Professional Documents
Culture Documents
Page 1 of 40
TABLE OF CONTENTS
1.0 SCOPE / OVERVIEW................................................................................................................. 4
Page 2 of 40
5.7.8 Common Pressure Transmitter Options............................................................. 32
6.0 LOCAL PNEUMATIC PRESSURE CONTROLLERS............................................................... 33
6.1 Purpose and Indications for Use ................................................................................... 33
6.2 Local Pneumatic Pressure Controller Construction ....................................................... 33
6.3 Local Pneumatic Controller Installation ......................................................................... 34
7.0 DIAPHRAGM SEALS .............................................................................................................. 34
7.1 Purpose and Indications for Use ................................................................................... 34
7.2 Seal Construction.......................................................................................................... 35
7.3 Fill Fluid Selection......................................................................................................... 36
7.4 Capillary Tube Construction.......................................................................................... 36
7.5 Recommended Diaphragm Sizes.................................................................................. 37
8.0 PRESSURE CALIBRATION DEVICES.................................................................................... 38
8.1 Deadweight Tester........................................................................................................ 38
8.2 Portable Electronic Test Equipment .............................................................................. 38
8.3 Precision Test Equipment ............................................................................................. 38
8.4 Required Accuracy of Test Equipment .......................................................................... 39
9.0 STANDARD TEMPERATURE AND PRESSURE .................................................................... 39
APPENDICES...................................................................................................................................... 40
Appendix 1: References .......................................................................................................... 40
.
Page 3 of 40
2.0 CODES , S TANDARDS, AND REFERENCES
These are the common definitions/acronyms used in this document.
API American Petroleum Institute
ISA International Society of Automation
MAWP Maximum Allowable Working Pressure
MOC Management of Change
NIST National Institute of Standards and Technology
P&ID Piping & Instrument Diagrams
PFD Process Flow Diagram
PIP Process Industry Practices
STP Standard Temperature and Pressure
SS Stainless Steel
Page 4 of 40
3.0 INTRODUCTION – WHAT IS P RES S URE?
Caution – references such as “5 pounds of vacuum” are not specific, can lead to
misinterpretation, and should not be used. This example could be interpreted two ways:
either as 5 psia, or as -5 psig (note that -5 psig = {0 psig – 5 psig} = 9.7 psia)
3.2 Why is Pressure Measurement Important?
Many processes must be held within a set of pressure limits. Pressure must be
measured for proper Process Control and Process Safety.
Page 5 of 40
Rev. 0
However, the following basic units of pressure are commonly found internationally for measurement of moderate or high
pressures:
• 1 bar = 14.5 psig
• 1 kg/cm2 = 14.5 psig • 1 kPa = 0.145 psig
Additionally, the following basic units of pressure are commonly found internationally for measurement of low pressures:
• 1 mbar = 0.402 inches of water (at 20 deg C) • 1 mmH2O = 0.0394 inches of
water
• 1 kPa = 0.145 psig
One recommended source for measurement units and conversion factors is API Manual of Petroleum Measurement
Standards Chapter 15—Guidelines for the Use of the International System of Units (SI) in the Petroleum and Allied Industries.
This document is found in the Wood Group Mustang Library IHS collection as API MPMS 15. This document is based on
metric units of pascals (Pa).
A detailed source of pressure conversion factors may be found on the website of the National Institute of Standards and
Technology (NIST), in Appendix B of The NIST Guide for the use of the International System of Units, at
http://physics.nist.gov/Pubs/SP811/contents.full.html or at
http://physics.nist.gov/cuu/pdf/sp811.pdf
Page 6 of 40
Rev. 0
.
Page 7 of 40
Rev. 0
Measurement of pressure at pump suction and pump discharge (in this example, tagged
PT and PG), and measurement of differential pressure (in this example, tagged PDG)
across pump suction strainer.
The ISA default suggestion for Pressure Differential Indicator tagging is “PDI”. Note that
some clients will tag Pressure Differential Gauges as “PDG”, to help differentiate from
the control system software tag “PDI” (the software readout for a PDT, which is not
shown here, but which may be installed across the suction strainer). Note that the
thermometer below is similarly tagged “TG”, and not “TI”.
.
Page 8 of 40
Rev. 0
Measurement of pressure on inlets and outlets of heat exchangers (in this example,
tagged PG on shell inlet and tagged PT and PG on shell outlet; tagged PT and PG on
tube inlet and tagged PG on tube outlet).
Refer to earlier discussion on tagging of pressure gauges as “PG” versus “PI”.
Page 9 of 40
Rev. 0
5.1 Manometer
5.1.1 Definition of a Manometer
A Manometer is a “U” tube measuring device, often made of glass, and normally limited
to the measurement of pressures close to atmospheric pressure.
5.1.2 Pressure Measurement by a Manometer
Manometers are rarely used in the process industries, but the principles described below
are the basis for many types of pressure and differential pressure measurement.
Manometers consist of a vertical column of liquid in a tube whose ends are exposed to
different pressures. The column will rise or fall until its weight is in equilibrium with the
pressure differential between the two ends of the tube. A very simple version is a U-
shaped tube half-full of liquid, one side of which is connected to the region of interest
while the reference pressure (which might be the atmospheric pressure or a vacuum) is
applied to the other. The difference in liquid level represents the applied pressure.
The pressure exerted by a column of fluid of height h and density r is given by the
hydrostatic pressure equation, P = rgh, where g= acceleration of gravity (9.81m/s2).
Therefore the pressure difference between the applied pressure P and the reference
pressure Po in a U-tube manometer can be found by solving P-P0 = rgh.
Any fluid can be used, but mercury is preferred for its high density (13.534 g/cm³) and
low vapor pressure. For low pressure differences which are well above the vapor
pressure of water, water is a commonly-used liquid (and "inches of water" is a
commonly-used pressure unit).
Note that reference fluid density may change with ambient temperature.
Page 10 of 40
Rev. 0
The bottom of the tube assembly shown above is the bourdon tube socket. It is
commonly made of the same materials as the bourdon tube. Connection sizes for
process gauge sockets are typically ½” MNPT, with ¼” MNPT used for air regulators,
etc.
The bourdon tube and socket are the only process wetted parts.
Page 11 of 40
Rev. 0
Except for small air pressure gauges (as found on air filter regulators), solid front,
blowout back construction is typically the default requirement for process pressure
gauges. The following is a picture of an Ashcroft 1279 phenolic gauge. Note the solid
front is part of the phenolic case, and note the blowout disc at the bottom of the rear
plastic cover.
Do
Page 12 of 40
Rev. 0
Process pressure gauge cases are commonly supplied either as 4.5” diameter phenolic
cases, or as 100mm diameter 304SS cases. Phenolic cases are typically resistant to
chemicals and corrosion, but may crack under high exposure to sunlight and UV rays.
Stainless steel cases are resistant to physical damage, but cost more than phenolic
cases.
Bourdon tubes and sockets are commonly supplied as 316SS for most services, or as
Monel for seawater or sour gas (H2S) services.
Pressure gauges in extremely corrosive fluids will often utilize 316SS bourdon tubes and
sockets, with the gauge installed on a diaphragm seal (see below).
Pressure gauge movements are often 316SS
5.2.3 Analog Gauge Pressure Ranges and Accuracies
For maximum readability, bourdon tube gauges should be typically specified such that
the normal range of pressures is in the middle half of the gauge. For example, if the
vessel normally operates at 25 to 75 psig, and the vessel maximum pressure is 90 psig,
then a 100 psig range gauge may be a good selection.
Process pressure gauges typically have an accuracy of +/- 1%
In the picture below, this 0 to 2000 psig range gauge (with stainless steel case) has 20
psi small graduations.
Note that if a vessel operates at a very low pressure relative to its maximum pressure,
digital gauges or indicating pressure transmitters may be indicated. For example, if the
vessel operates at 180 to 200 psig, but has a maximum pressure of 1800 psig, then
discerning pressure gauge needle movement between 180 and 200 psig is very difficult
if the gauge range is 2000 psig. In this case, an indicating pressure transmitter may be
a good alternative, as the transmitter often has 0.1% accuracy. Additionally, a
transmitter in this example could be calibrated, say, 0 to 300 psig, but still have an
overpressure limit in excess of 1800 psig.
Refer to Overpressure Limits, below, for additional discussion regarding range
selection.
.
Page 13 of 40
Rev. 0
The bourdon tube range selection table below is typical for many gauge suppliers.
.
Page 14 of 40
Rev. 0
Page 15 of 40
Rev. 0
Page 16 of 40
5.3 Pressure Gauge Options
5.3.1 Liquid Filling
The delicate links, pivots, and pinions of a traditional gauge are sensitive to both
condensation and vibration.
Process induced vibration is commonly found around positive displacement pumps (e.g.,
small chemical injection plunger type pumps). Vibration such as this will quickly destroy
a gauge.
Pressure gauges are often liquid filled. Liquids such as glycerin are used to fill the case
(inside the case, but outside the bourdon tube), thus dampening movement from
pressure spikes. The liquid also lubricates the gears and linkages in the gauge. The
presence of the fill fluid also prevents moisture penetration and icing.
Glycerine is the most common fill fluid. Silicone fill fluids are commonly used in
temperature extremes, such as -40 deg F. Insulating oils are typically used if the gauge
has electrical switch options. Other specialty fluids may be used with process media
such as oxygen and chlorine.
5.3.2 Syphons
Pressure gauge syphons (also called “pigtails”) are intended to protect the pressure
gauge from the effect of hot pressure media such as steam. Condensate of the
pressure medium that is collected inside the coiled or U-shaped portion of the syphon
prevents direct contact. When first installed the syphon should be filled with water or
any other suitable separating liquid.
Page 17 of 40
Rev. 0
Used for dampening and filtering, the snubber has a metal disc available in several
different grades of porosity.
Page 18 of 40
5.3.4 Gauge Protectors and Pressure Limiting Valves
As discussed above, the bourdon tube rating should exceed the system Maximum
Allowable Working Pressure. This goal is sometimes difficult to achieve, if the operating
pressure and desired pressure gauge range is low, compared to the MAWP (example:
the operating pressure is 180 psig, but the MAWP is 1800psig). How is it possible to
have a pressure gauge with a low range bourdon tube, if the MAWP is high?
Gauge protectors function to limit the pressure to which a pressure gauge is exposed.
When the process pressure reaches a pre-set value, an internal assembly acts to shut
off pressure to the gauge, to prevent the gauge from being exposed to more pressure
than its bourdon tube can withstand.
Gauge Protectors should NOT be default solutions, and should NOT be used
except in VERY clean fluids. There are multiple reasons:
• An operator can easily be misled regarding system pressure, if the gauge
reading is low, but the protector is blocking high actual pressure.
• A plugged unit (example: waxy crude oil) can lead to unsafe conditions, where
pressure is trapped inside the gauge, or blocked from the gage, resulting in
incorrect readings.
• The seals in the unit can leak, and the gauge might still be subjected to
pressures beyond its limits.
• The unit’s setpoint can easily drift or be accidentally changed.
Document is valid only at time of printing. See myMustang® for latest revision.
TM-IE-0602 Page 19 of 40
Rev. 0
Switches are commonly found where a pressure limit is being monitored via on-off type
indication, and are often characterized by low cost installations or installations where no
diagnostics are required (e.g., lube oil low pressure switches). Note -- pressure
transmitters are more expensive than pressure switches, but provide additional
information and diagnostics.
Page 20 of 40
Rev. 0
SPST
Single Pole,
Single Throw
(normally closed)
SPDT
Single Pole,
Double Throw
DPDT
Double Pole,
Double Throw
Shelf state -- condition of a switch when it is on the shelf (no power, no process fluid)
• Normally Closed contact is closed (connected to Common terminal)
• Normally Open contact is open
Page 21 of 40
Rev. 0
Page 22 of 40
.
Pressure Instrumentation
Rev. 0
Page 23 of 40
Rev. 0
.
Page 24 of 40
Rev. 0
.
Page 25 of 40
Rev. 0
D
Page 26 of 40
Rev. 0
Page 27 of 40
Rev. 0
.
Page 28 of 40
Rev. 0
Alternate style constructions are also available, including “stick” transmitters. Typically,
this style of transmitter does not have an electronics housing with wiring terminals, but
instead, has “flying leads” (signal wires that may be 18” to 72” long).
This type of construction is light-weight and
small, and is often used inside of control
panels or is line-mounted, directly on a ½”
valve.
Page 29 of 40
Rev. 0
Page 30 of 40
5.7.5 Pressure Transmitter Response Time
Transmitter response time is a function of the electronics processor and manufacturer.
Response times of “smart” transmitters range from a low of about 100msec, to a high of
over 1 second. Response times of some high-speed analog (“non-smart”) transmitters
are much faster, at around 7 msec.
Use of fast response time transmitters may be required by certain processes (e.g.,
compressor surge control normally requires response times of < 150msec).
5.7.6 Pressure Transmitter Ranges and Overpressure Limits
Instrument Range
The Instrument Range is the capability of the transmitter. Some manufacturers will refer
to this as the “range and sensor limit”, or “Upper Range Limit” (URL) and ”Lower Range
Limit” (LRL).
For example, a particular transmitter may have the following specifications:
• LRL = -14.7 psig
• URL = 150 psig
• Minimum Span = 1.5 psi
Calibrated Range
The Calibrated Range is the desired calibration, for the particular process application.
As shown above, the Calibrated Range consists of values less than or equal to the
capabilities of the Instrument Range.
Display Range
If the transmitter does not have a local integral indicator, the display range is “N/A”.
If the transmitter has a local indicator, the Display Range is typically the same as the
Calibrated Range.
Overpressure Limit
The Overpressure Limit is the maximum pressure that the unit can withstand without
damage. This value should be chosen to be greater than the process system’s
maximum working pressure, plus relief valve accumulation. For example, if the
transmitter is on a vessel that has a relief valve set at 1000 psig, and the relief valve is
specified to have 21% overpressure, the Overpressure Limit of the transmitter should be
at least 1210 psig.
Page 31 of 40
5.7.7 Pressure Transmitter Operating Temperature
Transmitter data sheets often carry a data field for operating temperature.
For the purposes of example, assume the transmitter is installed on a vessel with a
maximum temperature rating of 450 ºF,
If the transmitter is directly mounted on the vessel, then the transmitter could reach
450ºF. In this scenario, transmitter manufacturers may not be able to supply a unit for
these temperature extremes (because most transmitters cannot operate at ambient
temperatures above 180 ºF or so, or process temperatures above 350 ºF or so).
If the transmitter is remotely mounted, and connected to the vessel via tubing, the
transmitter will be at ambient temperature (non-flowing tubing temperature is typically at
ambient temperature within 2 or 3 feet of distance).
In the above example, if the data sheet Maximum Design Temperature field stated “450
ºF”, and the transmitter were also remotely mounted, an explanatory note regarding
remote mounting would clarify the transmitter temperature situation to the transmitter
vendor, so as to avoid a potential “no-bid”.
Caution – where “intelligent P&IDs” are used, line properties such as Maximum Design
Pressure and Temperature are often automatically associated with instruments on the
line. In this case, the engineer would need to decide whether to delete this data (to not
cause confusion for the vendor) or whether to add an explanatory note that the
transmitter is remote-mounted.
5.7.8 Common Pressure Transmitter Options
The project design criteria will typically determine the selection of the following:
• Mounting bracket – For the Clients who like to connect transmitters to the
process via tubing, and mount the transmitter at grade, the transmitter will need a
bracket to mount to a 2” pipestand. For the clients who like to purchase light-
weight transmitters and mount them directly on valves on the piping (to minimize
tubing costs and leak points), no bracket is needed.
• Hazardous area certificates – often required as part of the project documentation
package, for inspectors or insurance.
• Calibration – often required as part of the transmitter warranty (factory calibration
equipment is much more accurate than field equipment). If factory calibration is
purchased, field construction personnel need only to validate transmitter function,
and should not perform a recalibration.
• Transient protection – often required where transmitters are exposed to lightning
(such as areas with minimal overhead structures), but not typically required on
offshore platforms, with large amounts of overhead steel construction
• Custom software configuration – includes information such as HART tagging,
write protection on/off, special damping settings, etc.
• SIL Certification – this indicates that the particular design chosen has been
reviewed by a 3rd party and that Safety Integrity Level Documentation is
available. The choice of a particular transmitter model number series (and the
diagnostic capabilities of the transmitter) will determine if the unit is certified.
Page 32 of 40
Rev. 0
.
Page 33 of 40
6.3 Local Pneumatic Controller Installation
A local pneumatic controller may be pipe-stand mounted, but is more often yoke-
mounted to the control valve (picture below is an example Fisher C1 bourdon-tube
pressure controller).
In Downstream facilities, air supply regulators are often set at 20 psig, and the controller
output is 3 to 15 psig to the control valve. In Upstream facilities, air supply regulators
are often set at 35 psig, and the controller output is 6 to 30 psig to the control valve (the
doubled pressure permits smaller control valve actuators).
Page 34 of 40
Pressure Instrumentation
Flushing rings and flushing ports are used when debris build-up is possible. Many
arrangements are possible, but one common type is shown below
D
Page 35 of 40
Rev. 0
However, diaphragm seals are often remote mounted from the instrument. A capillary
tube is used to connect the seal to the instrument.
Capillary tubing is typically constructed of flexible 316SS tubing.
Capillary diameters typically range from 0.03” to 0.07” diameter. A smaller capillary
inside diameter (ID) creates more restrictions and slows down the pressure transport. A
larger capillary ID provides a faster response time.
For reliability reasons, a welded capillary tube is recommended. If the fill fluid leaks, the
seal system is rendered inoperative. Welding of the instrument to the seal (thus sealing
in the fill fluid) is a common option.
By minimizing the capillary length and inside diameter, fill volumes can be kept as low as
possible to reduce temperature effects.
Page 36 of 40
7.5 Recommended Diaphragm Sizes
Diaphragm seals are commonly available in process connection sizes from ½”to 4”.
Diaphragm stiffness is affected by the diaphragm surface diameter. Generally,
smaller diameter diaphragms are stiffer than larger diameter diaphragms. Smaller
diameter diaphragms also have more error when the fill fluid expands or contracts
with temperature changes.
Pressure transmitters will often utilize 2” diaphragm seals when measuring pressures
in the psig range. Differential pressure transmitters, and low pressure transmitters
will often utilize 3” diaphragm seals when measuring pressures in the inches of water
range.
The picture below shows pressure transmitters with 2” diaphragm seals.
.
Page 37
of 40
8.0 P RES S URE CALIBRATION DEVICES
This section does not relate to the pressure instrument specification process, or to pressure
instrument data sheets. This section is provided as introductory information only.
8.1 Deadweight Tester
Benchtop calibration devices include deadweight testers. A hand-pump is used to
balance the hydraulic force created by precision weights. Accuracies are typically
around +/-0.1% of reading. Most benchtop units are typically not accurate enough to
calibrate the latest generation of modern transmitters.
.
Page 38 of 40
8.4 Required Accuracy of Test Equipment
Pressure gauges have accuracies of +/-1%, but leading pressure transmitters accuracies
are typically around +/-0.025%. It is not valid to utilize a piece of test equipment with an
accuracy of +/-0.025%, to calibrate a transmitter to an accuracy of the same value.
The minimum required resolution of the test equipment is commonly 4 to 10 times better
than the required accuracy. Refer to literature on Metrology, from sources such as the
following, for additional details:
http://ts.nist.gov/WeightsAndMeasures/labmetrologypage.cfm
http://www.metrology.asn.au/files/PressureGaugesMSATestMethod2Rev3.pdf
Page 39 of 40
Rev. 0
AP P ENDICES
Appendix 1: References
www.ashcroft.com
www.ccsdualsnap.com
www.fisher.com
http://www.metrology.asn.au
http://ts.nist.gov/WeightsAndMeasures/labmetrologypage.cfm
www.neodyn.com
http://physics.nist.gov
www.rosemount.com
http://www.testequipmentdepot.com
www.wika.com
www.wikipedia.com
.
Page 40 of 40