Technical specifications - Control devices LV AC and DC

TECHNICAL SPECIFICATIONS

DIGITAL EQUIPMENT FOR CONTROL AND MONITORING


CIRCUITS LV AC and DC

Page 1 of 5
Oshea JSC 1 Address: Str. AZ Cajupi, Pll. Conad Tirana, Albania
TIN: K72410014H
Technical specifications - Control devices LV AC and DC

DIGITAL EQUIPMENT FOR CONTROL AND MONITORING


CIRCUITS LV AC and DC

1. General

In order to enable the delivery in the system of control monitoring of all alarms from the AC system,
System.Unfortunately DC-110 volt DC 48 volt system, telecommunication system and other alarms that can not be
taken by digital relays of each tract separate 110 kV, 35 kV or 10 kV, which is required for this purpose in the
monitoring and control panel installed in additional digital relay which must meet the following requirements

• Have sufficient binary entry to enable the submission of all information mentioned above in the
control-monitoring system to
substation
• Relay should enable communication with the control-monitoring system through the IEC61850
communication protocol.
• Relay should enable the delivery of key parameters in the system of measurement in AC and DC.

All settings and charging operations must be done using a menu-based operation of a program that is
installed on a PC connected to the relay device for this purpose.

relay protection device must be equipped with monitoring functions as vetesupervizim of Relay Protection,
supervisioni of measured values, logging of events.

Relay must have facilities Reserved for local communications and the distance relay should be built in
such a way that the necessary hardware and sofware, can be added at any time as needed.

Relay Protection need technical parameters are given in '' Tables with the following technical requirements.

TECHNICAL REQUIREMENTS FOR RELENE DIGITAL COLLECTION OF THE


INFORMATION SYSTEMS FROM AC / DC etc.
(Technical data sheets)
Digital 1.Relete

General requirements
standard IEC60255
communication protocol IEC61850
Temperaturamaksimalee environment for nominal °C - 5 + 40
accuracy (acu-)
storage Temperaturamaksimale °C - 10 + 55

maximum Humidity %

Page 2 of 5
Oshea JSC 1 Address: Str. AZ Cajupi, Pll. Conad Tirana, Albania
TIN: K72410014H
Technical specifications - Control devices LV AC and DC

Tests Electromagnetic Compatibility EN50081,


EN50082-1
​IEC60255-6
Tests Isolation IEC60255-5
IEC60870-2-1
testetmekanike (vibration and shock stresinga) IEC60068-2
IEC60255-2-1
DC supply VDC 40-250 volts
binary Inputs VDC 110 V DC
binary outputs (relays) VDC 110 V DC
Nominal voltage from TR Rymes A 1

Relay contacts outflows


for story
• max Operating voltage V DC 300
• current max. Labor (1s) A 30
• continuous stream A 5
• Labor force in nominal voltage V DC W 1000

for Shutdown

• number

• pressure max. the work V DC 300


• max current A 30
• Stream of continuous work A 5
• The power required in nominal voltage V DC W 1000

• Power opening the nominal voltage V DC L / R W 30


<40 ms

isolation
AC entries (one per minute to all regions and soil kV IEC 60255 / 60870-
tapes) 2-1
2.5, 50 Hz
Inputs and outputs DC (for 1 minute to all the regions and kV 3.5
to the earth tapes)
Resistance to impulse voltage kV peak 2.5

digital relay for collecting and adapting general


alarm for the SAS

fabrication Type /
name
Rated voltage of the food VDC 24-250

Page 3 of 5
Oshea JSC 1 Address: Str. AZ Cajupi, Pll. Conad Tirana, Albania
TIN: K72410014H
Technical specifications - Control devices LV AC and DC

binary Inputs V 110 V DC


binary outputs (relays) V 110 V DC
o C
The ambient temperature normal working conditions - 10 + 55

auto test yes


Tests Isolation Standard IEC
60255-5 and
60870-2
-
distance communication
• Protocol - 60870
• transmission rate Baud 960 min

Introduction Binary ≥12


Binary output ≥8
outgoing powerful contacts (Power Relay) 4
Contact us for faulty relay 1
LED
RUN (green) 1
ERROR (red) 1
LED indicator ≥14
Time Operating contacts NO
contact 8 ms
NO / NC contacts (selectable 8 ms
Fast contact NO 5 ms
Tests Isolation Standard IEC
60255-5 and
60870-2

Technical data

Power supply

nominal voltage Un 220, 240 V AC, 50 Hz


Auxiliary voltage variation 38 ... 110% Un (38 ... 264 V AC) 50 ... 120% Un12 ... 72 V DC Start-up threshold
DC 19.2 V (24 V DC * 80%)
Fuse type T4A / 250 V
Rated frequency 50/60 Hz
Current inputs Rated current, In 0.2 / 1 A1 1/5 A2

Binary inputs

Operating range Rated voltage Current drain

Signal output

Page 4 of 5
Oshea JSC 1 Address: Str. AZ Cajupi, Pll. Conad Tirana, Albania
TIN: K72410014H
Technical specifications - Control devices LV AC and DC

Rated voltage Continuous contact carry Make and carry for 3.0 s Make and carry for 0.5 s Breaking capacity When
the control-circuit time constant L / R <40 ms Minimum contact load

Signal outputs and IRF output

Rated voltage Continuous contact carry Make and carry for 3.0 s Make and carry 0.5 s Breaking capacity When
the control-circuit time constant L / R <40 ms, at 48/110/220 V DC Minimum contact load

Reference Standards and Tests

1 MHz / 100 kHz burst disturbance test IEC 61000-4-18 IEC


60255-22-1, class III IEEE
C37.90.1-2002

Electrostatic discharge test IEC 61000-4-2 IEC


60255-22-2 IEEE
C37.90.3-2001

Contact discharge 8 kV

Air discharge 15 kV

Radio frequency interference test

10 V (rms) IEC 61000-4-6


f = 150 kHz ... 80 MHz IEC 60255-22-6,
class III
10 V / m (rms) IEC 61000-4-3
f = 80 ... 2700 MHz IEC 60255-22-3, class III
10 V / m ENV 50 204
f = 900 MHz IEC 60255-22-3, class III
20 V / m (rms) IEEE C37.90.2-2004

Voltage inputs Rated voltage 60 ... 210 V AC

Voltage withstand:
• Continuous 240 V AC
• For 10 s 360 V AC

Burden at rated voltage <0:05 VA

Page 5 of 5