9 Facility to synchronised Relay time from from current flowing through line; no external
SCADA. power supply is needed for the relay. The
9 3 Optically isolated digital status input minimum requirement of current to build power
9 External latching type & Non latching type supply for relay electronics is 20% in any one of
potential free contacts. the phases or 12% in any 2 phases or 8% in all
9 Separate curve setting for phase and EF three phases. Relay also provides pulse output
9 5 nos. of Fault data stored with keypad to trip the RMU or compact CB having low
interface and time stamping. energy tripping coil.
9 Remote Trip (same as selected Auxiliary
¾ Measurement and Communication
supply voltage).
Function:
Description: In normal condition the relay displays actual
ADR241S is second generation of Numerical current flowing through the relay. Using the
Self Power Over Current IDMT/DMT Relay. It front keyboard all relay settings can be viewed.
consist all the necessary protection and If current is in fault range the relay gives trip
monitoring functions required for compact RMU, command. The type of the fault is displayed on
The High speed Digital Signal Controller LCD display. During the fault condition, the
continuously monitors line phase current and E/F relay measures the fault current and stores it in
current. Along with different status input, through non-volatile memory. The fault current can be
CTs, and optical isolated status connections. The read using keyboard on LCD display. All
high-speed micro-controller samples these settings can be done locally as well as remotely
current signals through A/D converter. The via communication port and saved in non-
Digital Signal performs powerful Numerical volatile memory.
Algorithms to find out RMS of fundamental &
¾ Impulse Output for the Tripping Coil :
harmonic contents of the current. All
Low Energy tripping coil of the circuit breaker
measurement is tuned to fundamental frequency
can be connected to the coil terminal marked as
i.e. 50Hz or 60Hz depending upon setting thus
(COIL + and –) at back terminal. The trip energy
relay remains stable during distorted waveform
(12 – 24 V DC ± 0.1 W/sec) is provided by a
by various industrial load. All these measured
capacitor in the protection relay. Length of the
values are then used for different protection
trip impulse is 40ms and pause between the
function such as IDMT Over Current Protection,
individual pulses depends on the impedance of
Instantaneous Over Current Protection, E/F
the tripping coil and the current level. The trip
Protection etc. These measured values are also
Pulse continues until the CB operates and the
displayed on large 16 x 2 LCD display for
fault current becomes zero.
metering purpose. The power supply module is
special electronics circuit which derives power
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
¾ External relay logic: E/F. The tripping current can be set to 20% to
The relay is provided with 1 C/O potential free 240% in steps of 1% for Phase and 10% to
contacts, which can be used for tele-signaling or 100% in steps of 1% for Earth Fault by keyboard
annunciation purpose. These contacts operate at provided on front panel. These settings are
the time of tripping and it is latching type contact. available on display. The unit has selection of
i.e. will get reset only when the LED RESET gets IDMT characteristic of IEC standard, Normal
pressed after supply gets resumed. The logic of Inverse1 (C1), Very Inverse (C3), Extremely
relay operation is as shown below. Inverse (C4), Long Time Inverse (C5). Or define
time (C6). Relay is having Time Multiplier
Setting (TMS) from x0.02 to x1.2 in steps of
x0.01 (separate for phase and EF) for IDMT
delay multiplication. Separate operating curve
can be programmed for phase and EF.
The each stage thresholds for phase (earth)
over current can be selected with an Inverse
Definite Minimum Time (IDMT) characteristic.
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
K * a
t= b
I
1
I r ef
Curve Description a b
Type
C1 Standard Inverse_1 0.14 0.02
C3 Very Inverse 13.5 1
C4 Extremely inverse 80 2
C5 Long Time Inverse 120 1
C6 Define Time - -
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
multiplies it with TMS setting and issue trip becomes RED & remain RED till manual reset.
command if fault is persist even after this time This flag can be reset by pressing the LED
delay. reset key, when power gets resumed.
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
Tolerance Over
Protectio
Clas Factor
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
XX = Communication Protocol
XX = PT.
02 IEC - 103
00 Not Applicable
XX = Auxiliary Supply.
XX = CT.
27 100 – 230 VAC/DC
02 5 Amps.
XX = Cabinet Size
XX = Cabinet Type
01 CSA - 150 (Flush
mounting) 04 Draw out
Ordering information:
A D R 2 4 1 S - A M - X X X - X X - X X - X X - X X - X X - X X
Example
ADR241S-AM-521-01-02-27-01-00-02
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
Technical Specifications:
General specifications
Sr. No. Specification Particulars
I. Current Input : Suitable for CT secondary 1 Amp. or 5 Amp to be specify while
ordering
II. VA burden on CTs : Refer the current transformer requirement chapter of this leaflet.
III. Minimum current : In 1Ø ≥ 20%, 2Ø ≥ 12% and 3Ø ≥ 8%.
require to energize the
relay
IV. Operating Frequency : 50Hz or 60Hz +/- 3Hz selectable by setting
V. Storage Temp. Range : -20°C to +80°C
VI. Operating Temp. : -20°C to +65°C
Range
VII. Aux. Supply : 100-230V AC/DC Tolerance :- +10% - 20%
VIII. VA burden on Aux. : For AC at nominal voltage range < 10VA
Supply
: For DC at nominal voltage range < 5Watt
IX. General Setting
New Password 0 – 99 in step of 1
Set Hours 0 – 23 in step of 1
Set Min. 0 – 59 in step of 1
Set Sec. 0 – 59 in step of 1
Set Date 0 – 31 in step of 1
Set Month 0 – 12 in step of 1
Set Year 0 – 99 in step of 1
Unit id 1 – 250 in step of 1
Com Port 001/ 002
(01= USB / 02 = RS 485)
Baud Rate 9600
Serial Parity None
Frequency 001/ 002
(01= 50Hz / 02 = 60Hz)
CT Primary 10 – 1000 in step of 1
Trip Block 001/ 002
(01= Yes / 02 = No)
Latch Relay 001/ 002
(01= On / 02 = Off)
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
XII. Accuracy
Accuracy of operating Pick-up Setting +10% / ± 5%
Value
Drop –off Above 0.90 x settings ± 5%
Minimum Trip Level of IDMT 1.05 x Settings ± 5%
Accuracy of operating IDMT Characteristic shape With ± 5%(as per 60255-151 cl.5.2) or
Time for Ip> and Ie> Relay Power ON condition
± 60ms whichever is greater
* (Under reference Condition)
DT Operation (C6 Curve) ± 5% or ± 60ms whichever is
greater
With Relay Power ON condition
IDMT Characteristic shape ± 5%(as per 60255-151 cl.5.2) or
With Relay Power OFF ± 90ms whichever is greater
condition * (Under reference Condition)
DT Operation (C6 Curve) ± 5% or ± 90ms whichever is
greater
With Relay Power OFF condition
*Reference Condition TMS=1 I>setting of 1A Operating
range 2-20In
Accuracy of operating Ip>>, Ip>>>, Ie>> & Ie>>> ± 5% or ± 40ms whichever is
Time for Ip>>, Ip>>>, operating time with Relay Power greater
Ie>> and Ie>>> ON Condition
**(Under reference Condition)
Ip>>, Ip>>>, Ie>> & Ie>>> ± 5% or ± 80ms whichever is
operating time with Relay Power greater
OFF Condition
**(Under reference Condition)
** Under reference Condition Fault current 1.5 time above set
value
XIII. Output Contact : One External latching type potential free change over Annunciation
duty Trip contact for Protection Healthy indication.
: One External non latching type potential free change over
Annunciation duty Trip contact for CB operation.
: One Potential free Trip Contact for SCADA indication for Phase.
: One Potential free Trip Contact for SCADA indication for EF.
XIV. Contact Rating : Alarm Duty
XV. Opto Isolated input : 4Nos. Rated for 230Vac ( 1 No. is dedicated for CB NO )
XVI. Impulse output for the : 12 V - 24 VDC (Energy < 0.1 W/sec). Suitable for sensitive RMU
tripping coil tripping coil
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
Note: When Relay is not power ON by any available power supply source i.e. neither line current
nor Auxiliary Supply. During this condition if fault is occurred relay takes some time (1 ½
to 2 cycles) to power ON and then executed the TRIP command. This power ON time is
added in the delay setting.
Conformance to Standards:
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
• Communication : 1KV in CM
IV. Electro static IEC 60255-22-2 and IEEE C37.90.3
Discharge • Contact discharge on conductive surface : 6KV, 8KV.
• Contact discharge on coupling planes : 6KV, 8KV.
• Air discharge : 8KV, 15KV.
V. Fast transient IEC 60255-22-4 and IEEE C37.90.1
interference/bursts • 4KV at Power supply, CT inputs, Binary inputs, Relay contact
outputs in common mode and Differential mode.
• Communication (CM) : 2KV
• Functional earth port (CM) : 4KV
VI. Surge Immunity IEC 60255-22-5
Test • At Power supply, CT inputs, Binary inputs (LL), Relay contact
outputs : up to 2KV in between line to earth
: up to 1KV in between line to line.
• Communication port : up to 1KV in between line to earth
VII. Conducted IEC- 60255-26 & CISPR 22 Class A
Emission Test • At Auxiliary Power Supply Port
CISPR 22 Class A
• At Communication Port
VIII. Radiated IEC- 60255-26 & CISPR 22
Emission Test
IX. Power Frequency IEC 61000-4-8
Magnetic Field • Frequency : 50 Hz
Test
• Continuous : 5 m
• Field Level : 30 A/m
• Short time : 3 s
• Field Level : 300 A/m
X. Conducted IEC 60255-22-6
Disturbance • Test at Power Supply, C.T., Relay Output, Binary Input and
induced by Radio Communication terminal
Frequency field
• Power supply Level : 10 V
• Frequency range : 0.15 to 80 MHz
• Spot frequencies : 27, 68 MHz
• Modulation AM : 1kHz, 80%
XI. Radiated 1) IEC 60255-22-3
Electromagnetic • Electromagnetic field strength : 10 V/m
Field Disturbance
• Frequency range : 80 – 1000 MHz , 1.4 – 2.7 GHz
Test
• Modulation AM : 80% @ 1 KHz
• Spot frequencies : 80, 160, 380, 450, 900, 1850, 2150 MHz
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.
Revison No.
Note: Due to our policy to upgrade our products constantly, we reserve the right to
supply products which may vary slightly from that indicated above.