the S Slightly tighten four screws securing oil
bearing sleeve D=92mm (see sketch). pump to bearing cover.

56 0171-487-EN
S Place chain wheel with hub Pos. 4 and 2 the cover Pos. 6A, it connects directly with
on pump shaft. The retainer nut can be the oil pressure chamber in the shaft seal
tightened once the entire chain drive has housing.
been mounted.
The oil pressure is regulated by a spring
S Place the assembled chain, hub and chain loaded cone, the spring pressure being ad-
wheel, Pos. 5, 1 and 3, in position; tighten justed by turning an adjusting screw in the
wheel firmly with screws Pos. 11Q from valve end. Use a screwdriver for this pur-
gearwheel drive. pose.
Turning to the right (clockwise) raises the oil
S Adjusting the chain drive: Tauten chain by
pressure; turning to the left (anticlockwise)
shifting oil pump. The correct tension of
lowers the pressure.
the chain is shown in the sketch.
Fig. 1 locking screw
22A

3.5 – 5.5mm

22B

T0177083_0

T0177085_0
Adjustment
Oil pressure: 4.5 bar.
Finally, when the proper centre distance
The oil pressure can be read off the suction
has been established, secure oil pump
pressure gauge or on UNISAB II.
tightly.
On more recent compressor models the
S Tighten chain wheel on oil pump. adjusting screw may be locked by means
Marking direction of rotation of an M6 pointed screw, fig. 1, which must
be loosened before adjustment can take
The arrow on the end cover of the compres-
place.
sor should be cancelled out and replaced by
one painted on the indicate the new direction Service
of rotation. Since the oil pressure valve is not subject to
any appreciable wear or soiling, it should not
Oil pressure valve be disassembled during routine services.
The oil pressure valve Pos. 22 regulates the In the event of a malfunction, the complete
oil pressure in the compressor. Mounted in valve should be replaced.

0171-487-EN 57
By-pass valve Pos. 24 Thus, watch out that hole pos. B does not
get covered or clogged.
The compressor is equipped with a built-in
mechanical by-pass valve, fig. 1, which safe- In case the pressure on the discharge side
guards it against any inadvertent excess exceeds the set pressure so that the by-pass
pressure if the electrical safety equipment valve opens, the valve will remain open until
fails. The by-pass valve safeguards against the pressure on the discharge side has fallen
any excess pressure between the discharge to approx. half the set pressure. The valve
and suction sides of the compressor. then closes automatically. However, at great
differential pressures across the compressor
If the by-pass valve goes into action, the the valve may remain open. In that case,
compressor must be immediately stopped stop the compressor and close the discharge
and the cause established. stop valve entirely. The equalization of pres-
sure in the compressor will then close the
The by-pass valve is supplied ready-set and safety valve and the compressor can be re-
sealed in accordance with the adjustment started.
pressures indicated in the table Pressure and
temperature settings. The actual set pressure The by-pass valve is supplied factory-set and
is stamped on the rating plate, pos. A. sealed and need normally not be disassem-
bled and readjusted.
The by-pass valve is of the high-lift type
If necessary, control of function and set pres-
which makes it very sturdy and durable.
sure must be made in accordance with local
regulations for safety valves.
Further, the by-pass valve is independent of
the pressure on the compressor suction side. On the outside the by-pass valve is sealed
Consequently, it only opens when the pres- with two O-rings, pos. 24B and 24C. Fasten
sure on the discharge side exceeds the set it to the compressor housing by means of
pressure in relation to atmospheric. screws pos. 24D and washers pos. 24E.

Fig. 1 24C 24B


A B T3137T02I_1

58 0171-487-EN
Oil filter ticles are intercepted before the oil flows on
to the oil pump.
All oil to the lubricating system of the com-
pressor is filtered through a oil filter installed Changing filter cartridge
in the crankcase. The filtration element is a The filter cartridge should be replaced at reg-
filter cartridge (Pos. 33A on the drawing) ular intervals. See the section entitled Servic-
which is non-cleanable and must be replaced ing compressors on this point. In particular, it
with a new one when the filter capacity is should be remembered that the filter car-
used up. tridge must often be replaced after a relative-
ly short operation time following initial
It is important, therefore, always to have start-up.
an extra filter cartridge available.
This is due to small particles of dirt originat-
The filtered oil further passes a magnetic fil- ing from the plant during the initial operating
ter Pos. 33J/33K where any small iron par- period.

33R

33B 33Q 33A 33J 33K 33E 33B 33P

33L
33F 33M 33G 33H 33D 33C 33O 33N

T4524042_0

When changing the filter cartridge, it is rec- S That the seal Pos. 33B is in position.
ommended that the whole oil filter be re-
moved by unscrewing the union nut at Pos. S That the O-rings Pos. 33Q and 33P are in
33R. position and in good order.
Strip the oil filter down by dismantling both
S That the screen Pos. 33E must cover the
nuts Pos. 33O and 33M, after which the indi-
top half of the filter cartridge.
vidual parts can be taken apart.
When reassembling, attention should be paid S That the union nut Pos. 33R is tightened
to the following: securely.

0171-487-EN 59
Suction filters Note:
Do not forget to remove the filter cartridge
The purpose of the filters is to collect impuri-
after 50 operating hours, as a blocked fil-
ties conveyed from the plant to the compres-
ter bag may cause the suction filter to
sor with the suction gas and thus prevent
burst and thus contaminate the compres-
them from penetrating into the compressor.
sor to an extreme degree.
The suction filters therefore have a very fine
mesh and as an additional precaution have a There are always two suction filters in the
filter bag insert, which should normally be compressor and these are removed through
used for 50 operating hours from the initial the flanged opening in the bottom end of the
start-up of the compressor. The filter bag is filter housing.
then removed and disposed of.

If the filter bag is badly soiled after the 50 op- Note:


erating hours mentioned, it is recommended It is important to keep the suction filters
that a new bag be fitted for an additional 50 clean and in good order. A soiled, clogged
operating hours. Similarly, a filter bag ought suction filter will reduce the capacity of the
to be fitted for a period of 50 operating hours compressor, at worst, the suction filter can
after any major repair work to the refrigera- burst and severely contaminate the com-
tion plant. pressor.

60 0171-487-EN
Stop valves

AK AC A AJ L P K R

AD

E S

F T

D U

C M

H B

Y J

POS. 25

Z AG Q G N T0177131_0 V14

The suction and discharge stop valves are S Mount threaded piece Pos. 25G in a
used to isolate the compressor from the re- soft-jawed vice and dismantle screw
frigeration plant. Pos. 25E.

They are closed completely by manual tight- Note:


ening and it is therefore advisable not to use The screw has a lefthand thread, and it
any tool to close the valve, as this will simply is therefore inadvisable to leave the
overload the valve parts. threaded piece in the valve holder while
dismantling the screw, as the guide pin
The valve seat is sealed with a teflon ring Pos. 25N will be overloaded.
Pos. 25H which, if necessary, can be re-
placed as follows: S The front and rear pieces Pos. 25C and
25D can now be separated and the teflon
S Once the pressure on the inlet and dis- ring Pos. 25H removed.
charge sides of the valve has been equal- The teflon ring will be flattened on one
ized to atmospheric, dismantle screws outer edge, which is normally of no impor-
Pos. 25AJ. The valve throat Pos. 25B, and tance to its sealing ability providing it is
with it the entire valve insert, can then be free of scratches and marks.
removed.
If required, the teflon ring can be reversed
S Turn spindle clockwise until cone and during reassembly so that the other outer
threaded piece Pos. 25G can be removed edge seals towards the valve seat in the
by hand. housing.

0171-487-EN 61
Reassembly of valve Changing the spindle sealing
The stop valve has a so-called retroseal,
Reassembly is done in the reverse order to
which enables the packing screw joint
that above. Note the following, however: Pos. 25M to be serviced even when there
is excess pressure in the valve housing.

S Before mounting the complete valve in- Adopt the following procedure:
sert, the valve cone with threaded piece S Using handwheel, open valve completely
Pos. 25G must be screwed right into the to achieve a seal between valve cone and
valve neck Pos. 25B. valve throat. The gasket Pos. 25Q acts as
a sealing element.
S The packing screw joint Pos. 25M can
S The O-ring Pos. 25J may have expanded then be screwed out for inspection or re-
under the influence of the oil in the plant placement of the O-ring Pos. 25R and
and will normally have to be replaced with 14P. Thoroughly lubricate all parts with oil
a new one. before reassembling.

62 0171-487-EN
Unloaded start and capacity regulation

The HPC compressors are equipped with an The unloader system is also used to regulate
automatic unloader system to provide full re- the capacity of the compressor.
lief to the compressor during the start-up
The following schematic outline shows the
phase. This reduces the starting torque of the
lubrication and hydraulics system on the
compressor considerably.
compressors together with unloader me-
chanism.

Fig. 1 12

2
12J

50

20 13 2
96.01

19D
15D
19B 2
0171-908-EN

15A
15B

1
3

22

11

38

33

T0177131_0 V10

Description of unloader mechanism Around each pair of cylinder linings a frame


and capacity regulation Pos. 13 is fitted, controlling two sets of rocker
arms Pos. 15A. The frame is connected by
No-load starting and capacity regulation are
means of a piston rod to the regulating piston
achieved by keeping the suction valve ring
in the unloading cylinder pos. 12.
plate in the open position; the refrigerant gas
thus aspired into the cylinder is not com-
pressed but thrust back out through the suc- When the regulating piston is unaffected by
tion valve. the oil pressure - i.e. when the connected so-
lenoid valve is de-energized or when the
See the blue spare parts drawing of the cylin- compressor is at standstill - the regulating
der linings at the end of this manual. piston and the entire frame are shifted to the

0171-487-EN 63
right by the pressure from the springs Pos. Note:
12J (see fig. 1) . Adjust the oil pressure on the regulating
valve Pos. 22 to 4.5 bar. At an oil pressure
The tension springs Pos. 15D will thus raise lower than 3.5 bar (the breaking pressure
the rocker arms Pos. 15A into the horizontal for the safety automatices), there is a risk
position, as these rotate in the ball sockets of the unloader system not being moved
Pos. 15B. effectively and thus being damaged.

This movement lifts the relief ring and the


Pilot solenoid valves
pins Pos. 19B, opening the suction valve by
force. The pilot solenoid valve is an electromagnet-
ic three-way valve which with a dead coil
If oil pressure is placed on the relief cylinder connects the unloading cylinder to the crank-
during operation, the unloader system is case (the path for the oil flow from pipe 2 to
shifted to the left (see sketch). This lowers pipe 3 is open). See sketch. If the coil is en-
the rocker arms Pos. 15A, and the relief ring ergized, the valve switches so that the path
with pins Pos. 19B is moved away from the for the oil flow from pipe 1 to pipe 2 is open
suction valve ring plate, allowing this to oper- and the connection to pipe 3 is closed off.
ate freely and close during the compression
phase. The solenoid valves are integrated in blocks
with 1, 2, 3, or 4 solenoid valves in each
During operation, the unloader system can block. In these blocks the solenoid valves
therefore regulate the capacity of the com- have a collective supply of pressure oil (pipe
pressor by causing the solenoid valve - which 1) and a collective connection to the crank-
is linked to the relief cylinder - to open or case (pipe 3). Each individual solenoid valve
close for oil pressure to the relief cylinders, has its own oil connection to the relevant un-
controlled by UNISAB Control. loading cylinder (pipe 2).

64 0171-487-EN
Sectional drawing of capacity regulating valve

Fig. 2

Danfoss 034F9034_1

Schematic outlines The S-valve is connected to the regulating


cylinder(s) not involved in capacity regula-
The following schematic outlines shows the
tion.
oil pipe connections and the wiring diagram
with cut-out functions. The valve is designed to prevent fast rising
The schematic outlines also indicate the per- oil pressure actuating the compressor cylin-
centual capacity at which the compressor op- ders before the motor starter has changed
erates at the various capacity stages. over to the delta position, or a gas or diesel
motor has reached full rotation speed.
The lowest capacity percentage indicated on
schematic outlines 1 corresponds to the low- See the application of the ”S” solenoid valves
est permissible capacity step at which the on the following pages.
compressor may work by continous opera-
tion. Note:
In special instances, e.g. where the start-up Please note that the S solenoid valve
phase is lengthy, it may prove necessary to must not be wired so as to form part of
relieve the compressor altogether until the the capacity regulation.
motor has achieved a sufficient torque. In The compressor may operate totally un-
such cases, an extra solenoid valve marked loaded for no more than 5 minutes, as its
’S’ can be mounted as shown on schematic operating temperature will otherwise be-
outlines 2. come too high.

0171-487-EN 65
Standard unloaded start and capacity regulation
The HPC compressor always start totally signal until the drive motor has achieved
unloaded and - in their standard design - will full torque.
activate a number of cylinders corresponding
to the lowest capacity stage once the oil Regulating sequence
pump has built up the necessary oil pressure. Cylinder pairs are relieved by cutting off the
voltage to the accompanying solenoid valve.
See discussion of the ’S’ solenoid valve in The unloading must be effected in numerical
the Totally unloaded start and capacity regu- order (1 - 2 - 3 - 4), while loading should be
lation section, however. done in reverse order (4 - 3 - 2 - 1).
It is recommended that solenoid valves be The regulating sequence may be seen from
wired so as not to receive the opening the schematic drawings:

Schematic drawings 1

HPC 108
HPC 104 HPC 106

3 4 1
%
2 1 1 2 2 3
% 100 1
% 100 1
75 2
100 67 50 3
1 2
50 33 25
N N N
L L L

T0177081_0/1

66 0171-487-EN
Totally unloaded start and capacity regulation
Futher to the standard equipment, as shown only as follows:
on the previous page, the compressor may
S Where total unloading is required until the
feature an extra solenoid valve marked S.
motor has achieved max. torque.
This makes total unloading of the compres-
sor possible, i.e. 0% capacity over a shorter S Where a refrigeration plant is occasionally
period during operation. However, the ’S’ so- subject to brief operating stops and com-
lenoid valve must never be involved in nor- pressor stop is not desirable. The com-
mal capacity regulation, as there is a risk of pressor may then be allowed to run for a
the compressor overheating if operated for maximum of 5 minutes at 0% capacity.
some length of time at 0% capacity.
The regulating sequence may be seen from
The ’S’ solenoid valve may therefore be used the schematic drawings:

Schematic drawings 2

HPC 104 HPC 106 HPC 108

% S 1
S 1 S 100 1
1 2 2 3
% 75 2
% S S
100 100 50 3
1 1
50 67 2 25 S
0 33
N 0
L 0 N
N
L L

T0177081_0/2

0171-487-EN 67
Service Note:
When starting a compressor this must be
Normally, it will not be necessary to service done at the lowest capacity stage and it
the solenoid valves, and it is therefore re- should be allowed to run for a few minutes
commended not to strip them down. (e.g. 3 to 5 minutes) before its capacity is
increased. This will prevent the oil in the
compressor from heavy foaming and the
In case you should consider it necessary to
refrigerant from being sucked into the
replace the solenoid valve, however, unscrew
compressor from the evaporating system;
it from the block and replace by a new one. something which can lead to liquid
See the spare parts list. strokes. For the same reasons the com-
pressor should always, when a new
stage has been loaded, be allowed to
run for 3 to 5 minutes at this stage before
Regulating sequence the next higher capacity stage is loaded.
Unloading of capacity on the compressor
The schematic outlines show that disconnec- can usually take place more quickly.
tion of a cylinder pair is done by cutting off
the current to the appurtenant magnetic coil. Automatic capacity regulation
Disconnection must be done by numerically
Where there is an automatic capacity regulat-
ascending sequence, while connection
ing facility the solenoid valves are controlled
should be done by numerically descending
by UNISAB II.
sequence.

Relief cylinder
The automatic gear which controls the sol- The relief cylinders vary in type, depending
enoid valves must cut off or connect the cur- on the position they have on the compressor.
rent to the number of solenoid valves needed The chart below shows the number and di-
to supply the compressor with the capacity mensions of the relief cylinders for the indi-
required. vidual compressor types.

Piston rod Relief Number in each


Pos. 1) Cylinder compressor
Dimension HPC
S mm L mm Part no. 104 106 108

12-1 21.5 75 3135-149 1 1 1


12-2 46.5 100 3135-150 1 1 1

12-3 71.5 125 3135-151 1 1

12-4 96.5 150 3135-152 1

1) See spare parts drawing at the end of the instruction manual

68 0171-487-EN
Heating rods, pos. 30

In order to keep the lubricating oil in the com- As illustrated on the drawing the heating rod
pressor warm during a period of standstill, consists of an electric heating element, incor-
the oil reservoir has one or two heating rods porated in a dia. 30 mm pipe. The entire hea-
built in. Before start-up, the heating rod (s) ting cartridge is screwed on tight at the
must have been activated for 6-8 hours in G 1 1/4” thread.
order to ensure that there is only a minimum
of refrigerant in the oil. When containing Note:
much refrigerant, the oil will lose its lubricat- The heating rod must not be energized if
ing property and the following operational in- the oil level in the reservoir is below the
terruptions may occur: minimum mark in the sight glass, and it
should generally be switched off during
In reciprocating compressors there is a
compressor operation. Remember to turn
serious danger of vigorous oil foaming when
off the heating rod whenever the crank-
the compressor starts as a result of a falling
98.05

case of the reciprocating compressor is


suction pressure.
opened for inspection.
For screw compressors starting with much
0170-017-EN

refrigerant dissolved in the oil, there is a risk The following table indicates which heating
of the compressor being stopped by the Flow rods are used for the various compressor
Switch as the oil will be foaming owing to the types. In the spare parts lists for compressor
fall in pressure through oil pipe and oil filter. or unit you will find the current part numbers.
Marking: Prod. nr.
NV 50 Watt
G 1 1/4” Volt
Manu. date

Ø 30
30
50

L1
80 L2

Heating rods
Power Voltage L1 L2 Used for:
Watt V mm mm
270 250
270 230 CMO - TCMO - SMC 100 - TSMC 100
270 115*
158 175
460 250 HPO - HPC, SMC 180 - TSMC 180
460 230 VMY 347 /447 – 536
460 115* SAB 110 – 128 – 163 – 202 – 330
* Can be delivered with a UL approval.
All heating rods are executed in Degree of Protection IP54.

0178-017 – EN 69
Stop valves pos. 23 and 42

23G

23A 23D 23F 23C 23B 23E

Fig. 1
Danv

42A 42H

Fig. 2

95.03
0171-463-EN
42G

42F 42E 42C

42D 42B
T0177156_0

The compressor is fitted with stop valves trating the valves whenever they are not
pos. 23 for charging of oil and pos. 42 for used.
draining of oil. They are service-free valves
and should as a rule not be dismantled. S If the valve is used as an oil charging
valve it is fitted with a nut pos. 23C and
The valves are safeguarded against inadver- threaded nipple pos. 23B as shown by
tent opening by means of a red cap. fig. 1.

The red cap can further be used for opening S If the valve is used as a purge valve it is
or closing the valve by unscrewing it and fitted with a screwed connection as illus-
turning it upside down. The square hole in trated by fig. 2.
the top of the cap fits the square in the valve
spindle. The purge valve is fitted either directly on
the top cover or by means of an intermedi-
The valves are equipped with a blank nut ate connection in the cast pressure chan-
pos. 23G/42H that prevents dirt from pene- nels in the frame.

70 0171-487-EN
Monitoring cylinder lining insertion

When reassembling the slide linings, it is im- no. 1 from the tools kit.
portant to check the clearance volume as Fit the locking devices diagonally as
described in section 1 below. shown in fig. 1.
When mounting new cylinder linings, both
the clearance volume and the so called lift- Fig. 1
ing reserve must be checked in the order S-L for SMC 100 type S
• E for SMC 100 type E
mentioned and as described in sections 1
and 2. It is recommended that the cylinder
linings be marked so that they can be reas-
sembled in the same place as before.

1. Checking clearance volume •

After each cylinder lining assembly, it is rec-


ommended that the clearance volume be
98.01

checked. pos. 19K

Adjustment of the clearance volume is done


0171-467-EN

by means of gasket pos. 19K which, in addi-


tion to its sealing function, is also used as an
adjusting element. Consequently, the gaskets
come in two sizes and may sometimes be
used at the same time under the same cylin-
der lining. S Turn crankshaft until piston is in top posi-
tion.
Gasket HPC SMC 180
thickness SMC 100 S Using a depth or slide gauge, measure ”X”
19K part no. part no. as shown in fig. 2
0.5mm 2356-111 2356-116
Fig. 2 Cylinder lining
0.8mm 2356-233 2356-249
X

Adjustment is made as follows:


S The rocker arm system is lowered by fit-
ting the long plug no. 4 from the tools kit in
the unloading cylinder pos. 12 instead of
screw pos. 12D.
Piston T0177131_0 v6
S Insert an 0.5mm gasket pos. 19K and
mount cylinder lining.
S ”X” must lie between the below mentioned
S Press cylinder lining against gasket pos. limits and may, as mentioned earlier, be
19K by means of two locking devices – adjusted by the use of gasket pos. 19K.

0178-910-EN 71
Clearance The rocker arms must be in their vertical
min. max.
volume position i.e. with the short screw pos. 12D
”X” mm mm
HPC and gasket 12E fitted. The measured dis-
SMC 100
0.6 1.0 tances ”Y1 and Y2” may not vary more
Mk1, Mk 2, Mk 3
SMC 180 than max. 0.25mm.
0.9 1.5
Mk1, Mk 2

S Adjustment of the lifting reserve can now In case this difference is greater, a shim
be performed if necessary. See point 2. Pos. 15E must be placed under the lowest
rocker arm bearing pos. 15B or a shim re-
2. Checking lifting reserve moved from the highest bearing. Normally,
When fitting a new cylinder, or if the com- there is no shim or max. 2 shims under
pressor is to be changed from running on the rocker arm bearing.
R717 to some other refrigerant, or vice versa,
or in the event of any major overhaul to the
compressor, the lifting reserve must be
checked.
Check lifting reserve:
Note:
The lifting reserve must not be checked S The lifting reserve of the rocker arm is im-
until the clearance volume has been ad- portant in order to make sure that the
justed. Start by checking that the mutual rocker arm in its upright position can keep
height of the rocker arms is the same as the suction valve ring plate open while the
described in the following: cylinder is unloaded. However, it must not
Having removed the cylinder lining, mea- be possible for them to be so upright that
sure distance ”Y” from the contact face of there is a risk of their jamming, this mak-
the cylinder lining in the frame to the top of ing them unable to be lowered again
the two rocker arms which interact on ei- when the cylinder is put into service. Per-
ther side of the cylinder lining. See fig. 3. form the adjustment as follows:
Fig. 3
S Position cylinder lining incl. the correct
Block
gasket pos. 19K in the compressor block
and press down against rocker arms by
hand.

Y1 Y2
S The rocker arms are in their upright posi-
Rocker arms tion as the normal plug pos. 12D as well
as gasket pos. 12E have been mounted in
T0177131_0 v4
the unloading cylinder.

72 0178-910-EN
S The difference in the two measurements
Fig. 4
of ”Z” must be within the limits stipulated
in the following table.
Z

Lifting reserve Min. Max.


”Z” mm mm

HPC
pos. 19K SMC 100 0,6 1,0
Mk 1, Mk 2, Mk 3
SMC 180 0,8 1,5
Mk 1, Mk 2

T0177131_0 v5

S If the difference between the two mea-


surements does not fall within the parame-
S Measure distance ”Z” as shown in fig. 4. ters stated, it must be regulated by insert-
Note down the ”Z” measure. ing or removing shims pos. 15E under the
S Replace normal plug pos. 12D with the rocker arm bearings.
long plug no. 4 from the tools kit, lowering S It is important that the long threaded plug
rocker arms in the process. is fitted while the top cover is being
mounted.
S Press cylinder lining down against gasket
pos. 19K using the two locking devices no. Note:
1 as shown in fig. 1, and repeat measure- Remember to put the normal plug in once
ment ”Z”. the top cover has been tightened.

0178-910-EN 73
Undersize Bearing Diameters for Crankshaft
Reciprocating Compressors with 4 to 8 Cylinders

B
A A

B C

R=2.5 R=2.5
R=d
a

b
°

96.05
45

c
T0177137_0

0171-904-EN
A B C a b c d
Main bearing Connecting rod bearing
Compressor First Super First Super
type grinding finish grinding finish
or or
Final Final
grinding grinding
mm mm mm mm mm mm mm mm mm
–0.060 –0.060 –0.030 –0.035 0.0 0.0
HPO 59.5 59.5 54.5 54.5 35 0.2 1.0 2.5 2.5
–0.070 –0.090 –0.049 –0.050 –0.1 –0.3
CMO 2
Ra=0,20 Ra=0,20

HPC, 0.0
40
SMC/TSMC –0.1
100 S
–0.070 –0.070 0.000 0.000
79.5 79.5 79.5 79.5 0.0
SMC/TSMC –0.080 –0.090 –0.010 –0.020 50 0.2 1 3 3.5
100 L Ra=0.35 Ra=0.35 –0.1

SMC/TSMC 0.0
60
100 E –0.1

–0.110 –0.110 0.000 –0.015 0.0


SMC/TSMC 134.0 134.0 134.0 134.0 70 0.16 1.15 5 6
180 –0.120 –0.140 –0.010 –0.040 –0.1
Ra=0,63 Ra=0,63

Undersize bearings: See SABROE spare parts list.

74 0172-133-EN
Sundry clearances and check dimensions

Bearing clearance All measurements stated are in mm


CMO 1 CMO 2 SMC 65 SMC 100 SMC 100 SMC180
CMP 1 TCMO 2 TSMC 65 TSMC 100 TSMC 100 TSMC 180
TCMO1 4–10 cyl. 12–16 cyl.
CMO4 HPO HPC Mk1 & Mk2

Main bearings manufactured 0.08 0.08 0.08 0.08 0.08 0.14


max. 0.20 0.20 0.20 0.20 0.20 0.35
Connecting rod manufactured 0.08 0.08 0.08 0.10 0.10 0.14
bearings max. 0.15 0.15 0.15 0.20 0.20 0.30

Piston pin manufactured 0.04 0.04 0.04 0.04 0.04 0.09


bearings max. 0.10 0.10 0.10 0.10 0.10 0.20

Parallel to manufactured 0.18 0.18 0.18 0.20 0.20 0.25


piston pin max.
Piston

– – – – – –
91.04

At right angles manufactured 0.11 0.11 0.11 0.15 0.15 0.35


to piston pin max. 0.30 0.30 0.30 0.40 0.40 0.90
0171-901-EN

If the maximum value has been exceeded, replace the parts.

Crankshaft end-play
min. 0.30 0.30 0.30 0.40 0.75 0.95
max. 0.55 0.55 0.55 0.64 1.00 1.20
The end–play can be adjusted by means of the gasket under the bearing cover.
The gasket is available in the following thicknesses: 0.3, 0.5, 0.75 and 1.0 mm.

Piston ring gap


min. 0.25 0.25 0.25 0.33 0.33 0.66
max. 1.00 1.00 1.00 1.30 1.30 2.50
The piston ring gap must be measured with the ring placed in the cylinder liner.

Dimensions of crankshaft bearing journal


–0.06 –0.06 –0.06 –0.07 –0.07 –0.11
Main bearing journals 55 60 55 80 80 135
–0.09 –0.09 –0.09 –0.09 –0.09 –0.14
New

Connecting rod –0.025 –0.030 0 0 0 –0.015


50 55 55 80 80 135
bearing journals –0.040 –0.049 –0.02 –0.02 –0.02 –0.040
–0.010
Intermediate journals 80
–0.029
–0.06 –0.06 –0.06 –0.07 –0.07 –0.11
Main bearing journals 54.5 59.5 54.5 79.5 79.5 134
Ground down

–0.09 –0.09 –0.09 –0.09 –0.09 –0.14


Connecting rod –0.025 –0.025 0 0 0 –0.015
bearing journals 49.5 54.5 54.5 79.5 79.5 134
–0.040 –0.040 –0.02 –0.02 –0.02 –0.040
–0.010
.
Intermediate journals 79.5
–0.029

Bushing and bearing halves can be supplied for all above journals.

0172-133-EN 75
Torque moments for screws and bolts

Metric thread (ISO 8.8)


M 4 5 6 8 10 12 14 16 18 20 22 24 27

Kpm 0.28 0.53 0.94 2.2 4.1 7.0 11 15 23 30 38 52 68

ft.lbf. 2.1 3.9 6.8 16 30 50 80 110 170 220 270 370 490

Nm 2.7 5.2 9.2 22 40 69 108 147 225 295 375 510 670

94.12
Metric thread (ISO 12.9)
M 4 5 6 8 10 12 14 16 18 20 22 24 27

0171-465-EN
Kpm 0.42 0.78 1.4 3.2 6.1 10 16 23 34 44 55 76 100

ft.lbf. 3.0 5.7 10 23 44 75 120 160 240 320 400 550 720

Nm 4.1 7.6 14 31 60 98 157 225 335 430 540 745 980

Connecting rods with UNF thread


HPO/CMO HPC/SMC 100 SMC 180

UNF 5/16” 3/8” 5/8”


Kpm 2.1 4.4 17
ft.lbf. 15 32 130
Nm 20 43 167

T0177082_0

76 0172-133-EN
Bolt on discharge valve
HPO/CMO HPC/SMC 100 SMC 180

Kpm 3.2 10.2 35


ft.lbf. 23 75 255
Nm 32 101 344

AMR A Torque (A)


Compressor type Coupling Thread
type Kpm. ft.lbf. Nm

HPO/CMO/TCMO AMR225 5/16” 3.5 25 34

104-108 AMR312S 7/16” 5.6 40 55


HPC/
SMC/ 112-116 AMR350S 1/2” 13 95 128
TSMC
A 186-188 AMR450S 11/16” 28 200 275
NORMEX
NORMEX

128 H148 M8 2.2 16 22

163 H168 M8 2.2 16 22


SAB
128 225 5/16” 3.5 25 34
Series 52

163 262 3/8” 4.2 30 41


Series 52 A
202 312 7/16” 5.6 40 55

200 5/16” 3.5 25 34

225 5/16” 3.5 25 34

262 3/8” 4.2 30 41


Series 52

depending
VMY on the 312 7/16” 5.6 40 55
motor size
350 1/2” 13 95 128

375 9/16” 18 130 177

425 5/8” 25 175 245

450 11/16” 28 200 275

0172-133-EN 77
Refrigeration Plant Maintenance

Operational reliability bled of refrigerant. Adjust any constant-


pressure valves to bring evaporator pres-
The prime causes of operating malfunctions
sure down to atmospheric.
to the plant are:

1. Incorrect control of liquid supply to the 3. Start up the compressor. Adjust regulat-
evaporator. ing system to lower suction pressure.

2. Moisture in the plant. 4. Keep a close eye on the suction pres-


sure gauge! When the suction pressure is
3. Air in the plant. equal to atmospheric, stop the compres-
sor and quickly shut off the discharge stop
4. Anti-freezing liquid is missing.
valve. Shut off any stop valve in the oil re-
5. Congestion due to metal shavings and turn line.

94.05
dirt.
If the receiver has an extra stop valve in
6. Congestion due to iron oxides. the feed line, this can be closed; practical-

0171-464-EN
ly the entire refrigerant charge will then
7. Congestion due to copper oxides. remain shut off in the receiver.
8. Inadequate refrigerant charge. Note:
Below, some information is given about ways The receiver must not be overfilled! There
of keeping contaminants out of the refrigera- should be a minimum gas volume of 5%.
ting system and at the same time facilitating 5. A slight overpressure should normally re-
day-to-day supervision of the refrigeration main in the piping system - this safe-
plant. guards the system against the penetration
of air and moisture.
Pumping down the refrigeration
6. Before dismantling parts, the operator
plant
should put a gas mask on.
Before dismantling any parts of the refrigera-
tion plant for inspection or repair, pump-down
must be carried out.
Dismantling plant
In order to prevent moisture penetrating into
1. Open suction and discharge stop valves the refrigeration plant during any repair work,
on compressor. it is advisable to follow the rules below:
2. Close liquid stop valve after condenser or 1. No component should be opened un-
receiver so that liquid refrigerant can be necessarily.
collected in the tank. Any solenoid valves
in the liquid line should be opened by 2. When dismantling the system, the pres-
force, adjusting the thermostat to its low- sure in the system should be a little higher
est position so that the liquid line can be than atmospheric.

78 0171-702-EN
3. Note: Tightness testing and pump-down
If the piping system is colder than the sur- of refrigeration plant
roundings, there is a considerable risk of
Before charging refrigerant into that part of
damp precipitation (condensation) on cold
the refrigeration plant which has been
plant parts. Plant components to be dis-
opened, this should be pressure-tested as
mantled must be warmer than the ambi-
described in the section entitled Pressure
ent temperature.
testing.
4. No two points in the system should be Afterwards, pump down in order to eliminate
opened at the same time. air and moisture. In this regard, consult the
section on Evacuation.
5. Plug, close or at least cover opening with
Otherwise, follow the instructions given in the
oiled paper or suchlike.
separate instruction manual on plant compo-
6. Be aware of the possibility of filters nents.
being very moist. Note:
If the oil in the crankcase of the piston
compressor or the oil separator of the
screw compressor has been in contact
with the atmospheric air for any length of
time, it must be replaced with fresh oil of
the same grade and make.

0171-702-EN 79
TroubleĆshooting on the Reciprocating Compressor
Plant

Operating condition lefthand column, the error being briefly de-


scribed in the next column. The third column
Experience shows that pressure and temper-
states code numbers for the possible causes
ature variations in a refrigeration circuit can
of the error.
provide information about the operating con-
dition of the refrigeration plant. The code numbers refer to the subsequent
chart.
In particular, suction and condenser pres-
sures as well as the temperatures of suction The section entitled Remedying malfunctions
and discharge gases may provide important states how to remedy the observed error.
information as to the operating conditions
See the following example for the correct
of the plant.
procedure.

91.05
It often takes only very slight modifications to
variable pressures and temperatures to pro- Example
duce considerable changes in operating con- Observed error: discharge pipe temperature

0170-335-EN
ditions. too low - error code 15.

Using the following troubleshooting chart, it is Cause codes:


possible to ascertain the cause of and reme- 26 (Liquid in suction line)
dy for any operating disturbance. 32 (Too much coolant/air to condenser)
39 (Expansion valve produces too little su-
Using the trouble-shooting chart perheating)

In the following chart, each individual error Any explanatory comments will be stated in
option is indicated by a code number in the the section that follows.

80 0171-231-EN
Error
code Observed error Cause code
1 Compressor fails to start 1, 2, 3, 4, 5, 6, 7, 9, 10, 12, 14.
2 Compressor starts and stops too often 9, 10, 11, 13, 21, 22, 23, 24, 32, 34, 35, 36, 37,
40, 41, 43, 44, 51, 52, 54, 56, 59.
3 Compressor starts but stops again immediately 3, 5, 6, 9, 10, 11, 12, 13, 14, 15, 17, 18, 41,
42, 49, 50, 55, 61.
4 Compressor operates continuously 8, 21, 22, 24, 41, 46, 52, 53, 56, 60.
5 Abnormal noise from compressor 16, 17, 18, 19, 26, 48, 49, 50, 51, 52, 53, 54, 56,
57, 58.
6 Insufficient capacity on compressor 13, 15, 17, 18, 20, 21, 22, 23, 24, 32, 34, 35, 36,
37, 40, 41, 44, 45, 46, 49, 50, 51, 52, 53, 56, 60.
7 Liquid stroke in compressor during start up 16, 18, 26, 37, 38, 39, 44, 56, 61.
8 Liquid stroke in compressor during operation 21, 23, 26, 37, 39.

9 Excessive condenser pressure 9, 25, 28, 29, 30, 31, 33.


10 Too low condenser pressure 22, 32, 51, 52, 54, 60.
11 Excessive suction pressure 13, 17, 26, 34, 39, 52, 53, 54, 5,. 60.
12 Too low suction pressure 11, 13, 20, 21, 22, 23, 32, 35, 36, 37, 40, 41, 42,
44, 45, 56, 59.
13 Too low oil pressure 12, 15, 17, 18, 26, 49, 50, 55.

14 Excessive discharge pipe temperature 11, 21, 22, 23, 28, 29, 30, 31, 33, 34, 35, 36, 37,
40, 41, 46, 52, 54.
15 Too low discharge pipe temperature 26, 32, 39.
16 Excessive oil temperature 33, 34, 35, 36, 37, 40, 50, 52.

17 Oil level in crankcase falling 16, 18, 20, 26, 51, 57, 58.
18 Oil foaming vigorously in crankcase 16, 26, 39, 61.
19 Crankcase sweating or frosting up 16, 18, 26, 37, 39.

20 Capacity regulating oscillating 13, 15, 16, 17, 18, 49, 55, 56.
21 Impossible to bleed plant 10, 43, 51, 52, 53, 54, 60.

0171-231-EN 81
Code Case Code Case

1 No power - master switch not cut in 34 External pressure equalization on


2 Blown fuses - loose wiring or expansion valve closed
connections 35 Expansion valve partly clogged by
3 Electrical voltage too low ice, dirt, wax
4 No control current 36 Expansion valve has lost charge
5 Motor protection device activated 37 Expansion valve sensor misplaced
6 Control current circuit open 38 Expansion valve is leaky
7 Pump/fan not started 39 Expansion valve provides too little
8 Welded contracts in motor protection superheating
9 High-pressure cut-out has cut 40 Expansion valve produces excessive
superheating
10 Low-pressure cut-out has cut
41 Filters in liquid/suction line clogged
11 Low-pressure cut-out differential too
42 Solenoid valve in liquid/suction line
small
closed
12 Oil pressure cut-out has cut
13 Capacity regulator incorrectly set 43 Solenoid valve leaky
14 Defrosting timer breaks current 44 Evaporator iced up or clogged
15 Oil charge insufficient 45 Cooling air being recirculated
16 Compressor capacity too high (short-circuited)
during start-up 46 Excessive load on plant
17 Oil pressure too low (adjust oil pres- 47 Refrigerant collecting in cold con-
sure regulating valve) denser (close off by-pass)
18 Oil foaming in crankcase 48 Coupling misaligned or loose bolts
19 Oil overcharge 49 Oil pump defective
20 Poor oil return - oil in evaporators 50 Bearings worn out or defective
51 Defective piston rings or worn
21 Restricted supply of refrigerant
cylinder
22 Refrigerant charge insufficient
52 Discharge valves defective or leaky
23 Refrigerant vapour in liquid line
53 Suction valves defective or leaky
24 Leaky refrigeration plant
25 Refrigerant overcharge 54 Compressor by-pass open - leaky
26 Liquid in suction line safety valve
27 At low temperature operation, de- 55 Compressor oil filter clogged
gree of charge in evaporators rises 56 Capacity regulator defective
28 Insufficient coolant/air to condenser 57 Solenoid valve in oil return clogged/
29 Temperature of coolant/air too high defective
30 Non-condensable gases in 58 Filter in oil return clogged
condenser 59 Compressor capacity too high
31 Condenser needs cleaning 60 Compressor capacity too low
32 Too much coolant/air to condenser 61 Heating element in crankcase
33 Water valve closed defective

82 0171-231-EN
Remedying malfunctions
1. Compressor fails to start

1.6 Control current circuit open owing Pinpoint open switch and
to activated: remedy cause of
pressure cut-outs interruption.
thermostats
motor protection device
defrosting timer
1.9 High-pressure cut-out has cut Reset pressure cut-out and investigate cause
of high condenser pressure.

1.10 Low-pressure cut-out has cut Compressor cannot start before suction pres-
sure has risen above set point for pressure
cut-out restarting.

1.12 Oil-pressure cut-out has cut Compressor starts at reset.


Check oil level. If oil
foams in crankcase, see section 18.

2. Compressor starts and stops too often

2.9 High-pressure cut-out cuts at High condenser pressure - see section 9.


high pressure
Check condenser cooling and adjust pressure
cut-out to correct breaking pressure -
see table Pressure and temperature settings.
Replace defective pressure cut-out.

2.10 Low-pressure cut-out cuts at too Low suction pressure - see section 12.
low suction pressure.
If low-pressure cut-out is set too high, adjust
pressure cut-out.

2.11 Low-pressure cut-out differential is Increase differential pressure - see also special
too small between stopping and instructions.
starting
2.13 Compressor capacity too high Check operating conditions and, if need be,
reduce capacity.

2.41 Filter in suction line clogged Check suction filters on compressor.

2.43 Solenoid valve in liquid line does Check direction of flow.


not close tight.
Replace defective valve.

2.52 discharge valves on compressor At compressor stop, pressure equalizes rela-


are leaky. tively quickly between suction and discharge
side
Clean or change discharge valves.

0171-231-EN 83
3. Compressor starts but stops again immediately

3.5 Motor protection cuts Look for cause of overloading.


If star-delta start, set starting time to minimum.

3.10 Low-pressure cut-out has cut Open any suction stop valve which is closed.

3.12 Defective oil-pressure cut-out Replace cut-out - see special instructions.

3.15 Oil charge insufficient Top up with oil and investigate cause of oil
shortage.
3.18 Oil pressure failing owing to for- Reduce capacity. See sections 17 and 18.
mation of foam in oil.

4. Compressor operates continuously

4.10 Thermostat or low-pressure Adjust operating points.


cut-out does not cut at too low
temperature/pressure

4.21 Restricted supply of refrigerant to Remove dirt in filters and check function of ex-
evaporator. Compressor working pansion device as per special instructions.
at too low suction pressure.

4.22 Refrigerant charge unsufficient Top up with refrigerant of correct type.

84 0171-231-EN
5. Abnormal noise from compressor

5.16 Compressor capacity too high du- Reduce capacity.


ring start-up

5.17 Oil pressure too low See section 13.

5.26 Liquid refrigerant in suction line Liquid stroke. See points 7 and 8.
Adjust expansion or float valves.

5.48 Incorrect alignment of motor and Check alignment as per special instructions.
compressor
Loose bolts in coupling Tighten with torque wrench

5.50 Worn or defective bearings Overhaul or replace.

5.51 Too much oil circulating Check oil level.


5.53 through the plant, resulting in too
5.57 Solenoid valve, filter or jets in oil return system
low oil level in
5.58 compressor may be clogged. Leaky suction valve ring
plates, piston rings and worn-out cylinder may
also produce such oil consumption.

5.56 Capacity regulation oscillating Low oil pressure - see section 13.
owing to failing oil pressure

6. Too little capacity on compressor

6.15 Insufficient oil charge Top up with fresh oil of same type and make.

6.44 Iced-up evaporator Defrost evaporator; adjust defrosting time if


required.
6.49 Defective oil pump and hence fail- Repair or replace oil pump
ing oil pressure
6.56 Defective capacity regulating sys- Cause is most often failure in oil pressure or
tem refrigerant in oil; see section 4.5.

0171-231-EN 85
7. Liquid stroke in compressor during start-up

Liquid stroke in the compressor should not occur, as in the worst instance this can
cause rupture to the valve ring plates and damage to the inbuilt relief devices. Fur-
thermore, it can result in damage to the connecting rod bearings and cylinders if the
coolant degreases the faces and impairs the lubricating capacity of the oil.

7.18 Adsorption of (H)CFC refrigerant Reduce compressor capacity or start with


in oil throttled suction stop valve.
Sudden reduction in pressure Follow instructions in section 18.
across the oil sump (suction pres-
sure) produces foaming

7.26 Refrigerant has condensed in suc- Heating element in crankcase should be con-
tion line or crankcase nected for 6-8 hours before starting, so that
refrigerant dissolved in oil can be boiled out
before starting compressor up.
Suction line has free fall towards Start with throttled suction stop valve - stop
compressor when hammering is heard.
Liquid separator should be mounted in suction
pipe.

8. Liquid stroke in compressor during operation

8.23 Refrigerant gas in liquid line Expansion valve is oscillating.

8.39 Superheating of expansion valve Adjust superheating, which should normally be


is set too low 5-8°C.

86 0171-231-EN
9. Excessive condenser pressure
In the event of abnormally high pressures in the refrigeration system, there is a risk of
damage to the compressor. At very high pressures (see pressure testing), the risk of
the components in the refrigeration plant exploding can constitute a threat to life.
Abnormally high pressures can occur in the case of:
- extreme heating of plant parts (fire, solar radiation or other abnormal heating);
- volumetric expansion of fluids in sealed-off premises.

9.25 Overfilling with refrigerant Refrigerant fills condenser and reduces its ef-
fective area.
Draw off coolant.

9.28 Insufficient condenser cooling, Regulate water/air supply or reduce compres-


e.g. if cooling water fails, fan/ sor capacity, if called for. Check condenser as
coling water pump clogs, soiling, per instructions for same.
scaling or fouling of heat-transmit-
ting surfaces
9.30 Presence of non-condensable Blow air out at condenser. Follow instructions
gases (especially air) in conden- for condenser.
ser.

10. Too low condenser pressure

10.32 Excessive condenser cooling Regulate condenser cooling.

10.51 Defective piston rings or worn cy- Replace worn parts. See compressor instruc-
linders tions.

10.52 Discharge valves are defective or See compressor instructions. Check valve ring
leaky plates and piston rings.

10.54 Bypass between high-pressure Check compressor for internal leakage by per-
side and suction side of compres- forming pressure-drop test.
sor
See compressor instructions.

10.60 Compressor lacks capacity. Check whether compressor capacity corre-


sponds to load on plant. Reduce condenser
cooling.

0171-231-EN 87
11. Excessive suction pressure

11.26 Error in setting of liquid regulation Liquid refrigerant in suction line.


valve
Adjust, repair or replace expansion valve.

11.53 Leaky suction valves See compressor instructions. Remove cylinder


covers; check valve plates. Renew if needed.

11.54 Open by-pass between suction si- Check system for any by-pass detectable as a
de and high-pressure side of com- warm connection.
pressor. Safety valve leaky, or
opens prematurely. Adjust or repair leaky valves.

11.60 Compressor lacks capacity. Regulate compressor capacity.


Check whether all cylinders are operating.
Check function of capacity regulator.

12. Too low suction pressure


Abnormally low pressure in the refrigeration plant will increase the compression ratio
of the compressor with a subsequent risk of damage to the compressor.
The danger of air being sucked into the refrigeration plant also increases at abnor-
mally low pressure.
12.20 Oil in evaporator Draw off oil.

12.22 Refrigerant charge on plant insuffi- Check refrigerant charge.


cient
Charge plant with refrigerant.
Bubbles in liquid line sight glass
and possibly a warm liquid line Find and seal any leak.

12.35 Freezing-up of expansion valve Thaw out expansion valve with hot, wet cloths.
(HFC/HCFC plant)
Replace dessicant in drying filter.

12.36 Thermostatic expansion valve has Valve fails to open - change valve.
lost charge

12.40 Excessive superheating of suc- Regulate expansion valves to higher capacity.


tion gas

88 0171-231-EN
12.41 Filter in liquid line clogged Check and clean filter in liquid line.

12.42 Solenoid valve in liquid line fails to Coil may have blown. Control signal lacking.
open

12.59 Compressor has excessive capa- Reduce compressor capacity.


city
Check capacity regulating system.

13. Oil temperature too low

13.15 Too little oil in compressor Top up compressor with oil and investigate
cause of oil consumption.

13.18 Oil foams in compressor See point 18.

13.49 Oil pump defective Repair or replace.

13.50 Bearings worn Repair or replace.

13.55 Oil filter clogged Change filter cartridge

14. Excessive discharge pipe temperature

If, after approx. 1 hour’s operation, the discharge pipe temperature is more than
10°C higher than indicated in the table, the error may be due i.a. to:

14.21 Excessive suction temperature as Check refrigerant charge


result of reduced refrigerant sup-
ply to evaporator (extensive su-
perheating) owing to insufficient
refrigerant charge.

14.22 Excessive suction temperature as Check thermostatic expansion valves


result of reduced refrigerant sup-
ply to evaporator (extensive su-
perheating) owing to incorrectly
adjusted liquid regulating valves

14.52 Leaky discharge valves Leaking in discharge valves gives rise to gen-
eration of heat.
Change defective valves.

14.54 Open by-pass between high and Localize by-pass and remedy any leakages.
low-pressure side of compressor,
e.g. leaky safety valve

0171-231-EN 89
15. Too low discharge pipe temperature

15.26 Low suction temperature as result Adjust liquid regulating valve. Increase super-
of overflow of liquid refrigerant heating.
from evaporator

16. Excessive oil temperature

During operation, the heat of the compressor crankcase must be 40-70°C. When
working with R717 and R22, it may be necessary to supply the compressor with oil
cooling.
See point 14.

17. Oil level in crankcase falling

Where HFC/HCFC refrigerants are used, there will be some blending of refrigerant
and oil during the initial operating period. It may therefore prove necessary to top up
the oil after initial start-up of the plant.
Note:
The oil level must always be visible in the oil level sight glass on the compressor.

17.20 Filter in solenoid valve or jet in oil Oil return pipe must be warm during opera-
return line clogged tions. Clean filter.

17.26 Liquid in suction line and crank- Examine evaporator system and check super
case may cause foaming in oil heating of suction gas.
and thus increase oil consumption

17.51 Worn-out piston rings or cylinders Renew piston rings and, if need be, renew pis-
tons and cylinder linings.

17.57 Solenoid valve in oil return line de- Coil in solenoid valve defective.
fective - Replace coil.
- Electrical control signal lacking.

90 0171-231-EN
18. Heavy oil foaming in crankcase

18.26 Liquid in suction line See 17.26.

18.61 Too much refrigerant dissolved in - Before starting compressor, heating element
oil must have been on for at least 8 hours in
order to boil refrigerant out of oil. During
start-up phase, capacity should be con-
nected at a slow rate to prevent sudden drop
in pressure on suction side with resultant
foaming.
- Under normal operating conditions, com-
pressor should operate under as stable
pressure conditions as possible.

19. Crankcase sweating or frosting up

19.26 Liquid in suction line See 17.26.

19.37 Expansion valve sensor misplaced Check positioning of expansion valve sensor -
cf. instructions for expansion valve.

19.39 Liquid regulating valve or float val- Increase superheating on thermostatic expan-
ve producing too much liquid sion valve.

20. Capacity regulation oscillating

20.18 Oil foaming in crankcase See point 18.

21. Impossible to bleed plant

21.43 Solenoid valve leaky Pinpoint and seal leak, or change leaky com-
ponent.

21.51 Defective piston rings Check and replace any defective parts.

21.52 Defective discharge valves Check and replace any defective parts.

21.53 Defective suction valves Check and replace any defective parts.

0171-231-EN 91
Selecting lubricating oil for SABROE compressors

During the past few years YORK Lubricating oils with relatively high viscosities
Refrigeration has experienced a number of must be used to ensure satisfactory lubrica-
problems with mineral oils, particularly in tion of refrigeration compressors.
R717 plants. The problems can be divided
To obtain the best lubrication, the oil must:
into two groups:
S Provide the required fluidity at the lowest
a: The oil changes viscosity evaporating temperature encountered in
b: The oil decomposes (becomes very black) the plant and at the highest permissible
temperatures in the compressors.
The problems have been seen with several
S Provide acceptable fluidity at start-up.
mineral oil brands, often occuring within a
few operating hours and resulting in severe S Provide sufficient oxidation stability (the oil
consequences for both compressor and must be moisture-free when added to the
system).
plants.
S Provide sufficient chemical stability when

99.02
Following the careful investigation undertak- used together with the particular refriger-
en by YORK Refrigeration during the past ant.
few years, it has been decided to introduce a In addition, the extent to which different re-

0170-151-EN
range of synthetic oils which can fulfil the de- frigerants dissolve in the oil must be deter-
mands of modern refrigeration plants. mined, so that the oil return systems, etc. can
be designed to function properly.
Mineral oils may continue to be used in re-
frigeration plants, providing the lubricating Stratification
quality is carefully monitored. For modern, It should be noted that in certain plants, par-
high capacity refrigeration plants, where long ticularly with HFC and HCFC refrigerants, the
lifetime for both lubricants and moving parts oil may stratify into layers in the refrigerant
is expected, YORK Refrigeration recom- receivers and evaporators at certain operat-
mends the choice of synthetic lubricating oils. ing conditions and at particular oil concentra-
tions.
The application areas and specifications for
these synthetic oils can be found in the fol- The Oil recommendation diagrams for
lowing pages. Installers and/or users are at SABROE compressors for HFC and HCFC
liberty to choose either YORK Refrigeration’s will indicate the limits for Sabroe oils at which
own or alternative oil brands which fulfil the this stratification occurs. The oil concentra-
necessary specifications. tions stated in these diagrams must not be
exceeded. This will enable suitable oil rectifi-
General cation/return systems to be designed to bal-
This recommendation only deals with the lu- ance with the compressor oil ”carry-over” so
brication of the compressor. The perfor- that the maximum concentration is not ex-
mance of the lubricant in the plant (receiver, ceeded.
evaporator, etc.) must, however, also be tak- For area A in the diagrams, the max oil con-
en into consideration. centration in liquid phase must not exceed

92 0170-151-EN
2%. For the other area, the max. oil con- In the oil recommendation diagrams for each
centration must not exceed 5%. For area B: refrigerant and compressor type, it is pos-
please contact YORK Refrigeration. sible to determine the code number for the
oil best suited to the operating conditions.
Plants with several different compressor With this code number, it is possible to se-
types/makes lect the correct Sabroe oil for the application.
In plants comprising several different inter- The marked area on each side of the sepa-
connected compressor types and makes, it is rating line in the diagram shows the zone
strongly recommended that all compressors where both oils are useable.
should use the same type of oil. This is es-
sential where automatic oil return systems Oil types and oil companies
are employed. As a result of the large number of oil compa-
nies world-wide that deals in oil for refrigera-
If it is intended to change the oil from one tion plants, it is impossible for YORK
type to another, please refer to the Oil chang- Refrigeration to test the many different
ing on SABROE compressors later in this brands of oil on the market. It is our experi-
publication. ence, however, that some oil brands during
use can change character and thus no longer
Selecting the lubricating oil fit the specifications given by the companies
There are a number of operating diagrams at delivery. We have thus experienced
for the selection of lubricating oils for Sabroe changes in the specifications as well as in
compressors operating with various refriger- the formula and performance without having
ants. Once the general conditions concern- had any information about this from the oil
ing the lubrication of the compressor and oil company. This makes it very difficult for
type in the plant have been considered, the YORK Refrigeration to give a general ap-
specific plant conditions must be taken proval of the various oil brands.
into consideration.

Use the Oil recommendation diagrams to se- For this reason YORK Refrigeration has, in
lect the appropriate oil code number. cooperation with a large recognised oil com-
pany, developed a series of three oils which
The oil code number consists of letters des- cover most purposes. YORK Refrigeration
ignating the oil type together with the Sabroe has however, also listed a limited number of
viscosity grade number. oils which can be supplied through YORK
Refrigeration. The typical data of these oils
Code can be found in the Data Sheet for Sabroe
Oil types
design Oils. We suggest you to use these Sabroe
M Mineral oil oils, which are delivered in 20 litre pails and
Synthetic oil based on 208 litre drums and can be ordered using the
A
Alkylbenzene
parts no. listed in the List of Oils.
Synthetic oils based on
PAO
Polyalphaolefin
AP Mixture of A and PAO-oils It is of course possible to use similar oils from
E Synthetic ester-based lubricants other oil companies, and in this connection,

0170-151-EN 93
the Data Sheet for Sabroe Oils may be help- Screw compressors:
ful. The oil temperature before injection in
the compressor, but after the oil cooler
Please note, however, that YORK
Refrigeration has not tested any other oils Max. permitted oil temperature = set-
than our own brand, and hence we cannot ting point for alarm
answer for the quality, the stability or the suit- Min. permitted oil temperature = set-
ability of other oils for any purposes. The oil ting point for alarm
company in question is thus solely responsi- • Condensing pressure
ble for the quality and suitability of the oil de- • Evaporating pressure
livered, and if any problems are experienced
S Oil viscosity in the compressor during
with these oils in the compressors or in the
operation and under the influence of:
refrigeration plant, the oil supplier should be
contacted directly. • Refrigerant type and solubility of refrig-
erant in the oil
When choosing oils from other oil compa-
• Operating temperatures
nies, please pay particular attention to the
oil’s effectiveness in the compressor and the • Vapour pressure in the oil reservoir
refrigeration plant as a whole. Reciprocating compressor: Suction
pressure and oil temperature in the
Pay particular attention to the following as- crankcase.
pects:
Screw compressor: Discharge pressure
S Oil type and gas temperature.

S Refrigerant type S Compatibility with the neoprene O-rings:


the aniline point gives an indication of how
S Compressor type
the O-ring material reacts to the oil.
S Miscibility between refrigerant and oil At an aniline point less than approximately
S Operating data for the compressor 100°C the material tends to swell, and at
• Discharge gas temperature an aniline point higher than approximately
• Oil temperatures: 120°C it tends to shrink.

Reciprocating compressors:
For this reason it is not recommended to
Normal oil temp. in the crankcase change oil type from M oil to PAO oil as a
50-60 °C leakage may occur if the O-rings are not
Max. permitted oil temperature = Set- changed. YORK Refrigeration therefore
ting point for alarm recommends using the Sabroe AP68 oil
Min. permitted oil temperatures = set- as it reduces the risk of leaks considerably
ting point for alarm - if fitted in this case.

94 0170-151-EN
YORK Refrigeration can supply a calculation YORK Refrigeration is aware, however, that
showing the operating data on request. several customers have been using mineral
oils for many years without problems. Those
Attention is drawn to the following viscosity customers who wish to continue using miner-
limits during operation: al oils in existing, as well as new, compres-
sors can do so, providing the compressor
S Optimum viscosity range
type and operating conditions are similar to
(to be designed for) = 20 to 50 cSt
the existing ones (excepting the HPC and
S Max. permissible viscosity =100 cSt HPO series compressors).
S Min. permissible viscosity =10 cSt
(only applicable to HCFC and HFC under YORK Refrigeration has therefore decided to
cartain operating conditions: 7cSt)
market a brand of mineral oil which has been
S Max. permissible viscosity during the tested and found to be suitable for most gen-
starting of the compressor = 500 cSt eral refrigerating purposes.
Maximum refrigerant concentration in the oil
at running condition: 25% - also if viscosity If another brand of mineral oil is chosen, the
requirements are met. specifications in the data sheet in this recom-
mendation should be followed as a guideline.
Use of mineral oil
Lately we have experienced a number of
Mineral oil can be used in refrigerating
problems with mineral oil, particularly in R717
plants, providing the lubricating quality is
plants. The problems can be divided into two
carefully monitored. For modern, high capac-
groups:
ity refrigeration plants, in which a long life-
a: The oil changes viscosity within a few time for both lubricant and moving parts is
operating hours. expected, YORK Refrigeration recommends
b: The oil decomposes (becomes very using synthetic lubricating oils.
black) within a few operating hours.
A benefit of using the synthetic lubricant oil is
The problems have been seen with several
a much lower oil carry-over to the plant and
oil brands and have resulted in severe con-
longer intervals between oil changes.
sequences for both compressors and plants.
A better fluidity at lower temperatures also
gives an easier drainage at the cold parts of
When using mineral oil, it is thus important
the plant.
that the plant is monitored very closely, that
oil samples are taken regularly (every
1-2,000 hours) and that the condition/colour
How to use the oil recommendation dia-
of the oil is checked on a weekly basis.
grams:
YORK Refrigeration therefore recom- To determine the code number, first refer to
mends only to use M oil at moderate oper- the Oil recommendation diagram for the re-
ating conditions - cf. the attached oil rec- frigerant and compressor type and then plot
ommendation diagrams. the proposed operating conditions.

0170-151-EN 95
Example (recip. compressors): the example above, a oil code number E5
Refrigerant: R134a can be selected.
Condensing temp. TC +35°C
Evaporating temp. TE –3°C Code no Area no
1 2
Please observe !
E5 Y
Plants may operate at different conditions
from time to time, for example at different E9 Y
evaporating temperatures due to plant
In plants which incorporate both screw and
variations or at different condensing tem-
reciprocating compressors and where the
peratures due to seasonal changes.
recommendations indicate the use of differ-
By plotting TC and TE in the oil recom-
ent oil types, please contact YORK
mendation diagram, this example would
Refrigeration for advice.
require a No 1 oil. If, however, TE
changes at certain times, e.g. from –3 to Changing oil on Sabroe compressors
+7°C, a No 2 oil should be utilised. But, as
The oil should never be changed to another
+7°C is inside the marked area, the No 1
type without consulting the oil supplier. Nor is
oil can be utilised also at this TE.
it advisable to ”top up” compressors with an
R134a other oil than the one already used for the

ÎÎ
TC
particular plant and compressor.
°F °C
158 70

140 60 ÎÎ
ÎÎ 2
Mixing different oils may result in operating
problems in the refrigerant plant and damage
122 50
ÎÎ
• ÎÎ
to the compressors. Incompatibility between
Condensing temperature


104 40
the different oil types may degrade the lubri-
86 30

68 20 1 ÎÎ
ÎÎ
cating properties or may cause oil residues to
form in the compressor or oil separator or in
50 10
the plant. These oil residues can block filters
32 0
and damage the moving parts in the com-
14 -10
pressor.
-4 -20

-22 -30 Furthermore, changing the oil from one type


-60 -50 -40 -30 -20 -10 0 10 20 30 ° C
or make to another should only be undertak-
TE
-76 -58 -40 -22 -4 14 32 50 68 86 ° F en in connection with a careful procedure in-
Evaporating temperature
volving the drainage and thorough evacua-
By referring to the Oil recommendation table tion of the refrigeration plant. Information on
placed at the bottom of each oil recommen- a suitable procedure can be obtained from
dation diagram, it is possible to select the YORK Refrigeration as well as from a num-
code number for the appropriate oil type. In ber of oil companies.

96 0170-151-EN
It is imperative that oil is only used from the Oil drums should, ideally, be ”racked” and
original container and that both the make and mounted with a proper barrel tap to ensure
type complies with the specification for the an effective airtight seal.
plant.
Oil changing intervals
Ensure that the original container is sealed A list of the recommended intervals for
during storage to prevent moisture from the changing the oil can be found in the com-
air being absorbed into the oil - many oils, pressor instruction manual. These are pro-
particulary the polyolester oils, are extremely vided for guidance only. The actual interval
hygroscopic. Consequently, it is recom- between oil changes will often be determined
mended that the oil is only purchased in con- by a variety of operating parameters within
tainers corresponding to the amount to be the plant.
used on each occasion.
It is strongly recommended to monitor the
If the oil is only partially used, make sure that quality of the oil by carrying out oil analyses
it is effectively re-sealed in the original con- with regular intervals. This will also give a
tainer and that it is stored in a warm, dry good indication of the condition of the plant.
place. Ideally with nitrogen blanking of the oil The service can be supplied by YORK
to keep the water content below 50 ppm. Refrigeration or the oil suppliers.

Oil recommendation diagram symbols:


YĂ : In case of a new plant. Very suitable.
lĂ : In case you wish to change from mineral oil
A : Max oil concentration in liquid phase at: TE: 2% W
B : Max oil concentration in liquid phase: contact YORK Refrigeration
C : Min suction temperature –50°C: at TE< –50°C superheating must be introduced.
* : Dry expansion systems only. Flooded systems to be considered individually: contact YORK Refrigeration

ÑÑÜ
SH : Suction gas superheat, K (Kelvin)

Ü
: Zone in which both oils are useable
: Calculation must be performed using COMP1

0170-151-EN 97
Data sheet for listed Sabroe oils
Typical data for lubricating oils for Sabroe compressors

Sabroe Viscosity Viscosity Spec. Flash p. Pour p. Anilin Acid no.


code cSt cSt Index grav. at COC °C °C mg
40°C 100°C 15°C °C point KOH/g
M1 63 6.4 14 0.91 202 –36 81 0.02
A3 97 8.1 13 0.86 206 –32 78 0.05
AP1 64 9.3 121 0.858 195 –51 121 0.04
PAO3 66 10.1 136 0.835 266 <–45 138 0.03
PAO5 94 13.7 147 0.838 255 <–45 144 0.03
PAO9 208 25 149 0.846 260 <–39 154 0.03
E3
Due to the big difference between polyolester-based lubricants from various suppliers, it is
E5
not possible to present typical data for these oils. When using another oil brand than the one
E9 recommended by YORK Refrigeration, please contact the oil supplier to select the correct
oil type.
E11

The listed data are typical values and are intended as a guideline only when selecting a similar
oil from a different oil company. Data equivalence alone does not necessarily qualify the oil for
use in YORK Refrigeration’s Sabroe compressors.

98 0170-151-EN
List of part numbers for available Sabroe oils

Part no.
Oil brand Oil code no.
20 litre pail 208 litre pail
Mobil Gargoyle Arctic 300 M 1 (M68) 1231-264 1231-296
Sabroe Oil A100 A 3 (A100) 1231-263 1231-262
Sabroe Oil AP68 AP 1 (AP68) 1231-257 1231-260
Sabroe Oil PAO68 PAO 3 (P68) 1231-256 1231-259
Mobil Gargoyle Arctic SHC 228 PAO 5 (P100) 1231-282 1231-283
Mobil Gargoyle Arctic SHC 230 PAO 9 (P220) 1231-284 1231-285
Mobil EAL Arctic 68 E 3 (E68) 1231-272 1231-273
Mobil EAL Arctic 100 E 5 (E100) 1231-274 1231-275
Mobil EAL Arctic 220 E 9 (E220) 1231-279
Sabroe H oil E11 (E370) 3914 1512 954 1) 9415 0008 000
1) 18.9 litre pail (5 US gallons)

The oils recommended by the former Stal Refrigeration correspond to the following oils:

Stal Refrigeration oil type Sabroe oil

A Mobil Gargoyle Arctic 300 – M1 (M68)


B Sabroe Oil PAO 68 – PAO 3 (PAO 68)
C Mobil Gargoyle Arctic SHC 230 – PAO 9 (PAO 220)
H Sabroe H oil – E 11 (E 370)

0170-151-EN 99
R717 TC
one-stage
°F °C
reciprocating
122 50
compressors
104 40
Condensing temperature
86 30

68 20 1

50 10

32 0

Code no Area no 14 -10


1
-4 -20
PAO 3 Y

-22 -30
AP 1 l/Y -60 -50 -40 -30 -20 -10 0 10 20 °C
TE
M1 See note -76 -58 -40 -22 -4 14 32 50 68 °F
Evaporating temperature

Note: YORK Refrigeration recommends that the use of M oils is restricted to moderately loaded compressors and
that the oil quality is monitored carefully via regular oil analyses.
Y : In case of a new plant. Very suitable.
lĂ : In case you wish to change from mineral oil

100 0170-151-EN
R717 TC
two-stage
°F °C
reciprocating
122 50
compressors
104 40
Condensing temperature
86 30
1
68 20

50 10

32 0

Code no Area no 14 -10


1
-4 -20
PAO 3 Y

-22 -30
AP 1 l/Y -60 -50 -40 -30 -20 -10 0 10 20 °C
TE
M1 See note -76 -58 -40 -22 -4 14 32 50 68 °F
Evaporating temperature

Note: YORK Refrigeration recommends that the use of M oils is restricted to moderately loaded compressors and
that the oil quality is monitored carefully via regular oil analyses.
Y : In case of a new plant. Very suitable.
lĂ : In case you wish to change from mineral oil

0170-151-EN 101
R717 TC
HPO and HPC
°F °C
reciprocating
176 80
compressors
158 70
Condensing temperature
140 60
1
122 50

104 40

86 30

68 20

50 10
Code no Area no
1 32 0
PAO 5 Y -30 -20 -10 0 10 20 30 40 50 °C
TE
-22 -4 14 32 50 68 86 104 122 °F
Evaporating temperature

Please observe: PAO 5 oil is the only oil which can be used in the HPO and HPC compressors.
Y : In case of a new plant. Very suitable.

102 0170-151-EN
R22 TC Contact YORK Refrigeration

one-stage
°F °C
reciprocating 2
122 50
compressors
104 40
Condensing temperature
86 30
1
68 20

50 10

32 0

14 -10 A
Code no Area no -4 -20
1
-22 -30
A3 Y
-60 -50 -40 -30 -20 -10 0 10 20 °C
TE
-76 -58 -40 -22 -4 14 32 50 68 ° F
C Evaporating temperature

YĂ : In case of a new plant. Very suitable.


A : Max oil concentration in liquid phase at: TE: 2% W
C : Min suction temperature –50°C: at TE< –50°C superheating must be introduced.

0170-151-EN 103
R22 TC
two-stage
°F °C
reciprocating
122 50
compressors
104 40
Condensing temperature
86 30 1
A
68 20

50 10

32 0

14 -10

Code no Area no -4 -20


1
-22 -30
A3 Y -60 -50 -40 -30 -20 -10 0 10 20 °C
TE
-76 -58 -40 -22 -4 14 32 50 68 °F
C Evaporating temperature

YĂ : In case of a new plant. Very suitable.


A : Max oil concentration in liquid phase at: TE: 2% W
C : Min suction temperature –50°C: at TE< –50°C superheating must be introduced.

104 0170-151-EN
R134a
TC

ÑÑ
°F °C
one-stage

ÑÑ
158 70
reciprocating
ÑÑ
140 60 2
compressors
122 50
ÑÑ
ÑÑ
Condensing temperature
ÑÑ
104 40

86

68
30

20 1
ÑÑ
ÑÑ
50 10

32 0

14 -10
Code no Area no
-4 -20
1 2
-22 -30
E5 Y
E9 Y
-60 -50 -40 -30 -20 -10 0 10 20 30 ° C
TE
-76 -58 -40 -22 -4 14 32 50 68 86 ° F
Evaporating temperature

ÑÑ
YĂ:

ÑÑ:
In case of a new plant. Very suitable.
Zone in which both oils are useable

0170-151-EN 105
R134a TC

two-stage °F °C
reciprocating 158 70
compressors 140 60

122 50
Condensing temperature 1
104 40

86 30

68 20

50 10

32 0

14 -10

-4 -20
Code no Area no
-22 -30
1
-40 -40
E5 Y
-70 -60 -50 -40 -30 -20 -10 0 10 20 30 °C
TE
-94 -76 -58 -40 -22 -4 14 32 50 68 86 ° F
Evaporating temperature

Y : In case of a new plant. Very suitable.

106 0170-151-EN
R407C TC
one-stage
°F °C
reciprocating
122 50
compressors
104 40
Condensing temperature
86 30

68 20

1
50 10

32 0

14 -10
B
Code no Area no -4 -20
1
-22 -30
E3 Y -60 -50 -40 -30 -20 -10 0 10 20 °C
TE
-76 -58 -40 -22 -4 14 32 50 68 °F
C Evaporating temperature

YĂ: In case of a new plant. Very suitable.


B : Max oil concentration in liquid phase: contact YORK Refrigeration
C : Min suction temperature –50°C: at TE< –50°C superheating must be introduced.

0170-151-EN 107
R407C TC
two-stage
°F °C
reciprocating
122 50
compressors
104 40
Condensing temperature
86 30 1
68 20 B

50 10

32 0

14 -10

Code no Area no -4 -20


1
-22 -30
E3 Y -60 -50 -40 -30 -20 -10 0 10 20 °C
TE
-76 -58 -40 -22 -4 14 32 50 68 °F
C Evaporating temperature

YĂ: In case of a new plant. Very suitable.


B : Max oil concentration in liquid phase: contact YORK Refrigeration
C : Min suction temperature –50°C: at TE< –50°C superheating must be introduced.

108 0170-151-EN
R404A TC
one-stage
°F °C
reciprocating
compressors
122 50 ÑÑ
ÑÑ
104 40
ÑÑ
ÑÑ
2

ÑÑ
Condensing temperature
86 30

68 20 ÑÑ
ÑÑ
50 10 1
ÑÑ
32 0

Code no Area no 14 -10

1 2
-4 -20
E3 Y
-22 -30
E5 Y -60 -50 -40 -30 -20 -10 0 10 20 °C
TE
-76 -58 -40 -22 -4 14 32 50 68 °F
C Evaporating temperature

ÑÑ
YĂ: In case of a new plant. Very suitable.

ÑÑ
C : Min suction temperature –50°C: at TE< –50°C superheating must be introduced.
: Zone in which both oils are useble

0170-151-EN 109
R404A TC
two-stage
°F °C
reciprocating
122 50
compressors
104 40
Condensing temperature
86 30
1
68 20

50 10

32 0

14 -10

Code no Area no -4 -20


1
-22 -30
E3 Y -60 -50 -40 -30 -20 -10 0 10 20 °C
TE
-76 -58 -40 -22 -4 14 32 50 68 °F
C Evaporating temperature

YĂ: In case of a new plant. Very suitable.


C : Min suction temperature –50°C: at TE< –50°C superheating must be introduced.

110 0170-151-EN
R410A TC
HPO og HPC
°F °C
reciprocating
122 60
compressors
50
104
40
86
Condensing temperature

30
68 20

10 1
50

0
32
A
-10
14
-20
Code no Area no -4
-30
1
-22 -40
E5 Y

-60 -50 -40 -30 -20 -10 0 10 20 30 40 50


TE
-76 -58 -40 -22 -4 14 32 50 68 °F
Evaporating temperature

YĂ: In case of a new plant. Very suitable.


A : Max oil concentration in liquid phase at: TE: 2%

0170-151-EN 111
R507 TC
one-stage
°F °C
reciprocating
122 50
compressors
104 40
Condensing temperature
86 30

68 20
1
50 10

32 0

14 -10

Code no Area no -4 -20


1
-22 -30
E5 Y -60 -50 -40 -30 -20 -10 0 10 20 °C
TE
-76 -58 -40 -22 -4 14 32 50 68 °F
C Evaporating temperature

YĂ: In case of a new plant. Very suitable.


C : must be introduced.
Min suction temperature –50°C: at TE< –50°C superheating most

112 0170-151-EN
R507 TC
two-stage
°F °C
reciprocating
122 50
compressors
104 40
Condensing temperature
86 30
1
68 20

50 10

32 0

14 -10

Code no Area no -4 -20


1
-22 -30
E5 Y -60 -50 -40 -30 -20 -10 0 10 20 °C
TE
-76 -58 -40 -22 -4 14 32 50 68 °F
C Evaporating temperature

YĂ: In case of a new plant. Very suitable.


C : Min suction temperature –50°C: at TE< –50°C superheating must be introduced.

0170-151-EN 113
R717 TC

Screw compressors °F °C
ÜÜÜÜÜÜÜ
122 50
ÜÜÜÜÜÜÜ
ÜÜÜÜÜÜÜ
Condensing temperature
104 40
ÜÜÜÜÜÜÜ
ÜÜÜÜÜÜÜ
ÜÜÜÜÜÜÜ
86 30

68 20
ÜÜÜÜÜÜÜ
ÜÜÜÜÜÜÜ
1

50

32
10

0
ÜÜÜÜÜÜÜ
14 -10
Code no Area no
1 -4 -20
PAO 3 Y
-22 -30
AP 1 l/Y 20 °C
-60 -50 -40 -30 -20 -10 0 10
TE
M1 See note -76 -58 -40 -22 -4 14 32 50 68 °F
C Evaporating temperature

Note: YORK Refrigeration recommends that the use of M oils is restricted to moderately loaded compressors and
that the oil quality is monitored carefully via regular oil analyses.
HLI: Calculation must be performed using COMP1
YĂ : In case of a new plant. Very suitable.
lĂ : In case you wish to change from mineral oil

ÜÜ
C :

ÜÜ :
Min suction temperature –50°C: at TE< –50°C superheating must be introduced.
Calculation must be performed using COMP1.

114 0170-151-EN
R22 TC

ÜÜÜÜÜÜ
ÒÒÒÒÒÒÒÒÒÒÒ
ÚÚÚÚÚÚÚÚÚÚÚ
ÔÔÔÔÔÔÔÔÔÔ
SH25
Screw compressors °F °C

ÜÜÜÜÜÜ
ÒÒÒÒÒÒÒÒÒÒÒ
ÚÚÚÚÚÚÚÚÚÚÚ
ÔÔÔÔÔÔÔÔÔÔ
ŠŠŠŠŠŠŠŠŠ
ÜÜÜÜÜÜ
ÒÒÒÒÒÒÒÒÒÒÒ
ÚÚÚÚÚÚÚÚÚÚÚ
ŠŠŠŠŠŠŠŠŠ
122 50
2
104 40
ÜÜÜÜÜÜ
ÒÒÒÒÒÒÒÒÒÒÒ
ÚÚÚÚÚÚÚÚÚÚÚ
ŠŠŠŠŠŠŠŠŠ
ÜÜÜÜÜÜ
ÒÒÒÒÒÒÒÒÒÒÒ
ÚÚÚÚÚÚÚÚÚÚÚ
ŠŠŠŠŠŠŠŠŠ
SH20
Condensing temperature

ÜÜÜÜÜÜ
ÚÚÚÚÚÚÚÚÚÚÚ
ŠŠŠŠŠŠŠŠŠ
86 30 SH5

68 20
ÜÜÜÜÜÜ
ÚÚÚÚÚÚÚÚÚÚÚ
ŠŠŠŠŠŠŠŠŠ
ÜÜÜÜÜÜ 1
SH10

50 10
ÜÜÜÜÜÜ
ÒÒÒÒÒÒÒÒ
32 0 ÒÒÒÒÒÒÒÒ
A

ÒÒÒÒÒÒÒÒ
Code no Area no
14 -10
ÒÒÒÒÒÒÒÒ
ÒÒÒÒÒÒÒÒ
ÒÒÒÒÒÒÒÒ
1 2* SH20
-4 -20
A3 Y
-22 -30
PAO 5 Y -60 -50 -40 -30 -20 -10 0 10 20 °C
TE
-76 -58 -40 -22 -4 14 32 50 68 °F
C Evaporating temperature

Using the calculating programme COMP1 it is possible to optimize the requirement for suction superheat values
(SH) as stated in the diagram. See Oil types and oil companies in this section. Due to the ongoing development of
lubrication oils, please contact YORK Refrigeration for an update on the requirement for superheat.

HLI: Calculation must be performed using COMP1.

YĂ : In case of a new plant. Very suitable.


A : Max oil concentration in liquid phase at: TE: 2% W
C : Min suction temperature –50°C: at TE< –50°C superheating must be introduced.
* : Dry expansion systems only. Flooded systems to be considered individually: contact YORK Refrigeration

ÜÜ
SH : Suction gas superheat, K (Kelvin)
: Calculation must be performed using COMP1

0170-151-EN 115
R134a TC

Screw compressors °F °C
ÜÜÜÜÜÜÜÜ
ÏÏÏÏÏÏÏÏ
ÒÒÒÒÒÒÒÒÒÒ SH30
158 70
ÜÜÜÜÜÜÜÜ
ÏÏÏÏÏÏÏÏ
ÒÒÒÒÒÒÒÒÒÒ
ÚÚÚÚÚÚÚÚÚÚ
ÜÜÜÜÜÜÜÜ
140 60 ÒÒÒÒÒÒÒÒÒÒ
ÚÚÚÚÚÚÚÚÚÚ
ŠŠŠŠŠŠŠŠŠ
ÜÜÜÜÜÜÜÜ
ÚÚÚÚÚÚÚÚÚÚ
ŠŠŠŠŠŠŠŠŠ
SH20

122 50
ÜÜÜÜÜÜÜÜ
ÚÚÚÚÚÚÚÚÚÚ
ŠŠŠŠŠŠŠŠŠ
ÑÑÑÑÑÑÑ
ÜÜÜÜÜÜÜÜ
Condensing temperature
104 40 ÚÚÚÚÚÚÚÚÚÚ
ŠŠŠŠŠŠŠŠŠ
ÑÑÑÑÑÑÑ
ÜÜÜÜÜÜÜÜ
ŠŠŠŠŠŠŠŠŠ
ÑÑÑÑÑÑÑ
2 SH10

ÜÜÜÜÜÜÜÜ
ŠŠŠŠŠŠŠŠŠ
ÑÑÑÑÑÑÑ
ŠŠŠŠŠŠŠŠŠ
ÑÑÑÑÑÑÑ
86 30
SH5
68 20
ÑÑÑÑÑÑÑ
ÒÒÒÒÒÒÒ
ÑÑÑÑÑÑÑ
50 10
ÒÒÒÒÒÒÒ
1
ÒÒÒÒÒÒÒ
Code no Area no
32 0
ÒÒÒÒÒÒÒ
ÒÒÒÒÒÒÒ
ÒÒÒÒÒÒÒ
(See note) 14 -10
1 2 SH20
E5 Y -4 -20
E9 Y -50 -40 -30 -20 -10 0 10 20 30 °C
TE
-58 -40 -22 -4 14 32 50 68 86 ° F
Evaporating temperature

Note: For the compressors type ”S”, ”Rotatune”, ”SAB 81”, ”SAB 83”, and ”SAB 85” only Sabroe oil H is approved.
Using the calculating programme COMP1 it is possible to optimize the requirement for suction superheat values
(SH) as stated in the diagram. See Oil types and oil companies in this section. Due to the ongoing development
of lubrication oils, please contact YORK Refrigeration for an update on the requirement for superheat.
HLI: Calculation must be performed using COMP1.
YĂ : In case of a new plant. Very suitable.

Ñ
SH : Suction gas superheat, K (Kelvin)

Ü
: Zone in which both oils are useable
: Calculation must be performed using COMP1

116 0170-151-EN
R404A TC

Screw compressors
ÜÜÜÜÜÜÜ
ÚÚÚÚÚÚÚÚÚÚ
ÖÖÖÖÖÖ
°F °C

ÜÜÜÜÜÜÜ
ÚÚÚÚÚÚÚÚÚÚ
ÖÖÖÖÖÖ
SH15
104 40

ÜÜÜÜÜÜÜ
ÚÚÚÚÚÚÚÚÚÚ
ÑÑÑÑÑÑÑÑ
ÜÜÜÜÜÜÜ ÖÖÖÖÖÖ
Condensing temperature
86 30
ÚÚÚÚÚÚÚÚÚÚ
ÑÑÑÑÑÑÑÑ
ÜÜÜÜÜÜÜ
ÑÑÑÑÑÑÑÑ 3 SH10
2 (3)

ÜÜÜÜÜÜÜ
ÑÑÑÑÑÑÑÑ
68 20

50 10
ÜÜÜÜÜÜÜ
ÑÑÑÑÑÑÑÑ
ÖÖÖÖÖÖÖÖ
ÜÜÜÜÜÜÜ ÖÖ
32 0 ÑÑÑÑÑÑÑÑ
ÖÖÖÖÖÖÖÖ
ÖÖ
ÑÑÑÑÑÑÑÑ
ÖÖÖÖÖÖÖÖ 1
(2)

14 -10
ÑÑÑÑÑÑÑÑ
ÖÖÖÖÖÖÖÖ
ÖÖÖÖÖÖÖÖ
B

ÖÖÖÖÖÖÖÖ
Code no Area no
(See note) -4 -20

ÖÖÖÖÖÖÖÖ
1 2 3 SH15

E3 Y -22 -30
E5 Y -70 -60 -50 -40 -30 -20 -10 0 10 °C
E9 Y TE
-94 -76 -58 -40 -22 -4 14 32 50 °F
C Evaporating temperature
Note: For the compressors type ”S”, ”Rotatune”, ”SAB 81”, ”SAB 83”, and ”SAB 85” only Sabroe oil H is approved.
Using the calculating programme COMP1 it is possible to optimize the requirement for suction superheat values
(SH) as stated in the diagram. See Oil types and oil companies in this section. Due to the ongoing development
of lubrication oils, please contact YORK Refrigeration for an update on the requirement for superheat.
HLI: Calculation must be performed using COMP1.

YĂ : In case of a new plant. Very suitable.


B : Max oil concentration in liquid phase: contact YORK Refrigeration

ÑÑ
C : Min suction temperature –50°C: at TE< –50°C superheating must be introduced.

ÑÑ
ÜÜ
SH : Suction gas superheat, K (Kelvin)
: Zone in which both oils are useable

ÜÜ : Calculation must be performed using COMP1

0170-151-EN 117
R407C TC

Screw compressors
°F
122
°C
50 ŠŠŠŠŠŠŠŠ
ÜÜÜÜÜÜÜ ÚÚÚÚÚÚ
ŠŠŠŠŠŠŠŠ
ÜÜÜÜÜÜÜ ÚÚÚÚÚÚ
ŠŠŠŠŠŠŠŠ
ÜÜÜÜÜÜÜ ÚÚÚÚÚÚ
SH10

ŠŠŠŠŠŠŠŠ
ÜÜÜÜÜÜÜ
104 40
SH5

ÜÜÜÜÜÜÜ
ÑÑÑÑÑÑÑÑ
Condensing temperature
86 30 2

ÜÜÜÜÜÜÜ
ÑÑÑÑÑÑÑÑ
ÜÜÜÜÜÜÜ
ÑÑÑÑÑÑÑÑ
68 20

50 10
ÜÜÜÜÜÜÜ
ÑÑÑÑÑÑÑÑ
ÑÑÑÑÑÑÑÑ
ŠŠŠŠŠ 1
32 0
B
14 -10
ŠŠŠŠŠ
ŠŠŠŠŠ
ŠŠŠŠŠ
Code no Area no -4 -20
(See note) SH5
1 2
-22 -30
E3 Y -70 -60 -50 -40 -30 -20 -10 0 10 20 °C
E9 Y TE
-94 -76 -58 -40 -22 -4 14 32 50 68 ° F
C Evaporating temperature

Note: For the compressors type ”S”, ”Rotatune”, ”SAB 81”, ”SAB 83”, and ”SAB 85” only Sabroe oil H is approved.
Using the calculating programme COMP1 it is possible to optimize the requirement for suction superheat values
(SH) as stated in the diagram. See Oil types and oil companies in this section. Due to the ongoing development
of lubrication oils, please contact YORK Refrigeration for an update on the requirement for superheat.
HLI: Calculation must be performed using COMP1.
YĂ : In case of a new plant. Very suitable.
B : Max oil concentration in liquid phase: contact YORK Refrigeration
C : Min suction temperature –50°C: at TE< –50°C superheating must be introduced.

Ñ
SH : Suction gas superheat, K (Kelvin)

Ü
: Zone in which both oils are useable
: Calculation must be performed using COMP1

118 0170-151-EN
R507 TC

Screw compressors
ÜÜÜÜÜÜÜ
ÑÑÑÑÑÑÑÑ
ŠŠŠŠŠ
°F °C

104 40
ÜÜÜÜÜÜÜ
ÑÑÑÑÑÑÑÑ
ÜÜÜÜÜÜÜ ŠŠŠŠŠ
ÑÑÑÑÑÑÑÑ
ŠŠŠŠŠ 2

ÜÜÜÜÜÜÜ
ÑÑÑÑÑÑÑÑ
ŠŠŠŠŠ
86 30 SH5

Condensing temperature ÜÜÜÜÜÜÜ


ÑÑÑÑÑÑÑÑ
ŠŠŠŠŠ
ÖÖÖÖÖÖÖÖÖÖÖ
ÜÜÜÜÜÜÜ
ÑÑÑÑÑÑÑÑ
ÖÖÖÖÖÖÖÖÖÖÖ
ŠŠŠŠŠŠŠŠŠŠŠ
68 20

50 10
ÜÜÜÜÜÜÜ
ÖÖÖÖÖÖÖÖÖÖÖ
ŠŠŠŠŠŠŠŠŠŠŠ
ÜÜÜÜÜÜÜ
1 SH5

ÖÖÖÖÖÖÖÖÖÖÖ
ŠŠŠŠŠŠŠŠŠŠŠ
ÖÖÖÖÖÖÖÖÖÖÖ
ŠŠŠŠŠŠŠŠŠŠŠ
ÏÏÏÏÏÏÏ
32 0
SH15

ÖÖÖÖÖÖÖÖÖÖÖ
ŠŠŠŠŠŠŠŠŠŠŠ
ÏÏÏÏÏÏÏ
ÖÖÖÖÖÖÖÖÖÖÖ
ŠŠŠŠŠŠŠŠŠŠŠ
ÏÏÏÏÏÏÏ
14 -10

Code no Area no -4 -20


ÖÖÖÖÖÖÖÖÖÖÖ
ŠŠŠŠŠŠŠŠŠŠŠ
ÏÏÏÏÏÏÏ
ÖÖÖÖÖÖÖÖÖÖÖ
ŠŠŠŠŠŠŠŠŠŠŠ
ÏÏÏÏÏÏÏ
(See note) SH30
1 2
-22 -30
E5 Y -70 -60 -50 -40 -30 -20 -10 0 10 °C
E9 Y TE
-94 -76 -58 -40 -22 -4 14 32 50 °F
C Evaporating temperature

Note: For the compressors type ”S”, ”Rotatune”, ”SAB 81”, ”SAB 83”, and ”SAB 85” only Sabroe oil H is approved.
Using the calculating programme COMP1 it is possible to optimize the requirement for suction superheat values
(SH) as stated in the diagram. See Oil types and oil companies in this section. Due to the ongoing development
of lubrication oils, please contact YORK Refrigeration for an update on the requirement for superheat.
HLI: Calculation must be performed using COMP1.

YĂ : In case of a new plant. Very suitable.


C : Min suction temperature –50°C: at TE< –50°C superheating must be introduced.

ÑÑ
SH : Suction gas superheat, K (Kelvin)

ÜÜ
: Zone in which both oils are useable
: Calculation must be performed using COMP1

0170-151-EN 119
List of major oil companies
The oil from the companies listed below are NOT tested by YORK Refrigeration and are there-
fore NOT approved by YORK Refrigeration either. The following list reflects the information pro-
vided by the companies themselves. The assessment of durability and suitability of specific oils
for specific purposes are entirely at the companies’ own discretion. Oils tested and approved by
YORK Refrigeration can be found in the ”List of part numbers for available Sabroe oils”.

Oil Oil Types


Company M A PAO AP E
Aral
• •
Avia

BP
• • • •
Castrol
• • • •
Chevron (UK: Gulf Oil)
• • •
CPI Engineering Services
• • •
DEA
• • • •
Elf / Lub Marine 1
• • •
Esso/Exxon
• • •
Fina
• • •
Fuchs
• • • •
Hydro-Texaco
• • • •
ICI

Kuwait Petroleum (Q8)
• •
Mobil
• • • • •
Petro-Canada

Shell
• • • •
Statoil
• •
Sun Oil
• •

120 0170-151-EN
Notes:

0170-151-EN 121
Alignment of unit, AMR coupling

Where the compressor and motor are directly manufacturer prior to delivery. The following
interlinked, an AMR coupling is used; this is a sections will deal with the individual points
torsionally rigid coupling with enough radial concerning the fitter.
and axial flexibility to assimilate small move-
ments between the two machines. Alignment of unit with foundation
Whenever installing a unit directly onto the
In order to ensure compressor and motor a
foundation or machine floor, it should stand
long life as well as noise- and vibration-free
free of stresses and press down evenly on all
operation, compressor unit and coupling
supports.
need to be aligned with care. Misalignment of
the compressor unit or coupling may The unit can be installed in the following
produce stresses and vibrations which can ways:
be transmitted to the compressor and motor
S on vibration dampers
bearings and thus cause major damage.
S straight onto a foundation, using founda-

95.03
Vibrations may be caused by the following:
tion bolts.
S Distortion between compressor unit and Whichever method is used, the unit must be

0171-460-EN
foundation. aligned before hooking the connection pipes
S Distortion between compressor and base up to the installation.
frame. Vibration dampers are supplied as shown at
S Distortion between motor and base frame. the top or bottom of drawing T0177040, de-
pending whether the compressor unit is in-
S Strains from pipe connections between
tended for use on land or at sea.
compressor and plant.
The purpose of the vibration dampers is to
S Misalignment of coupling linking compres-
diminish the vibrations from the compressor
sor and motor.
unit to the foundation. In addition, the marine
S Untruth in compressor or motor shafts. vibration dampers serve to cushion vibrations
S Untruth in coupling. from the foundation to the compressor unit,
at the same time securing the unit to the
S Imperfect balancing of coupling. foundation.
S Imbalance in compressor or motor.
It is imperative that the vibration dampers be
The points up to and including coupling align- placed correctly, as shown in the completed
ment are the responsibility of the fitter setting drawing forwarded to customer or distributor.
up the unit. The other points must be This drawing is valid only for the unit in
checked by the compressor or motor question .

122 0178-225-EN
Installation on vibration dampers

1
A1
A2
H Hmax

A1
A2

T0177040_0

The vibration dampers supplied are marked Industrial Marine-


with a code, for instance LM6-60. LM6 indi- type 1 type 2
cates the size; 60 indicates the rubber hard-
Flexion min 1,0 min 3,0
ness and is therefore an expression of bear- max 2,0 max 5,0
A1-A2
ing and damping ability.
Height adjustment H = H+12 with disks
max
supplied as shown
When using vibration dampers, the machine
room floor is assumed to have the necessary
The flexion of a damper is adjusted by in-
bearing stregth and to be level enough to en-
creasing or decreasing the load in relation to
able adjustment of the vibration dampers to
the other supports. The foot can be raised by
be made within the adjusting measurements
screwing the adjusting rod down or inserting
stated on the drawing submitted.
more disks between damper and foot (marine
design), thereby increasing load and hence
In order for the individual vibration damper to also the flexion.
cushion properly, a sufficient load must be
imposed. Measure A1 and H in an unloaded Once the installation has cooled down, check
and A2 in a loaded set-up, as shown in draw- during operation that the flexion of the damp-
ing T0177040. ers is still correct!

0178-225-EN 123
Installing directly on foundation Perform this check with the bolts loosened. If
slip occurs at one or more resting surfaces,
When installing a unit directly on a concrete
shim up before tightening. If unaligned, there
foundation, the foundation should be cast in
is a risk of stresses occurring in the compres-
accordance with the foundation drawings dis-
sor frame, which will damage the bearings.
patched.

When the foundation has been cast - with the Alignment of motor with base frame
holes shown for foundation bolts - and has Check the contact faces of the motor against
set, place the unit in position, allowing it to the base frame in the same way as for the
rest on beams levelled at a suitable height so compressor.
that the foundation plates are recessed
slightly into the foundation. Stresses from piping connections
In order to prevent stress being transmitted
Check that the foundation plates are right
from piping connections between unit and
next to the base frame. This can be achieved
plant, pipes must be laid so as not to gener-
by binding them to the resting surfaces of the
ate compressive stresses or tensile strains in
base frame with steel flex.
the event of expansions or contractions due
The concrete cast down around the founda- to temperature changes. Steel piping ex-
tion bolts should contain only a small amount pands approx. 1 mm per metre per 100°C.
of water, so that it can be well tamped around We recommend that piping be laid as shown
the bolts. Low water content produces no in example 2 of the sketch. Example 1 dem-
contraction of the setting concrete. onstrates too rigid pipe laying.

10-14 days should be allowed to elapse be-


fore removing the beams and tightening the
nuts for the foundation bolts. > 1.5 m

Before that, however, remove the steel flex


and check that there is no space between the
base frame and the foundation plates. If
there is, place shims between the plates be- 1 2
fore tightening.

Alignment of compressor with base


frame T0177057_0

Check that the entire footing of the compres- Final alignment of compressor and motor can
sor makes full contact against the milled-off be performed once all piping has been con-
faces of the base frame. nected to the unit.

124 0178-225-EN
Fitting and alignment of AMR-type coupling
Installation and alignment Important:
Before any work on the coupling, ensure
In principle, alignment involves manoeuvring
that the compressor motor cannot be
the motor so as to make the shaft form an
started inadvertenly.
extension of the crankshaft.

Fig. 1
1
Compressor Motor
Z
2

X
a

A
B
C
T0177120_0/V2

Max. variation measured with a feeler


Compressor AMR Distance Torque moment gauge at a 180° turning of the af coupling
type of C
coupling Pos. 1 Pos. 2
nominal* A B Horizontal Vertical
max. min./max. max.
mm Nm Nm mm mm mm
HPO/CMO 2 225 76,0 34 0,1 0,1/0,2 0,1

HPC/SMC
312 S 103,5 147 55 0,2 0,1/0,3 0,2
104-108

SMC
350 S 114,5 147 128 0,2 0,1/0,3 0,2
112-116

SMC
450 S 149,0 295 275 0,3 0,1/0,4 0,3
180
* See Final mounting, pt. 4

0178-225-EN 125
Preliminary installation Alignment
S Check tightening of coupling flange on Check that the motor with loose bolts stands
compressor. with all four feet on the base frame. Insert
any liner plates needed where there is an air
S Tighten 8 coupling bolts securing lamellar gap beneath the feet. Tauten the bolts slight-
segments to intermediate piece to pre- ly.
scribed moment stated in table. It is worth-
while doing this before placing the inter- Achieving parallel shafts in
mediate piece in position.
horizontal plane
S Mount retaining plate from coupling S Turn coupling so that alignment gauge is
screen onto compressor and insert sup- in upper position. See fig. 1.
port ring for coupling screen over motor S Guide measuring pin (Pos. 2) towards
flange. coupling flange, using a 1.0 mm feeler
gauge, and fix pin. Remove feeler gauge.
S Insert coupling intermediate piece. Create
space between flanges either by shifting S Rotate coupling 180° and measure
entire motor or just motor coupling flange. change in distance from measuring pin to
The intermediate piece should only be flange, using feeler gauges. This change
secured to the compressor flange. Do is called ”x”.
not insert the last four bolts in the mo- S Insert shims of thickness ”y” either under
tor flange until the coupling has been both front feet or both rear feet, thereby
aligned. tilting motor in direction required. Shim
As the compressor shaft rotates during the thickness ”y” is calculated using the fol-
alignment procedure, the motor must turn lowing formula (see drawings):
with it, as the bolts in the intermediate
b
piece engage in the free holes in the mo- y = X •
2xa
tor coupling flange.

S Line up motor so that free holes in motor


feet are right over threaded holes in base
frame.

S Shift motor coupling flange to make up


distance ”C” in table. See fig. 1.
y
S Tighten two bolts in coupling hub.
On CMO units, the motor flange must be b
correctly positioned before putting the mo-
tor into place.
S After tightening motor bolts, repeat meas-
S Tighten measuring pin on coupling flange urement and compare result with values in
of compressor, as shown in drawing. table under Pos. 2.

126 0178-225-EN
Achieving correct centre height S Turn coupling 180° and, using feeler
gauges, measure deviations from one mil-
S Turn coupling so that alignment gauge
limetre at both pins.
faces vertically down.
S Guide measuring pin (pos. 1) towards S Moving and turning motor and repeating
coupling flange, using a 1.0 mm feeler this measurement, align motor in accord-
gauge, and fix pin. Remove feeler gauge. ance with pos. 1 horizontal and pos. 2 in
S Rotate coupling 180° and measure in- table. Remember that the motor must be
crease in distance ”z” from one millimetre firmly secured during any measurements.
using feeler gauges.
Final installation
S Then lift motor by placing shims of thick-
ness equal to half value of ”z” under all S Tighten foundation bolts on motor (see
four feet. torque table).

S After securing motor, repeat measurement S Fit four bolts into motor coupling flange so
and compare result with table values in that thin shims are placed between flange
pos. 1 vertical. Remember that the centre- and lamellae, with rounded side facing la-
line of the motor shaft must be at least mella. There are no thin shims on cou-
0.05 mm higher than the centreline of the plings for CMO and HPO.
compressor, corresponding to a minimum
S Tighten bolts to torque specified in table.
of 0.1 mm distance less at the top position
of the alignment gauge. S Readjust flange distance ”C” so that la-
mellae are aligned, by moving motor
Achieving parallel shafts in vertical flange on shaft and fastening motor
plane flange.
S The motor is now positioned at its correct S Check alignment of coupling in horizontal
height. What now remains is to push and and vertical planes for pos. 1 and pos. 2.
turn the motor at the level on which it is
already lined up. S Dismantle measuring pin and tighten
screw to prescribed torque.
S Turn coupling so that alignment gauge
faces out to one side horizontally. S Fit coupling guard.

S Guide both measuring pins towards coup- S Once normal operating temperature has
ling with a 1.0 mm feeler gauge in be- been achieved, double-check coupling
tween. alignment.

0178-225-EN 127
Boring of motor flange for AMR coupling

A MAX. 0.02 mm

92.03
MAX. 0.02 mm
T0177131_0 V12

Unless the necessary data for the motor are S The bore should then be made to the rele-

010-502-EN
known prior to dispatch, the motor flange for vant dimensions and to the following toler-
the AMR coupling will not be supplied in ances:
ready bored form.
H8 for AMR 312, 350 and 450,
In such case, the motor flange is supplied H7 for AMR 225.
prebored and balanced.
S Cut keyways.
Finish-boring is done as follows:
For reasons of balance, coupling AMR
S Secure flange in lathe or jig-boring ma- 312, 350 and 450 must be executed with
chine. Observe following tolerances for the two keyways shown.
alignment purposes:
S Make the width of the keyway to a toler-
Max. axial eccentricity ance of H7.
measured at point A 0.02 mm
S The keyway must be deep enough to al-
Max. axial eccentricity 0.02 mm low a clearance between parallel keys
measured at point B
and hub of 0.2-0.3 mm.
Max. boring diameter:

Compressor CMO - TCMO - HPO SMC - TSMC 100 - HPC SMC - TSMC 180

Coupling size AMR 225 AMR 312 - 350 AMR 450

Max. bore 60 mm 95 mm 110 mm

Boring tolerance H7 H8 H8

128 0171-487-EN
Oil Separator OVUR
for HPC

Application from which it is returned to the compressor


crankcase through stop valve A.
The purpose of the oil separator is, under all
The purified discharge gas leaves the oil sep-
operating conditions - to separate the lubri-
arator through the side branch.
cation oil conveyed with the discharge gas
from the compressor so that it can be re- As shown on drawing a solenoid valve is
turned to the compressor crankcase. fitted in the oil return pipe. This is open only
Oil return takes place through a so-called so- during compressor operation but is kept
lenoid valve controlled oil return system as closed by the UNISAB II Control for 15
shown on below drawing. minutes from start-up of the compressor.

In the discharge branch of the combined stop


Solenoid valve-controlled design valve and filter housing, a nozzle has been
92.03

fitted, the opening of which has been


adapted to the compressor. After valve pos.
A has been closed, and the pressure in the
0171-495-EN

compressor has been equalized to atmo-


spheric, filter and nozzle can be cleaned by
dismantling the threaded nipples.

Checking oil return


The oil pipe must be warm while the com-
Solenoid valve
pressor is in operation. If the pipe is cold the
nozzle is likely to be clogged.

A To compressor
Nozzle
Filter in stop valve housing
Choice of nozzle size
T0177090_0
The correct nozzle size for HPC compressors
is 0.5 mm. It is recommended not to choose
Mode of operation a nozzle bigger than indicated as a nozzle
The discharge gas from the compressor - that is too big will increase the pressure in
always containing some drops of oil - is led the compressor crankcase and thus also in-
from the top of the oil separator through a crease oil consumption. In case excessive oil
number of stainless wire mesh filters. consumption is observed the filter in pos. A
or the nozzle may be clogged.
The oil is separated in these filters and
drained to the bottom of the oil separator

0171-487-EN 129
Connections on SMC 104Ć106Ć108 Mk3,
HPC 104SĆ106SĆ108S

X 1 AF, S
1


Z

2 • S

• •
2
AC
L • •• • H, Q
• F
• S


S
• •

• ••
K

• •
• •
• J
• •
P

•• •
O
• T

• •
AM U
V

AB G N
E C D B A T0177087_0/V1

97.10
Air- Air-
Thread Oil, cooled cooled Ther- Booster
Pos. RG Pressure gas or Water- w/built-in mo- with Normal application

0171-414-EN
(Inch) liquid cooled oil cooler pump oil cooler
A 1 1/4 suction oil + + + + Heating rod
B 3/4 suction oil + + + + Oil charging valve
C 1/2 suction oil + + + + Oil temperature
D 1/2 suction oil plugged + plugged + Oil temperature
E 1/4 suction gas plugged plugged plugged plugged Available
F 1/4 oil oil + + + + Oil pressure to unloading cylinder
G 1/2-1/4 suction gas plugged + + + Return from built-in oil cooler *
H 1/4 discharge gas + + + + High pressure connection (HP)
J 1/4 suction gas + + + + Oil return from solenoid valves
K 1/4 oil oil + + + + Oil pressure to solenoid valves
L 1/4 suction gas + + + + Low pressure connection (LP)
N 1/4 suction gas + + + + Oil return from oil separator
O 1/2-1/4 oil oil + + + + Oil pressure connection
P 1/4 suction gas plugged + + plugged Return from built-in oil cooler/
equalization from thermopump *
Q 1/4 discharge gas plugged plugged + plugged Return from oil cooler
(thermopump cooled)*
S 1/4 discharge gas plugged plugged + plugged Refrigerant cooling to top covers *
T 1/4 discharge gas – – + – Equalization to suction pressure end from
thermopump
U 1/4 discharge liquid – – + – Liquid inlet to thermopump*
V 1/2-1/4 suction liquid plugged + + + Supply to built-in oil cooler*
X 1/2 discharge gas + + + + Discharge gas temperature
Z 3/4 discharge gas + + + + Purge valve
AB 1/4 oil oil + + + + Prelubrication of bearings
AF 1/4 discharge gas plugged + + + Return from oil cooler (booster) *
AC 1/2 suction gas Used in connection with UNISAB II Suction temperature (superheat temp.)
AM 1/4 oil oil plugged plugged plugged plugged Available
1 Suction stop valve * These connections are not applied on HPC compressors
2 Discharge stop valve

130 0178-910-EN
Connections on TSMC 108 Mk3

1 AC Y 1 S

AF
• Z 2 • Q
H M

• S
• ••
• L X •
• • •
AL
• S

• 4
• •

• • • • •
• • •
F

O K • •
• • • • P

•• •
J

T
3
AM U

E C D B A
R AB G N

Thread Oil, Air-cooled Air-cooled Ther-


Pos. RG Pres- gas or Water- w/built-in mo- Normal application
(Inch) sure liquid cooled oil cooler pump
A 1 1/4 suction oil + + + Heating rod
B 3/4 suction oil + + + Oil charging valve
C 1/2 suction oil + + + Oil temperature
D 1/2 suction oil plugged + plugged Oil temperature
E 1/4 suction gas plugged plugged plugged Available
F 1/4 oil oil + + + Oil pressure to unloading cylinder
G 1/2-1/4 suction gas plugged + plugged Return from built-in oil cooler
H 1/4 high gas + + + High pressure connection (HP)
J 1/4 suction gas + + + Oil return from solenoid valves
K 1/4 oil oil + + + Oil pressure to solenoid valves
L 1/4 suction gas + + + Low pressure connection (LP)
M 1/4 suction gas + + + Intermediate pressure connection (IP)
N 1/4 suction gas + + + Oil return from oil separator
O 1/2-1/4 oil oil + + + Oil pressure to manometer and cut-outs
P 1/4 suction gas plugged + plugged Return from built-in oil cooler
Q 1/4 suction gas plugged plugged plugged Available
R 1/4 suction gas + + + Suction pressure to rear of unloading
cylinder
S 1/4 high gas plugged + + Refrigerant to HP top covers
T 1/4 suction gas – – + Equalization to suction pressure end from
thermo-pump
U 1/4 high liquid – – + Liquid supply from thermopump
V 1/2-1/4 suction liquid plugged + plugged Connection to built-in oil cooler
X 1/2 high gas + + + Discharge gas temperature
Y 1/2 interm. gas plugged plugged plugged Intermediate pressure temperature (IP)
Z 1/4 interm. gas + + + Purge valve
AB 1/4 oil oil + + + Prelubrication of bearings
AF 1/4 interm. gas plugged + + Return from built-in oil cooler (Booster)
AL 3/4 high gas + + + Purge valve
AC 1/2 suction gas Used in connection with UNISAB II Suction temperature
AM 1/4 oil oil plugged plugged plugged Available
1 Low pressure suction stop valve 3 Connection from intermediate pressure
2 Low pressure discharge stop valve 4 High pressure discharge stop valve

0178-910-EN 131
WaterĆcooling of reciprocating compressors
SMC 104Ć106Ć108 and TSMC 108
SMC 186Ć188 and TSMC 188
HPC 104ĂSĆ106ĂS and 108ĂS
The reciporcating compressor can be cooled sket. This will prevent water flowing into the
with water on the top and side covers, the compressor block.
cooling requirement being dependent on the
operating conditions and the refrigerant on Salt water-cooling
which the compressor operates. If it is expedient not to use fresh water for the
See page 1 for details. cooling of the top and side covers, salt water
dan be used to cool the side covers. The top
Water cooling is obtained by mounting an ex- covers must never be cooled with salt water
tra cover (water cover) Pos. 2B on the outsi- as the high temperature combined with the
de of top and side covers with an intervening salt water will corrode the covers in a short
seal Pos. 2D. period of time. For R717 compressors the top

99.11
covers may in some cases be cooled by me-
Tighten top and water covers with the bolts
ans of a thermal pump, see the diagram of
Pos. 2E, which are longer than the bolts for

0171-411-EN99
the operating range of the compressor in
the air-cooled version. See the Spare-parts
quistion.
list at the back of this instruction manual for
details. Fitting cooling water hoses
S When supplied, the compressor is not
For water cooling of the side covers, a spe-
fitted with cooling water hoses or any rele-
cial finned side cover Pos. 3A is used toget-
vant assembling parts. These are pro-
her with a water cover Pos. 3B and a seal
vided loose. This avoids damage to the
Pos. 3D. These are also listed in the spare-
parts in transit. Fit the cooling water hoses
parts list.
as shown in the following drawing, corre-
The water cover, together with the cover on sponding to the specification enclosed
which it is mounted, forms a channel system with the delivery.
in which the water is channelled back and
forth and effectively cools the top or side co- Please note:
ver. By virtue of their large surface area, the S The direction of water throughflow is
cooling fins on the interior of the side cover shown by arrows on the drawing.
Pos. 3A provide excellent cooling of the oil in
S The hose length is indicated opposite the
the crankcase.
respective Pos. nos. on the drawing.
When dismantling top or side covers with wa- S The hoses must not be in contact with the
ter covers, it is a good idea first to dismantle frame, covers, discharge pipe or similar
the topmost covers on the compressor. In components.
addition, you should ensure that the two co-
vers are kept tight against the intervening ga-

132 0171-487-EN
In the supply pipe to the water system a solenoid valve must be fitted which shuts off the water flow in
the refrigeration system at compressor standstill.
However, we do recommend to continue the water cooling for approx. 10 mins after the compressor has
been stopped as this protects the cooling water hoses against excessive temperatures

SMC 108
1
TSMC 108 SMC 188
1
HPC 108 TSMC 188
Pos Length Length
2 Nr. (mm) (mm)
1 300 325
3 *)2 790 1300
3
4 3 400 470
5 4 160 300
5 700 1100

SMC 106
HPC 106 SMC 186
1
6 Pos Length Length
Nr. (mm) (mm)
1 500 760
2
*)2 820 1300
3 3 325 525
3
4 4 150 300
5 5 670 1100
6 380 550

1 SMC 104
HPC 104
Pos Length
2 Nr. (mm)
3
1 610
3 *)2 750
4
3 370
5 4 160
5 670

Cooling of side covers only


SMC 104- SMC 186/
106-108 188
TSMC 108 TSMC 188
Pos Length Length
Nr. (mm) (mm)
1 300 400
2 1 3 2 200 300
3 800 1170
4
4 700 1100

*) To be secured to the vertical oil pipe using two pieces of plastic tape. T0177088_0/1

0171-487-EN 133
Necessary water consumption Max. permissible inlet temperature:
+40°C
To achieve satisfactory distribution of cooling
water and hence good compressor cooling, Min. permissible inlet temperature:
the following limit values should not be ex- +10°C
ceeded:
Max. permissible outlet temperature:
+55°C
Min. water through flow:
5.5 litres per hour per Kw motor output. Max. permissible temperature rise from
On water circulation plants, greater water inlet to outlet on the compressor:
throughflow is recommended. 15°C

134 0171-487-EN
Pressure loss in water cooling
on SMC/TSMC/HPC compressors

TSMC 108
Pressure loss SMC 108
p(mVS) HPC 108
SMC 106/HPC 106 SMC 104/HPC 104

4
SMC
112
T/SMC
116
3

2
SMC
186
T/SMC
1 188

100 500 1000 1500


Volumetric flow
V(l/hour)

T0177130_0

0171-487-EN 135
Ordering Spare Parts

When placing an order for spare parts, ber. If you are in any doubt, add the spare
please state the following: part no. too.

1. Shop No. 3. Forwarding instructions


All compressors are fitted with an identifica- When ordering spares, please advise the for-
tion plate, which states the type and shop no. warding address, and the address to which
of the compressor and indicates what refrig- the invoice should be sent. If appropriate,
erant is to be used. please state the name of your local bank, the
way in which you want the goods transported
2. Part No. and required delivery date.
Spare parts drawings and parts lists inserted
in an instruction manual identify spare parts 4. Classification certificate

94.05
with the following: If you require a certificate from a Classifica-
tion authority, please mark the order
a) Spare part no. – which is a reference
appropriately, as the inspection and issuing

0171-466-EN
number to facilitate finding a part in the
procedures take extra time and incur extra
drawing and cross-referencing in the parts
expenses.
list or vice versa.
b) Designation of the part.
5. Quotation No.
c) Part no. – a 7-digit number which refers to
If a quotation no. has been given during earli-
SABROE’s stores.
er correspondence, please refer to this when
When you order spare parts, please always placing your order – it will help us to identify
advise at least the designation and part num- and execute your order quickly.

136 0178-925-EN
Spare parts sets for compressors and units
HPO Ć HPC

On servicing compressor and unit it is always S Extended spare part set


an advantage if you, as our customer, have Further to the parts included in the stan-
some of the most commonly used spare dard spare part set this set contains a
parts at your disposal. This enables you or a cylinder lining and discharge valve as well
summoned SABROE service engineer to as an extended number and types of gas-
carry out the necessary service work without kets and fittings.
having to spend extra time on procuring the
spare parts needed.
Spare part set for Basic Unit
Spare parts are obtainable in sets as men-
S Standard spare part set
tioned in the following.
This is a set consisting mainly of O-rings
By contacting SABROE’s local representa-
and gaskets for some of the components
tive it is possible to receive a list of the spare
97.03

included in the unit.


part sets recommended by SABROE.

S Certificate spare part set


Compressor block
0171-942-EN

Further to the parts from the standard


S Standard spare part set spare part set this set contains other com-
Contains a suitable selection of O-rings ponents selected in accordance with the
as well as valve ring plates and valve requirements of the classification soci-
springs. eties.

0171-487-EN 137

You might also like