Revision 3.1
INSTRUCTION MANUAL
DRAEGER SAFETY, INC.
MODEL DRAEGERGARD 8/16 CHANNEL CONTROLLER
(Revision 3.1)
SECTION 1
WARNINGS:
• Shock Hazard - Disconnect or turn off power before servicing this instrument.
• NEMA 4X wall mount models should be fitted with a locking mechanism after
installation to prevent access to high voltages by unauthorized personnel (see
Figure 6.2).
! • Use a properly rated CERTIFIED AC power (mains) cable installed as per local
or national codes
• A certified AC power (mains) disconnect or circuit breaker should be mounted
near the controller and installed following applicable local and national codes. If
a switch is used instead of a circuit breaker, a properly rate CERTIFIED fuse or
current limiter is required to installed as per local or national codes. Markings for
positions of the switch or breaker should state (I) for on and (O) for off.
• Clean only with a damp cloth without solvents.
• Equipment not used as prescribed within this manual may impair overall safety.
1
DraegerGard Controller Users Manual
Revision 3.1
DraegerGard front panel is shown below in Figure 1.0 displaying the 8 channel bar graph
screen. Additional data screens are shown in Figure 2.0.
Figure1.0
2
DraegerGard Controller Users Manual
Revision 3.1
hour period. The SI field on the top right indicates number of seconds remaining in the
current 6 minute subinterval.
1.2 SPECIFICATIONS:
3
DraegerGard Controller Users Manual
Revision 3.1
The 7451291 150 watt power supply (Figure 3.8) is for powering the DraegerGard and up
to 16 detectors. A minimum of 5 watts per channel is available for powering of external
transmitters.
1.2.4 ALTITUDE
Recommended up to 2000 meters
1.2.5 HOUSINGS
• General purpose panel mount weighing 7 lbs and including hardware for 19” rack
mounting (Figure 6.1).
• *NEMA 4X wall mount in fiberglass enclosure weighing 17 lbs (Figure 6.2).
• *NEMA 7 wall mount suitable for DIV 1&2 Groups B,C,D weighing 110 lbs (Figure
6.4).
*Includes non-intrusive magnetic keypad.
1.2.6 APPROVALS
CSA C22.2 No 1010.1 and ISA S82.02
SECTION 2
4
DraegerGard Controller Users Manual
Revision 3.1
or automatically when no keys are pressed for 5 minutes. Alarm relays and front panel
alarm LED indicators remain active during the Setup mode. An AUTHORIZE menu
offers a password feature to prevent tampering with DraegerGard parameters.
Ch 0 1 0 P CT L E L C h 0 5 Me a s u r e me n t N a me 50 PCT L E L
Ra n g e = 0 t o 10 0 P C T L E L S I 12 5
Ch 0 2 10 P CT L E L 2 4 Hr Da t a 0 Mi n 8 0 Ma x 3 0 Av g
Ch 0 3 0 P CT L E L
Ch 0 4 50 P CT L E L
Ch 0 5 0 P CT L E L
Ch 0 6 0 P CT L E L
Ch 0 7 0 P CT L E L
1 2 3 4 5 6 7 8 Ch 0 8 0 P CT L E L
%F S Ch 0 2 Me a s u r e me n t N a me MA X 10 S ET UP ME N U
MI N 0
AVG 3 Sy s t e m Ch a n n e l 0 1 Ch a n n e l 09
SPAN 10 0 Co n t r a s t Ch a n n e l 0 2 Ch a n n e l 10
Au t h o r i z e Ch a n n e l 0 3 Ch a n n e l 11
0 1117 C OU N T S PCT L E L Z ERO 0
Di a g n o s t i c s Ch a n n e l 0 4 Ch a n n e l 12
U N L OC K E D Ch a n n e l 0 5 Ch a n n e l 13
Ch a n n e l 0 6 Ch a n n e l 14
Ch a n n e l 0 7 Ch a n n e l 15
Ch a n n e l 0 8 Ch a n n e l 16
03 10 MI N U T E S
Combination Setup
Figure 2.0
5
DraegerGard Controller Users Manual
Revision 3.1
Se t p o i n t 20.00
Lat c hi ng NO
T r i p On H I GH
On D e l a y 00s
Of f De l a y 00m
Ho r n Dr i v e YES
Alarm 1 or 2 menu
Ch a n n e l XX Ch a n n e l X X
A L A RM 3 S E T UP A L A RM 3 S E T UP
Se t p o i n t - 5.000 Se t p o i n t 60.00
Ty pe F AUL T Lat chi ng NO
T r i p On H I GH
On De l a y 00s
Of f De l a y 00m
Ty pe L EVEL
Se n s o r Di r e c t MO D B U S 8 BI T
Mi n Ra w 00800 Mi n Ra w 00050
Ma x Ra w 04000 Ma x R a w 00250
R e mo t e ID 01
Al i a s 33001
Ch a n n e l XX
Me a s u r e me n t N a me
Al a r m 1
Al a r m 2
Input From?: menu If input is Modbus
Al a r m 3 Ch a n n e l XX
Da t a F r o m Li near i z at i on
Li near i ze
Co n f i g u r e %I n p u t % Ou t p u t
Ca l i b r a t e 10 . 0 0 10 . 0 0
2 0 . 0 0 2 0 .0 0
3 0 . 0 0 3 0 .0 0
Entry menu 4 0 . 0 0 4 0 .0 0
5 0 . 0 0 5 0 .0 0
6 0 . 0 0 6 0 .0 0
70.00 70.00
80.00 80.00
90.00 90.00
Linearization menu
Ch a n n e l XX
C O N F I GU R A T I ON
Me a s u r e me n t N a me
Eu n i t s 6di gi t
Ze r o 0.000
Sp a n 10 0 . 0
De c i ma l P o i n t s 0
Ch a n n e l On ? YES
Co p y To XX
Co p y No w?
Ca l Z ERO 0.000
Ca l SPAN 50.00
Se t Zer o
Se t Sp a n
Un i t y Ga i n
If input is sensor
Figure 2.1
6
DraegerGard Controller Users Manual
Revision 3.1
EDIT
Al a r m 1 Se t p o i n t 20.00
Al a r m 2 Lat chi ng NO
Al a r m 3 T r i p On H I GH
Da t a F r o m On D e l a y 00s
Li near i ze Of f De l a y 00m
Input NEXT Ho r n Dr i v e YES
Ca l i b r a t e
Figure 2.2
The first entry determines the Setpoint value where the alarm trips. It is entered in
engineering units. For example, if a channel monitors 0-50 ppmH2S and the alarm must
trip at 10 ppm, the correct entry is 10.00.
• Latching determines either manual or automatic alarm reset operation. YES
requires a manual Alarm Reset to unlatch the alarm even though an alarm condition
no longer exists. YES also causes this alarm group’s common relay, front panel
LED, and optional discrete relay to latch. NO allows all outputs for this alarm to
automatically reset as soon as the alarm condition clears.
• TRIP ON. is set to HIGH for increasing alarms or LOW for decreasing alarms to
determine if the alarm activates upon exceeding or falling below the setpoint.
• The ON DELAY / OFF DELAY entries allow ON and OFF time delays affecting
how long the setpoint must be surpassed before an alarm event transition occurs. ON
delays are limited to 10 seconds while OFF delays may be as long as 120 minutes.
Delays are useful in many applications to prevent nuisance alarms and unwanted
cycling into and out of alarm conditions.
• The HORN ON entry allows linking this alarm to the common horn relay. NO
causes the alarm to have no effect upon the horn relay. Entering YES causes this
alarm to turn the horn relay on steady, or, to pulse it depending upon horn
configuration in they system menu (see section 2.3.1).
Discrete LED indicators on the front panel indicate the status of each alarm and relay.
Any new alarm event causes the associated LED to flash until Alarm Reset occurs
causing an acknowledged steady on condition. Operators should recognize new alarms
by a flashing LED. Alarm Reset also acknowledges, or deactivates, the horn relay until
another new alarm occurs.
7
DraegerGard Controller Users Manual
Revision 3.1
Figure 2.3
8
DraegerGard Controller Users Manual
Revision 3.1
Ch a n n e l XX Ch a n n e l X X Ch a n n e l X X Ch a n n e l X X
Me a s u r e me n t N a me I N P U T D A T A F R OM I N P U T D A T A F R OM I N P U T D A T A F R OM
EDIT
Al a r m 1 Se n s o r Di r e c t MOD B U S 8 BI T MOD B U S 32 BI T
Al a r m 2 Mi n Ra w 00800 Mi n R a w 00050 Mi n R a w 00050
Al a r m 3 Ma x Ra w 04000 Ma x R a w 00250 Ma x R a w 00250
Da t a F r o m R e mo t e I D 01 R e mo t e I D 01
Li near i ze Al i a s 33001 Al i a s 33001
Co n f i g u r e NEXT B y t e Or d e r A B C D
Ca l i b r a t e
Figure 2.4
If Modbus 32 BIT is selected, a Byte Order entry appears at the bottom of the menu.
This determines WORD and BYTE alignment of data at the remote Modbus transmitter
when sending it’s 4 byte IEEE Floating Point values. With the pointer on this entry, the
EDIT key toggles between the 4 possible modes. Min / Max Raw values are not used in
this mode.
Note: Each Data From: item has a matching default Min/Max counts value of 20% to
100% with ± 5% over/underrange applied. If the default value is incorrect for the input
device it should be edited.
9
DraegerGard Controller Users Manual
Revision 3.1
Ch a n n e l XX
Ch a n n e l XX Li near i zat i on
Me a s u r e me n t N a me
EDIT %I n p u t
10 . 0 0
% Ou t p u t
10 . 0 0
Al a r m 1
Al a r m 2 20.00 20.00
Al a r m 3 3 0. 00 3 0 .0 0
Da t a F r o m 4 0. 00 4 0 .0 0
Li near i ze 5 0. 00 5 0 .0 0
Co n f i g u r e NEXT 6 0. 00 6 0 .0 0
Ca l i b r a t e 7 0. 00 7 0 .0 0
8 0. 00 8 0 .0 0
9 0. 00 9 0 .0 0
Entry menu
Linearization menu
Figure 2.5
Entry menu
Input / Copy To: menu
Figure 2.6
10
DraegerGard Controller Users Manual
Revision 3.1
menu’s decimal point entry. For example, if three decimal points are entered, and the
range is 0 to 100ppm, the reading will be 0.000 at 0ppm and 100.0 at 100ppm. However,
this may be undesirable due to the high resolution at zero unless the sensor’s output is
extremely stable. If decimal points are limited to one, the 0ppm reading becomes 0.0 and
the 100ppm reading remains 100.0. Resolution may be limited further by setting decimal
points to 0. In the above example, this would cause 0ppm to display 0 and 100ppm to
display 100.
11
DraegerGard Controller Users Manual
Revision 3.1
exit. The procedure for span calibration is identical. For example, if an LEL combustible
sensor is to be spanned with 50% LEL span gas, the span set-point must be 50%. If 45%
LEL is to be used later, the span set-point must be changed to 45% to match the span
calibration gas. If the reading is only 40% LEL with the 50% gas applied a span
calibration is needed. Move the pointer to the Set Span entry and press EDIT twice.
Unity Gain may be used at anytime to cancel incorrect calibrations and start again.
Ch a n n e l XX Ch a n n e l XX
Me a s u r e me n t N a me C A L I B R A T I ON
EDIT
Al a r m 1 Ca l Z E RO 0.000
Al a r m 2 Ca l SPAN 50.00
Al a r m 3 Se t Ze r o
Da t a F r o m Se t Sp a n
Li near i ze Un i t y Ga i n
Co n f i g u r e NEXT
Ca l i b r a t e
Figure 2.7
A1/A2 Relays
Sy s t e m Se t u p
Ho r n Re l a y
Pi e z o A l a r m OF F
Ke y Be e p ON
Fai l s af e ON
Sy s t e m Se t u p Ho r n Gr o u p 9 - 16
Ve r s i o n #. ## Di s p l a y Al m NO
Al a r m 1 Re l a y
Al a r m 2 Re l a y
Ho r n / P i e z o Piezo/Horn Relay
Mo d b u s
8 / 16 C h Mo d e
Sy s t e m Se t u p
MO D B U S Po r t s
Sl a v e ID 01
Entry menu Sl a v e Ba u d 9 6 0 0
R mt T. O. 0 5 mS
R mt P. R. 0 15 0 mS
Modbus Ports
Sy s t e m Se t u p
8 / 16 C h a n n e l Mo d e
Ch a n n e l s 16
Figure 2.8
12
DraegerGard Controller Users Manual
Revision 3.1
Figure 2.9
• Horn Drive controls how this alarm level from each channel will affect the common
horn relay. Choices are OFF, ON or BEEP. As an example, A1 conditions might
pulse the horn (BEEP) and A2 conditions to cause a steady horn (ON). Any other
combination of these 3 choices is possible for A1 and A2 affecting the horn relay.
• Failsafe controls relay activation for the common relay and the optional discrete
relays if the controller is so equipped. Turning Failsafe ON causes these relays to
de-energize during alarm conditions and energize when there is no alarm. Thereby, a
power failure forces the relay contact to the alarm position. Note the common Fault
relay is always failsafe and may be monitored separately to indicate loss of power
conditions in many applications.
• The Group menu entry offers additional flexibility by controlling which channels
trip this menu’s common alarm relay. The 3 choices are 1-16, 1-8 or 9-16. Some
applications have different types of sensors, or, sensors in different areas connected to
the same DraegerGard Controller. In these cases, it may be undesirable for a sensor
on channel 9 to trip the same relay as a sensor on channel 2. The Group menus may
restrict this. For example, channels 1-8 might be set to trip the common Alarm 1
relay while channels 9-16 trip the common Alarm 2 relay. Another possibility is
channels 1-8 be set to trip the common Alarm 1 relay while channels 9-16 trip relays
on an optional discrete relay PCB configured for Alarm 1 (see section 3.2).
• Turning Acknowledge ON (not available on Alarm 1) allows the common relay to
be deactivated during alarm conditions by an Alarm Reset. This is useful if another
audible device is being driven by the relay. The common horn relay may always be
acknowledged.
13
DraegerGard Controller Users Manual
Revision 3.1
Sy s t e m Se t u p
Sy s t e m Se t u p
Ve r s i o n #. ##
EDIT Ho r n Re l a y
Al a r m 1 Re l a y Pi e z o A l a r m OF F
A l a r m 2 Re l a y Ke y Be e p ON
Ho r n / P i e z o
Mo d b u s Fa i l s af e OF F
8 / 16 C h Mo d e Ho r n Gr o u p 9 - 16
NEXT Di s p l a y Al m No
Figure 2.10
• Turning Piezo Alarm ON causes the audible piezo to duplicate the action of horn
relay. This feature may be used to provide a low decibel indication of the status of
the system’s horn.
• Turning Key Beep ON causes the audible piezo to chirp whenever a key is pressed.
• Failsafe & Group menu entries are identical to the descriptions for A1 & A2 in
section 2.3.1.
• Display Alm YES forces the LCD to display the Bar Graphs screen upon any new
alarm. This feature is offered to satisfy applications requiring channels in alarm to be
displayed automatically (all channels are displayed on the Bar Graphs screen).
Figure 2.11
14
DraegerGard Controller Users Manual
Revision 3.1
A l a r m 2 Re l a y
Ho r n / P i e z o
Mo d b u s
8 / 16 C h Mo d e
NEXT
Figure 2.12
E N T E R N A ME
En t e r Co d e # ## #
L o c k Sy s t e m
Figure 2.13
15
DraegerGard Controller Users Manual
Revision 3.1
SECTION 3
16
DraegerGard Controller Users Manual
Revision 3.1
J4
COMM1 COMM2 J2
Ribbon connector to TX1 RX1 TX2 RX2 J2 & J3 connect to
optional Auxilliary I2C optional I/O
Common Relay PCB
J3
A N A L OG A N A L OG A N A L OG A N A L OG A L A R M2
I NP UT I NP UT OU T P U T OU T P U T Re l a y
1- 8 9 - 16 1- 8 9 - 16 1- 8
F OU N D F OU N D F OU N D F OUN D F OUN D
A L A R M2
I NP UT
9 - 16
F OU N D
P RE S S NE X T KEY TO EXI T
Figure 3.2
17
DraegerGard Controller Users Manual
Revision 3.1
Figure 3.3
18
DraegerGard Controller Users Manual
Revision 3.1
19
DraegerGard Controller Users Manual
Revision 3.1
NO C NC NO C NC NO C NC NO C NC
CH1/9 CH3/11 CH5/13 CH7/15 TB1
NO C NC NO C NC NO C NC NO C NC
CH2/10 CH4/12 CH6/14 CH8/16
20
DraegerGard Controller Users Manual
Revision 3.1
D1 U9
D2 U10
Q16
Q17
Q15 JP1 determines if this 8 channel
U8
Q14 Analog Output PCB provides
outputs for CH’s 1-8 or 9-16.
J1
2 PCB assemblies are required
Q13 for 16 channels.
Q12 C2
C3 C6
Q3
Q2
Q1
24 VDC power for output Milliamp
Outputs
current loops must be Connect to Low's
supplied through TB2. “DC OUT” LO LO LO LO LO LO LO LO
Connect to main I/O PCB on I/O PCB TB1
terminals 10 & 12 of TB2.
High's
HI HI HI HI HI HI HI HI
TB2
+ -
24 VDC
INPUT
21
DraegerGard Controller Users Manual
Revision 3.1
Channels receiving input data from this board should have the Data From: menu set for
Sensor, as described in section 2.2.4. This activates Cal Mode menus described in
section 2.2.7 needed to zero and span sensor readings. After performing the one time
only Initial Setup as described below, all subsequent calibrations are by the
DraegerGard’s electronic Cal Mode menus.
22
DraegerGard Controller Users Manual
Revision 3.1
ASSY# 7451389
'CATBEAD' 8 CH INPUT
J1
# 7451389
JP9 sets for Ch’s
1-8 or 9-16 JP9
U2 U1
Disconnect power
Ch.2 Ch.4 Ch.6 Ch.8 LOW
MED GAIN CH’s 2,4,6,8,10,12,14 or 16
before removing JUMPER
S6 HIGH
or installing modules. S2 S4 BALANCE
LEL CH. B
JP1 JP3 JP5 JP7 ADJUST
S8
.4 - 2VDC T.P.
S1 S3 S5 CH. A BALANCE
R2 R4 R6 R8 ADJUST
S7
*100 ohm
Res.Sockets
R1 R3 R5 R7 TB2
# 7451390
1 2 Dual Channel “CATBEAD” Modules plug into sockets
1 3 5 7 9 11 13 15 17 19 21 23
Ch1/9 Ch3/11 Ch5/13 Ch7/15
on Main terminal board. Not required for 4-20mA
R C
+
A
-
R C
+
A
-
R C
+
A
-
R C
+
A
-
+ - channels.
2 4 6 8 10 12 14 16 18 20 22 24
Plug In, 100 ohm R. Install only
Ch2/10 Ch4/12 Ch6/14 Ch8/16 if channel is 4-20mA input!
R C A R C A R C A R C A
+ - + - + - + - R1
+ - Internal controller ckts.
1 3 5
Sensor wiring. Ch.1 shown.
For 4-20mA inputs use 3 & 5
REF ANA and do not install 7451390 module.
R-C-A are from Catalytic bead sensors. 4-20mA may be applied to LEL Sensor
any channel’s C & A terminals by addition of 100 ohm resistor Ch.1/Ch.9 (Typical)
(R1-R8) and setting LEL/4-20mA jumper to 4-20mA.
23
DraegerGard Controller Users Manual
Revision 3.1
24
DraegerGard Controller Users Manual
Revision 3.1
Figure 3.7
25
DraegerGard Controller Users Manual
Revision 3.1
Figure 3.8
Figure 3.9
26
DraegerGard Controller Users Manual
Revision 3.1
SECTION 4
Figure 4.1
27
DraegerGard Controller Users Manual
Revision 3.1
Figure 4.2
28
DraegerGard Controller Users Manual
Revision 3.1
SECTION 5
5.0 MODBUS RS-485 PORTS
The DraegerGard is equipped with Master (COMM 1), and Slave (COMM 2), modbus
RTU ports. Port configurations are described in sections 2.2 and 2.3 of this manual. This
section defines register locations of data when interrogating the DraegerGard slave port.
Notes: ASCII which may be read 2 characters at a time or in strings using a multiple register read.
Sixteen character channel tag name:
Type Channel First Last Read FC Write FC Notes
Channel Tag 1 40401 40408 3 n/a 2 characters per register
Channel Tag 2 40409 40416 3 n/a 2 characters per register
Channel Tag 3 40417 40424 3 n/a 2 characters per register
Channel Tag 4 40425 40432 3 n/a 2 characters per register
Channel Tag 5 40433 40440 3 n/a 2 characters per register
Channel Tag 6 40441 40448 3 n/a 2 characters per register
Channel Tag 7 40449 40456 3 n/a 2 characters per register
Channel Tag 8 40457 40464 3 n/a 2 characters per register
Channel Tag 9 40465 40472 3 n/a 2 characters per register
Channel Tag 10 40473 40480 3 n/a 2 characters per register
Channel Tag 11 40481 40488 3 n/a 2 characters per register
Channel Tag 12 40489 40496 3 n/a 2 characters per register
Channel Tag 13 40497 40504 3 n/a 2 characters per register
Channel Tag 14 40505 40512 3 n/a 2 characters per register
Channel Tag 15 40513 40520 3 n/a 2 characters per register
Channel Tag 16 40521 40528 3 n/a 2 characters per register
Display Value = MODBUS Value [ (Span Value -Zero Value) 1.1] + {Zero Value - [(Span Value - Zero Value) .05]}
32767
29
DraegerGard Controller Users Manual
Revision 3.1
----------------------------------------------------------------------------------------------------------------------
Memory Integer
Notes: Channel a/d value = direct a/d counts.
Analog Output:
Type Channel First Last Read FC Write FC Notes
Analog Out 1-16 31001-16 n/a 4 n/a 12bit integer
Alarm status words are bits packed into 16 bit integer where lsb = Channel 1 alarm status and msb =
Channel 16 alarm status.
Alarm status:
Type Channel First Last Read FC Write FC Notes
Alarm 1 Status 1-16 31033 n/a 4 n/a packed 16bit integer
Alarm 2 Status 1-16 31034 n/a 4 n/a packed 16bit integer
Alarm 3 Status 1-16 31035 n/a 4 n/a packed 16bit integer
Relay Status n/a 31036 n/a 4 n/a packed 16bit integer
Note: Relay status bits are as follows.
Alarm 1 Relay = bit0.
Alarm 2 Relay = bit1
Alarm 3 Relay = bit2
Horn Relay = bit3
----------------------------------------------------------------------------------------------------------------------
Coils
Notes: Set this coil to issue an alarm acknowledge via modbus.
Type Channel First Last Read FC Write FC Notes
Alarm Reset n/a 2001 n/a n/a 5 write 0xff to high byte to set
----------------------------------------------------------------------------------------------------------------------
Memory Discretes
Notes: May be read as single discrete or packed with multiple register read.
Type Channel First Last Read FC Write FC Notes
Chnl Alarm 1 1-16 12001-16 n/a 2 n/a discrete, may be packed
----------------------------------------------------------------------------------------------------------------------
Memory Reals
Notes: Real value represents float value without the decimal point such as 123.4 is returned as 1234.
Decimal devisor is returned as 1, 10, 100, or 1000 for decimal position of 1, 2, 3, or 4, where 123.4 would
return the value 10.
30
DraegerGard Controller Users Manual
Revision 3.1
This update requires several seconds. Therefore, a data ready register is available to notify the master upon
completion.
Type Channel First Last Read FC Write FC Notes
MIN Ready n/a 12065 n/a 2 n/a 0 = data ready; 1 = update in progress
AVG. Ready n/a 12066 n/a 2 n/a 0 = data ready; 1 = update in progress
MAX Ready n/a 12067 n/a 2 n/a 0 = data ready; 1 = update in progress
31
DraegerGard Controller Users Manual
Revision 3.1
SECTION 6
SIDE VIEW
5.22
FRONT VIEW
Figure 6.1
32
DraegerGard Controller Users Manual
Revision 3.1
Figure 6.2
33
DraegerGard Controller Users Manual
Revision 3.1
Figure 6.3
34
DraegerGard Controller Users Manual
Revision 3.1
24 5/8
Figure 6.4
35