7SJ611 V4_9_prn

66 kV Fixed Setting / RAHS / 40 MVA


SIMATIC Trafo / LV SBEF / 7SJ611 V4.9/7SJ611 21.04.17 14:33:16

66 kV Fixed Setting / RAHS / 40 MVA Trafo / LV SBEF / 7SJ611 V4.9

MLFB: 7SJ6112**B901FB0
Parameter set version: V04.90.05
Device path: D:\Network consultancy\L&T\REDMARKUP\RAHS\66kV\Digsi_RAHS\P7DI\GV\SD\
0000002b
Author:
Creation date: 12.12.12 16:37:01
Last modified: 21.04.17 14:27:30
Operating mode: Offline
Comment:
Setting values in: Secondary value description

PRINT - CONTENTS
1 Device Configuration ...................................................................................................................................................… 2
2 Power System Data 1 ..................................................................................................................................................... 3
2.1 Group Power System Data 1; Group Power System ..................................................................................................… 3
2.2 Group Power System Data 1; Group CT's ..................................................................................................................… 3
2.3 Group Power System Data 1; Group Breaker .............................................................................................................… 3
3 Oscillographic Fault Records ......................................................................................................................................… 4
3.1 Group Oscillographic Fault Records; Group Osc. Fault Rec. .....................................................................................… 4
4 Settings groups ...........................................................................................................................................................… 5
4.1 Group Power System Data 2; Group General ............................................................................................................… 5
4.2 Group Time overcurrent 1Phase; Group General .......................................................................................................… 5
4.3 Group Time overcurrent 1Phase; Group Settings .......................................................................................................… 5
4.4 Group Measurement Supervision; Group General .....................................................................................................… 5
4.5 Group Measurement Supervision; Group MeasSupervision .......................................................................................… 6
4.6 Group (Sensitive) Earth Fault; Group General ............................................................................................................… 6
4.7 Group (Sensitive) Earth Fault; Group DMT .................................................................................................................… 6
4.8 Group (Sensitive) Earth Fault; Group CT's ..................................................................................................................... 6
5 Additional Functions ....................................................................................................................................................… 7
5.1 Function blocks ...........................................................................................................................................................… 7
5.1.1 Group Flexible Function 01; Group General ...............................................................................................................… 7
5.1.2 Group Flexible Function 01; Group Meas. Quantity ....................................................................................................… 7
5.1.3 Group Flexible Function 01; Group Meas. Method .....................................................................................................… 7
5.1.4 Group Flexible Function 01; Group Settings ...............................................................................................................… 7

Page 1 of 8
7SJ611 V4_9_prn
Device Configuration
66 kV Fixed Setting / RAHS / 40 MVA
SIMATIC Trafo / LV SBEF / 7SJ611 V4.9/7SJ611 21.04.17 14:33:16

1 Device Configuration

No. Function Scope

0103 Setting Group Change Option Disabled


0104 Oscillographic Fault Records Enabled
0112 DMT / IDMT Phase Disabled
0113 DMT / IDMT Earth Disabled
0127 DMT 1Phase Enabled
0117 Cold Load Pickup Disabled
0122 2nd Harmonic Inrush Restraint Disabled
0131 (sensitive) Earth fault Definite Time only
0134 Dir. Intermittent earth fault protection Disabled
0140 Unbalance Load (Negative Sequence) Disabled
0142 Thermal Overload Protection Disabled
0170 Breaker Failure Protection Disabled
0172 Circuit Breaker Wear Monitoring Disabled
0182 Trip Circuit Supervision Disabled
Flexible Function Flx 01

Page 2 of 8
7SJ611 V4_9_prn
Power System Data 1
66 kV Fixed Setting / RAHS / 40 MVA
SIMATIC Trafo / LV SBEF / 7SJ611 V4.9/7SJ611 21.04.17 14:33:16

2 Power System Data 1

2.1 Group Power System Data 1; Group Power System


Group Power System Data 1; Group Power System
No. Settings Value Group

0214 Rated Frequency 50 Hz All


0209 Phase Sequence L1 L2 L3 All
0276 Unit of temperature measurement Degree Celsius All
0201 CT Starpoint towards Line All
0280 Holmgreen-conn. (for fast sum-i-monit.) NO All
0251A CT Connection IL1, IL2, IL3, (IE) All
0235A Storage of th. Replicas w/o Power Supply NO All
0250A Time Overcurrent with 2 phase prot. OFF All

2.2 Group Power System Data 1; Group CT's


Group Power System Data 1; Group CT's
No. Settings Value Group

0204 CT Rated Primary Current 750 A All


0205 CT Rated Secondary Current 1A All
0217 IE-CT rated primary current 750 A All
0218 IE-CT rated secondary current 1A All

2.3 Group Power System Data 1; Group Breaker


Group Power System Data 1; Group Breaker
No. Settings Value Group

0210A Minimum TRIP Command Duration 0.15 sec All


0211A Maximum Close Command Duration 1.00 sec All
0212 Closed Breaker Min. Current Threshold 0.04 A All

Page 3 of 8
7SJ611 V4_9_prn
Oscillographic Fault Records
66 kV Fixed Setting / RAHS / 40 MVA
SIMATIC Trafo / LV SBEF / 7SJ611 V4.9/7SJ611 21.04.17 14:33:16

3 Oscillographic Fault Records

3.1 Group Oscillographic Fault Records; Group Osc. Fault Rec.


Group Oscillographic Fault Records; Group Osc. Fault Rec.
No. Settings Value Group

0401 Waveform Capture Save with Pickup All


0402 Scope of Waveform Data Fault event All
0403 Max. length of a Waveform Capture Record 5.00 sec All
0404 Captured Waveform Prior to Trigger 0.20 sec All
0405 Captured Waveform after Event 0.50 sec All
0406 Capture Time via Binary Input 0.50 sec All

Page 4 of 8
7SJ611 V4_9_prn
Settings groups
66 kV Fixed Setting / RAHS / 40 MVA
SIMATIC Trafo / LV SBEF / 7SJ611 V4.9/7SJ611 21.04.17 14:33:16

4 Settings groups

4.1 Group Power System Data 2; Group General


Group Power System Data 2; Group General
No. Settings Value Group

1102 Measurement: Full Scale Current (100%) 750 A A

4.2 Group Time overcurrent 1Phase; Group General


Group Time overcurrent 1Phase; Group General
No. Settings Value Group

2701 1Phase Time Overcurrent ON A

4.3 Group Time overcurrent 1Phase; Group Settings


Group Time overcurrent 1Phase; Group Settings
No. Settings Value Group

2703 1Phase O/C I>> Pickup oo A A


2704 T 1Phase O/C I>> Time Delay oo sec A
2706 1Phase O/C I> Pickup 0.100 A A
2707 T 1Phase O/C I> Time Delay oo sec A

4.4 Group Measurement Supervision; Group General


Group Measurement Supervision; Group General
No. Settings Value Group

8101 Measurement Supervision ON A

Page 5 of 8
7SJ611 V4_9_prn
Group Measurement Supervision; Group MeasSupervision
66 kV Fixed Setting / RAHS / 40 MVA
SIMATIC Trafo / LV SBEF / 7SJ611 V4.9/7SJ611 21.04.17 14:33:16

4.5 Group Measurement Supervision; Group MeasSupervision


Group Measurement Supervision; Group MeasSupervision
No. Settings Value Group

8104 Current Balance Monitor 0.10 A A


8105 Balance Factor for Current Monitor 0.50 A
8111A T Current Balance Monitor 5 sec A

4.6 Group (Sensitive) Earth Fault; Group General


Group (Sensitive) Earth Fault; Group General
No. Settings Value Group

3101 (Sensitive) Earth Fault ON A


3121A Dropout Time Delay DMT 0.00 sec A

4.7 Group (Sensitive) Earth Fault; Group DMT


Group (Sensitive) Earth Fault; Group DMT
No. Settings Value Group

3113 IEE>> Pickup 0.400 A A


3114 T IEE>> Time Delay 4.50 sec A
3117 IEE> Pickup 0.400 A A
3118 T IEE> Time delay 3.50 sec A

4.8 Group (Sensitive) Earth Fault; Group CT's


Group (Sensitive) Earth Fault; Group CT's
No. Settings Value Group

3102 Current I1 for CT Angle Error 1.000 A A


3103 CT Angle Error at I1 0.0 ° A
3104 Current I2 for CT Angle Error 1.000 A A
3105 CT Angle Error at I2 0.0 ° A

Page 6 of 8
7SJ611 V4_9_prn
Additional Functions
66 kV Fixed Setting / RAHS / 40 MVA
SIMATIC Trafo / LV SBEF / 7SJ611 V4.9/7SJ611 21.04.17 14:33:16

5 Additional Functions

5.1 Function blocks

5.1.1 Group Flexible Function 01; Group General


Group Flexible Function 01; Group General
No. Settings Value Group

Flexible Function Alarm Only All


Mode of Operation Single-Phase All
Block while Freq. is out of range NO All

5.1.2 Group Flexible Function 01; Group Meas. Quantity


Group Flexible Function 01; Group Meas. Quantity
No. Settings Value Group

Selection of Measured Quantity Current All

5.1.3 Group Flexible Function 01; Group Meas. Method


Group Flexible Function 01; Group Meas. Method
No. Settings Value Group

Selection of Measurement Method Fundamental Component All


Pickup with Dropping below the Threshold All
Current IE sensitive All

5.1.4 Group Flexible Function 01; Group Settings


Group Flexible Function 01; Group Settings
No. Settings Value Group

Pickup Threshold 0.037 A All


Trip Time Delay 3600.00 sec All

Page 7 of 8
7SJ611 V4_9_prn

66 kV Fixed Setting / RAHS / 40 MVA


SIMATIC Trafo / LV SBEF / 7SJ611 V4.9/7SJ611 21.04.17 14:33:16

Group Flexible Function 01; Group Settings(2)


No. Settings Value Group

Pickup Time Delay 0.00 sec All


Dropout Time Delay 0.00 sec All
Dropout Ratio 1.05 All

Page 8 of 8