You are on page 1of 20

Committee on

" Standard on fire fighting equipment for


Drilling rigs, Work over rigs
and Production installations".

SN . NAME ORGANISATION POSITION IN THE


COMMITTEE

1 Sh. P.S.Narayanan Oil India Limited Leader

2. Sh. Gulab Singh OISD Co-ordinator

3 Sh. Neeraj Sharma ONGC Member

4. Sh. V.S.Kumar ONGC Member


FOREWORD

The purpose of this standard is to assist the oil industry in prevention of fire incidents.

It is recognised that the provision indicated in the standard cannot possibly cover all the problems
which may arise during the operation. However provision indicated in the standard will definitely help in
reducing the major fire hazards in oil industry. Employees available at site should always be kept alert to
unforeseen hazards and changing conditions will present new exposures, which must be met with
appropriate precautions. The standard will however, assist each individual worker to improve his work
methods and reduce accidents.

Suggestions are invited from the users after it is put into practice to improve the document further.
Suggestions for amendments to this document should be addressed to:

The Coordinator
Committee on" Standard on fire fighting equipment for Drilling rigs, Work over rigs and
Production installations".

OIL INDUSTRY SAFETY DIRECTORATE


7TH FLOOR, NEW DELHI HOUSE
27, BARAKHAMBA ROAD
NEW DELHI - 110 001.

The standard in no way supersedes the statutory requirements of bodies like DGMS, CCE or any
other Government Body which must be followed as applicable.
NOTE

OISD publications are prepared for use in the oil and gas industry under
Ministry of Petroleum & Chemicals. These are the property of Ministry of
Petroleum & Chemicals and shall not be reproduced or copied and loaned or
exhibited to others without written consent from OISD.

Though every effort has been made to assure the accuracy and
reliability of the data contained in this documents. OISD hereby expressly
disclaims any liability or responsibility for loss or damage resulting from their
use.

These documents are intended to supplement rather than replace their


prevailing statutory requirements.
CONTENT

SECTION DESCRIPTION PAGE NOS.

1. Introduction 1
2. Scope 1
3. Definitions 1
4. Fire protection philosophy 2
5. Fire fighting system -Drilling Rig 2
6. Fire fighting system - WOR 4
7. Fire fighting system- Production Installation 6
GGS/OCS
8. Fire fighting system- GCP/GCS 10
9. Fire fighting system- EPS 12
10. Fire fighting system- QPS/WHI 13
11. Material Specifications 14
12. Fire Alarm and communications 14
13. Fire safety organisation/Training 14
14. Fire emergency manual 15
15. Fire protection system inspection and testing 15
16. References 15
FIRE PROTECTION FACILITIES FOR DRILLING RIGS, WORKOVER RIGS, GROUP
GATHERING STATIONS/OIL COLLECTING STATIONS,
GAS COMPRESSOR PLANTS/GAS COMPRESSOR STATIONS,
EARLY PRODUCTION SET-UP AND QUICK PRODUCTION SET-UP/ WELL HEAD
INSTALLATION

1.0 INTRODUCTION
2.3 This standard does not cover plants
In the upstream petroleum industry processing Liquefied Petroleum Gas
companies are engaged in exploration and (LPG) handling, storage or bottling areas.
development of oilfields as well as production of The same are covered in OISD-STD-144,
crude oil and gas. It has been observed that most 116 OR 169 as the case may be.
of the activities like drilling operation, setting up
of GGS/OCS, GCP/GCS etc. are carried out
initially at remote areas away from the thickly 3.0 DEFINITIONS
populated locality. However, once the field is
established, it has been observed that the area gets 3.1 DRILLING RIG
surrounded by population and small industries.
These causes hazards to the oilfield installations as Drilling Rig is a compact unit including
well as to surrounding residents. derrick structure,power generating unit for running
For the protection of the costly the draw-works, mud preparation unit and all other
equipment and the safety of the surrounding areas, necessary equipment for carrying out drilling
it is important to install necessary in-built fire operation of the earth’s surface by mechanical
protection arrangement in the installations. It means to reach down to the oil bearing zones
would be highly costly affair to build systems to below the ground for exploration and development
control oil well blowout fire or any catastrophic of oil and gas field.
fire situation at each drill site. Here in the
standard, necessary minimum fire protection 3.2 WORKOVER RIG
arrangements which are required to fight initial
fire in the oilfield installations, workover Workover Rig is a compact mobile unit
rigs(WOR) and drilling rigs were included. along with some other external equipment for mud
However, while making the system, due preparation and power generation etc. The whole
consideration should be given to the availability of unit is mainly required for oil/gas well servicing
nearby city as well as industrial fire services. by performing variety of remedial operation on an
It may not be possible to oil/gas well as per the technical requirement with
build/incorporate all these fire fighting systems in the intention of restoring or increasing production.
the existing oilfield installations which are already
approved by the respective statutory authority long
back. However, it is desirable to incorporate 3.3 GROUP GATHERING
certain fire fighting system in these old STATION/OIL COLLECTING STATION
installations as and where practicable and
acceptable to the management. It is a production installation where
production from number of wells are collected
2.0 SCOPE together for treating and separating oil, water &
gas for further despatch to central tank farm.
2.1 This standard covers certain design
criteria and minimum requirement of fire 3.4 GAS COMPRESSION PLANT/GAS
protection facilities at drilling rigs, workover rigs COMPRESSOR STATION
and production installations (GGS/OCS,
GCP/GCS, EPS, QPS/WHI etc). It is an installation where gases are
collected from GGS/OCS and are compressed to
2.2 This standard does not cover fire different pressures for transportation..
protection facilities of refineries, petroleum
depots, terminals or any other gas processing plant
for which OISD - STD - 116 should be referred to.
1
3.5 EARLY PRODUCTION SET UP 4.2 Design criteria
(EPS)
Design criteria of any fire fighting system
It is a production installation similar to would depend upon the type of installation
GGS or OCS in nature; however, very small in involved. Following shall be the basic design
capacity. This type of set up is generally installed criteria for a fire protection system.
at a very early stage of development of any oilfield
area when the number of wells are limited and I) In drilling and workover rigs, fire water
their total production is also very less. storage/fire protection system should be designed
to initiate the fire fighting operation before the
3.6 QUICK PRODUCTION SET UP mobile fire tenders reach at site to provide back up
(QPS)/ Well Head Installation(WHI) service for prolonged period.

It is a production installation, generally II) In CTF/GGS/OCS and GCP/GCS fire


set up in case of extremely new oildfield area and protection, facilities shall be designed to fight one
its capacity is further smaller compared to any major fire within the installation.
EPS.
III) In EPS, QPS and WHI minimum fire
4.0 FIRE PROTECTION protection facilities shall be designed to initiate
PHILOSOPHY the fire fighting operation before the mobile fire
tenders reaches at site to provide back up service
Activities involved in exploration and for prolonged period.
production of crude oil are extremely risky and
may cause considerable financial burden for the IV) All the areas except QPS/WHI shall be
industry if any fire / exploration occurred in a covered with hydrants and water monitors.
drilling or any other installation. Hence, emphasis
should be given to design minimum fire protection V) Foam system should be provided for
facilities at various drilling and other production storage tank (fixed/floating roof)
installations, so that in case of fire, it can be protection at CTF/GGS /OCS.
Extinguished at its incipient stage to minimise the VI) All storage tanks (fixed/floating roof) at
loss of life and property and also to prevent further CTF/GGS/OCS having capacity more
spread of fire. than 500 KL and diameter more than 9.0
metres should be protected with water
4.1 GENERAL CONSIDERATIONS spray/drenching system.
VII) Fire fighting equipment shall be provided
All drilling and workover rigs are rigged- at all installations CTF/GGS/OCS as per
up for short duration and activities are similar in section 70 (2) & (3) OMR-84. A water
nature therefore basic fire protection facilities and ring main with adequate storage of water
design criteria would be similar in nature. at site, pump feeding hydrants and water
However, for GGS/OCS, GCP/GCS, EPS monitors shall be provided and
& QPS/WHI, fire protection facilities would maintained. Fixed roof storage tank shall
depend upon the size/capacity of the plant and its be provided with fixed foam connections.
layout. Layout of the plant shall be done in
accordance with the relevant OISD Standard
(Std.118 on Layouts). A good layout can 5.0 FIRE FIGHTING
minimise fire risk hazard by providing adequate SYSTEM/EQUIPMENT AT DRILLING RIG
fire fighting access, means of escape in case of
fire and also isolation/segregation of risks / In drilling rig following fire fighting
facilities, so that nearby facilities are not affected system/equipment should be provided:
during a fire incident. In this regard, safe distance - Fire water system
from various hazards to installations mentioned in - First aid fire fighting system
OMR-1984 may be referred.
The following fire protection facilities
shall be provided according to various categories 5.1 Fire Water System
of installations and risks associated therein: In drilling rig minimum fire water system
- Fire Water system should be considered to initiate the fire fighting
- Foam system operation at the incipient stage and before the
- First Aid fire fighting equipment arrival of the mobile fire tenders.
- Communication systems, etc.

2
5.1.1 Components of fire water system distance of 15.0 metres from the well head area.
The water line should be charged from the
The main components of fire water delivery of the trailer fire pump and also provision
system are fire water storage, fire water pumps shall be made to charge the line from the outside
and distribution network. fire tender/pump.
ii) Hydrants
5.1.2 Criteria Hydrants in the line should be located in
such a manner that the entire hazardous areas are
The fire water system in a drilling rig covered/protected. At least 2 nos. of hydrants
should be designed to meet the fire water flow should be provided on the line (one near bunk
required for fighting fire with a monitor of houses and other near generator area). Single
minimum 1600 LPM capacity. However, hydrant with landing valves and 4” stand post
provision should be made in the system to hook up shall be provided. All hydrant outlets shall be
from the mobile fire tender or any other water situated 1.2 mtrs above the ground level.
supply of adequate pressure to operate some
additional water monitors etc.

5.1.3 Water Storage iii) Monitors


Water monitors fixed/portable shall be
One water tank of capacity minimum 50 installed/provided at least 15.0 mtrs. away from
KL should be installed at the approach site of the the well head. Monitors shall be located to direct
drilling location. The tanks should be skid the water jet on the well head and other hazardous
mounted welded type with adequate thickness. area and also to provide water shield to the
Provision should be made to divert the fireman approaching a fire. The location of the
water available for mud preparation purpose to the monitors shall not exceed 30.0 mtrs. from the
fire water storage tank if required during any derrick area to be protected.
emergency. Water filling arrangement for the tank
should be made. iv) Minimum four numbers of fire hoses
In exploratory well drilling, one with two numbers of branch pipes should
additional tank/pit of 40 KL to be provided. be provided at site.

5.1.4 Fire Water Pump 5.2 FIRST AID FIRE FIGHTING


EQUIPMENT AT DRILLING RIG
One diesel engine driven trailer fire
pump of capacity 1800 LPM should be placed at 5.2.1 Portable Fire Extinguisher
the approach area of a drilling site. The pump Portable fire Extinguisher should be
should be capable of developing 7.0 kg/cm2 installed as per the IS-2190 . All the Extinguisher
pressure and it should be hooked up with the water should be located at a convenient location and
storage tank provided at the approach area. clearly visible and easily accessible. Maximum
running distance from any point to the nearest
5.1.5 Fire Water Distribution Line Extinguisher shall not exceed 10.0 metres. The
portable Extinguisher shall be installed in such a
i) One fire water distribution single line way that the top of the Extinguisher is not more
with minimum 4” size pipe/casing should be than
installed at the drilling rig with a minimum 1.5 mtrs above the floor level.

The minimum quantities of fire Extinguisher at various locations should be provided as per the followings:

Type of Area Portable Extinguisher


i) Derrick floor - 2 nos. 10 kg DCP Extinguisher

ii) Main Engine area - 1 No. 10 kg DCP Extinguisher


(catterpillar Engine 3 nos.) for each engine

iii) Electrical motor/pump for - 1 No. 10 kg DCP Extinguisher


water circulation for
mud preparation

iv) Mud gunning pump area - 1 No. 10 kg DCP Extinguisher for each mud gunning pump
3
v) Electrical Control Room - 1 No. 6.8 kg CO2 Extinguisher for
each unit
- 1 No. 10 kg DCP Extinguisher for
each unit
vi) Mud mixing tank area/ - 1 No. 10 kg DCP Extinguisher
Chemical laboratory
vii) Diesel storage area - 1 No. 50 ltrs Mechanical foam
Extinguisher
- 1 No. 50 kg DCP Extinguisher
2 Nos. 10 kg DCP Extinguisher
2 Nos. sand bucket or 1/2’ sand
drum with spade.

viii) Lube storage area - 1 No. 10 kg DCP Extinguisher


1 No. Sand bucket stand
ix) Air compressor area - 1 No. 10 kg DCP Extinguisher
x) Fire pump area - 1 No. 10 kg DCP Extinguisher
xi) Near DIC office - 1 No. Fire Extinguisher/Shed with
3 Nos. 10 kg DCP Extinguisher
and 2 Nos. sand bucket.
xii) Fire bell near bunk house - 1 No.

provided with one monitor and one hydrant point.


6.0 FIRE FIGHTING FACILITIES One point near approach should be provided for
AT WORKOVER RIG connecting fire tender. Tank available for
preparation of well work over fluid can also be
In Workover Rig following fire fighting used for fire fighting purpose, provided it is kept
arrangement should be made: at safe place and always kept full.
One additional TPC connection should be
- Fire water storage facilities with fire pump provided with the fire water storage tank for
- Portable fire Extinguisher connection of the fire tender in case of emergency.
Regular filling arrangement of the above
mentioned tank should be provided.
6.1 Fire Water Storage with fire pump Necessary hose storage facilities should
be provided for keeping 4 nos. Fire hose of full
One 40.0 KL capacity water storage tank should length with 2 nos. branch pipe.
be provided at the approach area and it should be In case more number of WORs are
connected with a trailer/skid mounted diesel operating in same area and fire fighting facilities
engine driven fire water pump of capacity 1800 are available within 15 minutes from nearby
LPM at 7.0 kg/cm2 pressure. The water storage GGS/CTF/WOR/Drilling rig than pumps and
tank should be skid mounted welded type of water tankers can be pooled suitably for WORs so
adequate thickness. Minimum 4” hydrant that resources are available during critical
line/Hoses to cover well head and hazardous area operations.
form approach side(Single line) should be

6.2 First Aid Fire Fighting Equipment at Workover Rig

Type of Area Portable Extinguisher

I) Workover rig’s engine area - 1 No. 10 kg DCP Extinguisher


ii) Rig’s compressor area - 1 No. 10 kg DCP Extinguisher
iii) Rig floor area - 2 No. 10 kg DCP Extinguisher
iv) Electrical generator house - 1 No. 10 kg DCP Extinguisher
- 1 No. 6.8 kg CO2 Extinguisher

v) Mud Water Pump/motor area - 1 No. 10 kg DCP Extinguisher


4
vi) Near DIC office area - 2 No. 10 kg DCP Extinguisher
2 Nos. Sand bucket
vii) Fire bell near office cabin - 1
viii) Lub. Oil area - 2 No. 10 kg DCP Extinguisher
2 Nos sand bucket

Note: Sufficient safety precaution should be taken while transporting the Extinguisher from location to
location.

7.0 FIRE FIGHTING FACILITIES IN and situated in the same dyke at a rate of 1
CTF/GGS/OCS lpm/m2 of tank shell area.

The fire fighting facilities in CTF should Water flow required for applying foam on a single
be done as per OISD Standard 117. largest tank by way of fixed foam system, where
provided, or by use of water/foam monitors.
7.1 FIRE WATER SYSTEM

Water is an essential and the most


important medium available to mankind for fire 7.1.3 HEADER PRESSURE
protection. Water is used for fire extinguishment,
fire control, cooling of equipment, exposure The fire water pressure system shall be
protection of equipment and personnel from heat designed for a minimum residual pressure of 7
radiation. For these purposes water is used in kg/cm2g at the hydraulically remotest point of
various forms such as straight jet, water fog, water application at the designed flow rate at that point.
curtain, water spray, deluge / sprinkler, oscillating
monitors for foam preparation etc.
7.1.4 STORAGE
7.1.1 Components of Fire Water System
Water for the hydrant service shall be
The main components of the system are stored in any easily accessible surface or
Fire Water Storage, Fire Water Pumps and underground lined reservoir or above ground tanks
Distribution Piping Network. of steel concrete or masonry. The effective
capacity of the reservoir / tank above the level of
7.1.2 Basis : suction point shall be minimum 2 hours aggregate
working capacity of pumps. Make –up water
The fire water system in an installation supply source shall be ensured.
should be designed to meet the fire water flow
required for fighting one largest risk at a time. Fire water supply shall be preferably
from fresh water source such as river, tubewell or
DESIGN FLOW RATE: lake. Where fresh water source is not easily
available, fire water supply may be sea water or
Fire water flow rate for a tank farm shall other acceptable source like treated effluent water.
be aggregate of the following: Where treated effluents is used as fire water
supply, it shall not have fecal waste
- Water flow calculated for cooling a tank contamination.
on fire at a rate of 3 lpm/m² of tank shell area.
The installation shall have facilities for
- Water flow calculated for exposure receiving and diverting all the water coming to the
protection for all other tanks falling within a installation to fire water storage tanks in case of an
radius of (R +30)m from centre of the tank on fire emergency.
(R-Radius of tank on fire) and situated in the same
dyke at a rate of 3 lpm/m² of tank shell area. Storage reservoir shall be in two
equal interconnected compartments to facilitate
- Water flow calculated for exposure cleaning and repairs. In case of steel tanks there
protection for all other tanks falling outside a
radius of (R+30)m from centre of the tank on fire shall be minimum two tanks each having 50 % of
required capacity.
6
affecting the flow in the rest. The isolation valves
Large natural reservoirs having water shall be located normally near the loop junctions.
capacity exceeding 10 times the aggregate water Additional valves shall be provided in the
requirement of fire pumps may be left unlined. segments where the length of the segment exceeds
300 mtrs.

7.1.5 FIRE WATER PUMPS (ii) Above / Underground Network :

Fire water pumps shall be installed to meet the The fire water network piping
design fire water flow rate and head. These should normally be laid above ground at a height
should have flooded suction. of 300 mm to 400 mm above finished ground
level. However, the fire water network piping shall
The pumps shall be capable of discharging 150% be laid below ground level at the following places
of its rated discharge at a minimum of 65% of the
rated head. The Shut-off head shall not exceed - Road crossings.
120% of rated head for horizontal centrifugal - Places where the above ground piping is
pumps and 140% for vertical turbine pump. likely to cause obstruction to operation, vehicle
movement and places where the above ground
A minimum of 50% standby pump(s) (minimum piping is likely to get damaged mechanically.
one no.) of the same type and capacity as the main
pumps shall be provided. - Where frost condition warrants, the
pipeline shall be laid under-ground beneath the
The fire water pump(s) including the standby frost layer.
pump(s) shall be of diesel engine driven type.
Where electric supply is reliable 50% of the (iii) Protection of underground pipelines:
pumps may be electric driven. The diesel engines
shall be quick starting type with the help of push - The mains shall have at least one mtr. earth
buttons located on or near the pumps or located at cushion in open ground and 1.5 mtrs cushion
a remote location. Each engine shall have an under the roads. In case of crane movement areas,
independent fuel tank adequately sized for 6 hours pipe may be protected with concrete/steel
continuous running of the pump. encasement.

Fire water pumps & storage shall be located at 30 - The mains shall be provided with protection
mtrs (minimum) away from equipment or where against soil corrosion by suitable
hydrocarbons are handled or stored. coating/wrapping.

Fire water pumps shall be exclusively used for fire In case of poor soil conditions it may be
fighting purpose only. necessary to provide concrete/masonry supports
under the pipe.
The fire water network shall be kept pressurised
by a static tank or jockey pump(s). Where jockey Protection of above ground pipes:
pumps are used, the capacity of pump shall be
sufficient to maintain the system pressure in the - The mains shall be supported at regular intervals
event of leakages from valves etc. The capacity of not exceeding 6 mtrs.
Jockey pump shall not be less than 3% (with a
minimum of 180 lpm) and not more than 10% of - The system for above ground portion shall be
the designed fire water rate at network pressure analysed for flexibility against thermal expansion
not less than 3 Kg/cm2g. and necessary expansion loops where called for
shall be provided.

7.1.6 FIRE WATER DISTRIBUTION (iv) SIZING:


NETWORK
Fire water distribution ring main shall be
(i) Looping: sized for 120% of the design water rate. Design
flow rates shall be distributed at nodal points to
The fire water network shall be give the most realistic way of water requirement in
laid in closed loops as far as possible to ensure an emergency. It may be necessary to assume
multi-directional flow in the system. Isolation several combinations of flow requirement for
valves shall be provided in the network to enable design of network. For large water requirement
isolation of any section of the network without for floating roof tank the network around the tank
6
farm shall be suitably designed. The analysis of building. Provision of hydrants within the building
network shall be preferably done through a shall be provided in accordance with IS : 3844.
computer programme.
Hydrant/Monitors shall be located along
The minimum residual pressure shall be road side for easy accessibility.
as defined in 7.1.3.
(iii) Double headed hydrants with two
v) The fire water network shall always be separate landing valves on 4" standpost shall be
kept pressurised by any of the following used. All hydrant outlets shall be situated 1.2
arrangements: mtrs. above ground level.

— If fire water is stored in above ground (iv) Monitors shall be located to direct water
storage tanks with water level more than 5 mtrs. on the object as well as to provide water shield to
above the highest point of fire water network, a firemen approaching a fire.
direct connection with a non-return valve shall be
provided to the fire water network from the Monitors shall not be installed less than
storage tank. 15mtrs. from hazardous equipment. The
requirement of monitors shall be established based
— If the fire water is stored in underground on hazards involved and layout considerations.
tanks, the fire water network shall be connected to
an overhead water tank if available in the The location of the monitors shall not
installation; otherwise a jockey pump shall be exceed 45 mtrs from the hazard to be protected.
installed to keep the mains pressurised.
(v) Hydrants and monitors shall not be
— Make up water shall be provided to installed inside the dyke areas. However, as an
account for leakages in the system so that fire additional requirement, oscillating monitors may
water storage is kept to the desired capacity. be provided in inaccessible area within dyke with
isolation valve or ROV outside the tank farm.
(vi) Connections for fixed water monitors
shall be provided with independent isolation (vi) Tanker Loading/unloading area should
valves. be provided with alternate water cum foam
monitors having multipurpose combination
(vii) Fire water mains shall not pass through nozzles for jet spray & fog arrangement and fire
buildings or dyke areas. hydrants located at a spacing of 30 mtrs. on both
sides of the gantry. The hydrants & monitors shall
(viii) In case of underground mains the be located at a minimum distance of 15 mtrs. from
isolation valves shall be located in RCC/brick the Tanker.
masonry chamber.
(vii) Hydrants/Monitors shall be preferably
located with branch connection.
7.1.7 HYDRANTS AND MONITORS:
7.1.8 FIXED WATER SPRAY SYSTEM
(i) Hydrants shall be located bearing in
mind the fire hazards at different sections of the (i) Fixed spray water system is a fixed pipe
premises to be protected and to give most effective system connected to a reliable source of water
service. At least one hydrant post shall be supply and equipped with water spray nozzles for
provided for every 30 mtrs of external wall specific water discharge and distribution over the
measurement or perimeter of battery limit in case surface of area to be protected. The piping system
of high hazard areas. For non-hazardous area, they is connected to the hydrant system water supply
shall be spaced at 45 mtrs. intervals. The through an automatically or manually actuated
horizontal range & coverage of hydrants with hose valve, which initiates the flow of water.
connections shall not be considered beyond 45
mtrs. (ii) Water supply patterns and their densities
shall be selected according to need. Fire water
(ii) Hydrants shall be located at a minimum spray system for exposure protection shall be
distance of 15 mtrs. from the periphery of storage designed to operate before the possible failures of
tank or equipment under protection. In case of any containers of flammable liquids or gases due
buildings this distance shall not be less than 2 to temperature rise. The system shall, therefore,
mtrs. and not more than 15 mtrs. from the face of be designed to discharge effective water spray
within shortest possible time.
7
(i) System be designed to create foam
7.2 FOAM SYSTEMS blanket on the burning surface in a reasonably
short period.

7.2.1 CONVEYING SYSTEMS (ii) Foam shall be applied to the burning


hazard continuously at a rate high enough to
The system consists of an adequate water overcome the destructive effects of radiant heat.
supply, supply of foam concentrate, suitable
proportioning equipment, a proper piping system, (iii) Foam makers/foam pourers shall be
foam makers and discharge devices designed to located not more than 24 mtrs. apart on the shell
adequately distribute the foam over the hazard. perimeter based on 600 mm foam dam height.

Conventional systems are of the open (iv) A minimum of two foam pourers shall be
outlet type, in which foam discharges from all provided.
outlets at the same time, covering the entire hazard
within the confines of the system. There are three
types of systems: 7.2.3 FIXED ROOF TANK PROTECTION

i) Fixed Foam conveying system shall have same


ii) Semi-Fixed features as of floating roof tank excepting that a
iii) Mobile vapour seal chamber is required before the foam
discharge outlet.
(i) Fixed Foam System
Features of the foam system for fixed
Fixed foam conveying system comprises roof protection shall be as follows:
of fixed piping for water supply at adequate
pressure, foam concentrate tank, eductor, suitable (i) The vapour seal chamber shall be
proportioning equipment for drawing foam provided with an effective and durable seal, fragile
concentrate and making foam solution, fixed under low pressure, to prevent entrance of vapour
piping system for onward conveying to foam into the foam conveying piping system.
makers for making foam, vapour seal box and
foam pourer. (ii) Where two or more pourers are required
these shall be equally spaced at the periphery of
(ii) Semi-Fixed Foam System the tank and each discharge outlet shall be sized to
deliver foam at approximately the same rate.
Semi-fixed foam system gets supply of
foam solution through the mobile foam tender. A (iii) Tanks should be provided with foam
fixed piping system connected to foam makers discharge outlets/pourers as indicated below:
cum vapour seal box in case of cone roof tanks
and foam maker and foam pourers in the case of Tank Diameter Minimum number of foam
floating roof tanks conveys foam to the surface of in mtrs. discharge outlet
tank.
>18 upto 20 2
(iii) Mobile System >20 upto 25 3
>25 upto 30 4
Mobile system includes foam producing >30 upto 35 5
unit mounted on wheels, which may be self >35 upto 40 6
propelled or towed by a vehicle. These units >40 upto 45 8
supply foam through monitors/foam towers to the >45 upto 50 10
burning surface.
The estimation of number of foam
7.2.2 FLOATING ROOF TANK discharge outlet is based on pourer capacity of
PROTECTION 1000 lpm at a pressure of 7 kg/cm2 g upstream of
eductor.
For floating roof tank, foam shall be
poured at the foam dam to blanket the roof seal.
Features of foam system for floating roof tank
protection shall be as follows:

8
7.2.4 FLOATING CUM FIXED ROOF shall be used for determining water quantity
TANK PROTECTION required.

Protection facilities shall be provided as


required for fixed roof tank. 7.2.9 FOAM QUANTITY REQUIREMENT

7.2.5 PROTECTION FOR DYKE The aggregate quantity of foam solution


AREA/SPILL FIRE should be calculated as below :

Portable monitors/foam hose streams (i) Foam solution application at the rate of 5
shall be considered for fighting fires in dyke area lpm/m2 for the liquid surface of the single largest
and spills. cone roof tank or at the rate of 12 lpm/m2 of seal
area of the single largest floating roof tank
7.2.6 FOAM APPLICATION RATE whichever is higher.

The minimum delivery rate for primary However, a foam solution application
protection based on the assumption that all the rate of 8.1 lpm/m2 of the liquid surface of the
foam reaches the area being protected shall be as largest floating roof tank for 65 minutes may be
indicated below : considered for a roof sinking case. (Refer
Annexure-IV for sample calculation)
For cone roof tanks containing liquid
hydrocarbons, the foam solution delivery rate shall (ii) Two hose streams of foam each with a
be at least 5 lpm/m2 of liquid surface area of the capacity of 1140 lpm of foam solution.
tank to be protected. The aggregate quantity of foam solutions should
be largest of (i) and (ii) as above for a
For floating roof tanks containing liquid minimum period of 65 minutes. From this the
hydrocarbons foam solution delivery rate shall be quantity of foam based on 3% or 6% proportion
at least 12 lpm/m2 of seal area with foam dam should be calculated.However, for installation
height of 600 mm of the tank to be protected. having aggregate storage not more than 10,000
KL, the foam concentrate storage shall be based
In case of floating roof sinking, the rate on (i) only.
considered should be 8.1 lpm/m2 of liquid surface
areas.
In determining total solution flow 7.2.10 FOAM COMPOUND STORAGE
requirements, potential foam losses from wind and
other factors shall be considered. Foam compound should be stored in plastic
containers of 20-30 ltrs capacity or 200/210 ltrs
7.2.7 DURATION OF FOAM DISCHARGE capacity barrels in case of protein, fluroprotein or
AFFF. Foam compound can also be stored in
The equipment shall be capable of overhead storage tank of suitable capacity for
providing primary protection at the specified quick filling of foam tender/nurser during
delivery rates for the following minimum period emergency.
of time.
Type of foam compound used can be
i) Tanks containing protein or fluroprotein or AFFF. Alcohol Resistant
Class 'A' & 'B' - 65 minutes Foam can be used for specific application.
Minimum life of foam compound shall be taken as
ii) Where the system's per manufacturer's data.
primary purpose is for
spill fire protection - 30 minutes Foam compound shall be tested
periodically for ensuring its quality and the
deteriorated quantity replaced. The deteriorated
foam compound can be used for fire training
purposes.
7.2.8 WATER FOR FOAM MAKING
Quantity of foam compound equal to
Water quantity required for making foam 1000 Ltrs. to be kept in GGS/OCS . Additional
solution depends upon the type of foam used. quantity required if any, during emergency shall
Protein foams in normal use have a 3% to 6% be arranged from the near by installations/ CTF.
proportioning ratio. However, foam supplier data
9
7.3 The minimum quantities of fire Extinguishers at various locations in GGS/OCS should be provided
as per following :

AREA PORTABLE EXTINGUISHER


i) Separator Area - For every 50.0 m2 one DCP
Extinguisher
ii) Dispatch Pump area - 1 No. 10 kg DCP / Pump
iii) Manifold Area - 2 No. 10 kg DCP/ manifold
iv) Storage Tank Area - 6 Nos. 10 kg DCP +
1 No. 50 kg DCP
v) Generator House Area - 1 No. 6.8 kg CO2 Extinguisher. &
1 No. 10 kg DCP Extinguisher.
vi) Fire Pump Area - 1 No. 10 kg DCP Extinguisher.
vii) Tanker Loading /unloading pt. - 3 Nos. 10 kg DCP
- 1 No. 50 kg DCP
- 1 No.50 ltr. Mechanical
Foam Extinguisher.

viii) Emulsion Treater Area - 3 Nos. 10 kg DCP Extinguisher.


1/2 cut Drum with sand & sawel
ix) Lub Oil/Fuel Storage Area - 2 Nos. 10 kg DCP Extinguisher.
x) Switchgear room - 4 Nos. 6.8 kg CO2 Extinguisher.
xi) Boiler Area/Bath heater - 2 Nos. 10 kg DCP
1 No. 6.8 kg CO2 Extinguisher.
xii) Chemical dozing pump area - 2 Nos. 10 kg DCP
xiii) Office building area - 2 Nos. 10 kg DCP Extinguishers
xiv) Disposal water pump area - 1 No. 10 kg DCP Extinguisher.
xv) Water Clarification plant - 2 Nos. 10 kg DCP Extinguishers.

8.1.2 BASIS
8.0 FIRE FIGHTING FACILITIES IN
GCP/GCS Gas Compressor Plant is an extra high
hazardous installation. Any fire incident may
Following fire fighting arrangement cause major damage to the compressor plant.
should be made in a Gas Compressor Plant/Gas Hence, system should be capable of handling any
Compressor Station: major outbreak of fire incident at any Compressor.
- Fire water system Design of water flow rate should be enough to
- First Aid fire fighting operate 2 nos. Water monitor (1600 LPM)
equipment
- Detection System and Alarm simultaneously from the two opposite sides of any
Compressor with full working pressure (7.0
8.1.1 FIRE WATER SYSTEM kg/cm2).

Water is an essential and the most


important medium available to mankind for fire 8.1.3 Component of fire water system
protection. Water is used for fire extinguishment,
fire control, cooling of equipment, exposure Main component of fire water system is
protection of equipment and personnel from heat fire water storage, fire water pump and
radiation. For these purposes water is used in distribution network.
various forms such as straight jet, water fog, water
curtain, water spray, deluge / sprinkler, oscillating
monitors for foam preparation etc.

10
8.1.3.1 FIRE WATER STORAGE centrifugal pumps and 140% for vertical turbine
pump.
In almost all cases, Gas Compressor A minimum of 50% standby pump(s) (minimum
Plants/Stations are situated adjacent to GGS/OCS one no.) of the same type and capacity as the main
where good fire water system with adequate water pumps shall be provided.
storage and pumping facilities are available.
Hence, as much as practicable this system should The fire water pump(s) including the standby
be hooked up with the GCP/GCS’s water ring pump(s) shall be of diesel engine driven type.
main to avoid separate water storage and pumping Where electric supply is reliable 50% of the
units. Otherwise, separate water storage and pumps may be electric driven. The diesel engines
pumps should be provided. shall be quick starting type with the help of push
buttons located on or near the pumps or located at
Minimum 300 K.L. of water storage a remote location. Each engine shall have an
shall be available at GCS/GCP. independent fuel tank adequately sized for 6 hours
Fire water supply shall be preferably continuous running of the pump.
from fresh water source such as river, tubewell or
lake. Where fresh water source is not easily Fire water pumps & storage shall be located at 30
available, fire water supply may be sea water or mtrs (minimum) away from equipment or where
other acceptable source like treated effluent water. hydrocarbons are handled or stored.
Where treated effluents is used as fire water
supply, it shall not have fecal waste Fire water pumps shall be exclusively used for fire
contamination. fighting purpose only.

The installation shall have facilities for The fire water network shall be kept pressurised
receiving and diverting all the water coming to the by a static tank or jockey pump(s). Where jockey
installation to fire water storage tanks in case of an pumps are used, the capacity of pump shall be
emergency. sufficient to maintain the system pressure in the
event of leakages from valves etc. The capacity of
Storage reservoir shall be in two Jockey pump shall not be less than 3% (with a
equal interconnected compartments to facilitate minimum of 180 lpm) and not more than 10% of
cleaning and repairs. In case of steel tanks there the designed fire water rate at network pressure
shall be minimum two tanks each having 50 % of not less than 3 Kg/cm2g.
required capacity.
8.1.3.3 Fire Water Distribution Network
Large natural reservoirs having water
capacity exceeding 10 times the aggregate water Fire water ringmain should be made available all
requirement of fire pumps may be left unlined. around the gas compressor plant. The size of the
ringmain should be of 8” diameter. Hydrants and
monitors should be provided in the entire ringmain
8.1.3.2 FIRE WATER PUMPS and distance between the two monitors or two
hydrants should not exceed 30.0 mtrs. Hydrant
i) Fire water pumps shall be installed to and monitors should be located at minimum
meet the design fire water flow rate and head. distance of 15.0 metres from the periphery of
These should have flooded suction. compressors or equipment under protection along
road side. However, total number of hydrants and
The pumps shall be capable of discharging monitors should depend upon the number of
150% of its rated discharge at a minimum of 65% compressor and the location of each compressor.
of the rated head. The Shut-off head shall not No area should be left uncovered from the range
exceed 120% of rated head for horizontal of the water monitors.

8.2 First Aid Fire Fighting Equipment at GCP/GCS

Type of area Portable Extinguisher

I) Near each compressor unit - 1 No. 10 kg DCP Extinguisher


ii) Glycol dehydration unit - 2 No. 10 kg DCP Extinguisher
iii) Air Compressor area - 1 No. 10 kg DCP Extinguisher

iv) Condensate recovery unit - 1 No. 50 kg DCP Extinguisher


- 1 No. 10 kg DCP Extinguisher
11
v) Main electrical switchgear - 1 No. 6.8 kg CO2 Extinguisher
area 1 No. 10 kg DCP Extinguisher

vi) Both side of the main - 1 No. 50 kg DCP Extinguisher


compressor shed area at each side of the main
compressor shed.

8.3 DETECTION SYSTEM AND 9.1 Fire Water System


ALARM
The fire water system should be capable
Human beings are excellent fire detectors since enough to fight/control any fire situation within
they possess sense of smell, sight, and touch. But the installation effectively before the fire tender
since human senses are also unreliable due to the reaches at site from the nearby fire station.
need for frequent rest and relaxation, a number of
mechanical, electrical and electronic devices have
been developed to mimic human senses in the 9.1.1 COMPONENT OF FIRE WATER
detection of gases / smoke / heat and flame. SYSTEM
A flammable gas detector is designed to give a
warning of the presence of flammable gases or Main component of fire water system is
vapours in air, well before they reach fire water storage, fire pump and distribution
explosive concentrations. Normally, the detector network.
provides visible and audible alarm signals, but
frequently it performs a further function by 9.1.2 BASIS
initiating control action such as increasing
ventilation or shutting off the source of gas. A Fire water system should be designed in
flammable gas detector can also be used for such a manner that at least one monitor of capacity
tracing leaks and checking that vessels or tunnels approx. 1600 LPM or 2 nos. hydrant can operate
are gas free before entering. in full pressure (7.0kg/cm2) in case of any
While designing a fire detection and emergency.
suppression system for GCP following criteria
may also be kept under consideration:-
9.1.3 FIRE WATER STORAGE
1) Gas detection system connected to
emergency shut down system on coincident logic. At least 2 nos. welded tanks of capacity
2) Ultraviolet (UV) detection system or 40.0 KL each or one static ground reservoir of
equipment, connected to FSD( Fire Shut Down ) similar capacity should be made for water storage
logic. Detection of any fire should lead to auto purpose at any EPS. Regular filling arrangement
shut off of the gas supply, total shutdown of the for the above mentioned tanks should be provided.
plant and blow down of the trapped gas to flare. Separate TPC connection should be provided in
the welded tanks for fire tenders connection.

8.3.1 AREAS TO BE COVERED WITH


DETECTORS 9.1.4 Fire Water Pump

The entire gas compressor area to be One trailer pump of capacity 1800 LPM
covered with hydrocarbon gas detector. The exact at 7.0 kg/cm2 pressure should be installed and
loocation and number of points shall be decided hooked up with the water storage facilities.
on need basis.
9.1.5 Fire Water Distribution Network

9.0 FIRE FIGHTING FACILITIES IN Fire water line of 4” size should be made
EARLY PRODUCTION SET UP at two sides of the EPS along road side. Line
(EPS) should be at least 15.0 mtrs away from the
In any early production set-up, the fire hazardous area. This line should be hooked up
fighting facilities should be of following types: with the delivery of the trailer fire pump.
- Fire water system Provision should be made to pressurise the
- First aid fire fighting equipment ringmain if required from the outside fire tender or
any other reliable pressurised water supply.
12
9.1.6 Above ground piping area. Distance between the two hydrants or two
monitors should not be more than 30.0 mtrs.
Piping network should be laid above the Monitors should be installed in such a manner that
ground level. Height should be 300 to 400 mm it should be able to cover all the tanks as well as
from the ground and it should be supported at group unit area. Height of the hydrant valve
every 6.0 mtrs distance. It should be ensured that should not be more than 1.2 mtrs. from the ground
proper coating etc. to be provided on pipe near level.
support. However, if required pipe can be laid
below ground with proper protection arrangement
as per OISD Standard 117. 9.2 First Aid Fire Fighting Equipment at
EPS

Hydrant/Monitors Portable fire Extinguisher should be


installed as per IS-2190. All fire Extinguisher
Hydrants and monitors should be should be kept under proper Extinguisher shed.
installed along the line to cover entire hazardous

The minimum quantities of fire Extinguisher at various locations should be provided as per the followings:

Area Portable Fire Extinguisher


i) Separator/Group unit area - 2 Nos. 10 kg DCP Extinguisher
and 2 nos. sand bucket under
one Extinguisher shed
ii) Dispatch pump area - 1 No 10 kg DCP Extinguisher
for each pump and with a minimum
of 2 nos 10 kg DCP Extinguisher
1 No. 50 ltrs Mechanical foam
Extinguisher and 2 nos sand bucket.
iii) Near storage tank area - 2 Nos 10 kg DCP Extinguisher
iv) Electrical switch gear - 1 No. 6.8 kg CO2 Extinguisher
area/Generator house 1 No. 10 kg DCP Extinguisher

10.0 FIRE FIGHTING EQUIPMENT 10.1 Fire water storage with fire pump
AT QUICK PRODUCTION
SETUP (QPS)/Well Head One 40.0 KL capacity water storage tank should
Installation (WHI) be provided at the approach area of the QPS. The
tank should be of welded type with adequate
Quick Production Setup is a small production unit thickness. One trailer pump of capacity 1800
of temporary nature. Following minimum fire LPM at 7.0 kg/cm2 pressure should be provided.
protection facilities should be installed: The pump should be hooked up with the water
- Fire water storage facilities with fire storage tank.
pump One additional TPC connection should be
- First Aid fire fighting equipment provided in the storage tank for connecting outside
fire tender in case of emergency. Regular filling
arrangement for the above mentioned tank should
be provided.

10.2 First Aid Fire Fighting Equipment at QPS/WHI

Area Portable Extinguisher


i) Separator/Group unit area - 2 Nos 10 kg DCP Extinguisher
and 2 Nos sand bucket under
an Extinguisher shed.
ii) Dispatch pump area - 1 No. 10 kg DCP Extinguisher for
each pump. Minimum 2 nos
10 kg DCP Extinguisher.

13
iii) Near tank storage area - 2 Nos 10 kg DCP Extinguisher
iv) Generator house - 1 No. 6.8 kg CO2 Extinguisher
1 No. 10 kg DCP Extinguisher

12.2 COMMUNICATION SYSTEM


11.0 MATERIAL SPECIFICATIONS
Adequate communication system like
All the materials to be used in fire water telephone/Public Address System/Paging System/
system shall be of approved type intrinsically safe Walkie-talkie system should be
i) Pipes: Carbon steel as per IS:3589/IS:1239 considered.
or its equivalent
In case of saline water service the fire water main
pipes shall be cu-ni, cement mortar/poly glass 13.0 FIRE SAFETY ORGANISATION/
lined internally. TRAINING
ii) Isolation valves: Cast iron/cast steel. Use of
cast steel valve is preferable
iii) Hydrant Standpost : carbon steel 13.1 ORGANISATION
Outlet valves: Stainless steel/Alluminium alloy
Landing valves : Stainless steel/Al - Zn Alloy (i) Overall responsibility for fire safety in
iv) Monitors :Carbon steel/Gun metal the oil installation shall be of the
v) Fire hose : IS 636 : (Type A) or Location-in-charge. He shall draw the
synthetic hose (Type B) necessary emergency plan. Since separate
Fire water network, hydrant, monitor etc shall be fire fighting set up is not usually
painted “Fire Red”. envisaged, one of the officers shall be
designated and responsible for inspection
of all
12.0 FIRE ALARM AND (ii) fire fighting equipment. He shall also
COMMUNICATION SYSTEM FOR coordinate the activities during fire
EPS/GCP/GCS fighting.

12.1 FIRE ALARM SYSTEM (ii) Hot work permit shall be issued by the
Installation Manager.
Electrical/hand operated fire siren shall
be installed at suitable location in installation. The
operating switch buttons shall be located near the
Risk Area at a safe, identifiable and accessible 13.2 TRAINING
location. The fire alarm shall be different from
shift sirens. (i) The fire fighting training shall be
compulsory to all officers, operators, and other
Fire siren code should be as follows: employees who are likely to be present in the
installation. There shall be regular mock fire
1. SMALL FIRE: No siren drills, once a month. The record of such drills
shall be maintained by the installation Manager.
2. MAJOR FIRE: A wailing siren for two
minutes. Sirens will be sounded three times for (ii) Every employee or authorised persons
thirty seconds with an interval of fifteen second in working in the oil installation should be
between. familiarised with the fire alarm signal and should
know the location of the fire alarm point nearest to
3. DISASTER: Same type of siren as in his place of work. Instructions on the action to be
case of Major Fire but the same will be sounded taken in the event of fire should be posted at each
for three times at the interval of two minutes. alarm point and familiarity with these instructions
should be ensured and recorded.
4. ALL CLEAR (For fire): Straight run
siren for two minutes. (iii) OISD-STD-154 - Safety Aspects in
Functional Training shall be adhered to in this
5. TEST: Straight run siren for two minutes. regard.

14

You might also like