SN Transducer details

1 AC Voltage Transducer, Nominal input voltage: 110V output:4-20 mA, Aux


Power Supply: 240v +/-20%, 1-Ph, 50 Hz, AC Accuracy: +/- 0.5% Insulation
Level: 2KV RMS for 1 Min, Maximum Continious Input Voltage: 137.5V, Short
Time Input Voltage: 165 V for 10 Sec, Transducer to be calibrated to 14.67mA
for 110VAC Input voltage, Projection mounting & wiring details shall be submitted
alongwith the offer.
2 AC Current Transducer, Nominal input: 1Amp AC Output:4-20 mA, Aux. Power
Supply: 240V+/- 20%, 1-Ph, 50 Hz, AC Accuracy: +/-0.5% Insulation Test level:
2KV RMS for 1 Min, Maximum Continuous Input: 2Amp, AC Short Time Input
15A for 10 Sec, transducer to be calibrated to 12mA for 1A AC Input Current,
Projection Mounting & wiring details shall be submitted alongwith the offer.

3 DC Voltage Transducer (Isolated) Input Range: (-)15V-0-(+)15V Output : 4-20


mA, Dual output , Aux Power Supply: 240v +/-20%, 1-Ph, 50 Hz, AC Accuracy: +/-
0.5% Insulation Level: 2KV RMS for 1 Min, Outputs shall be galvonically
isolated,Projection Mounting & wiring details shall be submitted alongwith the
offer.
4 DC Voltage Transducer (Isolated) Input: 0-10V Output: 4-20mA,Aux Power
Supply: 240v +/-20%, 1-Ph, 50 Hz, AC Accuracy: +/- 0.5% Insulation Level: 2KV
RMS for 1 Min, Outputs shall be galvonically isolated, Projection Mounting &
wiring details shall be submitted alongwith the offer.
5 Transducer Reactive Power, 3 Phase 3 Wire Unbalanced, Rated Input
Voltage:110VAC Rated Input Current: 1A Output: 4mA…12…20mA Equivalent
to 190.52VAR Lead…0…190.52VAR Lag, Power Supply : 240VAC +/-20%
1Phase, 50 Hz Frequency: 50 Hz Accuracy: +/-0.2% Maximum Continuous Input
Voltage:137.5VAC, Short time input voltage: 165V for 10 Sec.,Max continuous
input current :2A, Short time input current: 15A for 10 Sec.Projection Mounting &
wiring details shall be submitted alongwith the offer.

6 Transducer Active Power, 3 Phase 3 Wire Unbalanced, Rated Input


Voltage:110VAC Rated Input Current: 1A Output: 4mA…20mA Power Supply :
240VAC +/-20% 1Phase, 50 Hz Frequency: 50 Hz Accuracy: +/-0.2%, Maximum
Continuous Input Voltage:137.5VAC ,Short time input voltage: 165V for 10 Sec.,
Max continuous input current: 2A , Short time input current: 15A for 10 Sec.
Projection Mounting & wiring details shall be submitted alongwith the offer.

7 PF Transducer Unipolar, Three Phase Rated Input Voltage: 110VAC Rated Input
Current: 1A PF Range: 0.5 Lead-1-0.5 Lag Transducer Output: 4mA...12.. 20mA
Aux Sup. 240V+/-20% 1Ph 50 Hz Insulation level: 2KV RMS for 1 Min Accuacy:
0.5%, Max Continuous Input Voltage 137.5VAC ,Shot time input voltage: 165V
for 10Sec , Max continous input current: 2A Short time input current: 15A for 10
Sec.Projection Mounting & wiring details shall be submitted alongwith the offer.

8 DC Voltage Transducer input : 0-300 VDC Output: 4-20 mA Dual output, Aux
supply: 220VAC Test voltage: 4KV 50 Hz for 1 min Accuracy : 0.5% or Better.
Projection Mounting & wiring details shall be submitted alongwith the offer.
9 DC Voltage Transducer Input:0-60 mV DC output: 4-20mA Dual output, Aux
Supply: 220VAC Test Voltage: 4KV 50 Hz for 1 Min Accuracy: 0,5% or
Better.Projection Mounting & wiring details shall be submitted alongwith the offer.

10 DC Voltage Transducer Input: 0-40 VDC Output : 4-20 mA Dual output, Aux.
Supply : 230VAC Test voltage: 4KV 50 Hz for 1 min Accuracy : 0.5% or Better.
Projection Mounting & wiring details shall be submitted alongwith the offer.