Application Data Form:

F-2600 Series Meters for Steam Applications


Use this form to submit the application data that is required for vortex mass flow meter sizing and quotation

Company Name:

Contact Name:

Location and Contact Information:

Project Name: (include city & state)

Specified By: Engineering firm, city/ST


ONICON spec'd by name or submitted & approved?

APPLICATION INFORMATION: #1 #2 #3 #4 #5
METER TAG INFORMATION:

PIPE SIZE: (may differ from meter size)

FLUID TYPE: (Saturated or superheated steam)

PROCESS PRESSURE: (include seasonal changes if


applicable)

PROCESS TEMPERATURE: (include seasonal


changes if applicable)

MAXIMUM MASS FLOW RATE & UNITS:


Maximum flow per design (required)
(Also refer to Building Load Worksheet)

MINIMUM MASS FLOW RATE:


Minimum flow required to be measured
ANALOG FLOW RANGE & UNITS:
(4-20 mA = 0- ___ lb/hr, kg/hr, etc.)

APPLICATION TYPES:
1. HVAC Heating HW 4. Humidification
2. Steam Boiler Output 5. Process Heating
3. Domestic HW 6. Other: ________

LOCATION DATA: 1)Longest straight pipe length


available for metering run. 2) Proximity fo PRV or control
valve; indicate distance and if up or down stream.
Provide sketch or drawing (PDF) if possible.

AVAILABLE OPTIONS: These options may affect price. * Connection type other than ANSI class 300 flange will affect lead time and price.
** May include multiplier to limit max hz)
* CONNECTION TYPE:
Standard: ANSI class 150 or 300 flange

ENGINEERING UNIT FOR 4-20 mA OUTPUT:


Choose from: lb/hr, kg/hr, Btu/hr, other

** ENGINEERING UNIT FOR PULSE OUTPUT:


Choose from: lb, kg, Btu, other
INTEGRAL PRESSURE SENSOR:
Required for superheated steam application

FLOW STRAIGHTENER: To reduce the amount


of upstream pipe run required.

REMOTE MOUNT ELECTRONICS:


Includes mounting hardware and a 32ft. cable between
sensor body and electronics enclosure.

Input Power:
Standard: Loop Powered (for Std. output only)
Optional: External 12-36VDC or External 100-240VAC

Output Signals: (Optional requires ext. pwr.)


Standard: 4-20mA output, pulse output & frequency
Optional: (3)4-20mA & (3)Alarms outputs; with BACnet or
MODBUS

Optional D-100 Display Module:


A) 24VAC or 120VAC
B) Network Protocol

METER SIZING RESULTS: this section to be completed by ONICON in most cases


Meter Size:
(meter is generally smaller than pipe diameter)
Meter Operating Range:
(at design pressure and temperature)

Pressure Loss at Design Max Flow:

Meter Model:

Rev 03/21/14 1500 N Belcher Road, Clearwater, FL 33765 Tel (727) 447-6140 www.onicon.com
Building Steam Flow Worksheet
Instructions: This worksheet is a basic tool to assist in determining realistic
maximum steam flow rates for meter sizing purposes. Please list
any special steam loads in addition to those listed below. The
goal is to determine realistic maximum operating flow rate
(simply adding up heat exchanger values tends to show inflated
values). Expand and copy this sheet as necessary.

Please Submit Worksheet(s) with Application Data Form as


necessary.

METER TAG / LOCATION:

Heating HW Loop Data


Heat exchanger capacity This is typically oversized
HW loop pipe size Determine max operational load in Winter &
Design Max flow rate (gpm) Summer (low load for Reheat in Summer, if
Design Delta-T (deg F) applicable)
Btu/lb from steam table 1000 (1000 is "rule of thumb" value)
Calculated Max Btu/hr 0
Calculated Max lb/hr 0

Steam Heating Coils


Coil(s) Capacity (in Btu/hr or lb/hr) Identify any heat recovery devices, such as heat
wheels, that may lower the expected flow rate.
% of maxumum (operational max)
Apply expected % of maximum based on
Resulting Max flow rate 0 expected system operation.

Domestic HW Heating
Heat Exchanger Capacity
Tank based systems typically operate in a cyclical
Tank size (zero if tankless) manner once up to temperature. We generally see
800-1500 lb/hr when the unit cycles on. Control
valve never opens 100%.

Humidification Consider likely operation for this system.


Humidifier capacity (lb/hr)

Snow Melt System Snow-melt systems are the exception to the rule
Snow Melt System capacity (lb/hr) that most steam loads are "overstated". Use
design max value for this type of load.

Pool or Spa Heating


Heat Exchanger Capacity This is typically oversized
Circulating loop size
Loop flow rate (gpm)
Operating Delta-T (deg F) Typically much lower than system "capacity"
Btu/lb from steam table 1000 (1000 is "rule of thumb" value)
Calculated Btu/hr 0
Calculated lb/hr 0

Total Manually add or enter formula, based on


entries above.
Application Data Form:
F-2600 Series Meters for Liquids, Air & Gas Applications
Use this form to submit the application data that is required for vortex mass flow meter sizing and quotation

Company Name & City/St.:

Contact Name:

Location and Contact Information:

Project Name:
and location (city,ST)
Specified By: ONICON Specified? Yes or No
(Engineering firm, city, ST)

APPLICATION INFORMATION: #1 #2 #3 #4 #5
LOCATION / METER TAG INFO:

PIPE SIZE: (NOT Meter size)

FLUID TYPE:

PROCESS PRESSURE:

PROCESS TEMPERATURE :

DESIGN MAXIMUM FLOW RATE:


Maximum flow per design (required)
ANALOG FLOW RANGE & UNITS:
(4-20 mA = 0- ___ lb/hr, kg/hr, etc.)

TYPICAL FLOW RATE:


Expected "typical" flow rate for the system

MINIMUM EXPECTED FLOW RATE:


Minimum flow required to be measured

APPLICATION TYPES: Please list all uses for the


process fluid:

INSTALLATION LOCATION: Indicate straight pipe


section length available for metering run.

AVAILABLE OPTIONS:

* Connection Type:
Standard: ANSI class 150 or 300 flange

Integral Pressure Sensor: Required for accurate


density compensation for air & gas apps.

Remote Mount Electronics Kit:


Mounting hardware and a 32ft. cable between sensor
body and electronics enclosure

Input Power:
Standard: Loop Powered
Optional: External 12-36VDC or External 100-240VAC

Output Signals:
Standard: 4-20mA output, pulse output & frequency
Optional: 3 4-20mA & 3 Alarms outputs & MODBUS or
BACnet

Optional D-100 Display Module:


A) 24VAC or 120VAC
B) Network Protocol

FACTORY SIZING RESULTS: this section to be completed by ONICON


Meter Size: (meter is generally smaller than pipe
diameter)
Meter Operating Range:
(at design pressure and temperature)

Pressure Loss at Design Max Flow:

Meter Model:

Rev 10-29-2014 11451 Belcher Road South, Largo, FL 33773 Tel +1 (727) 447-6140 www.onicon.com