TEST REPORT FOR REL511

Sub Station ATPS Serial No.


Bay Name AMK-WAIDHAN Rating 110V, 1A AC
Ref Drawing RETROFIT Aux Supply 220V DC

Physical Inspection Mounting and Wiring


Mechanical Condition

Secondary Injection Test: ZFB Test Kit


Line Conductor +ve seq. Imp : Line Conductor -ve seq. Imp :
0.0804+j*0.3999 0.299+j*1.246

ZONE 1 Test Results


Fault Expected Optd Calucalation Settings on Test Kit
Value in % Value in %
RN 68 X1 15.148 CTR = 5
SN 22.15 68 X0 51.362 X= 8
TN 68 R1 6.109 R= 14
RS 79 z relay 16.333 Z box = 26.5
ST 24.65 79 Kn 0.797
TR 79

ZONE 2 Test Results


Fault Expected Optd Calucalation Settings on Test Kit
Value in % Value in %
RN 60 X1 22.722 CTR = 5
SN 33.15 60 X0 77.043 X= 8
TN 60 R1 9.163 R= 14
RS 54 z relay 24.500 Z box = 26.56
ST 36.90 54 Kn 0.797
TR 54

ZONE 3 Test Results


Fault Expected Optd Calucalation Settings on Test Kit
Value in % Value in %
RN 48 X1 37.87 CTR = 5
SN 55.38 48 X0 128.405 X= 8
TN 48 R1 15.272 R= 14
RS 57 z relay 40.833 Z box = 26.5
ST 61.64 57 Kn 0.797
TR 57
ZONE 4 Test Results
Fault Expected Optd Calucalation Settings on Test Kit
Value in % Value in %
RN 70 X1 3.07 CTR = 2.5
SN 72.10 70 X0 9.56 X= 4
TN 70 R1 0.61 R= 1
RS 82 z relay 3.130 Z box = 2.96
ST 84.60 82 Kn 0.705
TR 82

FAULT LOCATOR Test Results


Sl.No. Expected Optd Calucalation Settings on Test Kit
Value in % Value in % Apply %age V as below
1 Ph-E 40% 8.860217595 CTR = 5
2 Ph-ph 40% 9.8617092848 X= 8
3 Ph-E 25% 5.5376359969 R= 14
4 Ph-Ph 25% 6.163568303 Z box = 26.5
5 Ph-E 95% 26.5204037039 Keep settings as
6 Ph-Ph 85% 25.8283100904 zone 2

Other Checks

1. Fuse failure function =

2. Switch On to Fault =

3. Broken Conductor Check =

4. Auto recloser function =

5. Tripping out puts =

6. Scheme Check =

Tested By Witnessed By

Name

Sign