You are on page 1of 3

Gas density measurement

SF6-Quality-Analyser
Model GA11
WIKA data sheet SP 62.11

Applications
■■ Analysis of the SF6-quality in SF6-filled equipment
■■ Measures moisture, purity and SO2 or SO2/HF

Special features
■■ Integrated pump-back-function allows measurement in a
closed loop for zero emission measurement
■■ No internal pressure vessel, eliminates transportation
regulations (dangerous goods regulation)
■■ Dual power source: rechargeable battery and AC power
■■ Three operations modes for zero SF6 emissions:
- Pump back / up to 5 measurements possible with one
battery charge
- Using external bag for recovery
- Using external cylinder (up to 10 bar / 150 psig gaseous)
for recovery / up to 5 measurements possible with one
SF6-Quality-Analyser, model GA11
battery charge

Description

WIKA SF6-quality-analyser is an innovative and cost effective Naming the measurements is simplified by importing a list of
way to determinate SF6-quality. It is equipped with three measuring points before starting to use the device.
sensors (SF6-%, moisture, SO2) to evaluate the moisture
content, concentration of decomposition products and purity Measurements are carried out in a closed loop. The operator
of SF6-filled tanks. can then decide whether he wants to pump back the used
gas (max. 9 barabs / 130 psig abs) or to store it a connected
Up to 500 measurements can be stored inside the inter- bag or cylinder (max. 9 bar abs / 130 psig abs).
nal memory and can be downloaded using an external
USB-Stick. The measured test values are automatically
interpreted according to Cigré, IEC or a customer specified
standard for SF6 contamination/reuse.

WIKA data sheet SP 62.11 ∙ 03/2012 Page 1 of 3


Additional features Moisture sensor
■■ Battery and AC power Measuring principle
■■ Touch screen operation Polymer based capacitive moisture sensor
■■ Up to 500 measurements can be stored
Range
Connection +20 ... -60 °C dew point (68 ... 140 °F)
Self-sealing quick connector and inlet valve
Accuracy
Pressure ±2 °C dew point at +20 ... -40 °C dew point
With recovery bag 1.3 … 35 barabs (4.4 … 520 psigabs) ±4 °C dew point at < -40 °C dew point
Pump back or cylinder 1.3 … 9 barabs (4.4 … 116 psigabs)
With automatic flow control Resolution
1 °C
Display/keys
800 x 480, 7" TFT touchscreen (262.144 colors) Flow rate
1 button 20 litres/hour

Supply Units
Lithium-Ion battery (no shut down for the system for moving In °Ctd, ppmv, ppmw and °Ctdpr (dew point at compartment
to the next measuring point / approx. 5 measurements with pressure), related to ambient pressure and temperature
pump back (depending on pressure) compensated to 20 °C (68 °F)
Line power AC 120 ... 265 V (50/60 Hz), battery, can be
charged during operation Calibration
Every 2 years
Temperature
Storage: -10 ... 60 °C (14 ... 140 °F)
Operation: 0 ... 50 °C (32 ... 122 °F)
SF6 percentage sensor
Dimensions
W x H x L: 538 x 406 x 297 mm (21.2 x 16.0 x 11.7 in) Measuring principle
Velocity of sound
Weight
Approx. 25 kg (55 lbs) Range
0 … 100 %

Accuracy
±0.5 % based on SF6/N2 mixtures (calibration for SF6/N2
mixtures on request)

Resolution
0.1 %

Flow rate
3 litres/hour

Calibration
Every 2 years

Page 2 of 3 WIKA data sheet SP 62.11 ∙ 03/2012


HF sensor SO2 sensor

Measuring principle Measuring principle


Electrochemical HF sensor Electrochemical SO2 sensor

Ranges Range
0 … 10 ppmv 0 ... 10 ppmv
(only in combination with 0 … 10 and 0 … 20 ppmv 0 ... 20 ppmv
SO2 sensor) 0 ... 100 ppmv
0 ... 500 ppmv
Accuracy
±1 ppmv Accuracy
±0.5 ppmv (0 … 10)
Resolution ±1 ppmv (0 … 20)
0.1 ppmv ±3 ppmv (0 … 100)
±5 ppmv (0 … 500)
Flow rate
10 liters/hour in line with SO2 sensor Resolution
0.1 ppmv at 0…10/0….20 ppmv
Humidity range 1 ppmv at 0….100/0...500 ppmv
Up to 90 % (non-condensating)
Flow rate
Maximum zero shift 10 liters/hour
0.1 ppmv
Humidity range
Long-term stability Up to 90 % (non-condensating)
< 1 % signal degradation per month (linear)
Maximum zero shift
Lifetime 0.2 ppmv
2 year starting from installation
Long-term stability
< 1 % signal degradation per month (linear)
< 0.5 % at 0…500 ppmv

Lifetime
2 years starting from installation

Ordering information
Model / Sensor type and number / Range (for SO2 sensor)

© 2012 WIKA Alexander Wiegand SE & Co. KG, all rights reserved.
The specifications given in this document represent the state of engineering at the time of publishing.
We reserve the right to make modifications to the specifications and materials.

WIKA data sheet SP 62.11 ∙ 03/2012 Page 3 of 3


03/2012 GB

WIKA Alexander Wiegand SE & Co. KG


Alexander-Wiegand-Straße 30
63911 Klingenberg/Germany
Tel. (+49) 9372/132-0
Fax (+49) 9372/132-406
E-mail info@wika.de
www.wika.de

You might also like