NETWORK DATA
FAULT LEVEL AT 11 KV BUS OF Exist.RHBPRY4 (33/11KV)
Three phase max fault current: 11.96 KA
Single phase max fault current: 14.14 KA
Transformer data
Transformer capacity : 1.5MVA
Vector group : Dyn11
Voltage Rating : 11/0.415KV
Positivesequence : 6.00%
Zero sequence impedance : Same as positive sequence
CT ratio 100/1
Relay type FANOX- SIAC
1500 kVA TRANSFORMER
Selection of plug setting of Pick up of over current is selected at 120% of over load of
Over current relay for IDMT transformer i.e. (120*78.73)/100 which is equal to 94.47 amp.
element Therefore selected plug setting = 94.47/CT ratio
= 94.47/100
= 0.944
2 of 4
Selection of TMS Desired TMS = Desired op time /op time for 1 TMS
Desired op time = op time for over current relay at HV side should be coordinated
with LV protection . To have sec operation time for LV fault ,TMS will be calculated .
LV 3 phase fault = 35310.9 amp
Reflected fault at 11 KV side=1332 AMP
PSM for 1332 AMP current= 1332/94.47=14.09
Operating time = {.14/(If/Is)^.02-1)}
= {.14/(14.09)^.02-1)}
= 2.57sec
Therefore,
Desired TMS = 1/2.57 =0.39
Selected TMS = .4
SBEF Relay
CT ratio 1000/1
Relay type FANOX- SIAC
Selection of plug setting of Pick up of over current is selected at 20% CT rated current
Overcurrent relay for IDMT i. e 0.2 *In. =0.2*2086.81=417.36
element Therefore selected plug setting = 417.36/CT Ratio=417.36/1000
=0.4
3 of 4
Selected curve IEC EI
Selection of TMS Transformer of Dyn11 earth fault relay need not be coordinated with
earth fault protection at LV side .
Therefore selected op time = 0.8
Selection of pick up of Over current earth Disabled
fault relay for instantaneous element