Professional Documents
Culture Documents
“Normal operation” describes the full (or Inductive loads, like the chiller motor in 1 second Time 20 seconds
rated) load conditions of each system our example, behave differently than
component. For motors, it includes the resistive loads such as electric heaters.
amps intially drawn at start-up, i.e. Their current draw is greatest at start-up
inrush current, as well as the full- or and corresponds to the existing load
rated-load amps drawn while running. when running. In other words, a motor Fault Current, n.
The magnitude of inrush current for a operating normally draws rated amps Imagine a wrench inadvertently left in a
particular application depends on the (RLA) at rated load, fewer amps at less- starter following service. Touching two
type of starter used (e.g. wye-delta). than-rated load and more amps at terminals, it completes the circuit
greater-than-rated load. It’s the latter between them when the panel is
Normal operating conditions determine condition that necessitates overload energized. What results is a potentially
wire and transformer sizing. They’re also protection. dangerous situation or “fault condition”
used in conjunction with “fault caused by the low-impedance, phase-to-
Adding an overload protection device phase or phase-to-ground connection …
prevents the motor from drawing more a “short circuit.”
■ 4 ENEWS-27/3