Professional Documents
Culture Documents
There are various types of protections setting in MCCB, which define various protection
of Electrical Network.
In MCCB we can set most of protection are adjustable according to Electrical Load
profile.
The main adjustable Setting in MCCB are
Over current Setting
Short Circuit Setting
Ground Fault Setting
Long time delay (tr) sets length of time that the circuit breaker will carry a sustained
overload before tripping.
The delay bands are labeled in seconds of over current at six times the ampere rating.
Long-time delay is an inverse time characteristic in that the tripping time decreases as the
current increases.
The long-time delay (tr) sets the length of the time that the circuit breaker will carry an
over current (below the short-time or instantaneous pickup current level) before tripping.
The Long time delay can be set to I2t On and I2t OFF settings.
(A) I2t Response:I2t Out ,For coordination with other circuit breakers with electronic trip
devices and for coordination with thermal-magnetic circuit breakers.
(B) I2t Response: I2t In ,For coordination with fuses and upstream transformer
(2) For Short Circuit Protection (Magnetic Setting):
(C) Short Time pickup Current Setting (Im):
Short Time delay sets the amount of time the breaker will carry both a low level and high
fault currents before tripping.
tm sets length of time the circuit breaker will carry a short circuit within the short-time
pickup range.
Delays bands are labeled in seconds of short-circuit current at 10 times the ampere rating.
The short time delay can be set to I2t On and I2t OFF settings (Inverse Time Delay).
(A) I2t OFF: Gives Constant time delay usually in multiplication of 0.5 sec. It has not
inverse-time delay Characteristic. It is used for coordination with other circuit breakers
with electronic trip devices and for coordination with thermal-magnetic circuit breakers.
(B) I2t ON :Gives an inverse-time delay that resembles the time/current characteristics
of fuse It is used for coordination with fuses and upstream transformer
It is determines the level of fault current at which the ground fault trip delay countdown
is actuated.
(G) Ground Fault Delay Setting (Itg) :
It is determines the amount of time the breaker will carry a ground fault before tripping.
It can be set to I2t On and I2t OFF settings.
(A) I2t Response:I2t Out ,For coordination with other circuit breakers with electronic trip
devices and for coordination with thermal-magnetic circuit breakers.
(B) I2t Response: I2t In ,For coordination with fuses and upstream transformer
Here In=2000A
Instantaneous Tripping gives instant tripping without any delay for switching or short
Circuit current.
Instantaneous Tripping >= Short Circuit Tripping Setting
If We can set Ii=3xIn =3×2000=6000A , It will full fill our requirement
Here Ii>Isd=6000A>4000A.
Rate this: