Lansing Fire Department
Fire Marshal’s Office
Code Enforcement Section
3I6N, Capitol Ave Lansing, MI 48933-1238
(617) 483-4361 FAX (617) 377-0100
Mayor Vig Bernero
Notice Printed: April 05,2016
Refital inspection Sign and Return Notice
LANSING HOUSING COMMISSION
419 CHERRY ST
LANSING, MI 48933
Warning: Fallure to comply with the requirements of this notice may result In the issuence of
“a Municipal Civil infraction Violation Ticket. (Fines: $500 per day for each violation)
Violation Location: 2430 REO RD
Parcel No: 33-07-01-31-427-011
The above referenced address was found to have certain violations of the Lansing Housing and Premises
Code, Chapter 107 of the Code of Ordinances. The violations are listed below and must be corrected
by the compliance due date.
BUILDING: 1
UNIT: 2430
AREA: Basement
Sec 603.1 Furnace: Due to age and or condition, have a qualified mechanical
contractor that is registered vith the City of Lansing, visually inspect and
Perform a recognized test of the furnace heat exchanger for CO/CO2 leaks.
Inspect the heat exchanger for cracks, openings, excessive rust and
corrosion. Inspect furnace casing, check for proper venting and check
chimney for restrictions and obstructions. Submit a written report by
contractor detailing the results and repairs completed per code.
Sec 504.1 Waste pipe ¢ air admittance valve installed without the benefit of
a plumbing permit, a licensed plumbing contractor to conduct the work, &
final inspection/approval from the City of lansing Building Safety Office.
Sec 307.1 Lack of a guardrail at the open sides of the basement stairs.
AREA: First Floor
Sec 603.1 Clogged register cover at the ceiling of the entryway.
SEC 305.3 Damaged corner pieces at the first floor drywall.
SEC 305.3 Deteriorated caulk at the backsplash of the kitchen counter.
AREA: Second Floor
SEC 305.3 Damaged wall in the bathroom.
SEC 305.3 Peeling paint in the hallway.
“Equal Opportunity Employer"Texmaver's ConySec 604.3 Inoperable GFCI outlet in the bathroom.
yec 604.3 Cover plates missing and or damaged at outlets - switches.
Sec 504.1 Leak at the bathtub faucet.
Sec 504.1 Missing a bathroom sink stopper.
2432
AREA: Basement
Sec 603.1 Furnace: Due to age and or condition, have a qualified mechanical
contractor that is registered with the City of Lansing, visually inspect and
perform a recognized test of the furnace heat exchanger for CO/CO2 leaks.
Inspect the heat exchanger for cracks, openings, excessive rust and
corrosion. Inspect furnace casing, check for proper venting and check
chimney for restrictions and obstructions. Submit a written report by
contractor detailing the results and repairs completed per code.
Sec 603.1 Clogged heat register.
Sec 307.1 Lack of a guardrial at the open sides of the basement stair:
Seo 504.1 Soil pipe installation lacks a plumbing permit, a licensed
plumbing contractor to conduct the verk, & final inspection/approval fron the
City of Lansing Building Safety Office.
AREA: First Floor
Sec 504.1 Leak at the kitchen faucet.
SEC 305.3 Damaged drywall comers throughout the first floor.
SEC 305.3 Deteriorated/damaged linoleum at the kitche floor.
Sec 305 Missing kitohen cabinet door.
Sec 305.6 Missing kitchen closet door.
Sec 305.6 Damaged closet door in the entryway.
AREA: Second Floor
Sec 604.3 Inoperable bathroom GFCI outlet.
Sec 504.1 Leak at the bath faucet.
Sec 504.1 Damaged handle at the bathroom sink.
SEC 305.3 Damaged bathroom wall.
SEC 305.1 Mildew at the bathtub area.
2434
Basement,
Seo 603.1 Furnace: Due to age and or condition, have a qualified mechanical
contractor that is registered vith the City of Lansing, visually inspect and
perform a recognized test of the furnace heat exchanger for CO/CO2 leaks.
Inspect the heat exchanger for cracks, openings, excessive rust and
"qual Opportunity Emplayee*Taxpayer's Copycorrosion. Inspect furnace casing, check for proper venting and check
chimney for restrictions and obstructions. Submit a written report by
contractor detailing the results and repairs completed per code.
Sec 605.1 Lack of proper labeling for the olrouit breakers at the service
panel.
Sec 307.1 Lack of a guardrail at the open sides of the basement stairs.
AREA: Firat Floor
Sec 603.1 Clogged vent cover at the ceiling of the entryway.
AREA: Second Floor
Sec 504.1 Bathroom sink is missing the drain stopper.
Seo 305.6 Missing closet door harvare.
Sec 305.6 Damaged bedroom door trim.
SEC 305.3 Damaged dryvall in the bathroom.
SEC 305.3 Urine jugs & fecal matter in bowls in a bedroon.
UNIT: 2436
AREA: Basement
Sec 603.1 Furnace: Due to age and or condition, have a qualified mechanical
contractor that is registered with the City of Lansing, visually inspect and
Perform a recognized test of the furnace heat exchanger for CO/CO2 leaks.
Inspect the heat exchanger for cracks, openings, excessive rust and
corrosion. Inspect furnace casing, check for proper venting and check
chimney for restrictions and obstructions. Submit a written report by
contractor detailing the results and repairs completed per code.
Sec 307.1 Lack of a guardrail at the open side of the basement stairs.
Sec 504.1 Water heater lacks a final inspection/approval from the City of
Lansing Buidling Safety Office (PP14-0925) .
AREA: First Floor
Sec 603.1 Clogged heat register cover.
SEC 305.3 Missing/deteriorated caulk at the kitchen countertop backsplash,
SEC 305.3 Deteriorated kitchen floor tiles.
AREA: Second Floor
Sec 604.3 Cover pla
bedroom.
missing and or damaged at outlets - switches in a
Seo 604.3 Two damaged outlets in the bedroom.
Sec 403.2 Inoperable bathroom vent fan.
Sec 702.3 Bedroom door has a hasp with padlock. All egress doors shall be
easily opened from the side vhich egress is to be made without the need for
keys, spacial knowledge or effort.
“Bqusl Opportunity Employer"Taxpayer's CopySec 506.1 Improper connection at the kitche sink waste pipe
Se0 305.6 Damaged front bedroom door,
S80 305-3 Damaged drywall at the living room ceiling ¢ front bedroca vali
to cause ieieusantiness = Deoty of wurtaces within dvelling that te Likely
Goecinanee tues OF disease and render air, food or drink unvhorecoss i
doorar catintggthe besith of humans. Ali floors, valle, ceilings rintcrs,
Heres cabinets, countertops, pluabing tixtures and anpiiones seat ee
leaned and maintained in a sanitary sorditinn,
Sec 305 Missing kitchen cabinet door.
AREA! Second Floor
SEC 305.3 Damaged drywall at the vall in the staizvell.
SEC 305.3 Damaged dryvaii at a bedroom door.
Sec 604.3 Damaged bedroom outlet,
Sec 504.1 Danaged bathroom sink stopper.
S00 305.6 Damaged bedzooa door.
WIT: Genera
fee 609-1 Verity furnace filters are clean/nave been changed.
Pectectad onMmved/ capped exterior outlets to be replaced with Grct
protected outlets with the proper exterior vesther coven’
703.1 Verify proper fire stop at the basement pipe chases,
cei ansing Housing and Premises Code. it vacant, or should Kbecomna vacesa Sono all repairs are
completed, then it shall remain vacant unl this office has approved all covections
Failure to comply by the compliance due date may result inthe issuance of a Municipal Civil infraction
poration with Fines: $500 per day for each violation and may recul tne Property being vacated
by this office,
“Basal Opportunity Employer"Tarpayer's Copy
eeSec 506.1 Improper connection at the kitche sink waste pipe.
Sec 305.6 Damaged front bedroom door.
SEC 305.3 Damaged drywall at the living room ceiling ¢ front bedroom wall.
SBC 305.3 Uncleanliness - Decay of surfaces within a dwelling that is likely
to cause sickness or disease and render air, food or drink unwholesome or
detrimental to the health of humans. All floors, valls, ceilings windows,
doors, cabinets, countertops, plumbing fixtures and appliances must be
cleaned and maintained in a sanitary condition.
Sec 305 Missing kitchen cabinet door.
AREA: Second Floor
SEC 305.3 Damaged drywall at the wall in the stairwell.
SEC 305.3 Damaged drywall at a bedroom door.
Sec 604.3 Damaged bedroom outlet.
Sec 504.1 Damaged bathroom sink stopper.
Sec 305.6 Damaged bedroom door.
UNIT: General
Sec 603.1 Verify furnace filters are clean/have been changed.
Sec 604.3 Removed/ capped exterior outlets to be replaced with GFCT
protected outlets with the proper exterior veathar cover.
703.1 Verify proper fire stop at the basement pipe chast
This dwelling has been declared to have violations Of the Lansing Housing Code defined in section 107
of the Lansing Housing and Premises Code. If vacant, or should it become vacant before all repairs are
‘completed, then it shall remain vacant until this office has approved all corrections.
Failure to comply by the compliance due date may result in the issuance of a Municipal Civil Infraction
Violation with Fines: $500 per day for each violation and may result in the property being vacated
by this office.
"Equal Opportunity Employer"Taxpayer's CopyThe Owner or agent must complete, sign and return affidavit,
{certify that all violations have been corrected with approved matatils and methods. All required permits
have been obtained, Repairs requiring a permit have been inspected and approved by the appropriate
inspector.
Signatur
Printed Nam
__Owner or__ Manager, Date
Registered Owner's Copy for property located at- 2430 REO RD
Pursuant o Section 1072 of the IPMC, you have the rg to appeal this notice of violation, accordance with Section 1063 any action ken
by the City on such premises stall be charged against the rel estate upon which the strict I lcated and hall Be i upon ch el state
!fyou have any questions or concems about complying within the time indicated, you may contact at
(617) 483 7620 Monday through Friday between the hours of 8-9 - AM or 12-1 - PM,
Officer: Greg Scrimger
This dosnt guano acne or pag ofl cod lator ropy es, ran oa ch nt th propery np. Tw Cy of
eng ens nt yarn nays a why set ese ean daa onde
‘As specified by section 107- Notices and Orders - a copy ofthis violation was sent to:
Registored Rental Owner: LANSING HOUSING COMMISSION, 419 CHERRY ST, LANSING, Ml 48933.
“Equal Opportunity Employer"Taxpayer's Copy