Professional Documents
Culture Documents
The purpose of this standard is to assist the oil industry in prevention of fire incidents.
It is recognised that the provision indicated in the standard cannot possibly cover all the problems
which may arise during the operation. However provision indicated in the standard will definitely help in
reducing the major fire hazards in oil industry. Employees available at site should always be kept alert to
unforeseen hazards and changing conditions will present new exposures, which must be met with
appropriate precautions. The standard will however, assist each individual worker to improve his work
methods and reduce accidents.
Suggestions are invited from the users after it is put into practice to improve the document further.
Suggestions for amendments to this document should be addressed to:
The Coordinator
Committee on" Standard on fire fighting equipment for Drilling rigs, Work over rigs and
Production installations".
The standard in no way supersedes the statutory requirements of bodies like DGMS, CCE or any
other Government Body which must be followed as applicable.
NOTE
OISD publications are prepared for use in the oil and gas industry under
Ministry of Petroleum & Chemicals. These are the property of Ministry of
Petroleum & Chemicals and shall not be reproduced or copied and loaned or
exhibited to others without written consent from OISD.
Though every effort has been made to assure the accuracy and
reliability of the data contained in this documents. OISD hereby expressly
disclaims any liability or responsibility for loss or damage resulting from their
use.
1. Introduction 1
2. Scope 1
3. Definitions 1
4. Fire protection philosophy 2
5. Fire fighting system -Drilling Rig 2
6. Fire fighting system - WOR 4
7. Fire fighting system- Production Installation 6
GGS/OCS
8. Fire fighting system- GCP/GCS 10
9. Fire fighting system- EPS 12
10. Fire fighting system- QPS/WHI 13
11. Material Specifications 14
12. Fire Alarm and communications 14
13. Fire safety organisation/Training 14
14. Fire emergency manual 15
15. Fire protection system inspection and testing 15
16. References 15
FIRE PROTECTION FACILITIES FOR DRILLING RIGS, WORKOVER RIGS, GROUP
GATHERING STATIONS/OIL COLLECTING STATIONS,
GAS COMPRESSOR PLANTS/GAS COMPRESSOR STATIONS,
EARLY PRODUCTION SET-UP AND QUICK PRODUCTION SET-UP/ WELL HEAD
INSTALLATION
1.0 INTRODUCTION
2.3 This standard does not cover plants
In the upstream petroleum industry processing Liquefied Petroleum Gas
companies are engaged in exploration and (LPG) handling, storage or bottling areas.
development of oilfields as well as production of The same are covered in OISD-STD-144,
crude oil and gas. It has been observed that most 116 OR 169 as the case may be.
of the activities like drilling operation, setting up
of GGS/OCS, GCP/GCS etc. are carried out
initially at remote areas away from the thickly 3.0 DEFINITIONS
populated locality. However, once the field is
established, it has been observed that the area gets 3.1 DRILLING RIG
surrounded by population and small industries.
These causes hazards to the oilfield installations as Drilling Rig is a compact unit including
well as to surrounding residents. derrick structure,power generating unit for running
For the protection of the costly the draw-works, mud preparation unit and all other
equipment and the safety of the surrounding areas, necessary equipment for carrying out drilling
it is important to install necessary in-built fire operation of the earth’s surface by mechanical
protection arrangement in the installations. It means to reach down to the oil bearing zones
would be highly costly affair to build systems to below the ground for exploration and development
control oil well blowout fire or any catastrophic of oil and gas field.
fire situation at each drill site. Here in the
standard, necessary minimum fire protection 3.2 WORKOVER RIG
arrangements which are required to fight initial
fire in the oilfield installations, workover Workover Rig is a compact mobile unit
rigs(WOR) and drilling rigs were included. along with some other external equipment for mud
However, while making the system, due preparation and power generation etc. The whole
consideration should be given to the availability of unit is mainly required for oil/gas well servicing
nearby city as well as industrial fire services. by performing variety of remedial operation on an
It may not be possible to oil/gas well as per the technical requirement with
build/incorporate all these fire fighting systems in the intention of restoring or increasing production.
the existing oilfield installations which are already
approved by the respective statutory authority long
back. However, it is desirable to incorporate 3.3 GROUP GATHERING
certain fire fighting system in these old STATION/OIL COLLECTING STATION
installations as and where practicable and
acceptable to the management. It is a production installation where
production from number of wells are collected
2.0 SCOPE together for treating and separating oil, water &
gas for further despatch to central tank farm.
2.1 This standard covers certain design
criteria and minimum requirement of fire 3.4 GAS COMPRESSION PLANT/GAS
protection facilities at drilling rigs, workover rigs COMPRESSOR STATION
and production installations (GGS/OCS,
GCP/GCS, EPS, QPS/WHI etc). It is an installation where gases are
collected from GGS/OCS and are compressed to
2.2 This standard does not cover fire different pressures for transportation..
protection facilities of refineries, petroleum
depots, terminals or any other gas processing plant
for which OISD - STD - 116 should be referred to.
1
3.5 EARLY PRODUCTION SET UP 4.2 Design criteria
(EPS)
Design criteria of any fire fighting system
It is a production installation similar to would depend upon the type of installation
GGS or OCS in nature; however, very small in involved. Following shall be the basic design
capacity. This type of set up is generally installed criteria for a fire protection system.
at a very early stage of development of any oilfield
area when the number of wells are limited and I) In drilling and workover rigs, fire water
their total production is also very less. storage/fire protection system should be designed
to initiate the fire fighting operation before the
3.6 QUICK PRODUCTION SET UP mobile fire tenders reach at site to provide back up
(QPS)/ Well Head Installation(WHI) service for prolonged period.
2
5.1.1 Components of fire water system distance of 15.0 metres from the well head area.
The water line should be charged from the
The main components of fire water delivery of the trailer fire pump and also provision
system are fire water storage, fire water pumps shall be made to charge the line from the outside
and distribution network. fire tender/pump.
ii) Hydrants
5.1.2 Criteria Hydrants in the line should be located in
such a manner that the entire hazardous areas are
The fire water system in a drilling rig covered/protected. At least 2 nos. of hydrants
should be designed to meet the fire water flow should be provided on the line (one near bunk
required for fighting fire with a monitor of houses and other near generator area). Single
minimum 1600 LPM capacity. However, hydrant with landing valves and 4” stand post
provision should be made in the system to hook up shall be provided. All hydrant outlets shall be
from the mobile fire tender or any other water situated 1.2 mtrs above the ground level.
supply of adequate pressure to operate some
additional water monitors etc.
The minimum quantities of fire Extinguisher at various locations should be provided as per the followings:
iv) Mud gunning pump area - 1 No. 10 kg DCP Extinguisher for each mud gunning pump
3
v) Electrical Control Room - 1 No. 6.8 kg CO2 Extinguisher for
each unit
- 1 No. 10 kg DCP Extinguisher for
each unit
vi) Mud mixing tank area/ - 1 No. 10 kg DCP Extinguisher
Chemical laboratory
vii) Diesel storage area - 1 No. 50 ltrs Mechanical foam
Extinguisher
- 1 No. 50 kg DCP Extinguisher
2 Nos. 10 kg DCP Extinguisher
2 Nos. sand bucket or 1/2’ sand
drum with spade.
Note: Sufficient safety precaution should be taken while transporting the Extinguisher from location to
location.
7.0 FIRE FIGHTING FACILITIES IN and situated in the same dyke at a rate of 1
CTF/GGS/OCS lpm/m2 of tank shell area.
The fire fighting facilities in CTF should Water flow required for applying foam on a single
be done as per OISD Standard 117. largest tank by way of fixed foam system, where
provided, or by use of water/foam monitors.
7.1 FIRE WATER SYSTEM
Fire water pumps shall be installed to meet the The fire water network piping
design fire water flow rate and head. These should normally be laid above ground at a height
should have flooded suction. of 300 mm to 400 mm above finished ground
level. However, the fire water network piping shall
The pumps shall be capable of discharging 150% be laid below ground level at the following places
of its rated discharge at a minimum of 65% of the
rated head. The Shut-off head shall not exceed - Road crossings.
120% of rated head for horizontal centrifugal - Places where the above ground piping is
pumps and 140% for vertical turbine pump. likely to cause obstruction to operation, vehicle
movement and places where the above ground
A minimum of 50% standby pump(s) (minimum piping is likely to get damaged mechanically.
one no.) of the same type and capacity as the main
pumps shall be provided. - Where frost condition warrants, the
pipeline shall be laid under-ground beneath the
The fire water pump(s) including the standby frost layer.
pump(s) shall be of diesel engine driven type.
Where electric supply is reliable 50% of the (iii) Protection of underground pipelines:
pumps may be electric driven. The diesel engines
shall be quick starting type with the help of push - The mains shall have at least one mtr. earth
buttons located on or near the pumps or located at cushion in open ground and 1.5 mtrs cushion
a remote location. Each engine shall have an under the roads. In case of crane movement areas,
independent fuel tank adequately sized for 6 hours pipe may be protected with concrete/steel
continuous running of the pump. encasement.
Fire water pumps & storage shall be located at 30 - The mains shall be provided with protection
mtrs (minimum) away from equipment or where against soil corrosion by suitable
hydrocarbons are handled or stored. coating/wrapping.
Fire water pumps shall be exclusively used for fire In case of poor soil conditions it may be
fighting purpose only. necessary to provide concrete/masonry supports
under the pipe.
The fire water network shall be kept pressurised
by a static tank or jockey pump(s). Where jockey Protection of above ground pipes:
pumps are used, the capacity of pump shall be
sufficient to maintain the system pressure in the - The mains shall be supported at regular intervals
event of leakages from valves etc. The capacity of not exceeding 6 mtrs.
Jockey pump shall not be less than 3% (with a
minimum of 180 lpm) and not more than 10% of - The system for above ground portion shall be
the designed fire water rate at network pressure analysed for flexibility against thermal expansion
not less than 3 Kg/cm2g. and necessary expansion loops where called for
shall be provided.
— If fire water is stored in above ground (iv) Monitors shall be located to direct water
storage tanks with water level more than 5 mtrs. on the object as well as to provide water shield to
above the highest point of fire water network, a firemen approaching a fire.
direct connection with a non-return valve shall be
provided to the fire water network from the Monitors shall not be installed less than
storage tank. 15mtrs. from hazardous equipment. The
requirement of monitors shall be established based
— If the fire water is stored in underground on hazards involved and layout considerations.
tanks, the fire water network shall be connected to
an overhead water tank if available in the The location of the monitors shall not
installation; otherwise a jockey pump shall be exceed 45 mtrs from the hazard to be protected.
installed to keep the mains pressurised.
(v) Hydrants and monitors shall not be
— Make up water shall be provided to installed inside the dyke areas. However, as an
account for leakages in the system so that fire additional requirement, oscillating monitors may
water storage is kept to the desired capacity. be provided in inaccessible area within dyke with
isolation valve or ROV outside the tank farm.
(vi) Connections for fixed water monitors
shall be provided with independent isolation (vi) Tanker Loading/unloading area should
valves. be provided with alternate water cum foam
monitors having multipurpose combination
(vii) Fire water mains shall not pass through nozzles for jet spray & fog arrangement and fire
buildings or dyke areas. hydrants located at a spacing of 30 mtrs. on both
sides of the gantry. The hydrants & monitors shall
(viii) In case of underground mains the be located at a minimum distance of 15 mtrs. from
isolation valves shall be located in RCC/brick the Tanker.
masonry chamber.
(vii) Hydrants/Monitors shall be preferably
located with branch connection.
7.1.7 HYDRANTS AND MONITORS:
7.1.8 FIXED WATER SPRAY SYSTEM
(i) Hydrants shall be located bearing in
mind the fire hazards at different sections of the (i) Fixed spray water system is a fixed pipe
premises to be protected and to give most effective system connected to a reliable source of water
service. At least one hydrant post shall be supply and equipped with water spray nozzles for
provided for every 30 mtrs of external wall specific water discharge and distribution over the
measurement or perimeter of battery limit in case surface of area to be protected. The piping system
of high hazard areas. For non-hazardous area, they is connected to the hydrant system water supply
shall be spaced at 45 mtrs. intervals. The through an automatically or manually actuated
horizontal range & coverage of hydrants with hose valve, which initiates the flow of water.
connections shall not be considered beyond 45
mtrs. (ii) Water supply patterns and their densities
shall be selected according to need. Fire water
(ii) Hydrants shall be located at a minimum spray system for exposure protection shall be
distance of 15 mtrs. from the periphery of storage designed to operate before the possible failures of
tank or equipment under protection. In case of any containers of flammable liquids or gases due
buildings this distance shall not be less than 2 to temperature rise. The system shall, therefore,
mtrs. and not more than 15 mtrs. from the face of be designed to discharge effective water spray
within shortest possible time.
7
(i) System be designed to create foam
7.2 FOAM SYSTEMS blanket on the burning surface in a reasonably
short period.
Conventional systems are of the open (iv) A minimum of two foam pourers shall be
outlet type, in which foam discharges from all provided.
outlets at the same time, covering the entire hazard
within the confines of the system. There are three
types of systems: 7.2.3 FIXED ROOF TANK PROTECTION
8
7.2.4 FLOATING CUM FIXED ROOF shall be used for determining water quantity
TANK PROTECTION required.
Portable monitors/foam hose streams (i) Foam solution application at the rate of 5
shall be considered for fighting fires in dyke area lpm/m2 for the liquid surface of the single largest
and spills. cone roof tank or at the rate of 12 lpm/m2 of seal
area of the single largest floating roof tank
7.2.6 FOAM APPLICATION RATE whichever is higher.
The minimum delivery rate for primary However, a foam solution application
protection based on the assumption that all the rate of 8.1 lpm/m2 of the liquid surface of the
foam reaches the area being protected shall be as largest floating roof tank for 65 minutes may be
indicated below : considered for a roof sinking case. (Refer
Annexure-IV for sample calculation)
For cone roof tanks containing liquid
hydrocarbons, the foam solution delivery rate shall (ii) Two hose streams of foam each with a
be at least 5 lpm/m2 of liquid surface area of the capacity of 1140 lpm of foam solution.
tank to be protected. The aggregate quantity of foam solutions should
be largest of (i) and (ii) as above for a
For floating roof tanks containing liquid minimum period of 65 minutes. From this the
hydrocarbons foam solution delivery rate shall be quantity of foam based on 3% or 6% proportion
at least 12 lpm/m2 of seal area with foam dam should be calculated.However, for installation
height of 600 mm of the tank to be protected. having aggregate storage not more than 10,000
KL, the foam concentrate storage shall be based
In case of floating roof sinking, the rate on (i) only.
considered should be 8.1 lpm/m2 of liquid surface
areas.
In determining total solution flow 7.2.10 FOAM COMPOUND STORAGE
requirements, potential foam losses from wind and
other factors shall be considered. Foam compound should be stored in plastic
containers of 20-30 ltrs capacity or 200/210 ltrs
7.2.7 DURATION OF FOAM DISCHARGE capacity barrels in case of protein, fluroprotein or
AFFF. Foam compound can also be stored in
The equipment shall be capable of overhead storage tank of suitable capacity for
providing primary protection at the specified quick filling of foam tender/nurser during
delivery rates for the following minimum period emergency.
of time.
Type of foam compound used can be
i) Tanks containing protein or fluroprotein or AFFF. Alcohol Resistant
Class 'A' & 'B' - 65 minutes Foam can be used for specific application.
Minimum life of foam compound shall be taken as
ii) Where the system's per manufacturer's data.
primary purpose is for
spill fire protection - 30 minutes Foam compound shall be tested
periodically for ensuring its quality and the
deteriorated quantity replaced. The deteriorated
foam compound can be used for fire training
purposes.
7.2.8 WATER FOR FOAM MAKING
Quantity of foam compound equal to
Water quantity required for making foam 1000 Ltrs. to be kept in GGS/OCS . Additional
solution depends upon the type of foam used. quantity required if any, during emergency shall
Protein foams in normal use have a 3% to 6% be arranged from the near by installations/ CTF.
proportioning ratio. However, foam supplier data
9
7.3 The minimum quantities of fire Extinguishers at various locations in GGS/OCS should be provided
as per following :
8.1.2 BASIS
8.0 FIRE FIGHTING FACILITIES IN
GCP/GCS Gas Compressor Plant is an extra high
hazardous installation. Any fire incident may
Following fire fighting arrangement cause major damage to the compressor plant.
should be made in a Gas Compressor Plant/Gas Hence, system should be capable of handling any
Compressor Station: major outbreak of fire incident at any Compressor.
- Fire water system Design of water flow rate should be enough to
- First Aid fire fighting operate 2 nos. Water monitor (1600 LPM)
equipment
- Detection System and Alarm simultaneously from the two opposite sides of any
Compressor with full working pressure (7.0
8.1.1 FIRE WATER SYSTEM kg/cm2).
10
8.1.3.1 FIRE WATER STORAGE centrifugal pumps and 140% for vertical turbine
pump.
In almost all cases, Gas Compressor A minimum of 50% standby pump(s) (minimum
Plants/Stations are situated adjacent to GGS/OCS one no.) of the same type and capacity as the main
where good fire water system with adequate water pumps shall be provided.
storage and pumping facilities are available.
Hence, as much as practicable this system should The fire water pump(s) including the standby
be hooked up with the GCP/GCS’s water ring pump(s) shall be of diesel engine driven type.
main to avoid separate water storage and pumping Where electric supply is reliable 50% of the
units. Otherwise, separate water storage and pumps may be electric driven. The diesel engines
pumps should be provided. shall be quick starting type with the help of push
buttons located on or near the pumps or located at
Minimum 300 K.L. of water storage a remote location. Each engine shall have an
shall be available at GCS/GCP. independent fuel tank adequately sized for 6 hours
Fire water supply shall be preferably continuous running of the pump.
from fresh water source such as river, tubewell or
lake. Where fresh water source is not easily Fire water pumps & storage shall be located at 30
available, fire water supply may be sea water or mtrs (minimum) away from equipment or where
other acceptable source like treated effluent water. hydrocarbons are handled or stored.
Where treated effluents is used as fire water
supply, it shall not have fecal waste Fire water pumps shall be exclusively used for fire
contamination. fighting purpose only.
The installation shall have facilities for The fire water network shall be kept pressurised
receiving and diverting all the water coming to the by a static tank or jockey pump(s). Where jockey
installation to fire water storage tanks in case of an pumps are used, the capacity of pump shall be
emergency. sufficient to maintain the system pressure in the
event of leakages from valves etc. The capacity of
Storage reservoir shall be in two Jockey pump shall not be less than 3% (with a
equal interconnected compartments to facilitate minimum of 180 lpm) and not more than 10% of
cleaning and repairs. In case of steel tanks there the designed fire water rate at network pressure
shall be minimum two tanks each having 50 % of not less than 3 Kg/cm2g.
required capacity.
8.1.3.3 Fire Water Distribution Network
Large natural reservoirs having water
capacity exceeding 10 times the aggregate water Fire water ringmain should be made available all
requirement of fire pumps may be left unlined. around the gas compressor plant. The size of the
ringmain should be of 8” diameter. Hydrants and
monitors should be provided in the entire ringmain
8.1.3.2 FIRE WATER PUMPS and distance between the two monitors or two
hydrants should not exceed 30.0 mtrs. Hydrant
i) Fire water pumps shall be installed to and monitors should be located at minimum
meet the design fire water flow rate and head. distance of 15.0 metres from the periphery of
These should have flooded suction. compressors or equipment under protection along
road side. However, total number of hydrants and
The pumps shall be capable of discharging monitors should depend upon the number of
150% of its rated discharge at a minimum of 65% compressor and the location of each compressor.
of the rated head. The Shut-off head shall not No area should be left uncovered from the range
exceed 120% of rated head for horizontal of the water monitors.
The entire gas compressor area to be One trailer pump of capacity 1800 LPM
covered with hydrocarbon gas detector. The exact at 7.0 kg/cm2 pressure should be installed and
loocation and number of points shall be decided hooked up with the water storage facilities.
on need basis.
9.1.5 Fire Water Distribution Network
9.0 FIRE FIGHTING FACILITIES IN Fire water line of 4” size should be made
EARLY PRODUCTION SET UP at two sides of the EPS along road side. Line
(EPS) should be at least 15.0 mtrs away from the
In any early production set-up, the fire hazardous area. This line should be hooked up
fighting facilities should be of following types: with the delivery of the trailer fire pump.
- Fire water system Provision should be made to pressurise the
- First aid fire fighting equipment ringmain if required from the outside fire tender or
any other reliable pressurised water supply.
12
9.1.6 Above ground piping area. Distance between the two hydrants or two
monitors should not be more than 30.0 mtrs.
Piping network should be laid above the Monitors should be installed in such a manner that
ground level. Height should be 300 to 400 mm it should be able to cover all the tanks as well as
from the ground and it should be supported at group unit area. Height of the hydrant valve
every 6.0 mtrs distance. It should be ensured that should not be more than 1.2 mtrs. from the ground
proper coating etc. to be provided on pipe near level.
support. However, if required pipe can be laid
below ground with proper protection arrangement
as per OISD Standard 117. 9.2 First Aid Fire Fighting Equipment at
EPS
The minimum quantities of fire Extinguisher at various locations should be provided as per the followings:
10.0 FIRE FIGHTING EQUIPMENT 10.1 Fire water storage with fire pump
AT QUICK PRODUCTION
SETUP (QPS)/Well Head One 40.0 KL capacity water storage tank should
Installation (WHI) be provided at the approach area of the QPS. The
tank should be of welded type with adequate
Quick Production Setup is a small production unit thickness. One trailer pump of capacity 1800
of temporary nature. Following minimum fire LPM at 7.0 kg/cm2 pressure should be provided.
protection facilities should be installed: The pump should be hooked up with the water
- Fire water storage facilities with fire storage tank.
pump One additional TPC connection should be
- First Aid fire fighting equipment provided in the storage tank for connecting outside
fire tender in case of emergency. Regular filling
arrangement for the above mentioned tank should
be provided.
13
iii) Near tank storage area - 2 Nos 10 kg DCP Extinguisher
iv) Generator house - 1 No. 6.8 kg CO2 Extinguisher
1 No. 10 kg DCP Extinguisher
12.1 FIRE ALARM SYSTEM (ii) Hot work permit shall be issued by the
Installation Manager.
Electrical/hand operated fire siren shall
be installed at suitable location in installation. The
operating switch buttons shall be located near the
Risk Area at a safe, identifiable and accessible 13.2 TRAINING
location. The fire alarm shall be different from
shift sirens. (i) The fire fighting training shall be
compulsory to all officers, operators, and other
Fire siren code should be as follows: employees who are likely to be present in the
installation. There shall be regular mock fire
1. SMALL FIRE: No siren drills, once a month. The record of such drills
shall be maintained by the installation Manager.
2. MAJOR FIRE: A wailing siren for two
minutes. Sirens will be sounded three times for (ii) Every employee or authorised persons
thirty seconds with an interval of fifteen second in working in the oil installation should be
between. familiarised with the fire alarm signal and should
know the location of the fire alarm point nearest to
3. DISASTER: Same type of siren as in his place of work. Instructions on the action to be
case of Major Fire but the same will be sounded taken in the event of fire should be posted at each
for three times at the interval of two minutes. alarm point and familiarity with these instructions
should be ensured and recorded.
4. ALL CLEAR (For fire): Straight run
siren for two minutes. (iii) OISD-STD-154 - Safety Aspects in
Functional Training shall be adhered to in this
5. TEST: Straight run siren for two minutes. regard.
14