Professional Documents
Culture Documents
Where:
Am - is the amplitude of the waveform.
ωt - is the angular frequency of the waveform in radian/sec.
Φ (phi) - is the phase angle in degrees or radians that the waveform has
shifted either left or right from the reference point.
If the positive slope of the sinusoidal waveform passes through the horizontal
axis “before” t = 0 then the waveform has shifted to the left so Φ >0, and the
phase angle will be positive in nature, +Φ giving a leading phase angle. In
other words it appears earlier in time than 0o producing an anticlockwise
rotation of the vector.
Likewise, if the positive slope of the sinusoidal waveform passes through the
horizontal x-axis some time “after” t = 0 then the waveform has shifted to the
right so Φ <0, and the phase angle will be negative in nature -Φ producing a
lagging phase angle as it appears later in time than 0o producing a clockwise
rotation of the vector. Both cases are shown below.
Now lets consider that the voltage, v and the current, i have a phase
difference between themselves of 30o, so (Φ = 30o or π/6 radians). As both
alternating quantities rotate at the same speed, i.e. they have the same
frequency, this phase difference will remain constant for all instants in time,
then the phase difference of 30o between the two quantities is represented by
phi, Φ as shown below.
The voltage waveform above starts at zero along the horizontal reference
axis, but at that same instant of time the current waveform is still negative in
value and does not cross this reference axis until 30o later. Then there exists
a Phase difference between the two waveforms as the current cross the
horizontal reference axis reaching its maximum peak and zero values after the
voltage waveform.
As the two waveforms are no longer “in-phase”, they must therefore be “out-
of-phase” by an amount determined by phi, Φ and in our example this is 30o.
So we can say that the two waveforms are now 30o out-of phase. The current
waveform can also be said to be “lagging” behind the voltage waveform by the
phase angle, Φ. Then in our example above the two waveforms have
a Lagging Phase Difference so the expression for both the voltage and
current above will be given as.
Cosine Expression
The Cosine Wave, simply called “cos”, is as important as the sine wave in
electrical engineering. The cosine wave has the same shape as its sine wave
counterpart that is it is a sinusoidal function, but is shifted by +90o or one full
quarter of a period ahead of it.
Phase Difference between a Sine wave and a Cosine wave
Alternatively, we can also say that a sine wave is a cosine wave that has been
shifted in the other direction by -90o. Either way when dealing with sine waves
or cosine waves with an angle the following rules will always apply.
phase angle
phase angle: Of a periodic wave, the number of suitable units of angular measure
between a point on the wave and a reference point. Note 1: The reference point may
be a point on another periodic wave. The waves may be plotted on a suitable
coordinate system, such as a Cartesian plot, with degrees or other angular measure
usually plotted on the abscissa and amplitude on the ordinate. Usually, at least one
full cycle of each wave is plotted, with 360° (2 radians) encompassing one full
cycle. The reference points may be any significant instants on the waves, such as
where they cross the abscissa axis. Note 2: The use of angular measure to define the
relationship between a periodic wave and a reference point is derived from the
projection of a rotating vector onto the real axis of an Argand diagram. Note 3: The
value of the phase angle of a point on the wave is the point on the abscissa that
corresponds to the point on the wave. Note 4: The phase angle of a vector may be
Real power is mathematically determined by dividing time into a very large number of
small segments and multiplying the instantaneous voltage present in each time
segment by the instantaneous current flowing and averaging the results.
A wattmeter gives the same result in a real world circuit because the instrument reacts
to the simultaneous effects of the voltage and current present from instant to instant.
When separate measurements are made of voltage and current, the product is NOT a-
c power since each meter reads an average or rms value of the voltage or current over
time without reflecting the phase shift that may be present. If there is a difference in
phase between the voltage and current waveforms, the peak current may not be
present when the voltage reaches its peak. The apparent power will be the vector sum
of the real power and the imaginary power.
The angle is the phase shift. In a non-reactive circuit, the voltage and current will be in
phase, the imaginary power is zero and the real power will equal the apparent power.
Their ratio is expressed as power factor (PF) and when they are equal, the power factor
is unity (1).
Waveform distortion, of the type caused by capacitor input filter circuits following
rectifiers, is another source of low power factor. It results from the creation of
discontinuous waveforms as the current to the load flows for just the part of the cycle
where the voltage from the rectifier exceeds the d-c level across the capacitor. In terms
of rms values, there are an infinite number of waveforms that can yield the same rms
value. If the current is not sinusoidal, a narrow spike, for example, the rms value may
remain the same even though the average value can be quite different. Although the
voltage and current are in phase with each other, the power factor can differ from the
unity value that two sinusoidal waveforms would produce. A Fourier analysis would
show that changing the shape of either the voltage or current waveform reduces the
power factor from the unity value that you might expect from the in-phase relationship.
The input off-line capacitors of switch mode power supplies do significantly change the
current waveform. As the voltage reaches the stored level in the capacitor, the rectifier
diode switches on, forcing the current to flow for a shorter time interval than the
voltage. While the load current is drawn from the capacitor continuously, or at the high
switching frequency of the converter, the capacitor is recharged only during the interval
when the input rectifiers conduct. No current flows into the capacitor from any point
along the voltage waveform where its amplitude falls below the capacitor's d-c voltage.
Current only flows when it again rises above the d-c value during the next mains half
cycle.
Low power factor results when the load current is drawn over only a part of each mains
cycle. This is a common result in off-line rectifiers where the input diode does not
conduct until the peak of the rectified mains waveform exceeds the d-c level across the
input capacitors.
The period of time during which no current flows into the capacitor, expressed in terms
of degrees along the voltage waveform, is the rectifier's dead angle. Conversely, the
period during which current does flow into the capacitor is the rectifier's conduction
angle. The ratio of these angles depends upon the filter's capacitance and how much
energy is being withdrawn by the power converter which is the capacitor's load. This, in
turn, depends on the amount of power demanded by the output load on the converter.
With a light load, the conduction angle may be just a few degrees. At full rated load, the
conduction angle will be larger, but even with heavy loads, conduction is not
continuous. The current has the form of relatively large, short-duration pulses. Because
the a-c mains exhibit a non-zero source impedance, the high current peaks cause
some clipping distortion on the peaks of the voltage sinusoid. Fourier analysis would
show that this lowers the power factor significantly.
Since power factor represents the ratio of real to apparent power, the high apparent
power that yields a low power factor translates into a higher current than the load
actually needs to satisfy its real power requirement. The difference between the current
that produces the real power consumed by the load and the current measured on an
ammeter is known as the circulating current. It is so called because even though it does
no real work, it continuously flows back and forth between the mains and the load.
FIGURE 16 - Waveforms illustrating the peak flattening effect that the narrow current
pulses impose on the mains voltage
FIGURE 17 - Waveforms illustrating the reduced peak current when the current
waveform is made to conduct continuously by power factor correction
The European electrical system distributes power at 240 volts. This means that the
current is half what it would be in the USA for an equivalent load. Because of this,
European distribution systems use smaller gauge wire and lower amperage fuses. As a
result, they are more sensitive to circulating current than their USA counterparts. With
the goal of minimizing circulating current, the International Electrotechnical Committee
(IEC) took a look at the discontinuous currents produced by switch mode power
converters and other electrical equipment. Any discontinuous waveform consists of a
pure sine wave at the fundamental frequency plus sine waves of various amplitudes
occurring at each of the fundamental's harmonic frequencies. The IEC codified its
findings in IEC 555-2, setting limits for currents at each harmonic frequency through the
40th harmonic. The IEC divided equipment into four classes, each with its own set of
harmonic current limits. These limits have been codified into a “European norm,”
EN61000-3-2.
To meet these limits various power factor correcting (PFC) circuits are employed to
actively force the main rectifier(s) to conduct over the whole of each half cycle of the ac
power mains. These sometimes take the form of a high frequency boost converter that
preceeds the input filter capacitor.
At some sacrifice in efficiency and some loss of simplicity, the PFC boost converter
reduces the power factor to something between 0.95 and 0.99 (sufficient to meet the
harmonic current limits). Additionally, PFC enhances the energy storing function of the
input capacitor. A boost converter can also provide a relatively stable output over a
wide range of input voltages. The power factor correcting boost converter produces a
constantly high voltage across its input capacitor regardless of the input mains voltage.
Thus the hold-up time becomes independent of the mains voltage.
Power supplies with active power factor correction (PFC) include the
Kepco ABC (100W), MST (200W), RCW (350, 750 and 1500W), RKW (50, 100, 150,
300, 600 and 1500W), HSP (1000 and 1500W), BOP High Power (1000 and 2000W)
and HSM (1000 and 1500W).
http://www.kepcopower.com/hbkpfc.htm
We know that reactive loads such as inductors and capacitors dissipate zero power,
yet the fact that they drop voltage and draw current gives the deceptive impression
that they actually do dissipate power. This “phantom power” is called reactive power,
and it is measured in a unit called Volt-Amps-Reactive (VAR), rather than watts. The
mathematical symbol for reactive power is (unfortunately) the capital letter Q. The
actual amount of power being used, or dissipated, in a circuit is called true power, and
it is measured in watts (symbolized by the capital letter P, as always). The
combination of reactive power and true power is called apparent power, and it is the
product of a circuit’s voltage and current, without reference to phase angle. Apparent
power is measured in the unit of Volt-Amps (VA) and is symbolized by the capital
letter S.
As a rule, true power is a function of a circuit’s dissipative elements,
usually resistances (R). Reactive power is a function of a circuit’s reactance (X).
Apparent power is a function of a circuit’s total impedance (Z). Since we’re dealing
with scalar quantities for power calculation, any complex starting quantities such as
voltage, current, and impedance must be represented by their polar magnitudes, not
by real or imaginary rectangular components. For instance, if I’m calculating true
power from current and resistance, I must use the polar magnitude for current, and
not merely the “real” or “imaginary” portion of the current. If I’m calculating apparent
power from voltage and impedance, both of these formerly complex quantities must
be reduced to their polar magnitudes for the scalar arithmetic.
There are several power equations relating the three types of power to resistance,
reactance, and impedance (all using scalar quantities):
Please note that there are two equations each for the calculation of true and reactive
power. There are three equations available for the calculation of apparent power,
P=IE being useful only for that purpose. Examine the following circuits and see how
these three types of power interrelate for: a purely resistive load in Figurebelow, a
purely reactive load in Figure below, and a resistive/reactive load in Figure below.
Resistive load only:
True power, reactive power, and apparent power for a purely resistive load.
True power, reactive power, and apparent power for a purely reactive load.
Resistive/reactive load:
True power, reactive power, and apparent power for a resistive/reactive load.
Using the laws of trigonometry, we can solve for the length of any side (amount of any
type of power), given the lengths of the other two sides, or the length of one side and
an angle.
REVIEW:
Power dissipated by a load is referred to as true power. True power is symbolized by the
letter P and is measured in the unit of Watts (W).
Power merely absorbed and returned in load due to its reactive properties is referred to
as reactive power. Reactive power is symbolized by the letter Q and is measured in the
unit of Volt-Amps-Reactive (VAR).
Total power in an AC circuit, both dissipated and absorbed/returned is referred to
as apparent power. Apparent power is symbolized by the letter S and is measured in the
unit of Volt-Amps (VA).
These three types of power are trigonometrically related to one another. In a right
triangle, P = adjacent length, Q = opposite length, and S = hypotenuse length. The
opposite angle is equal to the circuit’s impedance (Z) phase angle.
https://www.allaboutcircuits.com/textbook/alternating-current/chpt-11/true-reactive-and-apparent-
power/
We saw in our tutorial about Electrical Power that AC circuits which contain
resistance and capacitance or resistance and inductance, or both, also
contain real power and reactive power. So in order for us to calculate the total
power consumed, we need to know the phase difference between the
sinusoidal waveforms of the voltage and current.
In an AC circuit, the voltage and current waveforms are sinusoidal so their
amplitudes are constantly changing over time. Since we know that power is
voltage times the current (P = V*I), maximum power will occur when the two
voltage and current waveforms are lined up with each other. That is, their
peaks and zero crossover points occur at the same time. When this happens
the two waveforms are said to be “in-phase”.
The three main components in an AC circuit which can affect the relationship
between the voltage and current waveforms, and therefore their phase
difference, by defining the total impedance of the circuit are the resistor, the
capacitor and the inductor.
The impedance, (Z) of an AC circuit is equivalent to the resistance calculated
in DC circuits, with impedance given in ohms. For AC circuits, impedance is
generally defined as the ratio of the voltage and current phasor’s produced by
a circuit component. Phasor’s are straight lines drawn in such a way as to
represents a voltage or current amplitude by its length and its phase
difference with respect to other phasor lines by its angular position relative to
the other phasor’s.
AC circuits contain both resistance and reactance that are combined together
to give a total impedance (Z) that limits current flow around the circuit. But an
AC circuits impedance is not equal to the algebraic sum of the resistive and
reactive ohmic values as a pure resistance and pure reactance are 90o out-of-
phase with each other. But we can use this 90o phase difference as the sides
of a right angled triangle, called an impedance triangle, with the impedance
being the hypotenuse as determined by Pythagoras theorem.
This geometric relationship between resistance, reactance and impedance
can be represented visually by the use of an impedance triangle as shown.
Impedance Triangle
Note that impedance, which is the vector sum of the resistance and
reactance, has not only a magnitude (Z) but it also has a phase angle (θ),
which represents the phase difference between the resistance and the
reactance. Also note that the triangle will change shape due to variations in
reactance, (X) as the frequency changes. Of course, resistance (R) will
always remain constant.
We can take this idea one step further by converting the impedance triangle
into a power triangle representing the three elements of power in an AC
circuit. Ohms Law tells us that in a DC circuit, power (P), in watts, is equal to
the current squared (I2) times the resistance (R). So we can multiply the three
sides of our impedance triangle above by I2 to obtain the corresponding power
triangle as:
But as their is no phase difference between the voltage and the current in a
resistive circuit, the phase shift between the two waveforms will be zero (0).
Then:
Where real power (P) is in watts, voltage (V) is in rms volts and current (I) is in
rms amperes.
Then real power is the I2R resistive element measured in watts, which is what
you read on your utility energy meter and has units in Watts (W), Kilowatts
(kW), and Megawatts (MW). Note that real power, P is always positive.
Unlike real power (P) which does all the work, reactive power (Q) takes power
away from a circuit due to the creation and reduction of both inductive
magnetic fields and capacitive electrostatic fields, thereby making it harder for
the true power to supply power directly to a circuit or load.
The power stored by an inductor in its magnetic field tries to control the
current, while the power stored by a capacitors electrostatic field tries to
control the voltage. The result is that capacitors “generate” reactive power and
inductors “consume” reactive power. This means that they both consume and
return power to the source so none of the real power is consumed.
To find reactive power, the rms voltage and current values are multiplied by
the sine of the phase angle, θ as shown.
As there is a 90o phase difference between the voltage and the current
waveforms in a pure reactance (either inductive or capacitive), multiplying VI
by sinθ gives a vertical component that is 90o out-of-phase with each other,
so:
Where:
P is the I2R or Real power that performs work measured in watts, W
Q is the I2X or Reactive power measured in volt-amperes reactive, VAr
S is the I2Z or Apparent power measured in volt-amperes, VA
θ is the phase angle in degrees. The larger the phase angle, the greater the
reactive power
Cosθ = P/S = W/VA = power factor, p.f.
Sinθ = Q/S = VAr/VA
Tanθ = Q/P = VAr/W
The power factor is calculated as the ratio of the real power to the apparent
power because this ratio equals cosθ.
We said previously that in a pure resistive circuit, the current and voltage
waveforms are in-phase with each other so the real power consumed is the
same as the apparent power as the phase difference is zero degrees (0o). So
the power factor will be:
That is the number of watts consumed is the same as the number of volt-
amperes consumed producing a power factor of 1.0, or 100%. In this case it is
referred to a unity power factor.
We also said above that in a purely reactive circuit, the current and voltage
waveforms are out-of-phase with each other by 90o. As the phase difference is
ninety degrees (90o), the power factor will be:
That is the number of watts consumed is zero but there is still a voltage and
current supplying the reactive load. Clearly then reducing the reactive VAr
component of the power triangle will cause θ to reduce improving the power
factor towards one, unity. It is also desirable to have a high power factor as
this makes the most efficient use of the circuit delivering current to a load.
Then we can write the relationship between the real power, the apparent
power and the circuits power factor as:
An inductive circuit where the current “lags” the voltage (ELI) is said to have a
lagging power factor, and a capacitive circuit where the current “leads” the
voltage (ICE) is said to have a leading power factor.
The apparent power is the vector sum of real and reactive power
Engineers use the following terms to describe energy flow in a system (and assign each of them a different unit to
differentiate between them):
In the diagram, P is the real power, Q is the reactive power (in this case negative), S is the complex power and the
length of S is the apparent power.
The unit for all forms of power is the watt (symbol: W). However, this unit is generally reserved for the real power
component. Apparent power is conventionally expressed in volt-amperes (VA) since it is the simple product of rms
voltage and rms current. The unit for reactive power is given the special name "VAR", which stands for volt-amperes
reactive (since reactive power flow transfers no net energy to the load, it is sometimes called "wattless" power). Note
that it does not make sense to assign a single unit to complex power because it is a complex number and it is
therefore defined as a pair of two units: W and VAR.
Understanding the relationship between these three quantities lies at the heart of understanding power engineering.
The mathematical relationship among them can be represented by vectors or expressed using complex numbers,
(where j is the imaginary unit).
Consider an ideal alternating current (AC) circuit consisting of a source and a generalized load, where both the
current and voltage are sinusoidal. If the load is purely resistive, the two quantities reverse their polarity at the same
time, the direction of energy flow does not reverse, and only real power flows. If the load is purely reactive, then the
voltage and current are 90 degrees out of phase and there is no net power flow. This energy flowing backwards and
forwards is known as reactive power.
If a capacitor and an inductor are placed in parallel, then the currents flowing through the inductor and the capacitor
oppose and tend to cancel out rather than adding. Conventionally, capacitors are considered to generate reactive
power and inductors to consume it. This is the fundamental mechanism for controlling the power factor in electric
power transmission; capacitors (or inductors) are inserted in a circuit to partially cancel reactive power of the load. A
practical load will have resistive, inductive, and capacitive parts, and so both real and reactive power will flow to the
load.
The apparent power is the product of voltage and current. Apparent power is handy for sizing of equipment or wiring.
However, adding the apparent power for two loads will not accurately give the total apparent power unless they have
the same displacement between current and voltage.
Power factor:
Power factor measures the efficiency of an AC power system. Power factor is the real power per unit of apparent
power. (pf = Wh/VAh) A power factor of one is perfect, and 99% is good. Where the waveforms are purely sinusoidal,
the power factor is the cosine of the phase angle (φ) between the current and voltage sinusoid waveforms.
Equipment data sheets and nameplates often will abbreviate power factor as "cosφ" for this reason.
Power factor equals 1 when the voltage and current are in phase, and is zero when the current leads or lags the
voltage by 90 degrees. Power factors are usually stated as "leading" or "lagging" to show the sign of the phase angle,
where leading indicates a negative sign. For two systems transmitting the same amount of real power, the system
with the lower power factor will have higher circulating currents due to energy that returns to the source from energy
storage in the load. These higher currents in a practical system will produce higher losses and reduce overall
transmission efficiency. A lower power factor circuit will have a higher apparent power and higher losses for the same
amount of real power transfer.
Purely capacitive circuits cause reactive power with the current waveform leading the voltage wave by 90 degrees,
while purely inductive circuits cause reactive power with the current waveform lagging the voltage waveform by 90
degrees. The result of this is that capacitive and inductive circuit elements tend to cancel each other out.
In power transmission and distribution, significant effort is made to control the reactive power flow. This is typically
done automatically by switching inductors or capacitor banks in and out, by adjusting generator excitation, and by
other means. Electricity retailers may use electricity meters which measure reactive power to financially penalise
customers with low power factor loads. This is particularly relevant to customers operating highly inductive loads such
as motors at water pumping stations.
Intelligent Battery:
Output current depends upon the battery's state. An intelligent charger may monitor the battery's voltage,
temperature and/or time under charge to determine the optimum charge current at that instant. Charging is
terminated when a combination of the voltage, temperature and/or time indicates that the battery is fully charged.
For Ni-Cd and NiMH batteries, the voltage across the battery increases slowly during the charging process, until the
battery is fully charged. After that, the voltage decreases, which indicates to an intelligent charger that the battery is
fully charged. Such chargers are often labeled as a ΔV, or "delta-V," charger, indicating that they monitor the voltage
change.
A typical intelligent charger fast-charges a battery up to about 85% of its maximum capacity in less than an hour, then
switches to trickle charging, which takes several hours to top off the battery to its full capacity.
Volt Amperes:
A volt-ampere in electrical terms, means the amount of apparent power in an alternating current circuit equal to a
current of one ampere at an emf of one volt. It is equivalent to watts for non-reactive circuits.
Hence;
While the volt-ampere and the watt are dimensionally equivalent one may find products rated in both VAs and watts
with different numbers. This is common practice on UPSs (Uninterruptible Power Supplies). The VA rating is the
apparent power that a UPS is capable of producing, while the watt rating is the real power (or true power) it is
capable of producing, as opposed to reactive power. Reactive power arises due to the effects of capacitance and
inductance of components in the load to be powered by the AC circuit. In a purely resistive load (incandescent lights
for example), the apparent power is equal to the true power and the amount of VAs and watts used would be
equivalent. However, in more complex loads, such as computers (which UPSs are intended to power) the apparent
power used (VAs) will be larger than the true power used (watts). The ratio of these two quantities is called the power
factor.
https://www.cableorganizer.com/articles/real-reactive-apparent-power.html
then the current through the power transmission line and load can be found:
where is the RMS or effective value of the current. Note that the
Consider the instantaneous power of the load defined as the product of the voltage
and current:
As shown in the plots below, the instantaneous power can be both positive
(energy consumed by the load) and negative (energy released by the load), and it can
The reactive power is not consumed but converted back and forth
between the energy source and the energy storing (inductive) elements in the
load.
product of and :
which represents the phase difference between the voltage and current in the system,
and the ratio between the real power and the reactive
to deliver the real power to the load with minimum reactive power (thereby
minimum current and power dissipation along the transmission line), it is desirable to
capacitor to cancel the inductive effect in the system, thereby reducing and
increasing . There are two possible ways to do this.
across and are times the voltage across , which is the same as the
source voltage (see this page):
load becomes ,
which could be much higher than the expected source voltage (without
Now the voltage across the inductive load is still the same as the voltage source
To reduce the cost of a large capacitance needed for the phase angle of the load to be
i.e.,
http://fourier.eng.hmc.edu/e84/lectures/ch3/node19.html
Posts: 75
o
Lots of good material on the web, but I've sometimes found it confusing to understand why
reactive power flow to an inductor is considered "positive", but at the same time you hear that
the phase angle of inductor current is lagging (which to my ear sounds "negative"). For
capacitors this is reversed (e.g. negative reactive power flow for leading current). Anyway, I
thought I'd outline a quick overview of how all this fits together.
We begin with a diagram that might be familiar to many. It shows real power flow on the x-axis
and reactive power flow on the y-axis. Since both forward and reverse (positive and negative)
real and reactive power flow is possible, there are four categories (+W/+vars, +W/-vars, -
W/+vars, -W/-vars) that the diagram places in separate quadrants. I've shown it with ABC
clockwise rotation (meaning that increasing angles are increasingly "lagging" which is explained
below).
The circle shows the line etched by a constant value of S at different values of θ (0 to 360
degrees).
The exact same value of S (VA or apparent power) can result in a variety of different P (real) and
Q (reactive) values just by changing the phase angle!
Let's say you just define the voltage reference right now to be 00 and you measure your current
to be θ degrees away from that axis. Depending on which way the angle points (above the x-
axis or below) determines whether the power factor is lagging (consuming vars) or leading
(producing vars), respectively.
Here's a diagram of system with where the current is lagging the voltage by 36.9 deg.
Here's where it gets somewhat tricky... the current is delayed by 36.9 degrees, which might
sound like a "negative" angle, but you can see from the phasor diagram as shown that it actually
is a more positive phase angle.
By the way, in these waveforms the peak voltage and current were both 1. When we calculate
power (whether real or reactive), we use root mean square versions of the signals. Since we
have a two nice sine waves the rms value can be calculated easily from the peak:
Note that sin (-36.90) = - sin (+36.90). This means that moving the phase of the current either
ahead or behind the voltage causes leading (positive) var production or lagging (negative) var
consumption, respectively.
That is not the case for the real power (cosine). Since cos(-36.90) = cos(+36.90) = 0.8 this tells
you that changing PF over this range doesn't affect real power flow over this small range.
The waveform and phasor diagrams show how the same value of S (in these cases it is assume
to be 1) can result in very different values of P (real) or Q (reactive) power.
The phase angle of the current relative to the voltage would need to increase to more than 90
degrees (but less than 270 degrees) in order for the the sign of the real (W or P) term to turn
negative. This makes sense since consider a signal exactly 180 degrees out of phase. 180
degree out of phase current would look like this:
It is by convention among power systems engineers that capacitive circuits "produce" vars and
have leading PF and inductive circuits "consume" vars and have lagging PF. Here's an example
where the current leads the voltage by 135 degrees resulting in negative real power, but positive
reactive power.
In the scheme of things this is totally arbitrary because ideal versions of both components never
"keep" the vars. They store energy during a portion of the half cycle and then return it the
next.
It is just convention to say that the reactive power is "consumed" when it is positive and
"generated" when it is negative. From the diagrams above, negative vars occur when you have
leading power factor.
Maybe then someone asks "why do capacitor circuits result in leading phase angles and inductors
result in lagging phase angles?"
As these phasors rotate (I'll assume clock-wise for ABC rotation, meaning first A, the B, then C
cross the 00 axis as it rotates...), the Ia phase will always cross any arbitrary angle before the Va
phasor "gets there".
Since current "gets there" before the voltage we say the current is leading the voltage.
Here's the "why" that this happens. Capacitors look like short circuits when discharged. For a
moment in time after you apply a non-zero charging current, the voltage is 0 until it begins to
charge up. A voltage of 0, by definition, is a short-circuit. In an ideal short circuit, infinite
current flows but there is no voltage drop. Now, in the physical world that isn't the case, but you
will see current flowing in a capacitor before the voltage changes. How fast that happens
depends on the size of the capacitor and the voltage applied. If you have current
flowing before voltage changes, then that is another way of saying current changes precede (or
lead) voltage changes -- or more simply, current leads the voltage. This can also be described
by looking at the mathematical relationship between current and voltage in a capacitor. Danger
Will Robinson - Differential Equations ahead :
What this says is that for voltage to change instantaneously (dt = 0) you would have to apply
infinite current. Guess that isn't going to happen! So for capacitors, any nominal current will
result in a delayed voltage change, or in the vernacular of speaking about current in relation to
the voltage we say the current leads the voltage.
If the phase angle was reversed, the voltage would cross any arbitrary angle before the current
and we'd say the current lagged the voltage. Here's that phasor diagram:
This is known to be an inductive circuit since with inductors no current flows immediately after a
voltage change is applied across the inductor. Mathematically we write:
According to this equation, for the current in an inductor to change instantaneously (dt = 0)
you would have to apply infinite voltage. That ain't gonna happen either, so the result is that
current can't change instantaneously with a voltage change and we say the current lags the
voltage.
Armed with this fabulous knowledge, we can then attack the problem using our standard trig
equations that show how to solve for unknown values of a right triangle.
If, for example, you know its hypotenuse (S or VA or apparent power) and you have been given
either one other side (kW) or the angle (PF) you're good to go.
W = Wh / h
Q = varh / h
S2 = W2 + Q2
cos-1(W/S) = θ
W = S cos θ
cos θ= W/S
sin-1(Q/S) = θ
Q = S sin θ
sin θ = Q/S
tan θ= sin θ/ cos θ = (Q/S)/(W/S) = Q/W
To help visualize these phase angles, I've attached two Excel spreadsheets that can be used to
create a voltage waveform, then superimpose on the same graph the current waveform. I went
ahead and included the ability to add harmonic currents (which is a topic for a future discussion).
1-phase_harmonics.xls
Allows entering the phase shift as power factor. The spreadsheet will perform the math
to shift the current waveform.
1-phase_harmonics_Phase_shift.xls
Allows entering the phase shift in degrees.
X over R2.xls
Converts PF to X/R and reverse. Calculates Z, %Z, X/R, R, X and L for a given voltage,
desired and current. Useful when creating a simulation and you want to choose an R
and X to limit current to a particular short circuit value at a particular X/R ratio.
phase_angle_diagram_V1_V2.xls
Allows entering the phase shift in degrees and seeing corresponding changes to real,
reactive and apparent power.
https://pps2.com/smf/index.php?topic=33.0
Apparent Power
Apparent Power is the power delivered by a power source to a load like a motor. In almost all real
world situations that use AC, you need to supply more power (Apparent Power) to a device than it
will do work (Real Power).The (vector) difference between the two represents the work done to
overcome the inductive and capacities effects of the load.Apparent Power is measured in units of VA
– Volt-amperes. These are actually Watts but we use the new unit name to reduce confusion. Thus
when you see VA on a data sheet you can reasonably conclude that they are talking about Apparent
Power.Apparent Power is calculated:S(Common symbol for Apparent Power) = Veff / rms x Ieff /
rms – Single Phase Calc
Current phase lags the Voltage Typical – Transformers and motors (wound conductors)
Capacitive Loads
Current phase leads the Voltage Typical – Buried Cables, capacitor banks There is nothing
‘wrong’ with having a power factor that isn’t 1.0.
Index
Requirements of a Balanced 3-Phase Set
Requirements of a Balanced 3-Phase Circuit
Terms and Naming Conventions
Where Does that Come From?
Wyes and Deltas
Y to Conversions
The One-Line Diagram
3-Phase Power
Collection of Important 3-Phase Equations
What to Assume
Unbalanced Circuits
Wattmeters
va = Vm cos ( t + )
vb = Vm cos ( t + - 120o )
vc = Vm cos ( t + - 240o ) = Vm cos ( t + +120o )
Notice that we have assumed (and will continue to assume) positive (abc) phase
sequence, i.e., phase "b" follows 120o behind "a" & phase "c" follows 120o behind
phase "b"
In terms of phasors, we write the same balanced set as follows. Note that the phasors
are in rms, as will be assumed throughout this course.
Va = Vm m
Vb = Vm - 120o
Vc = Vm - 240o = Vm +120o
Thus,
Having a balanced circuit allows for simplified analysis of the 3-phase circuit. In fact,
if the circuit is balanced, we can solve for the voltages, currents, and powers, etc. in
one phase using circuit analysis. The values of the corresponding variables in the
other two phases can be found using some basic equations. This type of solution is
accomplished using a "one-line diagram", which will be discussed later. If the
circuit is not balanced, all three phases should be analyzed in detail.
Figure 3 illustrates a balanced 3-phase circuit and some of the naming conventions to
be used in this course
this .
Line
refers to the "transmission line" or wires that connect the source (supply) to the
load. It may be modeled as a small impedance (actually 3 of them), or even by
just a connecting line.
Neutral
the 4th wire in the 3-phase system. It's where the phases of a Y connection
come together.
Phase Voltages & Phase Currents
the voltages and currents across and through a single branch (phase) of the
circuit. Note this definition depends on whether the connection is Wye or
Delta!
Line Currents
the currents flowing in each of the lines (Ia, Ib, and Ic). This definition does not
change with connection type.
Line Voltages
the voltages between any two of the lines (Vab, Vbc, and Vca). These may also
be referred to as the line-to-line voltages. This definition does not change with
connection type.
Line to Neutral Voltages
the voltages between any lines and the neutral point (Va, Vb, and Vc). This
definition does not change with connection type, but they may not be
physically measureable in a Delta circuit.
Line to Neutral Currents
same as the line currents (Ia, Ib, and Ic).
Vab = Va - Vb = Vm - Vm - 120o
= Vm (1 - (-1/2) + j ( / 2 ) ) = Vm (3 / 2) + j ( / 2 ))
Vab = Va 30o
The relationships between the currents can be developed similarly. Summing currents
at the "A" node in Figure 3 yields the starting equation,
Ia = IAB - ICA
This time choose Ia to be the phasor reference (at 0o). The final result is:
Ia = IAB -30o
These relationships can also be remembered graphically using Figures 4 and 5 below.
Figure 4 illustrates the voltage relationship. By looking at the phasor equation as the
sum of two vectors (Va and -Vb ) we obtain the resulting Vab shown in the figure.
and since Vab is ahead of Va, we know that, . . . . (the angle of Vab) = (the angle of
Va) + 30o
Figure 4: Graphical Voltage Relationship
Figure 5 illustrates the current relationship. Now the phasor equation is the sum of
two vectors (Iab and -Ica ) we obtain the resulting Ia shown in the figure.
|Ia| = |Iab| ,
Y to Conversions
In terms of power, currents & line voltages, the following sources are the same and
may be used interchangably in most cases. Note, the Y connection should be used in a
one-line diagram.
Wye connected source ____ Delta connected source
Similarly, the two loads given below are the same in terms of the resulting power, line
currents and line voltages and can usually be substituted as desired. Note that the Y
connection is the one needed for the one-line diagram!
IN = Ia + Ib + Ic
Why must this be so? Because the sum of a balanced set of 3-phase variables is equal
to zero. This can be verified mathematically using the definition, or visually by
considering using vector addition to add the balanced set in Figure 5.
Because the neutral current is zero, this means that if the neutral in the load is
connected to the neutral in the source, no current will flow. Thus, the voltage at each
of the neutrals must be the same. This means they can be considered to be the same
point.
Now consider the circuit of Figure 12. In general, any circuit with a source, load, and
line configuration can be converted to a circuit of this type by replacing any Delta -
connected sources or loads with the equivalent Wye connected sources or loads.
If the Neutral points in Figure 12 are actually the same point, Figure 12 can be
redrawn as shown in Figure 13.
Figure 13: ReDrawn All-Y Circuit
From this figure we see that each of the phase currents depends only on the source in
the corresponding loop. In other words,
Recall that in balanced set of variables, once we know one variable, the other two can
be found by simply adding and subtracting 120o. Thus, we only need to consider and
solve one loop of Figure 13 --- this is the one-line diagram!
Figure 14 shows the one-line diagram for the circuit of Figure 13. Usually the one line
that is considered is the "a" phase. The "b" phase quantities are then found by
subtracting 120o, and the "c" phase quantities are found by adding 120o.
3-Phase Power
The 3-phase (3 ) power of a circuit is simply the sum of the power in the three
individual phases. Thus for a Wye circuit, the equation is
S3 = Sa + Sb + Sc
Another adavantage of having a balanced circuit is that each phase has the same
power. That is,
S3 = 3 S = 3 Sab = 3 Sa
Just in case you didn't know, right now you should be thinking "This is very
cool!"
We can do some interesting rearrangements to get the power in terms of the line
voltage (Vab) and line current (Ia) only.
Note:
In balanced systems, all the S 's and S3 have the same power factor (pf) and
thus the same power factor angle = impedance angle = .
What to Assume
If you are given a voltage, current, or power value and not told specifically which
variable it is, you should assume that you have been given a "line" value. That is,
assume the following:
Voltage => Line voltage = |Vab|
Current => Line current = |Ia|
Power => Three Phase Power = S3 , P3 , or Q3
Unbalanced Circuits
When we have an unbalanced circuit, we CANNOT use the one-line diagram to solve
for "a" phase values and then get the answers for the other phases by adding or
subtracting 120o.
In general, a unbalanced three-phase circuit requires that you draw the complete
circuit including all 3-phase and single-phase loads and perform a circuit analysis of
the whole thing. Normal methods such as "meshes" or "node voltages" may be used.
If you have the simple case in which a balanced 3-phase load is connected directly to
a source and a single phase load is connected in parallel to the same source, you may
calculate the currents in the balanced load using a one-line method. The single phase
current is calculated separately and then individual line currents can be found by
summing the currents at certain nodes in the system.
Remember any circuit that does not have all loads with the same impedance in all
three branches is an unbalanced circuit.
Wattmeters
The schematic for a wattmeter is given in Figure 15 below. Note that in order to
measure power, we need to measure a current and a voltage. The wattmeter doesn't
care which current or which voltage you use. It will give you a reading regardless of
whether or not it means anything. It is up to the user (you) to make sure the meter is
sensing the correct voltage and current to give a meaningful measurement!
Figure 15: The Basic Wattmeter
Under balanced conditions and conditions in which there are only three wires in the
system, we can measure the power in all three phases of a load (or source) by using
only two meters. This is called the "Two Wattmeter Method."
This method is quite convenient when all you have access to are the three wires going
into a three-phase motor (for example). You want to measure P3 , where do you
connect your meter?
connect the positive terminals of the voltage coils to the same two phases
(where you're measuring the current)
Figures 16 and 17 below show two possible connections with phases "b" and "c"
respectively, used as the voltage reference. Note that the "plus-minus" symbol marks
the positive voltage terminal & the negative terminal is generally unmarked.
similarly, for the balanced condition, the magnitude three phase reactive power can be
found using . . . |Q3 | = |W1 - W2|
the sign of Q may vary depending on how the wattmeters are connected. So, it is
generally safer to determine the sign using other means.
Shelli Starrett
starret@eece.ksu.edu
http://www.ece.k-state.edu//~starret/581/3phase.html
required. In delta
connection, the line voltage is same with that of phase voltage. And the line
current is √3 times of phase current. It is shown as expression below,
In three phase circuit, star and delta
connection can be arranged in four different ways-
1. Star-Star connection
2. Star-Delta connection
3. Delta-Star connection
4. Delta-Delta connection
But the power is independent of the circuit arrangement of the three phase
system. The net power in the circuit will be same in both star and delta
connection. The power in three phase circuit can be calculated from the
equation below, Since, there is three phases,
so the multiple of 3 is made in the normal power equation and the PF is power
factor. Power factor is a very important factor in three phase system and some
times due to certain error, it is corrected by using capacitors.
https://www.electrical4u.com/three-phase-circuit-star-and-delta-system/
The three conductors leading away from the voltage sources (windings) toward a load
are typically called lines, while the windings themselves are typically called phases. In
a Y-connected system, there may or may not (Figure below) be a neutral wire
attached at the junction point in the middle, although it certainly helps alleviate
potential problems should one element of a three-phase load fail open, as discussed
earlier.
Three-phase, three-wire “Y” connection does not use the neutral wire.
However, the “Y” configuration is not the only valid one for connecting three-phase
voltage source or load elements together. Another configuration is known as the
“Delta,” for its geometric resemblance to the Greek letter of the same name (Δ). Take
close notice of the polarity for each winding in Figure below.
Three-phase, three-wire Δ connection has no common.
At first glance it seems as though three voltage sources like this would create a short-
circuit, electrons flowing around the triangle with nothing but the internal impedance of
the windings to hold them back. Due to the phase angles of these three voltage
sources, however, this is not the case.
One quick check of this is to use Kirchhoff’s Voltage Law to see if the three voltages
around the loop add up to zero. If they do, then there will be no voltage available to
push current around and around that loop, and consequently, there will be no
circulating current. Starting with the top winding and progressing counter-clockwise,
our KVL expression looks something like this:
Indeed, if we add these three vector quantities together, they do add up to zero.
Another way to verify the fact that these three voltage sources can be connected
together in a loop without resulting in circulating currents is to open up the loop at one
junction point and calculate voltage across the break: (Figure below)
Voltage across open Δ should be zero.
Starting with the right winding (120 V ∠ 120o) and progressing counter-clockwise, our
KVL equation looks like this:
Sure enough, there will be zero voltage across the break, telling us that no current will
circulate within the triangular loop of windings when that connection is made
complete.
Having established that a Δ-connected three-phase voltage source will not burn itself
to a crisp due to circulating currents, we turn to its practical use as a source of power
in three-phase circuits. Because each pair of line conductors is connected directly
across a single winding in a Δ circuit, the line voltage will be equal to the phase
voltage. Conversely, because each line conductor attaches at a node between two
windings, the line current will be the vector sum of the two joining phase currents. Not
surprisingly, the resulting equations for a Δ configuration are as follows:
Let’s see how this works in an example circuit: (Figure below)
With each load resistance receiving 120 volts from its respective phase winding at the
source, the current in each phase of this circuit will be 83.33 amps:
So each line current in this three-phase power system is equal to 144.34 amps, which
is substantially more than the line currents in the Y-connected system we looked at
earlier. One might wonder if we’ve lost all the advantages of three-phase power here,
given the fact that we have such greater conductor currents, necessitating thicker,
more costly wire. The answer is no. Although this circuit would require three number 1
gage copper conductors (at 1000 feet of distance between source and load this
equates to a little over 750 pounds of copper for the whole system), it is still less than
the 1000+ pounds of copper required for a single-phase system delivering the same
power (30 kW) at the same voltage (120 volts conductor-to-conductor).
One distinct advantage of a Δ-connected system is its lack of a neutral wire. With a Y-
connected system, a neutral wire was needed in case one of the phase loads were to
fail open (or be turned off), in order to keep the phase voltages at the load from
changing. This is not necessary (or even possible!) in a Δ-connected circuit. With
each load phase element directly connected across a respective source phase
winding, the phase voltage will be constant regardless of open failures in the load
elements.
Perhaps the greatest advantage of the Δ-connected source is its fault tolerance. It is
possible for one of the windings in a Δ-connected three-phase source to fail open
(Figure below) without affecting load voltage or current!
Even with a source winding failure, the line voltage is still 120 V, and load phase
voltage is still 120 V. The only difference is extra current in the remaining functional
source windings.
The only consequence of a source winding failing open for a Δ-connected source is
increased phase current in the remaining windings. Compare this fault tolerance with
a Y-connected system suffering an open source winding in Figure below.
Open “Y” source winding halves the voltage on two loads of a Δ connected load.
With a Δ-connected load, two of the resistances suffer reduced voltage while one
remains at the original line voltage, 208. A Y-connected load suffers an even worse
fate (Figure below) with the same winding failure in a Y-connected source
Open source winding of a “Y-Y” system halves the voltage on two loads, and looses
one load entirely.
In this case, two load resistances suffer reduced voltage while the third loses supply
voltage completely! For this reason, Δ-connected sources are preferred for reliability.
However, if dual voltages are needed (e.g. 120/208) or preferred for lower line
currents, Y-connected systems are the configuration of choice.
REVIEW:
The conductors connected to the three points of a three-phase source or load are
called lines.
The three components comprising a three-phase source or load are called phases.
Line voltage is the voltage measured between any two lines in a three-phase circuit.
Phase voltage is the voltage measured across a single component in a three-phase
source or load.
Line current is the current through any one line between a three-phase source and load.
Phase current is the current through any one component comprising a three-phase
source or load.
In balanced “Y” circuits, line voltage is equal to phase voltage times the square root of 3,
while line current is equal to phase current.
In balanced Δ circuits, line voltage is equal to phase voltage, while line current is equal
to phase current times the square root of 3.
Δ-connected three-phase voltage sources give greater reliability in the event of winding
failure than Y-connected sources. However, Y-connected sources can deliver the same
amount of power with less line current than Δ-connected sources.
https://www.allaboutcircuits.com/textbook/alternating-current/chpt-10/three-phase-y-delta-
configurations/
While 3-phase power allows utilities to deliver more power over smaller, less expensive
wires, there are more compelling reasons for using three-phase in the data center—
specifically 3-phase Wye.
Why 3-Phase?
To understand electric power in the data center, you need to first understand single-
and 3-phase power distribution. Most homes are wired with single-phase that uses one
ac voltage delivered over two hot wires and one neutral wire. The voltage across the
two hot wires measures 240VAC (for your oven or dryer) and across any hot to neutral
measures 120VAC (for everything else).
Most commercial businesses are wired with 3-phase that consists of three ac voltages
separated from each other by 120 electrical degrees, or by a third of a cycle. These
systems deliver power over three hot wires where the voltage across any two hot wires
measures 208VAC.
Another
way to
look at 3-
phase
power is
as a
combinati
on of
three
single-
phase
circuits
that
deliver
power in a
way that it
never falls
to zero,
meaning
that the
load is the
same at any instant (the concept is easy to grasp when you look at the waveform).
Because the load is constant, 3-phase power is ideal for motors—it eliminates the need
for starting capacitors. It also allows for smaller wires (i.e., less copper) and lower
voltages for the same power transmission as single-phase, making it less expensive
and safer.
Why Wye?
There are two types of circuits used to maintain equal load across the three hot wires in
a 3-phase system—Delta and Wye. The Delta configuration has the three phases
connected like a triangle, whereas the Wye (or “star”) configuration has all three loads
connected at a single neutral point.
Delta systems have four wires—three hot and one ground. Wye systems have five
wires—three hot, one neutral and one ground. While both Delta and Wye systems
measure 208VAC between any two hot wires, Wye systems also measure 120VAC
between any hot wire and neutral. In other words, it’s the neutral wire of the Wye
system that allows for providing two different voltages and powering both 3-phase and
single-phase devices in the data center.
That’s not to say that Delta doesn’t have its place—we mainly see Delta used for any
large motors or heaters that don’t need a neutral. Delta is also used in power
transmission because it’s expensive to run a fourth neutral wire all those miles. That’s
why distribution transformers are wired as Delta-Wye. This creates the neutral that
allows the transformer to deliver power for single-phase loads.
Delta-wired devices can also be fed from a Wye source by simply omitting the neutral. That
means that in a data center, a Delta power distribution unit (PDU) can be used when there is
only a need for 208VAC, while Wye PDUs are used when there is a need for both 120VAC and
208VAC.
Many of today’s larger blade servers only accept 208VAC because their power
requirements can’t be met with 120VAC. However, most data centers still need the
flexibility of also being able to power 120VAC devices. So now you know why 3-phase
Wye power distribution is the best option for today’s data center.
Belden’s wide range of three-phase rack-mounted and vertical PDUs available in both
Delta and Wye configurations to accommodate a broad range of electrical
characteristics, outlet requirements, plug and receptacle styles, and remote monitoring
and management.
https://www.belden.com/blog/data-centers/3-phase-power-wye-it-matters
In mechanical power, many terms describe the pressure or force (Foot Pounds, Pounds per Square Inch, etc.) and many terms
describe the speed or flow (Rotating Speed, Gallons per Minute, etc.). In electric power, one term describes the pressure or force
(Voltage) and two terms describe the speed or flow (Current and Amperes).
In the earliest days Direct Current (DC), where the power flows in one direction like a water hose, was the standard for delivering
electrical power. Now Alternating Current (AC), where the power flow is constantly alternating direction, is the standard for
delivering electrical power.
The standard for delivering electrical power changed from Direct Current (DC) to Alternating Current (AC) because Alternating
Current (AC) delivers electrical power more efficiently over long distances.
In the US, 60 Hertz (cycles per second) is the Alternating Current (AC) frequency.
In some countries, 50 Hertz (cycles per second) is the Alternating Current (AC) frequency.
What is 1 (Single) Phase Power ?
If you’re not electrically minded, think of 1 (Single) phase power like a bicycle where only one leg (phase) is pushing
on one pedal rotating around a crankshaft axis (neutral).
1. Mechanically, power is calculated as leg pressure (Foot Pounds) times speed (Rotating Speed).
2. Electrically, power is calculated as leg force (Voltage) times flow (Current).
Single Phase power is a two wire Alternating Current (AC) power circuit. Most people use it every day because it’s the most
common household power circuit and powers their lights, TV, etc. Typically there’s one power wire and one neutral wire and
power flows between the power wire (through the load) and the neutral wire.
In the US, 120V is the standard single phase voltage with one 120V power wire and one neutral wire.
In some countries, 230V is the standard single phase voltage with one 230V power wire and one neutral wire.
If you’re not electrically minded, think of 2 (Dual / Split) phase power like a bicycle where one leg (phase) can push
on one pedal, or both legs (phases) can push on both pedals (180 degrees out of phase with one another) rotating around
a crankshaft axis (neutral).
1. Mechanically, power is calculated as leg pressure (Foot Pounds) times speed (Rotating Speed).
2. Electrically, power is calculated as leg force (Voltage) times flow (Current).
Dual Phase or Split Phase power is also Single Phase because it’s a two wire Alternating Current (AC ) power circuit. In the US,
this is the standard household power arrangement with two (Phase A, Phase B) 120V power wires (180 degrees out of phase with
one another) like two bicycle pedals and one neutral wire. This arrangement is used in most US households because of its
flexibility.
Low power loads (lights, TV, etc.) powered using either either of (2) 120V power circuits
High power loads (Water Heaters, AC Compressors) powered using (1) 240V power circuit
What is 3 (Three) Phase Power ?
If you’re not electrically minded, think of 3 (Three) phase power like a three cylinder engine where three pistons
(phases) located (120 degrees out of phase with one another) push rotating around a crankshaft axis (neutral).
Low power loads (Lights, etc.) powered using any of (3) 120V single phase power power circuits
Medium power loads (Water Heaters, etc.) powered using any of (3) 208V single phase power circuits
High power loads (HVAC Systems, etc.) powered using (1) 208V three phase power circuit
Most US industrial facilities use a 3 Phase 4 Wire 480Y/277V power arrangement because of its power density.
Compared to 208V 3 Phase, 480V 3 Phase provides 2.3 (480 /208) times more power with the same current or 43%
(208/480) less current with the same power. This yields additional benefits.
Reduced construction costs with smaller electrical service, wiring, conduits, and electrical devices.
Reduced energy costs will less energy lost as electrical current resistance (converted to heat).
http://www.oempanels.com/what-does-single-and-three-phase-power-mean