Specification for Surge Protection Device as Per IS/IEC 62305 Part4

Sl.No Description Unit Qty Rate Amount

1 Surge Protection Devices for Main Panel: 3PTTBCD

This panel should include Pluggable type surge arrester Class B & Class C/ Class 1 & Class 2 as per
IEC 61643 (IP 20) with potential free contact,with IP 66 completely assembled enclosure &
provision for inbuilt common remote indication for defective arresters 3 nos of encapsulated spark
gap & 3 nos of single large block of MOV with series thermal fuse and cooling gel to connect
between Line and Neutral and one number arrester encapsulated spark gap type to connect
between Neutral and Earth of following ratings including base element & pluggable arresters.
Nominal voltage -230V 50Hz, Impulse current-150 KA (10/350µ sec) & 60KA (8/20µ sec) for Line to
Neutral & 125 KA(10/350µ sec) for Neutral to Protective Earth, voltage protection level <1.3 KV ( L
to N) & <1.3 KV ( N to E). Operating temp -40º to +85ºC. Response time <100 nano sec
Rate to be quoted for
Supply Each 49,350.00 0
Labour Each 2000 0
2 EBB Stainless Steel Rail for Panel application: 0

Equipotential bonding rail for main panel applications. Main potential equalisation to VDE 0100 Part
410 and Part 540 and also lightning protection potential equalisation to VDE 0185-305 (IEC 62305).
Insulation Feet. Quick, simple assembly of connection conductors to contact rail using M 10. The
high grade stainless steel versions (V2A) are suitable for outdoor use also. Complete with anchors
and bolts for wall mounting. With lock washer (DIN 137) for bolt locking against loosening. With
Stainless steel V2A OBO Bettermann cover 0
Rate to be quoted for
Supply Each 5875 0
Labour Each 325 0
3 Surge Protection Device For VDB/DB: 0

This panel should include pluggable type surge arrester in suitable enclosure Class B+C/ Class 1+2
as per IEC 61643 (IP 20) with potential free contact, thermal dis connector & provision for inbuilt
common remote indication for defective arresters to connect between Line and Neutral and one
number arrester Spark Gap type to connect between Neutral and Earth of following ratings
including base element & pluggable arresters. Nominal voltage -230V 50Hz, type single MOV with
built in thermal fuse and cooling gel(L to N) & spark gap encapsulated / non exhausting (N to E) .
Lightning Impulse Current - 21 kA (10/350µ sec) for Line to Neutral & 25 kA(10/350µ sec) for
Neutral to Earth,Nominal discharge current-90 kA (8/20µ sec) for Line to Neutral & 30 kA(8/20µ sec)
for Neutral to Earth, max discharge current 150 kA (8/20µ sec) for Line to Neutral & 50 kA(8/20µ
sec) for Neutral to Earth. Voltage protection level 1300V (L to N) & 1200V (N to E). Operating temp
-40º to +80ºC. Response time <25 nano sec (L to N), < 100 nano sec (N to E) DIN rail mounting type
etc complete with back up fuse as required and as directed. 0
Rate to be quoted for 0
Supply Each ₹11,475.00 0
Labour Each ₹500.00 0
4 Surge Protection Device For UPS Panel: 0

This panel should include pluggable type surge arrester in suitable enclosure Class B+C/ Class 1+2
as per IEC 61643 (IP 20) with potential free contact, thermal dis connector & provision for inbuilt
common remote indication for defective arresters to connect between Line and Neutral and one
number arrester Spark Gap type to connect between Neutral and Earth of following ratings
including base element & pluggable arresters. Nominal voltage -230V 50Hz, type single MOV with
built in thermal fuse and cooling gel(L to N) & spark gap encapsulated / non exhausting (N to E) .
Lightning Impulse Current - 21 kA (10/350µ sec) for Line to Neutral & 25 kA(10/350µ sec) for
Neutral to Earth,Nominal discharge current-90 kA (8/20µ sec) for Line to Neutral & 30 kA(8/20µ sec)
for Neutral to Earth, max discharge current 150 kA (8/20µ sec) for Line to Neutral & 50 kA(8/20µ
sec) for Neutral to Earth. Voltage protection level 1300V (L to N) & 1200V (N to E). Operating temp
-40º to +80ºC. Response time <25 nano sec (L to N), < 100 nano sec (N to E) DIN rail mounting type
etc complete with back up fuse as required and as directed. 0
Rate to be quoted for 0
Supply Each 11475 0
Labour Each 500 0
5 Surge Protection Device Single Phase Application: 0
Sl.No Description Unit Qty Rate Amount

This panel should include pluggable type surge arrester in suitable enclosure Class B+C/ Class 1+2
as per IEC 61643 (IP 20) with potential free contact, thermal dis connector & provision for inbuilt
common remote indication for defective arresters to connect between Line and Neutral and one
number arrester Spark Gap type to connect between Neutral and Earth of following ratings
including base element & pluggable arresters. Nominal voltage -230V 50Hz, type single MOV with
built in thermal fuse and cooling gel(L to N) & spark gap encapsulated / non exhausting (N to E) .
Lightning Impulse Current - 7 kA (10/350µ sec) for Line to Neutral & 25 kA(10/350µ sec) for Neutral
to Earth,Nominal discharge current-30 kA (8/20µ sec) for Line to Neutral & 30 kA(8/20µ sec) for
Neutral to Earth, max discharge current 50 kA (8/20µ sec) for Line to Neutral & 50 kA(8/20µ sec) for
Neutral to Earth. Voltage protection level 1300V (L to N) & 1200V (N to E). Operating temp -40º to
+80ºC. Response time <25 nano sec (L to N), < 100 nano sec (N to E) DIN rail mounting type etc
complete with back up fuse as required and as directed. 0
Rate to be quoted for 0
Supply Each ₹5,500.00 0
Labour Each ₹500.00 0
6 Surge Protection Devices For Independent DB: 0

This panel should include pluggable type surge arrester in suitable enclosure Class C/ Class 2 as per
IEC 61643 (IP 20) with potential free contact, thermal dis connector & provision for inbuilt common
remote indication for defective arresters to connect between Line and Neutral and one number
arrester Spark Gap type to connect between Neutral and Earth of following ratings including base
element & pluggable arresters. Nominal voltage -230V 50Hz, type single MOV with built in thermal
fuse and cooling gel(L to N) & spark gap encapsulated / non exhausting (N to E). Lightning Impulse
Current – 25 kA(10/350µ sec) for Neutral to Earth. Nominal discharge current-60 kA (8/20µ sec) for
Line to Neutral & 30 kA(8/20µ sec) for Neutral to Earth, max discharge current 120 kA (8/20µ
sec)for Line to Neutral & 50 kA(8/20µ sec) for Neutral to Earth voltage protection level 1400V (L to
N) & 1200V (N to E). Operating temp -40º to +80ºC. Response time <25 nano sec (L to N), < 100
nano sec (N to E)DIN rail mounting type etc complete with back up fuse as required and as directed. 0
Rate to be quoted for 0
Supply Each 6875 0
Labour Each 500 0
7 EBB Stainless Steel Rail for VDB/DB/UPS/Independent DB application: 0

Equipotential bonding rail for DB applications. Equipotential bonding rail for equipotential bonding
according to DIN VDE 0100-410/540 and lightning protection equipotetial bonding according to DIN
VDE 0185-305. Base plate and cover hood from polystyrene. Colour: Black, UV resistant. Can be
used outdoor also. Screw and crossbar made of VA. Capable of carring lightning current 100KA
(10/350). Connection options: 7 x single or multi-core conductors to 25mm square or fine core
conductors to 16mm square. 1 x round cable Rd 8-10. 1 x flat strip to FL 30 or round cable RD 8-10 0
Rate to be quoted for
Supply Each 630 0
Labour Each 125 0
8 Surge Protection Device For EPABX: 0
The surge protection device shall be suitable to protect 10 pair of telephone lines designed to with
stand both lightning current and switching surges. Technology: GD tube, Nominal Voltage:
180 V, Pulsed Current (10/350 µs ) Iimp: 1 KA, Nominal Discharge Current (8/20
µs )/phase In: 5KA, Maximum discharge current:10 KA,Voltage Protection
Level(sym)<700V, Response time<1n sec 0
Rate to be quoted for 0
Supply Each 12260 0
Labour Each 50 0
9 Surge Protection Device For Camera (coaxial): 0

In aluminium housing. BNC connector for 10base2. Simple mounting with adapter. Two stage
protection circuit. Total impulse 10KA (8/20µ sec). Voltage protection level line to earth <500V. 0
Rate to be quoted for 0
Supply Each 7285 0
Labour Each 100 0
10 Surge Protection Device For TV lines: DS F M/W 0

The surge protection devices shall be with two stage protection circuit suitable for the protection of
video signals and cameras. The housing of the surge protection devices shall be of Aluminium to
avoid the EMI effects. The surge protection device should ensure the equipotential bonding
between PE/Shield and the data cables to reduce over voltages to a safe protection level.
Technology: Spark Gap, MCOV: 185 DC,130 AC,Bandwidth: 0-863 Mhz, Connection System: SAT-F,
Wave Resistance: 75 ohms, Insertion Loss: 0.18dB @ 863Mhz,Voltage protection level:800, Impulse
Current: 5KA, Nominal Discharge Current: 10KA. 0
Sl.No Description Unit Qty Rate Amount
Rate to be quoted for 0
Supply Each 10015 0
Labour Each 100 0
11 Surge Protection Device For RJ 11 line: RJ 11 Tele 4C/ RJ 11 Tele 4 F 0
The surge protection device shall be suitable to protect 1 pair of telephone lines designed to with
stand both lightning current and switching surges. Technology: Spark Gap, MoV and Zener
Diode combination, U max AC: 122V, U max DC: 170 V, Pulsed Current (10/350 µs )
Iimp: 1.5 KA, Nominal Discharge Current (8/20 µs )/phase In: 7.5KA, Maximum
discharge current:10 KA,Voltage Protection Level(sym)<300V, Response time<1n sec 0
Rate to be quoted for 0
Supply Each 9950 0
Labour Each 150 0
12 Surge Protection Device For Network Lines: ND-CAT 6A/EA 0

The surge protection devices for high speed networks up to 10Gbps (Class EA/ CAT 6A): High Quality
RJ 45 Sockets. Support for power over Ethernet to 1A. Tested Transmission quality in Networks up to
10Gbits. Rapid installation through connect able design. U max AC:41V, U max DC:58V, LPZ zone 1-3,
Total Impulse durability: 7 KA, Voltage Protection Level <700v (line-earth) , <120 (line-line).
Transmission Frequency 500 Mhz, Degree of protection enclosure IP 10. 0
Rate to be quoted for 0
Supply Each 15150 0
Labour Each 100 0
Total 0