[ Protection Relays Guide ] Overcurrent Protections 6

MiCOM P120 / MiCOM P121


OVERCURRENT PROTECTION RELAY
Functions: 50/51, 50N/51N

Application Measurements
• Phase and earth fault overcurrent protections • Phase currents
applicable in HV and MV substations and to • Earth current
protect MV and LV transformers
Other Functions
Protections • 2 setting group
• P120: • Circuit breaker control
• Single-phase or earth fault overcurrent, 3-stage • CB status monitoring
DT or IDMT, co-operation with core balanced CT • Protection blocking logic
or in Holmgreen arrangement • Output contact latching
• P121: • Programmable binary inputs, outputs relays and
• 3-phase overcurrent, phase-to-phase, 3-stage, LEDs, 2 inputs / 4 outputs
DT or IDMT • Communication in RS485/RS232 standard
• Earth fault, 3-stage DT or IDMT, co-operation • Transmission protocols: Courier, Modbus,
with core balanced CT or in Holmgreen IEC60870-5-103 and DNP 3.0
Documents
arrangement • Recording of:
• Catalogue card
• Events - 250
• User manual
• Faults - 25 (1600 Hz, 3s window)
• Triggers - 25
• Trips - 5 (display)

MiCOM P122 / MiCOM P123


OVERCURRENT PROTECTION RELAY (3-phase)
Functions: 50/51, 50N/51N, 37, 49, 46, 46BC, 50BF, 79, 74TCS, 50HS
Application Other Functions
• Phase and earth fault overcurrent protections • 2 setting group
applicable in HV and MV substations and to • Circuit breaker control
protect MV and LV transformers • CB status monitoring
• Protection blocking logic
Protections • Output contact latching
• 3-phase overcurrent, phase-to-phase, 3-stage, • Programmable binary inputs, outputs relays and
DT or IDMT LEDs:
• Earth fault, 3-stage, DT or IDMT • P122 3 inputs / 6 outputs
• Thermal overload with 1 thermal time constant • P123 5 inputs / 8 outputs
• Undercurrent, single stage • Communication in RS485/RS232 standard
• Negative phase sequence overcurrent, IDMT and • Transmission protocols: Courier, Modbus,
DT IEC60870-5-103 and DNP 3.0
• Recording of:
Measurements • Events - 250
• Phase currents • Faults - 25 (1600 Hz, 3s window)
• Earth current • Triggers - 25
• Thermal state • Trips - 5 (display)