You are on page 1of 4

providing insights for

today’s HVAC system designer

Protecting The Electrical Distribution System…


Short-Circuit Withstand Ratings Demystified
“Normal” and “overload” conditions … conditions” to select overcurrent than its rated amperage for an extended
“fault current”…”interrupt” versus protection devices such as circuit period. Basic overload devices simply
“withstand” ratings…”current-limiting.” breakers and fuses. Rating factors are open the circuit when current draw
Knowing what these terms mean and applied, based on the type and number reaches the “trip” point. More
applying them correctly is fundamental of connected loads, to assure that the sophisticated devices attempt to restore
to designing safe, reliable electrical devices selected adequately protect the normal motor operating conditions by
distribution systems. This is especially motor as it starts and while it’s running. reducing the load, but will disconnect
true in light of more stringent code the motor if overloading persists.
enforcement and the current design Let’s look at an example. Suppose a 500-
trend to deliver energy savings by ton chiller has a 480-volt motor that For most overload protection devices,
selecting low-impedance transformers. draws 400 amps at rated load “trip” time is determined by the
Why? Lower transformer conditions. The electrical distribution magnitude of the overload. Figure 1
impedances mean higher short- system includes a wye-delta starter illustrates a straight-line, time/current
circuit currents. powered by a 1,500-kVA transformer. “trip” curve that shows response times
Operating “normally,” the chiller motor for current draws greater than
Simply choosing a circuit breaker with a draws about 800 amps during the 110 percent of RLA. A device with these
high interrupt rating won’t assure 4 seconds it takes to start; then 400 characteristics would allow our example
adequate protection under short-circuit amps or less at running speed. chiller motor to draw 480 amps for
conditions. With an “ounce of 8 seconds before disconnecting it.
prevention,” you can avoid the code The size of the interconnecting wires
official’s “red tag” at your next system between the transformer and starter
start-up. Let’s review the meaning of the reflects the type and rated amperage Figure 1
terms that opened this article, define draw of the load, i.e. the chiller motor.
some of the issues related specifically to Sizing the wires on this basis assures that 140%
HVAC motor starter applications and they can carry the inrush current at start-
identify practical, effective solutions. up without overheating. Rated
Load
Amps

Normal Operation, n. Overload Operation, n. 110%

“Normal operation” describes the full (or Inductive loads, like the chiller motor in 1 second Time 20 seconds
rated) load conditions of each system our example, behave differently than
component. For motors, it includes the resistive loads such as electric heaters.
amps intially drawn at start-up, i.e. Their current draw is greatest at start-up
inrush current, as well as the full- or and corresponds to the existing load
rated-load amps drawn while running. when running. In other words, a motor Fault Current, n.
The magnitude of inrush current for a operating normally draws rated amps Imagine a wrench inadvertently left in a
particular application depends on the (RLA) at rated load, fewer amps at less- starter following service. Touching two
type of starter used (e.g. wye-delta). than-rated load and more amps at terminals, it completes the circuit
greater-than-rated load. It’s the latter between them when the panel is
Normal operating conditions determine condition that necessitates overload energized. What results is a potentially
wire and transformer sizing. They’re also protection. dangerous situation or “fault condition”
used in conjunction with “fault caused by the low-impedance, phase-to-
Adding an overload protection device phase or phase-to-ground connection …
prevents the motor from drawing more a “short circuit.”

© American Standard Inc. 1998 Volume 27, No. 3 August 1998 ■


Fault current, also called “short-circuit heats components to very high Underwriters Laboratories Inc. (UL)
current” (Isc ), describes current flow temperatures that destroy insulation, defines the short-circuit test methods
during a short. It passes through all melt metal, start fires … even cause an and parameters for HVAC equipment.
components in the affected circuit. Fault explosion if arcing occurs. The inherent Essentially, the test subjects an enclosure
current is generally very large and, likelihood of severe equipment and to the recommended current, i.e. 4,000
therefore, hazardous. Only the combined property damage, as well as the risk of amps if the unit RLA exceeds 40 amps
impedance of the object responsible for personal injury or death, underscores the and 3,500 amps if it’s less. If the doors
the short, the wire, and the transformer importance of sufficient electrical blow open or if it emits flames or sparks,
limits its magnitude. distribution system protection. the enclosure fails the test. For those that
pass, it’s “acceptable”—even probable—
One objective of electrical distribution that the internal components will be
system design is to minimize the effect of damaged beyond repair. Given the
a fault, i.e. its extent and duration, on Interrupt Rating, n. destructiveness and expense of this test,
the uninterrupted part of the system. Determined under standard conditions, it’s not surprising that most
Coordinating the sizes of circuit breakers the “interrupt rating” specifies the manufacturers prefer not to pursue
and fuses assures that these devices maximum amount of current a protective higher-than-normal short-circuit
isolate only the affected circuits. Put device can cut off safely … i.e. without withstand ratings for their equipment
simply, it prevents a short at an outlet harm to personnel or resulting damage unless there’s a documented need.
from shutting down power to the entire to equipment, the premises or the device
building! itself. For example, a circuit breaker that Recall that when a fault occurs, all
trips “safely” successfully interrupts the components in the circuit experience the
Calculating the magnitude of short- fault, can be reset and will function brunt of the short circuit until it’s
circuit current is prerequisite to selecting properly afterward. To safely stop the stopped. Therefore, it’s important to
appropriate breakers and fuses. If the fault current calculated for our chiller- assure that all components “at risk” can
distance between transformer and starter motor scenario, the interrupt rating of withstand a fault condition without
is brief, the calculation can be simplified the circuit breaker or fuses selected must causing injury or damaging the
by ignoring the impedance of the be at least 31,400 amps. surroundings. The National Electric Code
interconnecting wiring … a simplification (NEC) states this requirement in Section
that errs on the side of safety. We can Before leaving this topic, let’s dispel a 110-10, “Circuit Impedance and Other
also assume that the source of the fault common misconception: “An overcurrent Characteristics”:
has zero impedance, i.e. a “bolted” protection device with a comparatively
short. Given these assumptions, the only high interrupt rating limits current to The overcurrent protective devices, the
impedance left to consider is that of the other components.” Not so —not total impedance, the component short-
transformer. (Impedance upstream of the unless it’s also a true current-limiting circuit withstand ratings, and other
transformer is usually negligible.) device as described on page 3. Even characteristics of the circuit to be
though the device successfully breaks the protected shall be selected and
Suppose the 1,500-kVA transformer in circuit, all components in the circuit will coordinated to permit the circuit
our example has impedance of 5.75 be exposed to the full magnitude of fault protective devices used to clear a fault to
percent. With this value and the current (as well as the severe thermal and do so without extensive damage to the
equation below, we can determine how magnetic stresses that accompany it) for electrical components of the circuit. This
much fault current a short circuit will the time it takes the device to respond. fault shall be assumed to be either
produce. As you can see, a short would between two or more of the circuit
force our wiring to carry more than conductors, or between any circuit
30,000 amps when it was designed to conductor and the grounding conductor
handle only 400 amps! Withstand Rating, n. or enclosing metal raceway.
Though often confused, “interrupt
rating” and “withstand rating” are not Commentary in the 1996 National
1500 kVA ⋅ 1000 -
I sc = ----------------------------------------------------- interchangeable terms. Unlike the Electrical Code® Handbook further
480 V ⋅ 1.73 ⋅ 0.0575
interrupt rating, which defines the explains Section 110-10:
= 31,400 amps performance limit of an overcurrent
protection device (e.g. circuit breaker or Overcurrent protective devices (such as
fuse), the “withstand rating” is a fuses and circuit breakers) should be
Short-circuit current is often two orders performance limit for an enclosure. In selected to ensure that the short-circuit
of magnitude greater than normal other words, it identifies the maximum withstand rating of the system
operating current. Unless a circuit short-circuit amperage an enclosure can components will not be exceeded should
breaker or fuse successfully interrupts the contain without injuring personnel or a short circuit or high-level ground fault
fault, this enormous amperage rapidly damaging the premises. occur.

■ 2 Trane Engineers Newsletter — Vol. 27, No. 3


System components include wire, bus Figure 2 also shows the effect of a process, and should address both normal
structures, switching, protection and current-limiting device. To be truly operation and fault conditions.
disconnect devices, distribution current-limiting, the interrupting
equipment, etc., all of which have limited device must open the circuit within one- Occasionally, the calculated fault current
short-circuit ratings and would be quarter cycle (1/240 second), i.e. before exceeds the short-circuit withstand
damaged or destroyed if these short- the fault current peaks. ratings of available starters. Such cases
circuit ratings are exceeded. Merely require adding an appropriate current-
providing overcurrent protective devices Remember our chiller-motor scenario? If limiting device or redesigning the
with sufficient interrupting ratings will there’s no starter available with a short- electrical system to reduce fault current.
not ensure adequate short-circuit circuit withstand rating greater than
protection for the system components. 31,400 amps, compliance with NEC The fault-current analysis in the chiller-
When the available short-circuit current Section 110-10 requires that we either: motor scenario consisted of a simplified,
exceeds the withstand rating of an worst-case calculation. While this is often
electrical component, the overcurrent ■ Add a current limiting device, i.e. sufficient to select system components, a
protective device must limit the let- usually a fuse, but sometimes a circuit number of factors demand more detailed
through energy to within the rating of breaker and fuse in series, that analysis. To learn more, refer to The IEEE
that electrical component. restricts the fault current to a value Buff Book: Recommended Practice for
less than the starter’s short-circuit Protection and Coordination of Industrial
To comply with this section of the NEC, withstand rating. Or … and Commercial Power Systems
all of the component selections in our published by The Institute of Electrical
chiller-motor scenario must be based on ■ Redesign the electrical distribution and Electronics Engineers, Inc. ■
a minimum short-circuit withstand rating system to reduce the fault current.
of 31,400 amps … a requirement well Choosing this approach warrants a By Dave Guckelberger,
above UL’s standard ratings. more detailed fault-current analysis. applications engineer, and Brenda
Bradley, information designer,
The Trane Company.

Current Limiting, n. Summary If you’d like to comment on this article,


All components and wiring in an Protecting HVAC equipment is a critical send a note to The Trane Company,
electrical distribution system offer some element of electrical distribution system Engineers Newsletter Editor, 3600
degree of resistance. Under normal design. Proper selection and Pammel Creek Road, La Crosse WI
conditions, the heat produced when coordination of overcurrent protection 54601, or to www.trane.com.
current flows against this resistance devices should occur early in the design
readily dissipates to the surroundings.
However, the enormous current
generated during a short circuit produces
damaging heat at a much faster rate Figure 2
than can be safely dispersed. Interrupt Prospective available short-circuit current
the current and you stop adding heat to 100,000 that would flow when a fuse is not used.
the system.

As Figure 2 suggests, time is a critical


determinant of the amount of heat
(energy) added. An electrical short that
Current
lasts three cycles, for example, adds six
times the energy of one lasting just one-
half cycle. It’s in this sense that all circuit
breakers and fuses “limit” current.
Peak Fuse
10,000 “Let-Thru”
Current
0
tc Time

Total Fuse Clearing Time

“providing insights for today’s HVAC system designer” 3 ■


A publication of
The Trane Company
Worldwide Applied Systems Group
La Crosse, WI 54601-7599

Sharing Insights About HVAC System Design …


The Engineers Newsletter
“ … HVAC is more than a rule-of-thumb Who Publishes It? The Trane
business. It requires a high level of applications engineering team oversees Looking Ahead …
education and knowledge for one to be publication of the Engineers Newsletter, We appreciate your interest in the
effective and efficient in this business.” carefully selecting topics based on Engineers Newsletter and extend a
relevance and timeliness. Material is special thank you to those who
We received this comment from one of gleaned through frequent contact with completed the reader survey.
nearly 1,200 Engineers Newsletter customers and professionals in the HVAC
readers who responded to the survey industry, as well as from technical experts If there’s a topic you’d like us to tackle in
issued at the beginning of the year. It within and outside the Trane a future EN, let us know. We value your
aptly states the logic behind the organization. suggestions and comments. Send them
EN’s mission to provide HVAC system via e-mail to bbradley@trane.com or to
designers and engineers with How’s It Distributed? Most of the The Trane Company, Attn: Applications
reliable, technologically current 40,000 recipients receive their copy of Engineering, 3600 Pammel Creek Road,
information in an “easy-to-digest” the Engineers Newsletter by mail, La Crosse, WI 54601-7599. ■
form. courtesy of their local Trane commercial
sales office. Electronic versions are
The survey responses received so far posted on the Web at www.trane.com,
(summarized below, right) provide a too.
snapshot of how readers perceive the
Engineers Newsletter. If these results and
the comments that accompanied them EN Readers Respond …
represent the entire EN readership, then ■ How do you usually receive this newsletter? 93% by mail
the publication is fulfilling its mission. 2% delivered by my Trane rep
2% from the Trane Web site
3% other
■ How would you prefer to receive it? 90% by mail
Looking Back … 6% by e-mail
Last year marked the silver anniversary 2% delivered by my Trane rep
of the Engineers Newsletter. If you’re 1% from the Trane Web site
new to the publication, here’s a bit of 1% other
background. ■ Do you read the Engineers Newsletter? 72% yes, in detail
29% yes, I skim it
What Is It? The Engineers Newsletter 0% no
is a free, 4- to 8-page periodical ■ Do the topics covered interest you? 100% yes
published several times each year. Each 0% no
edition tackles a specific, timely issue ■ In general, how would you describe the 93% just right
related to commercial HVAC system level of detail that’s provided? 4% too little
design. The “ad-free” discussion is 3% too much
concise and supported with illustrations
■ How do you use this publication? 87% as a technical reference
and case studies. (The last page is usually
(Check all that apply.) 48% as a source for innovative design ideas
reserved to promote a new product, 14% to develop specifications
service or system concept.) 32% for personal or in-house training
37% for problem-solving
■ What is your job title? 56% design engineer
1% architect
7% contractor
12% project manager
9% facility manager
1% building owner
14% other
Printed on recycled paper as part of
The Trane Company’s recycling program.

■ 4 ENEWS-27/3

You might also like