THIS SHEET IS FOR INFORMATION AND REFERENCE ONLY AND IS NOT A SUBSTITUTE FOR ACCURATE DRAWINGS PREPARED FOR EACH PROPOSED CONSTRUCTION PROJECT.
PROPERTY LINE
WHERE STUCCO IS APPLIED
OVER WOOD STR. PANEL, DOUBLE TOP PLATE
PROVIDE 2-LAYERS 2X STUD WALL @16" oc (STUD GRADE)
EXTERIOR BEARING WALL
8"
12" MIN.
D/4 MAX.
D/4 MAX.
D/6 MAX.
'D'
'D'
5/8" MIN. 5/8" MIN.
D/3 MAX.
2" MIN.
1/3 'D'
'D'
2" MIN.
'D'
2-16d EACH SIDE
ROOF SHEATHING D/4 MAX.
JOIST DEPTH
AT TAPER CUT
EDGE NAIL
HEADER
CONT. DOUBLE TOP PLATE
(SEE PAGE 2 FOR SPAN)
3
NOTES:
48" MIN. FOR
METHOD WSP 1. BRACED WALL LINES AT EXTERIOR WALLS SHALL HAVE A
AND BRACED WALL PANEL LOCATED AT EACH END OF THE
96" MIN. FOR SEE NOTE 1.
BRACED WALL LINE.
GB & PCP
EXCEPTION: FOR METHOD WSP, THE BRACED WALL
H (HEIGHT OF PANEL) 10' MAX.
A
MIN. 2 BRACED WALL PANELS ARE REQUIRED IN
EACH BRACED WALL LINE
BWL
EXTERIOR WALL
DOUBLE FLOOR JOIST
UNDER PARALLEL PARTITION
INTERIOR BEARING WALL
GIRDER GIRDER
18" MIN.
24" MIN.
18" 18" MIN.
3" MIN.
(TYP.)
12"/15" 12"/15"
See Note 3. 16" SQUARE See Note 3.
(SINGLE STORY)
20" MIN.
TWO LAYERS OF
2-INCH SAND FILL
WITH 6 MIL. 18" MIN. 24" MIN.
#4 DOWELS @ 16" O.C.
MOISTURE BARRIER
MEMBRANE BETWEEN FOR TWO POUR TYP.
THE TWO LAYERS
3" MIN.
12"/15" (TYP.)
See Note 3.
NOTES: 12"/15"
1. SOLID BLOCKED CRIPPLE WALLS (IF USED), SHALL NOT EXCEED 14" IN HEIGHT WITHOUT ENGINEERING ANALYSIS. See Note 3.
2. PERIMETER WALLS, INTERIOR BEARING WALLS AND POSTS SUPPORTED ON CONTINUOUS FOUNDATIONS.
3. 12"/15" - MIN. FOOTING FOR SUPPORTING ONE AND TWO FLOORS RESPECTIVELY.
4. SHEAR TRANSFER DETAILS AND OTHER REQUIREMENTS NOT SHOWN FOR CLARITY.
VER 7.0 (4-12-2017)
5
TOP 1/3
RECOMENDATION
VENT INSTALLATION
SEISMIC STRAPS: TWO MIN. PER. MANUF. SPECIFICATION
PER MANUF.
APPROVED SEISMIC STRAPS
APPLIED PER MANUF. SPECS
EXTERIOR WALL
FLAT TO <6:12
NO THREADS ALLOWED IN BOTTOM PIPING
12" MIN.
LISTED CAP
BOTTOM 1/3
FLAT TO <6:12
24" MAX
6" MIN.
IN GARAGE
RAISE 18"
GARAGE FLOOR
20" CLEAR
30" CLEAR
OPENABLE
2-6 X 3-6 4-0 X 4-0
AREA
DOUBLE CASEMENT: 4-8 X 4-0 5-0 X 3-6
SINGLE/ DOUBLE HUNG:
44" MAX
24" CLEAR
MIN. SIZE WINDOW NOTE: SIZES ARE TAKEN FROM DATA SUPPLIED BY
MIN. SIZE WINDOW WINDOW MANUFACTURERS. HOWEVER, THESE ARE
FOR 20" CLEAR WIDTH AND 5.0 S.F.
44" MAX
FOR 24" CLEAR HEIGHT AND 5.0 S.F. GENERAL DIMENSIONS AND MUST BE VERIFIED WITH
OPENABLE AREA OPENABLE AREA ACTUAL WINDOWS INSTALLED TO MEET MINIMUM
FLOOR LEVEL EGRESS REQUIREMENTS.
1. 20" MIN. CLEAR WIDTH
2. 24" MIN. CLEAR HEIGHT
3. 5.0 SF MIN. OPENABLE AREA AT GRADE-FLOOR ONLY, 5.7 SF MIN. ELSEWHERE.
FLOOR GIRDER
6"
BELOW FOOTING
2'-0" MIN.
PIPE DEPTHS
TO 3'-0" MAX.
NO SURCHARGE ALLOWED
ON SEWER PIPE
P.T. SILL
NOTE: THE GARAGE SHALL NOT VENTILATION OPENINGS SHALL BE COVERED WITH CORROSION RESISTANT
OPEN INTO A SLEEPING ROOM.
MESH W/ LEAST DIMENSION NOT EXCEEDING 1/4".
PIPE BOLLARD OR OTHER 2. THE NET FREE VENTILATING AREA OF ENCLOSED ATTICS AND ENCLOSED
PROTECTIVE MEASURE
WHEN APPLIANCES ARE RAFTER SPACES SHALL NOT BE LESS THAN 1/150 OF THE AREA OF THE SPACE
SUBJECT TO DAMAGE VENTILATED. EXCEPT THAT REDUCTION OF TOTAL THE AREA TO 1/300 IS
3" MIN. DIA. (PC507.13) PERMITTED PROVIDED THAT AT LEAST 50% AND NOT MORE THAN 80% OF THE
REQUIRED VENTILATING AREA IS PROVIDED BY VENTILATORS LOCATED IN
GARAGE THE UPPER PORTION OF THE SPACE TO BE VENTILATED AT LEAST 3- FEET
ABOVE THE AVE OR CORNICE VENTS WITH THE BALANCE OF THE REQUIRED
(SEE NOTE 3) VENTILATION PROVIDED BY EAVE OR CORNICE VENTS. AS AN ALTERNATIVE,
THE NEW FREE CROSS-VENTILATION AREA MAY BE REDUCED TO 1/300 WHEN
A CLASS I OR CLASS II VAPOR BARRIER IS INSTALLED ON THE
WARM-IN-WINTER SIDE OF THE CEILING. A MINIMUM OF 1-INCH CLEARANCE
SHALL BE PROVIDED BETWEEN THE INSULATION AND ROOF SHEATHING.