You are on page 1of 112

4010ES

Fire Alarm System

Installation
Guide

579-989
Rev. G
Copyrights, Trademarks, Cautions, Warnings and Regulatory Info

Copyrights and ©2011 - 2013 Tyco Fire Protection Products. All rights reserved.
Trademarks
Specifications and other information shown were current as of publication and are subject to
change without notice. TYCO, SIMPLEX, and the product names listed in this material are
marks and/or registered marks. Unauthorized use is strictly prohibited.

Cautions, READ AND SAVE THESE INSTRUCTIONS- Follow the instructions in this installation
Warnings and manual. These instructions must be followed to avoid damage to this product and associated
Regulatory equipment. Product operation and reliability depend upon proper installation.
Information

DO NOT INSTALL ANY SIMPLEX® PRODUCT THAT APPEARS DAMAGED- Upon


unpacking your Simplex product, inspect the contents of the carton for shipping damage. If
damage is apparent, immediately file a claim with the carrier and notify an authorized Simplex
product supplier.

ELECTRICAL HAZARD - Disconnect electrical field power when making any internal adjust-
ments or repairs. All repairs should be performed by a representative or authorized agent of
your local Simplex product supplier.

STATIC HAZARD - Static electricity can damage components. Handle as follows:


• Ground yourself before opening or installing components.
• Prior to installation, keep components wrapped in anti-static material at all times.

EYE SAFETY HAZARD - Under certain fiber optic application conditions, the optical output of
this device may exceed eye safety limits. Do not use magnification (such as a microscope or
other focusing equipment) when viewing the output of this device.

FCC RULES AND REGULATIONS – PART 15 - This equipment has been tested and found to
comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful interference when the
equipment is operated in a commercial environment. This equipment generates, uses, and can
radiate radio frequency energy and, if not installed and used in accordance with the instruction
manual, may cause harmful interference to radio communications. Operation of this equipment
in a residential area is likely to cause harmful interference in which case the user will be
required to correct the interference at his own expense.

SYSTEM REACCEPTANCE TEST AFTER SOFTWARE CHANGES - To ensure proper system


operation, this product must be tested in accordance with NFPA 72® after any programming
operation or change in site-specific software. Re-acceptance testing is required after any
change, addition or deletion of system components, or after any modification, repair or
adjustment to system hardware or wiring.

All components, circuits, system operations, or software functions, known to be affected by a


change must be 100% tested. In addition, to ensure that other operations are not inadvertently
affected, at least 10% of initiating devices that are not directly affected by the change, up to a
maximum of 50 devices, must also be tested and proper system operation verified.

NFPA 72® is a registered trademark of the National Fire Protection Association.

iii
Table of Contents

Copyrights, Trademarks, Cautions, Warnings and Regulatory Info............................. iii


Copyrights and Trademarks ................................................................................................... iii
Cautions, Warnings and Regulatory Information ................................................................... iii

Chapter 1 Overview ........................................................................................... 1-1


Introduction ..........................................................................................................................1-1
In this chapter ......................................................................................................................1-1
Standalone Configuration ............................................................................................... 1-2
Overview ..............................................................................................................................1-2
Standalone System Layout ..................................................................................................1-2
Network Configuration .................................................................................................... 1-3
Overview ..............................................................................................................................1-3
Connecting Network Loops ..................................................................................................1-4
Network Communication ......................................................................................................1-4

Chapter 2 Basic Hardware ................................................................................ 2-1


Introduction ..........................................................................................................................2-1
In this chapter ......................................................................................................................2-1
CPU ................................................................................................................................... 2-2
Overview ..............................................................................................................................2-2
CPU LEDs ............................................................................................................................2-3
CPU Jumper Settings ..........................................................................................................2-5
CPU Switches ......................................................................................................................2-6
CPU Connectors/Ports/Terminal Block ................................................................................2-6
CPU Card Specifications .....................................................................................................2-7
Operator Interface ........................................................................................................... 2-8
Overview ..............................................................................................................................2-8
Main System Supply (MSS) ............................................................................................. 2-9
Overview ..............................................................................................................................2-9
MSS LEDs and Jumpers ....................................................................................................2-11
MSS Specifications ............................................................................................................2-12
48-LED Module ............................................................................................................... 2-14
Overview ............................................................................................................................2-14
48-LED Module Specifications ...........................................................................................2-15
System Power ................................................................................................................ 2-16
Main System Power ...........................................................................................................2-16
Backup Batteries ................................................................................................................2-16

Chapter 3 Panel Configurations ....................................................................... 3-1


Introduction ..........................................................................................................................3-1
In this chapter ......................................................................................................................3-1
One-Bay 4010ES Panels ................................................................................................. 3-2
Overview ..............................................................................................................................3-2
Optional Modules .................................................................................................................3-4
Back Box Mechanical Specifications ...................................................................................3-5
Two-Bay 4010ES Panels ................................................................................................. 3-6
Overview ..............................................................................................................................3-6
Optional Modules .................................................................................................................3-9
Back Box Mechanical Specifications ...................................................................................3-9

v
Table of Contents

Chapter 4 Orderable Panels and Devices ........................................................ 4-1


Introduction ..........................................................................................................................4-1
In this chapter ......................................................................................................................4-1
Panels ............................................................................................................................... 4-2
One-Bay 4010ES Panels .....................................................................................................4-2
Two-Bay 4010ES Panels .....................................................................................................4-2
Optional Modules ............................................................................................................ 4-3
Local Optional Modules .......................................................................................................4-3
Remote Devices ...................................................................................................................4-4
Adjunct Features ..................................................................................................................4-5
End User Programming Tools ..............................................................................................4-5
LED Kits for the 48-LED Module ..........................................................................................4-5

Chapter 5 Installing 4010ES Systems .............................................................. 5-1


Introduction ..........................................................................................................................5-1
In this chapter ......................................................................................................................5-1
Mounting the Panel ......................................................................................................... 5-2
Installing the Back Box .........................................................................................................5-2
Attaching the Dead Front .....................................................................................................5-3
Attaching Doors ...................................................................................................................5-4
General Field Wiring Guidelines .................................................................................... 5-5
Power-Limited Guidelines ....................................................................................................5-5
Connecting 4010ES Basic Components ........................................................................ 5-7
Connecting the CPU and the Operator Interface .................................................................5-7
Connecting the MSS ............................................................................................................5-9
Connecting the 48-LED Module .........................................................................................5-10
RUI Wiring ...................................................................................................................... 5-11
Overview ............................................................................................................................5-11
Installing the Optional Modules ................................................................................... 5-13
Overview ............................................................................................................................5-13
Installing One-Block and Two-Block Cards ........................................................................5-13
Address Configuration DIP Switch .............................................................................. 5-14
Overview ............................................................................................................................5-14
Connecting Main System Power .................................................................................. 5-16
Overview ............................................................................................................................5-16
Panel Power-up Sequence ................................................................................................5-16

Chapter 6 MSS Field Wiring ............................................................................. 6-1


Introduction ..........................................................................................................................6-1
In this chapter ......................................................................................................................6-1
Power Supply Wiring Distances ..................................................................................... 6-2
Overview ..............................................................................................................................6-2
Class A NAC Wiring Table ...................................................................................................6-2
Class B NAC Wiring Table ...................................................................................................6-3
MSS NAC Field Wiring Guidelines ................................................................................. 6-4
Guidelines ............................................................................................................................6-4
MSS NAC Wiring .............................................................................................................. 6-5
Class A NAC Wiring .............................................................................................................6-5
Class B NAC Wiring .............................................................................................................6-6
vi
Table of Contents

MSS IDNet Wiring ............................................................................................................ 6-7


Overview ..............................................................................................................................6-7
Wiring Parameters ...............................................................................................................6-7
Class A Wiring .....................................................................................................................6-8
Class B Wiring .....................................................................................................................6-9
MSS Auxiliary Power Wiring ......................................................................................... 6-10
Guidelines ..........................................................................................................................6-10
Wiring .................................................................................................................................6-11
MSS Auxiliary Relay Wiring .......................................................................................... 6-12
Guidelines ..........................................................................................................................6-12
Wiring .................................................................................................................................6-12

Chapter 7 PC Software Connections ............................................................... 7-1


Introduction ..........................................................................................................................7-1
In this chapter ......................................................................................................................7-1
Software Modes ............................................................................................................... 7-2
Software Modes ...................................................................................................................7-2
Ethernet Service Port ...................................................................................................... 7-4
Ethernet Service Port Overview ...........................................................................................7-4

Chapter 8 System Wiring Checkout and Earth Fault Diagnostics ................ 8-1
Introduction ..........................................................................................................................8-1
In this chapter ......................................................................................................................8-1
Checking System Wiring ................................................................................................ 8-2
Overview ..............................................................................................................................8-2
Using the Multimeter ............................................................................................................8-2
Meter Readings ....................................................................................................................8-3
Earth Fault Diagnostics .................................................................................................. 8-4
Overview ..............................................................................................................................8-4
General Guidelines ..............................................................................................................8-4
Earth Fault Searching from the Front Panel ................................................................. 8-6
Overview ..............................................................................................................................8-6
Access Level Selection ........................................................................................................8-6
Starting the Earth Fault Search ............................................................................................8-6
Search Option A: Select Location ........................................................................................8-7
Search Option B: Select Location ........................................................................................8-7
Search Option C: Last Search Result ..................................................................................8-8
Completing the Search ........................................................................................................8-8
Earth Fault Search Results ............................................................................................. 8-9
Overview ..............................................................................................................................8-9
Non-Point Faults ..................................................................................................................8-9
Point Faults ..........................................................................................................................8-9
Fault Not Found .................................................................................................................8-10
No Fault .............................................................................................................................8-10
Result Not Available ...........................................................................................................8-10

Chapter A ULC Programming Requirements ..................................................A-1


Introduction ......................................................................................................................... A-1
In this chapter ..................................................................................................................... A-1

vii
Table of Contents

Common Earth Fault Ground Indicator ........................................................................ A-2


Overview ............................................................................................................................. A-2
Step 1. Open CPU Card Properties Dialog ......................................................................... A-2
Step 2. Program the LED .................................................................................................... A-3
Simultaneous Alarm Display ......................................................................................... A-4
Overview ............................................................................................................................. A-4
Creating Annunciation Zone Lists ....................................................................................... A-4
Programming the Address and Mode for Each LED ........................................................... A-5
Setting Alarm Verification Timer to Canadian Operation ........................................... A-7
Introduction ......................................................................................................................... A-7
Procedure ........................................................................................................................... A-7
Setting Alarm Reset / Inhibit Timer ............................................................................... A-8
Overview ............................................................................................................................. A-8
Enabling Alarm Reset/Inhibit Timer .................................................................................... A-8
Alarm Cutout Timer ........................................................................................................ A-9
Overview ............................................................................................................................. A-9
Enabling Alarm Cutout Timer .............................................................................................. A-9

Chapter B UL Programming Requirements .....................................................B-1


Introduction ......................................................................................................................... B-1
In this chapter ..................................................................................................................... B-1
Setting Alarm Verification to US Operation ................................................................. B-2
Overview ............................................................................................................................. B-2
Procedure ........................................................................................................................... B-2
Alarm Cutout Timer ........................................................................................................ B-3
Overview ............................................................................................................................. B-3
Enabling Alarm Cutout Timer .............................................................................................. B-3
Non-Steady Visual Evacuation System Option ............................................................ B-4
Overview ............................................................................................................................. B-4

Chapter C Simplex Special Application NAC-Compatible


Notification Appliances and Accessories .......................................................C-1

Chapter D Cooper Wheelock Appliances Compatible


With 4010ES Wheelock Protocol For Special Applications ...........................D-1
Overview ............................................................................................................................. D-1
Synchronizing Horn Strobes ............................................................................................... D-1
Synchronizing Strobes ........................................................................................................ D-2
Appliances with Synchronizing Strobes .............................................................................. D-3
Synchronizing Horns ........................................................................................................... D-4
Coded Audible Appliances .................................................................................................. D-5
Non-Synchronizing Appliances ........................................................................................... D-5

viii
Chapter 1
Overview
Introduction The 4010ES panel is an expandable fire alarm panel that can be used either as a standalone
system or can be networked with other 4100, 4010, 4100U, 4100ES and 4010ES panels. It
comes with basic system components already installed. This chapter provides an overview of
the standalone and network 4010ES panel concepts:
Standalone. Comprised of one 4010ES FACP and its assorted notification appliances,
initiating devices, and signaling line circuit devices.
Network. Multi-FACP systems connected by 4120 network cards. Each panel maintains the
status and control of its own circuit points while monitoring and controlling activity at other
locations. Network nodes may perform similar tasks, or may be dedicated to specific
functions.

In this chapter This chapter covers the following topics:

Topic Page

Standalone Configuration 1-2

Network Configuration 1-3

1-1
Standalone Configuration

Overview The standalone version of the 4010ES is used for smaller or single-building applications. A
standalone system is ideally placed into a small building that requires a limited number of
notification appliances and initiating devices.
If a small building is being expanded, or if other buildings are being constructed in the same
general area (as in a campus application), the standalone 4010ES can be upgraded to a network
system and linked with other 4010, 4100, 4100U, 4100ES and 4010ES panels to create a larger
network.

Note: You must order and install the 4010-9902 and the 4010-9922 network cards into the
standalone system to enable network functionality.

Standalone Figure 1-1 below shows the layout of the 4010ES standalone configuration.
System Layout

To additional IDNet devices

TrueAlarm Smoke
Sensor with Base
Supervised TrueAlert Non-Addressable
to Device(s) IAM Devices

Remote Line Powered


TrueAlert Non-Addressable
Isolator
Devices
4009A Series
Devices

Addressable Station
TrueAlert Non-Addressable
Devices
Monitor and
to Device(s)
Control ZAMs

TrueAlert Non-Addressable TrueAlarm Thermal


Devices Sensor with Base

IDnet
4010ES NAC

TrueAlert Addressable Note: Some 4009-series


Devices devices are controlled
through RUI and not
IDNet

4009T or Remote Annunciation 4010ES Panel


4009TPS (Graphical or LCD) RUI

Figure 1-1. Standalone 4010ES System

1-2
Network Configuration

Overview The 4010ES can be expanded to a network system by using the 4010-9902 and the 4010-9922
network interface cards (NICs). When a NIC is installed into a 4010ES host panel, it is used to
connect to up to 98 other network nodes. Nodes may consist of other host 4010ES panels, or
they may be completely different: 4010ES FACPs and TrueSite Workstation (TSW) are
examples of what could be used as nodes. A node is a self-sufficient FACP that controls
appliances and devices, which also has the capability of controlling and communicating with
other nodes.

The network configuration supports two prevalent architectures (or wiring configurations):
hub (or ring), or star. A networked system can also use a combination of the two.
The hub configuration consists of a main loop with nodes connected in a radial manner. The
star configuration consists of several nodes connected directly to one common node. Physical
bridge cards are used for the star configuration. Physical bridges reduce the amount of wire that
would otherwise be needed to connect all nodes in a loop. A combination of the two styles is
illustrated in Figure 1-2.

Ring Topology

TSW Network Display Unit


(NDU) Hub Node

Physical Bridge Links


(Star Topology)

Note: Physical Bridge


links in a 4010ES
requires a two-bay box Distributed Remote
Node Locations

Figure 1-2. Hub/Ring Configuration

1-3
Network Configuration, Continued

Connecting Network loops can be joined via physical bridge cards. There may be no more than two Style 7
Network Loops network loops (two hub configurations) connected in tandem. For every two loops that are
interconnected (using one physical bridge), there can be a maximum of three physical bridges
used in a star configuration. See Figure 1-3.

Remote
Node

Physical
Bridge
Link

Hub
Remote Loop Node Local Loop

Hub Node Physical Bridge Link


TSW

Physical Bridge Link Physical Bridge Link

Physical Bridging
(Star Configuration)

Figure 1-3. Interconnected Loop Configuration

Network Network communication is achieved via the 4010-9902 and the 4010-9922 NICs. Each
Communication network node requires a NIC. Once the FACP is a network node, it may be programmed to be
fully in control of other nodes, or to be fully passive, or anywhere in between.
The 4010-9902 and the 4010-9922 NICs are option cards that use a PDI connector to
communicate with the CPU. The NICs allow for communication between each panel via fiber
or twisted shielded pair wire in a Style 4 or Style 7 wiring configuration.
The NICs are designed to be connected in a point-to-point arrangement, so that one wire fault
does not cause the entire system to fail. The point-to-point arrangement provides the most
secure and fault-tolerant wiring possible.
Two types of media cards can be used with the NICs.
• The Fiber-Optic Media (4010-9919) card can be used for electrically noisy environments
or for connecting externally to other buildings.
• The Wired Media Card (4010-9918) is used in all other types of applications.
Up to two media cards can be plugged into each NIC. The same NIC can use a combination of
different types of media boards (for example, a NIC may have a Wired Media card connected
to the Left Port, a Fiber-Optic Media card connected to the Right Port).
For setup and installation of a physical bridge card, refer to document 579-184: 4100/4120/
4010-Series Physical Bridges and Media Modules.
For setup and installation of network interface cards, refer to document 579-956: 4010ES
Network Interface and Media Card Installation Instructions.

1-4
Chapter 2
Basic Hardware
Introduction The 4010ES FACPs are one-bay or two-bay back boxes with a dead front and glass door,
containing a set of pre-installed basic system components:

• Dead front-mounted CPU (2x40 character LCD or InfoAlarm)


• Operator interface
• Main System Supply (MSS) (notification appliance circuits and system power)
• 48-LED Module (for certain 4010ES configurations)
• IDNet or MX Loop circuit (for initiating and other devices)

In addition to the basic modules, optional modules can be installed inside the one-bay or two-
bay 4010ES panels. The types of modules available depend on the panel configuration as well
as the accessibility and availability of the Power Distribution Interface (PDI) blocks. The
number of available PDI blocks depends on the system ordered. See Chapter 3: “Panel
Configurations”.

In this chapter This chapter covers the following topics:

Topic Page

CPU 2-2

Operator Interface 2-8

Main System Supply (MSS) 2-9

48-LED Module 2-14

System Power 2-16

2-1
CPU

Overview The CPU card (Figure 2-1 and Figure 2-2) is the main decision maker in the 4010ES FACP. It
holds all job information, current system status and communicates to all slaves connected to
the 4010ES panel. A 4010ES CPU contains the following features:

• 2X40 LCD display and piezo (non-InfoAlarm systems only) - Annunciation for
supervisory, trouble and alarm signals.
• Compact Flash Socket (Card Pre-Installed) - Alternate Exec and Job storage.
• Ethernet Service port - PC connection used by Simplex service personnel.
• Serial Service port - Interface for service equipment or Simplex service personnel.
• Style 4 / 7 Remote Unit Interface - Remote connection to system components not located
within 4010ES box.

SUPERVISORY LED (LED17)

2x40 LCD

USER-DEFINABLE LEDs TROUBLE LED (LED16)


(LED11-LED14, LED21, LED22)

CONTROL KEY LEDs PRIORITY 2 ALARM LED AC POWER LED (LED20)


(LED23-LED25) (LED18)

FIRE ALARM LED (LED19) ALARM SILENCED LED (LED15)

Note: All LEDs on the front side of the board are used for standard fire
alarm functions and are visible through the dead front membrane.

Figure 2-1. Dead Front-Mounted CPU with a 2x40 Display (Front View)

Continued on next page

2-2
CPU, Continued

Overview
RUI TROUBLE LEDs (LED1-LED3)

RUI ENABLE JUMPER (P1)

BATTERY (BT1)
PIEZO CONNECTION (BUZ1)

BATTERY ENABLE LCD CONTRAST RUI SHIELD


COMPACT FLASH (P3) JUMPER (P5) ADJUST (R23) JUMPER (P2)

COLD START KEYPAD MEMBRANE 24V POWER/COMMS


SWITCH (SW3) CONNECTOR (P8) CONNECTORS (P9 & P10)

BOOTLOADER STATUS LEDs (LED7-LED10) SERIAL SERVICE PORT (P11)

RESET SWITCH (SW1) ETHERNET SERVICE PORT (J7)

ETHERNET STATUS LED (LED5) & ACTIVITY LED (LED6)

RUI PLUGGABLE TERMINAL BLOCK (TB1)

Figure 2-2. Dead Front-Mounted CPU with a 2x40 Display (Back View)

CPU LEDs The tables below outline the functions of the LEDs on the CPU card.

Table 2-1. Reset LED

Reference
Silkscreen Name Color Status
Designator

ON = CPU is in reset
FLASHING = Board is unable to come
LED4 RESET Yellow out of reset. Possibly corrupt CFIG or
board needs to be replaced.
OFF = CPU is running normally

Continued on next page

2-3
CPU, Continued

CPU LEDs
Table 2-2. Ethernet LEDs

Reference
Silkscreen Name Color Status
Designator

LED5 STATUS Green ON = Cable connected

LED6 ACTIVITY Red FLASHING = Ethernet activity

Table 2-3. RUI Trouble LEDs

Reference
Silkscreen Name Color Status
Designator

LED1 OPEN Yellow ON = Class A fault (open-circuit) or a short

LED2 B SHORT Yellow ON = Short-circuit on the Primary side

LED3 A SHORT Yellow ON = Short-circuit on the Secondary side

Table 2-4. Front Panel LEDs

Reference
Silkscreen Name Color Status
Designator

LED11 Red ON = User-definable Key A active (Note)


USER-DEF A
LED12 Yellow ON = User-definable Key A active (Note)

LED13 Yellow ON = User-definable Key B active (Note)


USER-DEF B
LED14 Red ON = User-definable Key B active (Note)

ALARM
LED15 Yellow ON = Alarm silenced
SILENCED

LED16 TRBL Yellow ON = Trouble

LED17 SUPV Yellow ON = Supervisory

LED18 PRI2 Red ON = Priority 2 alarm

LED19 FIRE Red ON = Alarm

ON = System power is functioning


LED20 AC POWER Green
properly

LED21 Yellow ON = User-definable Key C active (Note)


USER-DEF C
LED22 Green ON = User-definable Key C active (Note)

LED23 CTRL 1 Yellow ON = Control Key 1 active

LED24 CTRL 2 Yellow ON = Control Key 2 active

LED25 CTRL 3 Yellow ON = Control Key 3 active

Note: Only one LED in each user-definable pair will be ON at a time, never both

Continued on next page

2-4
CPU, Continued

CPU LEDs
Table 2-5. Bootloader Status LEDs

Reference
LED7 LED8 LED9 LED10
Designator

Silkscreen
A B C D
Name

Color Green Green Green Green

Bootloader On (0.25 s) On (0.25 s) On (0.25 s) On (0.25 s)


Initialization Off (0.25 s) Off (0.25 s) Off (0.25 s) Off (0.25 s)

Bad Master
CRC or No
Off Off Off On
Master
Present

Diagnostic
On Off Off On
Fail - RAM

Diagnostic
Fail -
Off On Off On
Bootloader
Status CRC

Downloading
On On Off On
Master

Downloading
Off Off On On
CFIG

Downloading
On Off On On
MsgLib

Downloading
Off On On On
Bootloader

Download
On On On On
Successful

CPU Jumper
Settings
Table 2-6. CPU Settings

Reference Designator Silkscreen Name Position Function

1-2 Enable RAM Battery Backup


P5 BATTERY
2-3 (default) Disable RAM Battery Backup

1-2 (default) Disable RUI


P1 RUI CKT
2-3 Enable RUI

1-2 (default) RUI shield tied to 24C (Note)


P2 RUI SHIELD
2-3 RUI shield tied to Earth

Note: Some devices that connect to RUI have inherently grounded shield terminals, in
which case, 24C cannot be used. If 24C is used, a Negative Earth Fault will occur.

2-5
CPU, Continued

CPU Switches
Table 2-7. Switches

Reference
Silkscreen Name Function
Designator

Short press (< 3 seconds) to activate a software-controlled


reset (warm start).
Press and hold (> 3 seconds) to force a hardware reset
(also a warm start).
SW1 RESET
Generally, unless the CPU card appears to be locked up,
you should always use the software-controlled reset.
A warm start preserves the logs and the disabled status of
any points that are in the disabled state.

During startup, press and hold this button to clear all history
SW3 COLD START
logs and enable any points that were previously disabled.

CPU Connectors/
Ports/Terminal
Table 2-8. Connectors/Ports/Terminal Block
Block
Reference
Silkscreen Name Function
Designator

Used for alternative job/exec storage (card does not “run”


P3 COMPACT FLASH
out of compact flash).

KEYPAD Used to communicate user inputs from the keypad


P8
MEMBRANE membrane to the CPU card.

Used to provide the necessary connections to daisy


24 V POWER / chain 4100 Comms and 24 VDC card power in an in-out
P9 & P10
INTERNAL COMMS fashion. 24 VDC card power originates from the MSS.
4100 Comms originates from the CPU card.

Used to connect the CPU card to the Remote Service


SERIAL SERVICE
P11 Gateway. It may also be used as a service port if the
PORT
Ethernet Service Port is not available.

Used to connect the panel to a local PC (through the


ETHERNET
J7 Front Panel Ethernet connection board or 4010-9914
SERVICE PORT
BNIC).

RUI A-, RUI A+,


Remote User Interface (RUI) used for communication
TB1 SHIELD, RUI B-, RUI
between the CPU and remote slaves.
B+

2-6
CPU, Continued

CPU Card Table 2-9 shows the battery current draw for the CPU card.
Specifications
Table 2-9. Battery Standby (24 V)

Configuration Supervisory Current Draw Alarm Current Draw

RUI Disabled 124 mA 173 mA

RUI Enabled - No Load 149 mA 198 mA

RUI Enabled - Full Load 176 mA 225 mA

Table 2-10 shows the maximum draw over the voltage range.

Table 2-10. Maximum Draw over Voltage Range

Configuration Supervisory Current Draw Alarm Current Draw

RUI Disabled 144 mA 208 mA

RUI Enabled - No Load 167 mA 226 mA

RUI Enabled - Full Load 186 mA 248 mA

Note: CPU InfoAlarm supervisory and alarm current draws are both the same as the
supervisory current draw.

2-7
Operator Interface

Overview Shown below are the two operator interfaces which are available with the 4010ES.
The Operator Interface is used to obtain alarm, supervisory, trouble, and other statuses via the
Display and LEDs. Control functions are accessed using dedicated and user-programmable
keys.

Figure 2-3 is the standard 2x40 LCD Operator Interface. This model includes a 2 line by 40
character Liquid Crystal Display. The membrane is available in both English and French.

Figure 2-3. Standard Operator Interface

Figure 2-4 is the InfoAlarm operator interface. This model includes a larger graphical display,
which can display more information simultaneously.

Note: The InfoAlarm Operator Interface can only be installed on two-bay 4010ES panels. See
Chapter 3: “Panel Configurations” for details on two-bay panels.

Waterflow-East
ABC DE F G HI
Waterflow-West ZONE SIG AUX
Page Up 1 2 3
Ground Fault
J KL M NO PQ R
FB IO IDNet

Manual Evac Previous 4 5 6


STU V WX YZ /
P A L
Next
City Disconnect 7 8 9
' SP' ( ) ,# :
Door Holder Page Dn
NET ADDR
Bypass 0 C/Exit

Drill
Menu Enter
Smoke Sensor
Almost Dirty Check Fire Priority 2 System System Alarm AC
Alarm Alarm Supervisory Trouble Silenced Power
Language
Toggle

Fire Alarm Priority 2 Supv Trouble Alarm System


Lamp Test Ack Ack Ack Ack Silence Reset

ALARMS WARNINGS

Figure 2-4. InfoAlarm Operator Interface

2-8
Main System Supply (MSS)

Overview The MSS is the power source for the FACP. It provides 24 VDC card power to the 4010ES.
Table 2-11 lists the MSS capabilities.
The MSS also performs standard fire alarm functions, such as brownout detect, battery transfer,
battery recharge, earth fault detection and power limiting per UL 864. It is shipped installed
and connected in the 4010ES panel. Figures 2-5 and 2-6 illustrate a 4010ES MSS.

Table 2-11. MSS Capabilities

MSS with IDNet MSS without IDNet


8 A of available power 8 A of available power
4 Class A NACs 4 Class A NACs
Battery charger (Note) Battery charger (Note)
1 AUX Relay (2 A, 32 V) 1 AUX Relay (2 A, 32 V)
1 AUX Power Tap (2 A) 1 AUX Power Tap (2 A)
Single Channel, Dual Loop IDNet+
Note: The 4010ES can hold a maximum of 33 Ah batteries in the one-bay box and
50 Ah in the two-bay box. The MSS charger is listed for 110 Ah UL and 50Ah
ULC.

Note: Which MSS you get depends on the base panel selected. See Chapter 3: “Panel
Configurations”.

Optional City Card


or Relay Card
Mounting Space

MSS

Option Card AC Block


Blocks

Top Bay
PDI card

Rectifier
Transformer

Figure 2-5. MSS (Shown with IDNet)

Continued on next page


2-9
Main System Supply (MSS), Continued

Overview

Figure 2-6. MSS LEDS and Switches

2-10
Main System Supply (MSS), Continued

MSS LEDs and Tables 2-12 and 2-13 list the details associated with the LEDs and jumpers on the MSS.
Jumpers
Table 2-12. MSS LED Functions and Indications

LED Number Silkscreen Name Status


LED1 IDNet POS. EARTH ON = IDNet POS. EARTH (Note)
LED2 IDNet NEG. EARTH ON = IDNet NEG. EARTH (Note)
STEADY = NO DEVICE DETECTED
LED3 IDNet
BLINK = SHORT CIRCUIT TRBL
LED4 IDNet CIRCUIT A ON = CLASS A / OPEN TRBL
LED5 IDNet CIRCUIT B ON = CLASS A / OPEN TRBL
LED6 4100 COMMS ON = COMM LOSS
STEADY = OVERCURRENT
SINGLE BLINK = POS. EARTH
LED7 GENERAL POWER TRBL DOUBLE BLINK = NEG. EARTH
TRIPLE BLINK = BATTERY TRBL
QUAD BLINK = CHARGER TRBL
LED8 AC POWER ON = MSS POWER FROM AC MAIN
LED9 NAC1 NAC1 TRBL or NAC1 “ON”
LED10 NAC2 NAC2 TRBL or NAC2 “ON”
LED11 NAC3 NAC3 TRBL or NAC3 “ON”
LED12 NAC4 NAC4 TRBL or NAC4 “ON”
Note: The IDNet circuit on the MSS is electrically isolated and has its own earth fault
detection circuit. The IDNet earth fault detection circuit detects a 10 KOhms (or less)
stray impedance to earth ground.

Table 2-13. MSS Jumper Functions

Jumper
Silkscreen Name Position Function
Number
CLASS B (STYLE 4) (Note 1) 1-3, 2-4
P1 IDNet CIRCUIT B
CLASS A (STYLE 7) 3-5, 4-6 (DEFAULT)
CLASS B (STYLE 4) (Note 1) 1-3, 2-4
P2 IDNet CIRCUIT A
CLASS A (STYLE 7) 3-5, 4-6 (DEFAULT)
ENABLE 1-2 (DEFAULT)
P3 EARTH DETECT (Note 2)
DISABLE 2-3
LOW BATTERY DISABLE (DOMESTIC) 1-2 (DEFAULT)
P7
DISCONNECT ENABLE (CANADA) 2-3
Note 1: When jumpers are set for Class B (Style 4) on IDNet, you may use both the B-side
and the A-side to wire devices. Thus, for Circuit B, you can have two pairs of wires per
side or four branches per circuit.
2: Only one power module should be set for earth fault monitoring for each location
within a system. Normally, the MSS is set to monitor for earth faults. The earth fault
detection circuit will detect a 10 KOhms (or less) stray impedance to earth ground.
The expansion battery charger (XBC, 4081-9306, -9308) may also be set to monitor
for earth faults. When an XBC is used to provide battery backup for a 4010ES panel,
disable the earth fault detection on the XBC.

2-11
Main System Supply (MSS), Continued

MSS Table 2-14 lists the specifications for the MSS.


Specifications
Table 2-14. Input and Output Specifications

AC Input Specifications
MSS in 120V FACP 4 A Maximum
120 VAC @ 60 Hz, nominal (Note 1)
MSS in 220/240V FACP 2 A Maximum
220/230/240 VAC @ 50 or 60 Hz (Note 1)
DC Output Specifications
All MSSs Minimum: 19.9 VDC (Special Applications)
Maximum: 31.1 VDC
Ripple: 2 VDC p-p @ full load (8 A)
MSS with IDNet Output (see 30 V or 35 V (Note 2)
note)
Battery Charger Specifications (Note 3)
Input Voltage Range 21-33 VDC
Output Float Voltage 27.4 VDC ±500 mV @ 20 oC, temperature compensated at -
24 mV to -36 mV/×C (32 oF to 120 oF or 0 oC to 49 oC)
High Voltage Output 29.1 V @ 3.3 A
Output Current Limit 1.4 A (For 6.2 - 18 Ah battery)
3.3 A (Default; for 18-50 Ah battery- Canadian; for 18-
110 Ah battery - U.S.)

Note: 1. The MSS detects a low or missing AC input and switches to batteries automatically.
The system returns to AC when it has detected the presence of acceptable AC levels
for a minimum of 30 seconds. AC wiring has to run from a dedicated AC branch circuit
and the breaker / wiring sized according to local codes.
2. When it is necessary to activate large numbers of output devices on IDNet peripherals
(such as piezo sounders), the output voltage is increased to 35 V to provide sufficient
voltage at the end of line to activate the piezo. The higher voltage state is an alarm con-
dition for the purpose of standby battery calculation. The 30 V output is the normal con-
dition and is used to prolong battery standby. The CPU will activate the boost feature
when 10 LED, Piezo or other outputs are activated.
3. The battery circuit is supervised for overcurrent, low battery and missing/depleted
battery.

Continued on next page

2-12
Main System Supply (MSS), Continued

MSS Tables 2-15 and 2-16 list the battery current draw for the MSS. The assumed voltage is
Specifications 24 VDC, which is rated battery voltage for lead-acid type batteries.
Table 2-15. MSS with IDNet Current Specifications

Current Current
Standby Conditions (Note 1)
(Battery standby 24 V) (Max)
No alarms (NACs normal); TBL Relay activated; IDNet LED ON, No IDNet devices connected 140 mA 190 mA
Add to above for each additional set of 50 IDNet devices in standby 40 mA
Total current for fully loaded IDNet channel (248 devices) in standby 339 mA 450mA
Current Current
Alarm Conditions (Note 2)
(Battery standby 24 V) (Max)
4 NACs ON (Note 3); TBL Relay Activated; IDNet LED ON, No IDNet devices connected 165 mA 220 mA
Add to above for each set of 50 IDNet devices in alarm 50 mA
Add to above for 20 LEDs ON 40 mA
Total current for a fully loaded IDNet channel (248 devices) in alarm (20 LEDs ON) 453 mA 600 mA

Table 2-16. MSS without IDNet Current Specifications

Current Current
Standby Conditions (Note 1)
(Battery standby 24 V) (Max)

No Alarms (NACs normal); TBL Relay activated 70 mA 110mA


Current Current
Alarm Conditions (Note 2)
(Battery standby 24 V) (Max)
4 NACs ON (Note 3); TBL Relay activated 100 mA 150 mA

Note: 1. Additional standby conditions: Auxillary relay activated, power trouble LED on, battery
charger off, auxiliary power load = 0 mA.
2. Additional alarm conditions: Auxillary relay activated, power trouble LED on, battery
charger off, auxiliary power load = 0 mA, NAC alarm load = 0 mA, IDNet = 35 V.
3. Notification power must also be taken into account for alarm current. Consult the notifi-
cation appliances, used installation manuals to determined the current draw for each
appliance used.

The Notification Appliance Circuits on the MSS are rated for Special Application and for
Regulated 24 VDC operation per UL864, 9th Edition.
When used with the Notification Appliances listed in Table C-1 (Appendix C) or Table D-1
(Appendix D), each NAC is rated for 3 A, and total MSS capacity is rated at 8 A. This rating is
the UL864 Special Application rating. Appliances listed in Tables C-1 or D-1 are synchronized
per UL864 between all NACs on the MSS, and any NACs on a MSS or 4009As within the
same 4010ES system.
When using Notification Appliances not listed in Tables C-1 or D-1, each circuit is rated for
2 A maximum, with a total Notification Appliance load of 4 A per MSS. This rating is the
UL864 Regulated 24 VDC rating. Synchronization of strobes and other appliances requires use
of the associated, listed, compatible Synchronization Module. Consult the supplier of
Notification Appliances for synchronization limits and details.
Simplex Appliances (Table C-1) may not be mixed with Wheelock Appliances (Table D-1) on
a single power supply. A 4010ES system with mix of appliances from Tables C-1 and D-1 will
not meet the UL864 9th Edition requirement for Visual synchronization (10 milliseconds)
between power supplies. Appliances listed in Table C-1 will be consistently out of visual sync
with appliances in Table D-1 by about 30 milliseconds. Appliances listed Table C-1 will be
notably out of audible sync with appliances in Table D-1 by a consistent time (Wheelock
leading by 1/2 second). In order to meet the requirements for visual and audible sync system
wide, all appliances in the system must be exclusively from either Table C-1 or D-1. Non-
pulsing, linear-type Notification Appliances, such as horns or bells may be used up to the full
rating (3 A / NAC, 8 A total for the MSS).

2-13
48-LED Module

Overview The 48-LED Module (Figure 2-7) comes pre-installed inside some base configurations of the
4010ES panel. Each LED can be associated with a point, or group of points. By default, the
module is supplied with red LEDs, except for the last column which has yellow LEDs. All of
them can be replaced by different color LEDs. Refer to section “LED Kits for the 48-LED
Module” inside Chapter 4 for a list of LED kits. Refer to Chapter 5: “Installing 4010ES
Systems” for instructions on replacing LEDs.

Figure 2-7. 48-LED Module (Front View)


Figure 2-8 outlines what the different LEDs, jumpers and switches represent.

Figure 2-8. 48-LED Module LEDs, Jumpers and Switches (Rear View)

2-14
48-LED Module, Continued

48-LED Module
Specifications
Table 2-17. 48-LED Module Current Specifications

Standby Current Current


LED Controller Circuit 20 mA
Add to above for each additional LED that is ON 1.89 mA
Total current for fully loaded 48-LED Module 111 mA
Maximum Alarm Current) Current

LED Controller Circuit 20 mA


Add to above for each additional LED that is ON 2.39 mA
Total current for fully loaded 48-LED Module 135 mA

2-15
System Power

Main System The 4010ES FACP is powered primarily by the MSS. The MSS draws power from the main
Power power line, via an AC block, a transformer and a rectifier (Figure 2-5). In the case of main
power failure, backup power is provided by backup batteries.

Backup Batteries A pair of 12 V sealed lead acid batteries are used as a backup power source in the event of AC
failure. The backup batteries are ordered and shipped separately from the 4010ES system. They
are installed at the bottom of the 4010ES back box.
Batteries larger than 33 Ah for a one-bay 4010ES and 50 Ah for a two-bay 4010ES can be
used. However, they must be accepted and installed per UL and local authority requirements
using 4100-5128 Battery Distribution Terminal Block. The connection from the battery box to
the 4010ES panel must be within 20 feet and in conduit.
For 50 Ah external batteries with a one-bay box, use box 2081-9282 Remote Battery Cabinet
(Red). For 110 Ah external batteries with a one or two-bay box, use box 2081-9280 Remote
Battery Cabinet (Red).

2-16
Chapter 3
Panel Configurations
Introduction The 4010ES comes in either in a one-bay or a two-bay configuration. Each of these can be
ordered in a variety of base systems to satisfy various market needs.

In this chapter This chapter covers the following topics:

Topic Page

One-Bay 4010ES Panels 3-2

Two-Bay 4010ES Panels 3-6

3-1
One-Bay 4010ES Panels

Overview The basic components are shipped pre-assembled inside the 4010ES panel. The optional
components need to be ordered and installed separately.
The one-bay 4010ES panel comes in three configurations. Table 4-1 of Chapter 4: “Orderable
Panels and Devices” lists the basic components that are shipped with each of the three
configurations.

Note: The dead front on a one-bay 4010ES panel is different for 48-LED Module configurations,
as seen in Figure 3-1. See Figure 3-2 for detailed diagrams of one-bay 4010ES panels.

With 48 LED Module

Without 48 LED Module

Figure 3-1. One-Bay Dead Front with and without 48-LED Module

Continued on next page

3-2
One-Bay 4010ES Panels, Continued

Overview

Glass Door
Without 48-LED Module

Option Card
Mounting Space

CPU

Dead
Front Back
Box

Glass Door With 48-LED Module

Option Card
Mounting Space

CPU

48-LED
Module
Back
Dead Box
Front

Figure 3-2. One-Bay 4010ES Panel

3-3
One-Bay 4010ES Panels, Continued

Optional Modules In addition to the basic modules, optional modules can be installed inside the one-bay 4010ES
panels. The types of modules available depend on the panel configuration as well as the
accessibility and availability of the Power Distribution Interface (PDI) blocks.

Note: Out of four PDI blocks in the top-bay PDI card, three are available since the MSS card
utilizes one (Figure 2-5).

Table 3-1 lists the optional modules that can be installed inside the different configurations of
the 4010ES panels. Refer to the user manual associated with each card for specifications and
installation instructions. The list of these manuals is available in Table 4-3 in Chapter 4:
“Orderable Panels and Devices”

Table 3-1. Optional Modules

Optional Modules Description Blocks


4010-9818 Network Media Card Wired (Mounts on 4010-9902 and 4010-9922) none
4010-9819 Network Media Card Fiber Optic (Mounts on 4010-9902 and 4010-9922) none
4010-9901 VESDA Interface Card 1
4010-9902 and 4010-9922 4120 Network Interface Card 2
4010-9903 and 4010-9924
4120 Network Interface w/ Modem physical Bridge Style 4 2
(Note 2)
4010-9904 and 4010-9925
4120 Network Interface w/ Modem physical Bridge Style 7 2
(Note 2)
4010-9905 and 4010-9926
4120 Network Interface TCP/IP physical Bridge Style 4 3
(Note 2)
4010-9906 and 4010-9927
4120 Network Interface TCP/IP physical Bridge Style 7 3
(Note 2)
4010-9907 4010 IDNet+ Card 2
4010-9908 4-Point Flat AUX Relay (2 A) 1
4010-9909 City Connect Card with Disconnect Switches (MSS Mounted) none
4010-9910 City Connect Card without Disconnect Switches (MSS Mounted) none
4010-9911 Alarm Relay Card (MSS Mounted) none
SDACT Card
4010-9912 1
(Mounts in Top Bay Block D Only)
4010-9913 SafeLinc Internet Interface (FPII) Card 2
4010-9914 Building Network Interface Card (BNIC) 2
4010-9916 25 VDC Voltage Regulator Card 1
4010-9917 MX Digital Loop Card 2
4010-9918 Dual RS232 Card 1
TrueInsight Remote Service Gateway (Perle)
4010-9919 none
(Mounts on Dead Front)
4010-9920 8 Zone Initiating Device Circuit, Class B 2
4010-9921 8 Zone Initiating Device Circuit, Class A 2

Notes: 1. Consult your local sales office to determine which modules are available in your area.
2. Physical Bridge cards must also be installed with a network interface card. Therefore,
the 4010ES one-bay systems do not have enough option card space left to install a
physical bridge after a NIC is added.

3-4
One-Bay 4010ES Panels, Continued

Back Box Back boxes come shipped with the panel and can only be ordered separately as a service part.
Mechanical Table 3-2 lists the specifications for the one-bay back boxes.
Specifications

Table 3-2. Back Box Specifications

Depth with
PID Number Height Width Depth
Door

699-467 (Platinum) 6-15/16 in. 11-11/16 in. (297


22 in. (559 mm) 24 in. (610 mm)
699-466 (Red) (176 mm) mm)

3-5
Two-Bay 4010ES Panels

Overview A two-bay system is used when more option card space is required than is given in a one-bay
system, or when InfoAlarm is the primary display. Refer to Figure 2-4 for an illustration of the
InfoAlarm interface.
The basic components of the two-bay panels are the same as for the one-bay panels and are
pre-installed in the top bay. The expansion bay contains another PDI card with eight available
blocks. Those can be used to connect optional modules to the 4010ES panels. The Expansion
Bay PDI card comes pre-installed inside the two-bay panel.
See Figures 3-3 through 3-5 for two-bay 4010ES diagrams.

%THERNET3ERVICE0ORT

'ROUNDING3TRAP 0IEZO

/PERATOR)NTERFACE

#05#ARD

$EAD&RONT,ATCH

3TANDARD5SER)NTERFACE

)NFO!LARM5SER
)NTERFACE
'ROUNDING3TRAP

'ROUNDING3TRAP

#05#ARD

$EAD&RONT,ATCH

)NFO!LARM!PPLIQUE

)NFO!LARM5SER)NTERFACE
Figure 3-3. Two-Bay, Standard and InfoAlarm Dead Fronts

Continued on next page


3-6
Two-Bay 4010ES Panels, Continued

Overview

Glass Door

Back Box

Top Bay

Dead Front Expansion PDI


CPU MSS

Figure 3-4. Two-Bay 4010ES Panel with Standard User Interface

Continued on next page

3-7
Two-Bay 4010ES Panels, Continued

Overview

Glass Door

Back Box

Top Bay

CPU
Dead Front InfoAlarm
Expansion PDI MSS
Interface

Figure 3-5. Two-Bay 4010ES Panel with InfoAlarm Interface

3-8
Two-Bay 4010ES Panels, Continued

Optional Modules The same optional modules can be used with the two-bay panels as with the one-bay panels.
For a complete list of optional components, see Chapter 4: “Orderable Panels and Devices”.

Back Box Table 3-3 lists the specifications for the two-bay back boxes.
Mechanical
Specifications
Table 3-3. Back Box Specifications

Depth with
PID Number Height Width Depth
Door

699-465 (Platinum) 6-15/16 in. 11-11/16 in.


40.0 in. (1016 mm) 24 in. (610 mm)
699-464 (Red) (176 mm) (297 mm)

3-9
Chapter 4
Orderable Panels and Devices
Introduction The following chapter lists the 4010ES panels and optional modules that can be ordered. It
also lists the installation manuals that are associated with each optional device.

In this chapter This chapter covers the following topics:

Topic Page

Panels 4-2

Optional Modules 4-3

4-1
Panels

One-Bay 4010ES
Panels

Table 4-1. One-Bay 4010ES Systems

Panel Language
Panel PIDs Panel Color Panel Components
and AC Voltage
4010-9401 Red English
4010-9402 Platinum 120 V
---
4010-9501 Red English
4010-9502 Platinum 220 V-240 V Three Free
MSS with an
Option
4010-9403 Red IDNet Channel
English CPU with a Standard Blocks
4010-9404 Platinum 120 V 2X40 Display Operator 48-LED Module
and a Piezo Interface (Door-Mounted)
4010-9405 Red French
4010-9406 Platinum 120 V

4010-9503 Red One MX Loop


English One Free Option Card
MSS (No IDNet)
4010-9504 Platinum 220 V-240 V Option Block Pre-Installed
(4010-9917)

Two-Bay 4010ES
Panels

Table 4-2. Two-Bay 4010ES Systems

Panel Language
Panel PIDs Panel Color Panel Components
and AC Voltage
4010-9421 Red
English 120 V
4010-9422 Platinum CPU with a One IDNet+ Card
Standard Operator
2X40 Display Pre-Installed
4010-9521 Red Interface
English and a Piezo (4010-9907)
4010-9522 Platinum 220 V-240 V
MSS with an
4010-9425 Red IDNet Channel --
English 120 V
4010-9426 Platinum InfoAlarm Interface --
CPU
4010-9525 Red (Display and Piezo) --
4010-9526 Platinum --
4010-9523 Red CPU with a Two MX Loop Option
Standard Operator
2X40 Display Cards Pre-Installed
4010-9524 Platinum Interface
and a Piezo (4010-9917)
English
4010-9527 Red 220 V-240 V One MX Loop Option
MSS
Card Pre-Installed
4010-9528 Platinum (No IDNet)
InfoAlarm Interface (4010-9917)
CPU
4010-9529 Red (Display and Piezo) Two MX Loop Option
Cards Pre-Installed
4010-9530 Platinum (4010-9917)

4-2
Optional Modules

Local Optional
Modules
Table 4-3. Local Optional Modules Installation Instructions

Installation
PID Description
Instructions

4010-9818 Wired Network Media Card 579-956

4010-9819 Fiber Optic Network Media Card 579-956

4010-9901 4010ES/4100/4120-Series VESDA Card 579-963

4010-9902
579-956
and Network Interface Card
574-041
4010-9922

4010-9903 579-818
and Style 4 Network Modular Physical Bridge 579-184
4010-9924 574-041

4010-9904 579-818
and Style 7 Network Modular Physical Bridge 579-184
4010-9925 574-041

4010-9905 579-818
and Style 4 Network TCP/IP Physical Bridge 579-184
4010-9926 574-041

4010-9906 579-818
and Style 7 Network TCP/IP Physical Bridge 579-184
4010-9927 574-041

4010-9907 IDNet+ Module 579-957

4010-9908 4-Point Flat AUX Relay Card 579-220

4010-9909 City Connect Module with Disconnect Switches (MSS Mounted) 579-955

4010-9910 City Connect Module without Disconnect Switches (MSS Mounted) 579-955

4010-9911 Alarm Relay Module (MSS Mounted) 579-955

4010-9912 SDACT 579-954

4010-9913 SafeLinc Internet Interface (FPII) 579-349

4010-9914 Building Network Interface Card (BNIC) 579-949

4010-9916 25 VDC Voltage Regulator Module (International Only) 579-812

4010-9917 MX Digital Loop (International Only) 579-833

4010-9918 Dual RS232 Module 574-910

4010-9919 TrueInsight Remote Service Gateway 579-953

4010-9920 8 Zone Initiating Device Circuit, Class B 579-205

4010-9921 8 Zone Initiating Device Circuit, Class A 579-991

4606-9102 4010ES RUI LCD Annunciator 579-977

4-3
Optional Modules, Continued

Remote Devices

Table 4-4. Remote Power and Notification Devices Installation Instructions

Installation
PID Description
Instructions

4010-9818 Wired Network Media Card 579-956

4010-9819 Fiber Optic Network Media Card 579-956

4009-9401 4009T TrueAlert Controller 574-762

4100U External Battery Charger 120 V (With


4081-9306 579-268
Cabinet; Holds 11 Ah Batteries)
4009-9201 4009A 120 V 574-181

4009-9202CA 4009A 120 V ULC-listed Model 574-181

4009-9301 4009A 240 V 574-181

4009 Remote TrueAlert Power Supply (TPS)

4009-9813 Transponder Interface Card (TIC) 579-875

4100-5120 120 V Domestic TPS 579-875

4100-5121 120 V Canadian TPS 579-875

4100-5122 220-240 V International TPS 579-875

Table 4-5. Remote Display and Annunciation Devices Installation Instructions

Installation
PID Description
Instructions

4100-9401 Remote InfoAlarm - Red 579-687

4100-9402 Remote InfoAlarm - Beige 579-687

4100-9421 Remote InfoAlarm (French) - Red 579-687

4100-9422 4100-9422 Remote InfoAlarm (French) - Beige 579-687

4100-9441 Remote InfoAlarm (International) - Red 579-687

4100-9442 Remote InfoAlarm (International) - Beige 579-687

24-Point I/O Graphic Module (Requires Mounting


4100-7401 574-348
Cabinet)

4-4
Optional Modules, Continued

Adjunct Features

Table 4-6. Adjunct Features

Installation
PID Description
Instructions

4100U External Battery Charger 220/230/240 V (With


4081-9308 579-268
Cabinet. Holds 110 Ah Batteries)

Red Fiber Modem Expansion Cabinet with Left Port


4190-9021 579-831
Modem – Single Mode

Beige Fiber Modem Exp Cabinet with Left Port Modem -


4190-9022 579-831
Single Mode

4190-9023 Right Port Modem for Exp Cabinet – Single Mode 579-831

Red Fiber Modem Exp Cabinet with Left Port Modem –


4190-9024 579-831
Multimode

Beige Fiber Modem Exp Cabinet with Left Port Modem -


4190-9025 579-831
Multimode

4190-9026 Right Port Modem for Expansion Cabinet – Single Mode 579-831

End User
Programming
Tools Table 4-7. End User Programming Tools

PID Description

4100-0292 Custom Label Editing (USB Dongle)

4100-0295 Port Vectoring Setup and Control (USB Dongle)

4100-0296 User Group/Passcode Editing (USB Dongle)

4100-0298 Walktest Configuration Setup and Control (USB Dongle)

4100-8802 Programming Unit Software

LED Kits for the


48-LED Module
Table 4-8. LED Kits for the 48-LED Module

PID Description

4100-9843 8 Yellow LEDs

4100-9844 8 Green LEDs

4100-9845 8 Red LEDs

4100-9855 8 Blue LEDs

4-5
Chapter 5
Installing 4010ES Systems
Introduction This chapter describes how to mount the 4010ES back boxes to a wall, and install basic
system components into the boxes.
Before beginning the installation, review this chapter to get a sense of the types of bays and
modules that make up the FACP.

IMPORTANT: Verify ES Panel Programmer, Executive, and Slave Software


compatibility when installing or replacing system components.
Refer to the technical support website for up-to-date compatibility
information.

In this chapter This chapter covers the following topics:

Topic Page

Mounting the Panel 5-2

General Field Wiring Guidelines 5-5

Connecting 4010ES Basic Components 5-7

RUI Wiring 5-11

Installing the Optional Modules 5-13

Address Configuration DIP Switch 5-14

Connecting Main System Power 5-16

5-1
Mounting the Panel

Installing the Store the system electronics containers in a safe, clean, and dry location until the back box
Back Box installation is completed, and you are ready to install additional modules. Make certain that you
have the necessary hardware before you begin the installation procedure.
Install the back box as shown in Figure 5-1. Use the holes in the back box to secure it to the
wall.

Note: • Conductor entrance and routing restrictions apply to power-limited systems only.
• While the pre-installed system components may be left in the backbox during
installation, due to the danger of metal fragments falling into electronics, it is
recommended to remove the dead front and any bay pans in the system.
• For surface or flush mounting to a wooden wall structure, the back box must be
attached with four 1-½-inch-long (38 mm) lag bolts and four ½-inch-diameter (13 mm)
washers.
• For surface mounting, secure the box to the wall using the tear-drop mounting holes
on the back surface. For flush and semi-flush mounting, secure the box to the wall
studs using the indicated areas (dents in the metal) on the sides of the box. Note that
the front surface of the back box must protrude at least three inches from the wall
surface for semi-flush installations.
• Power-limited systems have entrance and routing restrictions for field wiring. See
section “General Field Wiring Guidelines” on page 5-5 for more details.

6-15/16”” 6-15/16”
(176 mm) (176 mm)
DOOR 24” DOOR 24”
(610 mm) (610 mm)

16” 16”
(406 mm) (406 mm)

22” 40”
(559 mm) (1016 mm)
(ONE USE 4 HOLES TO (ONE USE 4 HOLES TO
BAY) SECURE BACKBOX BAY) SECURE BACKBOX
TO THE WALL TO THE WALL

RESERVED RESERVED
FOR FOR
BATTERIES BATTERIES
(SEE NOTE 6) (SEE NOTE 6)

SIDE SIDE
VIEW VIEW
4-3/4” 4-3/4”
(121 mm) (121 mm)
One-Bay Back Box Two-Bay Back Box

Note:

1. Use suitable punch when conduit is required. Cut conduit entrance holes on-site to
ensure proper location.
2. Minimum distance between boxes is 3 1/4 inches (83mm) to ensure proper door opening.

Figure 5-1. Back Box Installation

5-2
Mounting the Panel, Continued

Attaching the To attach the 4010ES panel dead fronts containing the Operator Interface and the 48-LED
Dead Front Module (where applicable), follow the steps below:
1. Align the dead front hinges with the hinge pins on the back box, and slide the door down
onto the hinge pins.
2. Attach the two grounding straps to the back box with the # 6 hex flange nuts (Figure 5-3).
The grounding straps should already be attached to the dead front.

%THERNET3ERVICE0ORT

%THERNET3ERVICE0ORT 'ROUNDING3TRAP 0IEZO

'ROUNDING3TRAP
/PERATOR)NTERFACE
/PERATOR)NTERFACE

#05
#ARD
#05
#ARD
 ,%$ 0IEZO
-ODULE

$EAD&RONT,ATCH

$EAD&RONT,ATCH
,%$-ODULE/VERLAY

One-Bay Two-Bay

Figure 5-2. 4010ES Dead Fronts

Top Bottom
Figure 5-3. Dead Front Grounding Straps

5-3
Mounting the Panel, Continued

Attaching Doors To attach the glass doors (Figure 5-4) to the cabinet, follow the steps below:
1. Align the door hinges with the hinge pins on the back box, and slide the door down onto the
hinge pins.
2. Attach the two grounding straps to the back box with the # 6 hex flange nuts. The grounding
straps should already be attached to the door.

Note: The hinge pins for the glass door are located higher and further to the side than the dead
front hinge pins.

One-Bay

Two-Bay

Figure 5-4. One-Bay and Two-Bay Glass Doors

5-4
General Field Wiring Guidelines

Power-Limited For wiring guidelines, see the applicable installation documentation or contact your authorized
Guidelines Simplex Product supplier. Make sure these guidelines are accounted for before wiring for
power-limited systems:

• Non-power limited field wiring (AC power, batteries, City connection) must be installed
and routed in the shaded areas shown in Figure 5-5.
• Power-limited field wiring must be installed and routed in the non-shaded areas shown in
Figure 5-5, with the exception of City wiring.
• Excess slack should be kept to a minimum inside the back box enclosure. The wiring
should be neatly dressed and bundled together using wire ties.

NON-POWER LIMITED
WIRING AREA

POWER LIMITED
WIRING AREA

Figure 5-5. Field Wiring Guidelines

• Tie the wiring located between bays to the internal wiring troughs, if applicable.
• When powering remote units or switching power through relay contacts, power for these
circuits must be provided by a power-limited power supply listed for fire-protective
signaling use. An EOL relay must be used to supervise the auxiliary power circuit.
• Auxiliary power only: Supervision must be provided if the auxiliary power circuit is to be
wired as a power-limited circuit. In order to connect a circuit using power-limited wiring,
the devices being powered must all be addressable, or a UL Listed EOL relay must be used
to supervise the circuit. Refer to Figure 5-6 for wiring directions for the EOL relay.

Continued on next page


5-5
General Field Wiring Guidelines, Continued

Power-Limited
Guidelines

TO AUX POWER

Note: The 2098-9739 Relay is RED BLACK

used as an example.
Other UL Listed 24VDC
2098-9739
EOL relays can be used, END OF
depending on the LINE RELAY
application.

YELLOW

LAST IDC
IDC DEVICE RESISTOR

Figure 5-6. The EOL Relay

5-6
Connecting 4010ES Basic Components

Connecting the Note: All the basic components come pre-installed with the system. The connections are shown
CPU and the for reference purposes.
Operator Interface To connect the CPU and the Operator Interface, follow the steps below:
1. Place the white spacer on the dead front.
2. Attach the CPU card and the piezo to the dead front, using metal screws provided.
3. Attach the Keypad Membrane cable of the Operator Interface to port P8 on the CPU card
(Figure 5-7). To do so:
a. Slide down the keypad connector shroud on the CPU card.
b. Insert the Keypad Membrane cable into the connector. Do not twist the flat cable.
c. Slide the shroud back up into the connector while holding the flat cable in place.
4. Attach the Ethernet connection board using the 734-232 RJ45 cable.
5. Attach the Perle box using the 734-229 cable.
6. Connect port P9 or P10 of the CPU card to the Dead Front Connection (P1) port on the
top-bay Power Distribution Interface (PDI) card (Figure 5-7 and Figure 5-8). Use the
734-008 4-pin connector harness provided.

KEYPAD MEMBRANE

SERIAL SERVICE PORT (P11) ETHERNET SERVICE PORT (J7)

Figure 5-7. CPU Card (Rear View)

Continued on next page

5-7
Connecting 4010ES Basic Components, Continued

Connecting the
CPU and the
Operator Interface

Top Bay
PDI

MSS

Rectifier

Transformer AC Terminal
Block

Back Box

Figure 5-8. Top Bay

5-8
Connecting 4010ES Basic Components, Continued

Connecting the Follow the steps below:


MSS
1. Connect the MSS to the MSS (Block C) connector on the Top Bay PDI.
2. Attach the MSS to the back box using metal screws and standoffs.
3. Connect the rectifier to the Bridge HARN1 connectors on the MSS (Figure 5-9). The red
wire connects to the tab labeled “+” on the Bridge. The black wire connects to the tab
labeled “-” on the rectifier. See Figure 5-8 for the location of the rectifier.
4. Connect the backup batteries to the Battery connectors on the MSS. The red wire connects
to the tab labeled "RED" on the MSS, the black wire connects to the “BLK” tab. The backup
batteries must be wired in series such that you have 24 V. Use the white wire provided to
bridge the batteries together. The batteries can be placed on the bottom of the 4010ES back
box.

Notes: 1. A fused harness is required to connect the backup batteries. That harness is shipped
with the panel. The mating spade lug on the battery should be 0.250” X 0.032". If
another size is needed, you will need to replace the battery terminal connectors on the
supplied battery harness.

2. One-bay system back boxes support up to 33 Ah batteries. Two-bay system back


boxes support up to 50 Ah batteries. If 50 Ah batteries are used, you must also order
the 4100-0650 Battery Shelf.

3. To minimize the power losses due to wiring from the battery box to the 4010ES, use at
least a 12 AWG wire and keep the battery box at the minimum distance possible from
the 4010ES.

Figure 5-9. MSS Bridge HARN1 Connector

5-9
Connecting 4010ES Basic Components, Continued

Connecting the Connect port P1 or P2 of the 48-LED Module card to either port P9 or P10 of the CPU card
48-LED Module (Figure 5-10). Use the 734-181 4-pin connector harness provided.

00

 
 

0 0
0

, %$ , %$ , %$ , %$  , %$ , %$




, %$ , %$ , %$ , %$ , %$ , %$

!$$2%33 37
, %$ , %$ , %$ , %$ , %$ , %$
#OMM ,OSS
, 3" -3"
, %$
, %$ , %$ , %$ , %$ , %$ , %$

, %$ , %$ , %$ , %$ , %$ , %$

, %$ , %$ , %$ , %$ , %$ , %$

, %$ , %$ , %$ , %$ , %$ , %$

, %$ , %$ , %$ , %$ , %$ , %$

"AR #ODE ,ABEL

Figure 5-10. 48-LED Module (Rear View)

Swapping LEDs
To swap any of the 48 LEDs on the 48-LED Module, follow the steps below:
1. Turn off AC power at the breaker, then remove the battery + connection at the panel.
2. Remove the 48-LED module from the dead front by following the steps below:
1. Disconnect any cables in P1 or P2 of the module
2. Remove the four screws holding the card to the dead front.
3. Remove the card from the dead front.
3. Pull out any necessary LEDs from the module.
4. Insert new LEDs in the vacated slots. For correct polarity, the flat line of the LED outline
on the card must line up with the flat side on the LED.
5. Re-attach the 48-LED module back on its spot on the dead front.
6. Re-attach the batteries and re-apply AC power to the 4010ES panel.

5-10
RUI Wiring

Overview The CPU card’s RUI channel supports the following devices:
• 4009T
• 4009 TPS
• 24 I/O Graphic Annunciator
• Remote LCD Annunciator
• InfoAlarm User Interface
Wire from the CPU card’s RUI interface to the RUI terminal block (Figure 5-11). From there,
wire to each RUI device. The wiring may be Class A or Class B:
Class A wiring allows devices to communicate with the FACP even in the event of a single
open circuit somewhere in the loop. Class A wiring requires that two wires are routed from the
CPU card to each device, and then back again to the CPU card.
Class B wiring allows “T” tapping, and therefore requires less wiring distance per installation
than Class A.

Figure 5-11. Location of the RUI Terminal Block

Continued on next page

5-11
RUI Wiring, Continued

Overview Figure 5-12 depicts Class A and Class B wiring.

DASHED LINES ARE FOR


CLASS A OPERATION
SHLD SHLD

RUI RUI

RUI
4010ES CPU Card Terminal
Block

RUI A-
RUI A+
RUI Device RUI Device
SHIELD

RUI B-
RUI B+

Notes:
2 2
1. Wire size must be between 18 AWG (0.8231 mm ) and 12 AWG (3.309 mm ).
2. Maximum wiring distance: 2,500 feet (762 m) to device from CPU card.
3. Maximum “T” tapping length: 10,000 feet (3,048 m).
4. Maintain correct polarity on terminal connections. Do not loop wires under terminals.
5. If Class A is not used, leave loop back wires from A+ to B+ and A- to B- on RUI terminal blocks.
6. Shield wire is not required. Twisted wire is recommended for improved noise immunity

Figure 5-12. RUI Wiring to the Host Panel


For more detailed field wiring information on each device, refer to its specific installation
instructions manual. See Chapter 4: “Orderable Panels and Devices” for a list of instructions
manuals.

5-12
Installing the Optional Modules

Overview Note: Skip this section if no optional modules need to be installed.


This page contains the general placement guidelines for the optional modules that can be used
with the 4010ES panels. If this information conflicts with the installation instructions for the
optional modules, the installation instructions take precedence. Refer to Table 4-3 in Chapter 4:
“Orderable Panels and Devices” for a list of these installation instructions.
In addition to basic system components, the 4010ES panel has space on the PDI to
accommodate the following option card configurations:
1. One Two-Block 4”X10” option card (such as a NIC or a SafeLINC card) and one 4” X 5”
option card.
or
2. Three 4” X 5” single-block option cards.
If the system is a two-bay system, an eight-block PDI card in the second bay allows for
additional mounting space beyond the three blocks in the top bay.

Note: Some systems come with option cards pre-installed. In these cases, the number of
available option card blocks is reduced. See the PID list table in Chapter 4 for details.

Installing One- The PDI cards are mounted to the back of each bay and carry power and data across all bays.
Block and Two-
Use the following instructions and Figure 5-13 to mount cards into a 4010ES panel bay
Block Cards
1. Screw standoffs and washers to the appropriate holes in the back of the cabinet. These holes
must line up with the screw holes in the card.
2. Plug the card into the appropriate blind mating connector. Seat the card firmly onto the PDI
when installing to ensure complete insertion of the power connector into the PDI.
3. Secure the card to the standoffs with screws and washers.

Figure 5-13. Card Connection to a PDI

5-13
Address Configuration DIP Switch

Overview Addressable cards include a bank of eight DIP switches. From left to right (Figure 5-14) these
switches are designated as SWx-1 through SWx-8. The function of these switches is as
follows:

• SWx-1. This switch sets the baud rate for the internal 4010ES communications line
running between the card and the CPU. Set this switch to ON.
• SWx-2 through SWx-8. These switches set the card’s address within the 4010ES FACP.
Refer to Table 5-1 for a complete list of the switch settings for all of the possible card
addresses.

Note: You must set these switches to the value assigned to the card by the ES Panel
Programmer.

DIP Switches SWx-2 through


4100 Comm. Baud Rate. SWx-8 set the Card Address.
Switch (SWx-1) Figure shows an Address of 3.
Must Be Set to ON

ON

OFF

1 2 3 4 5 6 7 8

Figure 5-14. DIP Switch SWx

Continued on next page

5-14
Address Configuration DIP Switch, Continued

Overview
Table 5-1. Card Addresses

Address SW 1-2 SW 1-3 SW 1-4 SW 1-5 SW 1-6 SW 1-7 SW 1-8 Address SW 1-2 SW 1-3 SW 1-4 SW 1-5 SW 1-6 SW 1-7 SW 1-8
1 ON ON ON ON ON ON OFF 61 ON OFF OFF OFF OFF ON OFF
2 ON ON ON ON ON OFF ON 62 ON OFF OFF OFF OFF OFF ON
3 ON ON ON ON ON OFF OFF 63 ON OFF OFF OFF OFF OFF OFF
4 ON ON ON ON OFF ON ON 64 OFF ON ON ON ON ON ON
5 ON ON ON ON OFF ON OFF 65 OFF ON ON ON ON ON OFF
6 ON ON ON ON OFF OFF ON 66 OFF ON ON ON ON OFF ON
7 ON ON ON ON OFF OFF OFF 67 OFF ON ON ON ON OFF OFF
8 ON ON ON OFF ON ON ON 68 OFF ON ON ON OFF ON ON
9 ON ON ON OFF ON ON OFF 69 OFF ON ON ON OFF ON OFF
10 ON ON ON OFF ON OFF ON 70 OFF ON ON ON OFF OFF ON
11 ON ON ON OFF ON OFF OFF 71 OFF ON ON ON OFF OFF OFF
12 ON ON ON OFF OFF ON ON 72 OFF ON ON OFF ON ON ON
13 ON ON ON OFF OFF ON OFF 73 OFF ON ON OFF ON ON OFF
14 ON ON ON OFF OFF OFF ON 74 OFF ON ON OFF ON OFF ON
15 ON ON ON OFF OFF OFF OFF 75 OFF ON ON OFF ON OFF OFF
16 ON ON OFF ON ON ON ON 76 OFF ON ON OFF OFF ON ON
17 ON ON OFF ON ON ON OFF 77 OFF ON ON OFF OFF ON OFF
18 ON ON OFF ON ON OFF ON 78 OFF ON ON OFF OFF OFF ON
19 ON ON OFF ON ON OFF OFF 79 OFF ON ON OFF OFF OFF OFF
20 ON ON OFF ON OFF ON ON 80 OFF ON OFF ON ON ON ON
21 ON ON OFF ON OFF ON OFF 81 OFF ON OFF ON ON ON OFF
22 ON ON OFF ON OFF OFF ON 82 OFF ON OFF ON ON OFF ON
23 ON ON OFF ON OFF OFF OFF 83 OFF ON OFF ON ON OFF OFF
24 ON ON OFF OFF ON ON ON 84 OFF ON OFF ON OFF ON ON
25 ON ON OFF OFF ON ON OFF 85 OFF ON OFF ON OFF ON OFF
26 ON ON OFF OFF ON OFF ON 86 OFF ON OFF ON OFF OFF ON
27 ON ON OFF OFF ON OFF OFF 87 OFF ON OFF ON OFF OFF OFF
28 ON ON OFF OFF OFF ON ON 88 OFF ON OFF OFF ON ON ON
29 ON ON OFF OFF OFF ON OFF 89 OFF ON OFF OFF ON ON OFF
30 ON ON OFF OFF OFF OFF ON 90 OFF ON OFF OFF ON OFF ON
31 ON ON OFF OFF OFF OFF OFF 91 OFF ON OFF OFF ON OFF OFF
32 ON OFF ON ON ON ON ON 92 OFF ON OFF OFF OFF ON ON
33 ON OFF ON ON ON ON OFF 93 OFF ON OFF OFF OFF ON OFF
34 ON OFF ON ON ON OFF ON 94 OFF ON OFF OFF OFF OFF ON
35 ON OFF ON ON ON OFF OFF 95 OFF ON OFF OFF OFF OFF OFF
36 ON OFF ON ON OFF ON ON 96 OFF OFF ON ON ON ON ON
37 ON OFF ON ON OFF ON OFF 97 OFF OFF ON ON ON ON OFF
38 ON OFF ON ON OFF OFF ON 98 OFF OFF ON ON ON OFF ON
39 ON OFF ON ON OFF OFF OFF 99 OFF OFF ON ON ON OFF OFF
40 ON OFF ON OFF ON ON ON 100 OFF OFF ON ON OFF ON ON
41 ON OFF ON OFF ON ON OFF 101 OFF OFF ON ON OFF ON OFF
42 ON OFF ON OFF ON OFF ON 102 OFF OFF ON ON OFF OFF ON
43 ON OFF ON OFF ON OFF OFF 103 OFF OFF ON ON OFF OFF OFF
44 ON OFF ON OFF OFF ON ON 104 OFF OFF ON OFF ON ON ON
45 ON OFF ON OFF OFF ON OFF 105 OFF OFF ON OFF ON ON OFF
46 ON OFF ON OFF OFF OFF ON 106 OFF OFF ON OFF ON OFF ON
47 ON OFF ON OFF OFF OFF OFF 107 OFF OFF ON OFF ON OFF OFF
48 ON OFF OFF ON ON ON ON 108 OFF OFF ON OFF OFF ON ON
49 ON OFF OFF ON ON ON OFF 109 OFF OFF ON OFF OFF ON OFF
50 ON OFF OFF ON ON OFF ON 110 OFF OFF ON OFF OFF OFF ON
51 ON OFF OFF ON ON OFF OFF 111 OFF OFF ON OFF OFF OFF OFF
52 ON OFF OFF ON OFF ON ON 112 OFF OFF OFF ON ON ON ON
53 ON OFF OFF ON OFF ON OFF 113 OFF OFF OFF ON ON ON OFF
54 ON OFF OFF ON OFF OFF ON 114 OFF OFF OFF ON ON OFF ON
55 ON OFF OFF ON OFF OFF OFF 115 OFF OFF OFF ON ON OFF OFF
56 ON OFF OFF OFF ON ON ON 116 OFF OFF OFF ON OFF ON ON
57 ON OFF OFF OFF ON ON OFF 117 OFF OFF OFF ON OFF ON OFF
58 ON OFF OFF OFF ON OFF ON 118 OFF OFF OFF ON OFF OFF ON
59 ON OFF OFF OFF ON OFF OFF 119 OFF OFF OFF ON OFF OFF OFF
60 ON OFF OFF OFF OFF ON ON

5-15
Connecting Main System Power

Overview The 4010ES panel is shipped with the AC block, the transformer and the rectifier already
interconnected. You only need to wire the AC block to the main power line. The Ground wire
on the power line connects to a screw, located on the top right back box (Figure 5-15). The
other wires connect to the AC terminal block, as indicated by the labels (Figure 5-16).

Ground Screw

Ferrite Bead

AC Block Label
Location

Figure 5-15. Grounding Wire

Connect the “hot” wire to the


appropriate voltage, depending on
your installation.

The Neutral wire always connects


to the lowest terminal.

6%30!.%,3  6%30!.%,3

Figure 5-16. AC Block Labels for AC Power Connections

Note: In 220-240 V panels, the 4010ES requires a true transformer output of 220-240 V. Do not
connect two out of phase "hot"s to create the desired voltage.
When connecting the AC power wire to the AC block, it needs to pass through a ferrite bead to
reduce radiated emissions. Route the black and white AC power wires to the supplied ferrite
bead. Loop the wires twice through the bead and secure with two cable ties as shown in
Figure 5-17. The cable ties are supplied in the ship group that comes with the panel.
4/0/7%20,5'
%!24(#/..%#4/.7)2%
4/"%0!33%$/543)$%
4(%&%22)4%"%!$
#!",%4)%3

&%22)4%"%!$

4/!#",/#+
Figure 5-17. AC Power Line Ferrite Bead

Panel Power-up Follow the steps below to power-up the 4010ES panel:
Sequence
1. Connect the negative (-) connector on the battery.
2. Connect the positive (+) connector on the battery.
3. Apply AC power.

5-16
Chapter 6
MSS Field Wiring
Introduction This chapter shows how 4010ES devices are wired to notification appliances. Most of the
connections shown here are reverse-polarity NACs, IDNet circuits, and power circuits.

In this chapter This chapter covers the following topics:

Topic Page

Power Supply Wiring Distances 6-2

MSS NAC Field Wiring Guidelines 6-4

MSS NAC Wiring 6-5

MSS IDNet Wiring 6-7

MSS Auxiliary Power Wiring 6-10

MSS Auxiliary Relay Wiring 6-12

6-1
Power Supply Wiring Distances

Overview Before wiring from any type of power supply to notification appliances, check Tables 6-1 and
6-2 for wiring distances.

Class A NAC Table 6-1 lists the maximum distances from the NAC terminal block to the last appliance in a
Wiring Table Class A configuration, depending on wire gauge and current. Use Table 6-1 to calculate wire
distances for your application if you are using Class A wiring.

Table 6-1. Class A Wiring Distances

Max Distance Max Distance Max Distance Max Distance


Alarm Current w/ 18 AWG w/ 16 AWG w/ 14 AWG w/ 12 AWG DC
@ 24V DC Resistance
(0.8231 mm2) (1.309 mm2) (2.081 mm2) (3.309 mm2)
0.25 A 420 ft (128 m) 667 ft (203 m) 1,063 ft (324 m) 1,691 ft (515 m) 6 Ohms
0.50 A 210 ft (64 m) 334 ft (102 m) 532 ft (162 m) 845 ft (258 m) 3 Ohms
0.75 A 140 ft (43 m) 222 ft (68 m) 354 ft (108 m) 564 ft (172 m) 2 Ohms
1.00 A 105 ft (32m) 167 ft (51 m) 266 ft (81 m) 423 ft (129 m) 1.5 Ohms
1.25 A 84 ft (26 m) 133 ft (41 m) 213 ft (65 m) 338 ft (103 m) 1.2 Ohms
1.50 A 70 ft (21 m) 111 ft (34 m) 177 ft (54 m) 282 ft (86 m) 1 Ohm
1.75 A 60 ft (18 m) 95 ft (29 m) 152 ft (46 m) 242 ft (74 m) 0.86 Ohm
2.00 A 53 ft (16 m) 83 ft (25 m) 133 ft (41 m) 211 ft (64 m) 0.75 Ohm
2.25 A 47 ft (14 m) 74 ft (23 m) 118 ft (36 m) 188 ft (57 m) 0.67 Ohm
2.50 A 42 ft (13 m) 67 ft (20 m) 106 ft (32 m) 169 ft (51 m) 0.60 Ohm
2.75 A 38 ft (12 m) 61 ft (19 m) 97 ft (30 m) 154 ft (47 m) 0.55 Ohm
3.00 A 35 ft (11 m) 56 ft (17 m) 89 ft (27 m) 141 ft (43 m) 0.50 Ohm

Notes:
• Max Distance = distance from MSS to last appliance.
• This table is calculated at 49 oC (120 oF). If you are installing in locations that could be
exposed to higher temperatures, refer to NEC Table 8.
• Distances are based on a 3 V drop, and take into account the worst-case panel output
voltage.
• If circuit integrity wire is used instead of housing cable in a fire-rated enclosure, reduce
wiring distances by 38 ft (12 m) for every 10 ft (3 m) of potential exposure.

6-2
Power Supply Wiring Distances, Continued

Class B NAC Table 6-2 lists the maximum distances from the NAC terminal block to the last appliance in a
Wiring Table Class B configuration, depending on wire gauge and current. Use Table 6-2 to calculate wire
distances for your application if you are using Class B wiring.

Table 6-2. Class B Wiring Distances

Max Distance Max Distance Max Distance Max Distance


Alarm Current w/ 18 AWG w/ 16 AWG w/ 14 AWG w/ 12 AWG DC
@ 24 VDC Resistance
(0.8231 mm2) (1.309 mm2) (2.081 mm2) (3.309 mm2)
0.25 A 840 ft (256 m) 1,335 ft (407 m) 2,126 ft (648 m) 3,382 ft (1,031 m) 12 Ohms
0.50 A 420 ft (128 m) 667 ft (203 m) 1,063 ft (324 m) 1,691 ft (515 m) 6 Ohms
0.75 A 280 ft (85 m) 445 ft (136 m) 709 ft (216 m) 1,127 ft (344 m) 4 Ohms
1.00 A 210 ft (64 m) 334 ft (102 m) 532 ft (162 m) 845 ft (258 m) 3 Ohms
1.25 A 168 ft (51 m) 267 ft (81 m) 425 ft (130 m) 676 ft (206 m) 2.4 Ohms
1.50 A 140 ft (43 m) 222 ft (68 m) 354 ft (108 m) 564 ft (172 m) 2 Ohms
1.75 A 120 ft (37 m) 191 ft (58 m) 304 ft (93 m) 483 ft (147 m) 1.71 Ohms
2.00 A 105 ft (32 m) 167 ft (51 m) 266 ft (81 m) 423 ft (129 m) 1.5 Ohms
2.25 A 93 ft (28 m) 148 ft (45 m) 236 ft (72 m) 376 ft (115 m) 1.33 Ohms
2.50 A 84 ft (26 m) 133 ft (41 m) 213 ft (65 m) 338 ft (103 m) 1.2 Ohms
2.75 A 76 ft (23 m) 121 ft (37 m) 193 ft (59 m) 307 ft (94 m) 1.09 Ohms
3.00 A 70 ft (21 m) 111 ft (34 m) 177 ft (54 m) 282 ft (86 m) 1 Ohm

Notes:
• Max Distance = distance from MSS to last appliance.
• This table is calculated at 49 oC (120 oF). If you are installing in locations that could be
exposed to higher temperatures, refer to NEC Table 8.
• Distances are based on a 3 V drop, and take into account the worst-case panel output
voltage.
• If circuit integrity wire is used instead of housing cable in a fire rated enclosure, reduce
wiring distances by 38 ft (12 m) for every 10 ft (3 m) of potential exposure.

6-3
MSS NAC Field Wiring Guidelines

Guidelines Review the following guidelines for NACs before you begin NAC field wiring.

• All wiring is 18 AWG (0.8231 mm2) (minimum) to 12 AWG (3.309 mm2) (maximum).
• All wiring is supervised and power-limited.
• The maximum alarm current is 3 A per circuit. The supervisory current is 2.03 mA at
24V DC.
• When NACs are used for REGULATED notification appliances, maximum current per
NAC is reduced to 2 A.
• The nominal voltage rating is 24 VDC, 2 Vp-p ripple (maximum).
• The total available current from the MSS is 8 A, unless it is used for REGULATED
24 VDC notification appliances, where the MSS is rated for 4 A notification. Any current
used for card power by modules plugged into the PDI, as well as any auxiliary 24 VDC
current, must be deducted from the total available current.
• Terminal designations “+” and “-” are for the alarm state.
• Compatible TrueAlert non-addressable appliances for NACs are:
- 4901-series Horn
- 4903-series A/V
- 4903-series S/V
- 4904-series V/O
- 4906-Multicandela series A/V, V/O, S/V, and others.
• A maximum of 70 appliances can be supported per circuit.
• Notification appliances are rated per individual nameplate label.
• Maintain correct polarity on terminal connections. Do not loop wires under terminals.

6-4
MSS NAC Wiring

Class A NAC To connect the MSS to reverse-polarity, non-addressable notification appliances using Class A
Wiring wiring, read the instructions below and refer to Figure 6-2.

1. When connecting the NAC wires to the terminal block, they need to pass through a ferrite
bead to reduce radiated emissions. Route the wires to the supplied ferrite bead. Loop the
wires twice through the bead and secure with two cable ties as shown in Figure 6-1. The
cable ties are supplied in the panel’s ship group.

#!",%4)%3

&%22)4%"%!$

Figure 6-1. NAC Ferrite Bead Wiring

2. Route wire (between 12 AWG [3.309 mm2] and 18 AWG [0.8231 mm2]) from the “B+”, “B-
”, and SHIELD (if used) outputs on TB2 of the MSS to the appropriate inputs on a periph-
eral notification appliance. Use NAC1, NAC2, NAC3 or NAC4.
3. Route wire from the first appliance to the next one. Repeat for each appliance.
4. Route wire from the last appliance to the A+ and A- inputs on the same NAC circuit of TB1
of the MSS.
5. Repeat steps 1 through 4 for each NAC output you want to use.
6. Leave the 10 KOhms, ½ W, brown/black/orange resistor (378-030) on each unused circuit.
The circuit must connect “B+” to “B-” terminals. No external end-of-line resistor is needed
for circuits in use.

BLK

RED 2
12 AWG (3.309 mm ) to
2
18 AWG (0.8231 mm )
TYPICAL
APPLIANCE

Important: Conductors must test free of RED BLK


all grounds.
TYPICAL Leave the 378-030 EOL
APPLIANCE
Resistor (10 KOhms, ½ W;
brown/black/orange) on
unused circuits

RED BLK

Ferrite beads
required for RF immunity
to CE specified levels.

" " ! ! " " ! ! " " ! ! " " ! ! !58
0/7%2

.!#.!#.!#.!#

Figure 6-2. Class A NAC Wiring

6-5
MSS NAC Wiring, Continued

Class B NAC To connect the MSS to appliances using Class B wiring, read the following instructions and
Wiring refer to Figure 6-3.

1. When connecting the NAC wires to the terminal block, they need to pass through a ferrite
bead to reduce radiated emissions. Route the wires to the supplied ferrite bead. Loop the
wires twice through the bead and secure with two cable ties as shown in Figure 6-1. The
cable ties are supplied in the panel’s ship group.
2. Route wire (between 12 AWG [3.309 mm2] and 18 AWG [0.8231 mm2]) from the B+, B-,
and SHIELD outputs on TB2 of the MSS to the appropriate inputs on a peripheral notifica-
tion appliance. Use NAC1, NAC2, NAC3 or NAC4.
3. Route wire from the first appliance to the next one. “T” tapping is not allowed. Repeat for
each appliance.
4. Route wire from the last appliance to the EOLR harness (10KOhms, 1/2 W: P/N 733-894,
PID# 4081-9008).
5. Repeat steps 1 through 4 for each NAC output you want to use.
6. Leave the factory installed EOL Resistor (10 KOhms, ½ W; brown/black/orange) on each
unused circuit. The circuit must connect “B+” to “B-” terminals.

4081-9008 EOL Harness


10K 1/2W (133-894)

RED BLK
RED
Leave the factory installed
TYPICAL EOL Resistor (10 KOhms, ½ W
APPLIANCE brown/black/orange) on
RED BLK
RED
unused circuits
Important: Conductors must test free of
TYPICAL
all grounds. APPLIANCE

2
12 AWG (3.309 mm ) to RED BLK
BLK
2
18 AWG (0.8231 mm )

Ferrite bead
required for RF
immunity to CE
specified levels.

" " ! ! " " ! ! " " ! ! " " ! ! !58
0/7%2

.!#.!#.!#.!#

Figure 6-3. Class B Wiring

6-6
MSS IDNet Wiring

Overview Up to 248 IDNet remote devices can be connected to IDNet using either Class A or Class B
wiring. Typical devices include smoke and heat sensors, QuickConnect sensors and a variety of
addressable input and/or output modules. Refer to datasheet S4090-0011 for a list of
compatible IDNet devices.

Class A wiring provides an alternate communication path that provides communications to


all devices when a single open circuit fault occurs. Class A wiring requires two wires to be
routed from the IDNet+ Primary Terminals (B+, B-) to each IDNet device, and then back to the
IDNet+ Secondary Terminals (A+, A-).

Note: Wiring is in/out. “T” tapping is not allowed.

Class B wiring allows “T” tapping, and typically results in less wiring used per installation
compared to Class A. IDNet wiring is inherently supervised due to individual device level
communications, and end-of-line resistors are not required.

Wiring Table 6-3 identifies the MSS with IDNet wiring parameters that must be considered when
Parameters applying this module. For additional wiring information, see the applicable installation
documentation or contact your authorized Simplex Product supplier.

Table 6-3. MSS with IDNet Wiring Parameters


IDNet Wiring Capacitance Parameters
Parameter Value
Maximum Supported Channel Capacitance; The sum of line-to-line capacitance, plus the capacitance of either line-to-
Total of both Isolated Outputs shield (if shield is present) = 0.6 µF (600 nF)
Capacitance between IDNet+ SLCs wiring
(between wires of the same polarity; plus to 1 µF maximum (this is for multiple IDNet+ channels)
plus, minus to minus)
IDNet+ Wiring Distance Limits (see notes below)
Class B Wiring, Total Channel Wiring Class A Wiring,
Channel Loading Parameters, Including T-Taps Total Channel Wiring Parameters
Up to 125 devices 126 to 248 devices Up to 125 devices 126 to 248 devices
Total Loop Resistance 50  maximum 35  maximum 50  maximum 35  maximum
2 12,500 ft (3.8 km) 4000 ft (1219 m) 2500 ft (76 2m)
18 AWG (0.82 mm )
16 AWG (1.31 mm2) 12,500 ft (3.8 km) 5000 ft (1524 m) 2500 ft (762 m)

14 AWG (2.08 mm2) 12,500 ft (3.8 km) 5000 ft (1524 m) 2500 ft (762 m)

12 AWG (3.31 mm2) 12,500 ft (3.8k m) 5000 ft (1524 m) 2500 ft (762 m)


Notes: Maximum wiring distance is determined by either reaching the maximum resistance, the maximum capacitance, or the
stated maximum distance, whichever occurs first. Class A maximum distances are to the farthest device on the loop
from either “B” or “A” terminals. For Class B wiring, the maximum distance to the farthest device is limited to the stated
Class A wiring distances.
Note: External wiring must be shielded (for lightning suppression) and 2081-
9044 Overvoltage Protectors must be installed at building exit and entrance
locations.
IDNet+ Wiring Considerations using 2081-
9044 Overvoltage Protectors Capacitance; each protector adds 0.006µF across the connected line.

(2081-9044 is UL listed to Standard 60950-1, Resistance; each protector adds 3  per line of series resistance; both IDNet
Standard for Safety of Information Technology lines are protected; 6  per protector will be added to total loop resistance.
Equipment) Maximum distance of a single protected wiring run is 3270 ft (1 km).
Refer to document number 574-832, 2081-9044 Overvoltage Protector
Installation Instructions, for additional information.

6-7
MSS IDNet Wiring, Continued

Class A Wiring To connect the MSS with IDNet to devices using Class A wiring, read the following
instructions and refer to Figure 6-4:
1. Route wiring from the IDNet Circuit Primary Terminals (B+, B-), and SHIELD Terminals on
TB1 of the IDNet+ module to the appropriate inputs on the first IDNet device.

Note: Shielded wiring is optional. SHIELD terminations are connected to Earth.

2. Route wiring from the first IDNet device to the next as in/out as shown in Figure 6-4. Repeat
for each device.
3. Route wiring from the last IDNet device to the IDNet Circuit Secondary Terminals (A+, A)
and SHIELD Terminals (if used) on TB1 of the IDNet+ module.
4. Ensure that circuit jumpers are configured for Class A operation.

IDNet Devices

+ - + - + - + - + - + -
18 to 12 AWG
(0.82 to 3.31 mm2)

IDNet Circuit A IDNet Circuit B


B+ B- SHLD A+ A- B+ B- SHLD A+ A-
TB1

MSS with IDNet

2 4 6 5 3 1

Position 3-5 and 4-6


P2 P1
Class A Wiring
1 3 5 6 4 2

Circuit A jumpers Circuit B jumpers

Notes: Set jumpers to Positions 3-5 and 4-6 to


select Style 6 (Class A) operation. (Refer
to P1 and P2 in Figure for correct
orientation)

For this application, the Shield (if present)


can be terminated at both ends for
improved EMI susceptibility.

Figure 6-4. Class A Wiring

Note: There are two considerations for addressing Class A wired IDNet devices connected to
the IDNet+ module:
1. If no remote isolators or isolator bases are on the loops, device addressing can be
assigned without concern for sequence.
2. If remote isolators or isolator bases are on the loops, the required addressing
approach is to start from the “B” side of the A Loop output and assign each successive
isolator a higher address than the isolator it proceeds. Follow this sequencing through
to the “B” side of the B Loop.

6-8
MSS IDNet Wiring, Continued

Class B Wiring Class B wiring requires the configuration jumpers to be set to Positions 1-3 and 2-4. Two
jumpers must be set for each circuit (refer to Figure 6-5 for locations). Each of the four IDNet
outputs provides short circuit isolation between itself and the others. A short on one output is
isolated from the others.

For Class B wiring only, both the B+, B- and A+, A- terminals are available for parallel
connections. A+ is connected to B+, and A- is connected to B- as shown in Figure 6-5.
Additionally, two wires can be connected to each screw terminal. The result is that for Class B
wiring only, four parallel output branch circuits can be connected at the IDNet+ module
terminals.

I D N e t D ev i c e s IDNet Devices

18 to 12 AWG
(0.82 to 3.31 mm2)

IDNet Circuit A IDNet Circuit B


B+ B- SHL D A + A- B+ B- SHL D A + A-
TB1

M S S w i t h I D N et

2 4 6 5 3 1

P o s i t i o n 1- 3 a n d 2 - 4
P2 P1
Clas s B Wi ring
1 3 5 6 4 2

Circuit A jumpers Circuit B jumpers

For Class B wiring only, up to 4 parallel


wiring “T” taps may be made at the output
o f t h e t e r m i na l b l o c k s Note: S e t j u m p e r s t o P o s i t i o ns 1 - 3 a n d 2 - 4 t o
select Class B operation. (Refer to P1 and
1 3 P2 in Figure for correct orientation)
2 4

B+ B- SHL D A+ A-

Figure 6-5. Class B Wiring

Note: There are two considerations for addressing Class B wired IDNet devices connected to
the IDNet+ module.
1. If no remote isolators or isolator bases are on the loops, device addressing can be
assigned without concern for sequence.
2. If remote isolators or isolator bases are on the loops, the required addressing approach
is to start at the A Loop output and assign each successive isolator a higher address
than the previous one. Follow this sequencing through to the B Loop, then to the C
Loop, and then to the D Loop.
3. For Class B wiring only, the “A” output and “B” output per loop are connected together
in parallel for wiring convenience.

6-9
MSS Auxiliary Power Wiring

Guidelines • All wiring is 18 AWG (0.8231 mm2) and 12 AWG (3.309 mm2).
• All wiring is power-limited.
• When a NAC is configured as an auxiliary power circuit, no end-of-line resistor is used.
• Auxiliary power may be taken from the dedicated auxiliary power tap or from an unused
NAC. The Aux power circuit can be used to power four-wire detectors. It can also control
unit accessories and other supplemental devices.
• If auxiliary power is taken from NAC terminals, the NAC must be configured as an
auxiliary power point type in the ES Panel Programmer.
• Remove end-of-line resistors from NACs when used for auxiliary power.
• External wiring from the dedicated auxiliary power tap is not supervised unless an end-of-
line relay is wired to auxiliary power, and Normally Open contacts are monitored by a
system power point. Relay current must be considered as part of the load. When NACs are
used as AUX power taps, they are supervised for overcurrent or short-circuit faults. When
only addressable devices are connected to the auxiliary power tap, an end-of-line relay is
not required. This is because the power for the addressable devices is supervised due to the
device being addressable.
• All wiring that leaves the building requires overvoltage protection. Install module
2081-9044 wherever wire enters or exits the building.
• Voltage rating: 24 VDC (nominal), 2 Vp-p ripple (maximum).
• The following devices are compatible with 24VDC aux. power:
- 2088-series relays and door holders
- 2098-series four-wire smoke detectors
- 4090-series IDNet ZAMs
- 4098-series four-wire smoke detectors and duct detectors
- 4190-9050/9051 4-20 mA ZAMs
- 4606-9102 LCD Annunciator
- 4100-94XX InfoAlarm Remote Annunciators
- 4100-7401, -7402 Graphic Annunciator Modules
• The total auxiliary current available is 4 A. The total current available for the entire MSS
is 8 A (special application) or 4 A regulated 24 VDC, including NAC, auxiliary, and card
power.

6-10
MSS Auxiliary Power Wiring, Continued

Wiring The MSS can connect to auxiliary power appliances via the dedicated auxiliary power tap. If
more power is needed, any of the three NAC outputs can be used for auxiliary power.

Ferrite bead
Required for RF
2
immunity to CE
12 AWG (3.309 mm ) to specified levels.
2
18 AWG (0.8231 mm ) Use kit 4100-5129.

2
12 AWG (3.309 mm ) to
2
AUXILIARY AUXILIARY AUXILIARY AUXILIARY 18 AWG (0.8231 mm )
POWER POWER POWER POWER
AUXILIARY
POWER
Dedicated auxiliary
power screw terminal
(configured in the
Programmer)

" " ! ! " " ! ! " " ! ! " " ! ! 66 Devices
!58
0/7%2
.!#.!#.!#.!#
4" 4" 4"
Primary Return

NAC points must be


reconfigured as
auxiliary power TB1 TB2 TB1 TB2
output points in the
programmer 4090-9117 4090-9117
24V
ISOLATOR 0V ISOLATOR

MSS To MSS

Class A aux power wiring requires the use


of 4090-9117 IDNet Power Isolators, as
shown above.

• Maximum allowed NAC current consumption (aux power plus NACs): 8 A


(Special Application) or 4 A regulated 24 VDC.
Maximum per NAC: 3 A
• Maximum allowed auxiliary power current consumption: 4 A (total supply).
Maximum per auxiliary output: 2 A
• Class A wiring is possible only if a 4090-9117 Power Isolator is used.
• International systems require ferrite beads. Use kit 4100-5129.
Figure 6-6. Auxiliary Power Wiring

6-11
MSS Auxiliary Relay Wiring

Guidelines The MSS includes one on-board, programmable relay.

• All wiring must be between 18 AWG (0.8231 mm2) and 12 AWG (3.309 mm2).
• When power through auxiliary contacts is provided by the MSS, wiring is power-limited.
• When power through auxiliary contacts is not provided by the MSS, use an in-line fuse
(208-165). If the power source is not power-limited to the requirements of UL864, wiring
is to be segregated to the non-power-limited spaces of the cabinet.
• The relay circuit is not supervised.
• The relay circuit is rated to switch 2 A at 30 VAC or 30 VDC, resistive load.
• Relay contacts are Form C dry contacts. Suppression is provided to Earth. Do not switch
voltages greater than rating, or damage may result.

Wiring Figure 6-7 shows MSS auxiliary relay wiring.

Dedicated auxiliary
)$.ET#IRCUIT )$.ET#IRCUIT .!#.!#.!#.!# relay terminal block
!58
" " 3(,$! ! " " 3(,$! ! " " ! ! " " ! ! " " ! ! " " ! ! 0/7%2

NORMALLY

.##./
OPEN
COMMON
NORMALLY
CLOSED
!58
4"

12 AWG (3.309 mm2) to


18 AWG (0.8231 mm2)

MSS

Figure 6-7. Auxiliary Relay Wiring

6-12
Chapter 7
PC Software Connections
Introduction The service port on the CPU allows the 4010ES panel to connect to a PC running utilities,
such as diagnostics, programming, CPU firmware downloading, and channel monitoring.

In this chapter This chapter covers the following topics:

Topic Page

Software Modes 7-2

Ethernet Service Port 7-4

7-1
Software Modes

Software Modes There are three basic software modes that the service port can be used to connect to:
• Service and Diagnostics Mode
• Data Transfer Interface Mode
• Master Bootloader Interface Mode

Each mode is described below.

Service and Diagnostics Mode:


This is the default functionality when a PC is connected to the FACP. On a PC, this mode
provides application startup messages, an ASCII interface to a UI command set for diagnostics,
and event reporting. A pre-configured terminal emulator is part of the 4010ES software and
can be launched from the programmer. The connection to a PC is made through the Ethernet
port. If it is not available, the serial port can be used instead.
Note: Ethernet connection is the preferred connection for service.

serial download or
standard Ethernet cable

Laptop/PC running 4010ES Panel


terminal emulation software

Figure 7-1. Service and Diagnostic Interface

Data Transfer Interface Mode:


In this mode, the ES Panel Programmer is used. This allows for slave downloading and
uploading a configuration or history log from the FACP. Connection to a PC is made through
the Ethernet port. If it is not available, the serial port can be used instead.

serial download or
standard Ethernet cable

Laptop/PC running 4010ES Panel


Programmer software

Figure 7-2. Data Transfer Interface

Continued on next page

7-2
Software Modes, Continued

Software Modes Master Bootloader Interface Mode:


This interface should be used when the Master executable is not functioning. It downloads the
CPU Exec firmware and the CFG.TXT file to the CPU via the serial or the Ethernet port.

serial download or
standard Ethernet cable

Laptop/PCrunning
Laptop/PC running 4010ES Panel
terminal emulation
programming software
file transfer running Bootloader

Figure 7-3. Bootloader Interface

7-3
Ethernet Service Port

Ethernet Service The Ethernet service port J7 on the CPU card is used to connect the panel to a local PC. See
Port Overview Figure 7-4 for the port location.

ETHERNET SERVICE PORT (J7)


RJ45 TYPE

Figure 7-4. Ethernet Service Port

The Ethernet service port connects to the front panel Ethernet connection through a standard
straight (non-crossover) Ethernet Patch Cable. The front panel Ethernet connection is located
on the top left of the 4010ES front panel. The service technician should connect his PC to the
CPU card through this front panel connection with a standard straight Ethernet cable. If this
connection is not available, you may plug the CPU Card connector J7 directly to the PC with a
standard straight Ethernet cable.

Note: If a BNIC card is used with the system, the CPU card Ethernet connection connects to it.
The BNIC card then connects to the Front Panel Ethernet Connection board
.

Figure 7-5. Front Panel Ethernet Service Port

7-4
Chapter 8
System Wiring Checkout and Earth Fault Diagnostics
Introduction This chapter describes how to check system wiring and run the Earth Fault Diagnostics in the
panel.

In this chapter This chapter covers the following topics:

Topic Page

Checking System Wiring 8-2

Earth Fault Diagnostics 8-4

Earth Fault Searching from the Front Panel 8-6

Earth Fault Search Results 8-9

8-1
Checking System Wiring

Overview This section contains instructions on how to use a multimeter to check system wiring

Using the When using the multimeter to check each circuit, make sure to adhere to the notes and
Multimeter instructions below.

Note:
• Ensure that no power is applied to the 4010ES fire alarm panel and that all wiring
is properly connected (terminal blocks, LED/switch module ribbon cables, etc.)
• Use the grounding lug with the Earth ground symbol inside the control panel for all
measurements to ground.
• Each circuit must test free of all grounds and extraneous (stray) voltages.
• If there are problems removing all power from the fire alarm system, there is an
alternate method of testing for stray voltage. The wires may be lifted from the
panel and terminated with appropriate resistors. Use 3.3 Kohms across conductor
pairs and 50 Kohms connected from any conductor under test to ground. All
conductors must read less than 1.0V AC or DC.

Use a multimeter as described in the steps below to check each circuit type.

1. At the control panel, locate wires from each initiating device or indicating appliance
circuit.
2. Check each circuit for extraneous voltage by setting the volt/ohm meter to AC. Place the
meter probes so that the black probe is on the “-” wire and the red probe is on the “+” wire.
Meter readings must show less than 1.0 VAC.
3. Set the multimeter to DC and repeat step 2. The meter must read less than 1.0 VDC.
4. Check all conductors for extraneous voltage to ground. The meter must read less than 1.0V
AC and DC.
5. Set the multimeter to OHMS and place the meter probes as described in step 2. Check the
circuits using the resistance measurements in Table 8-1. Locate and correct any abnormal
conditions at this time.

Note: Note: If the reading indicates an open circuit in an initiating circuit, make sure the smoke
detector heads are properly mounted and seated. The circuit may be open if smoke
detector power is not present, and if separately powered 4-wire devices are used.

6. Check all other system wiring to verify that each circuit is free of grounds and extraneous
voltages.

8-2
Checking System Wiring, Continued

Meter Readings Table 8-1 lists the correct meter readings for indicating appliances and initiating devices.

Table 8-1. Acceptable Zone and Signal Circuit Meter Readings

Circuit Type Meter Reading


Class B/Style B Initiating Device (Zone) Circuit
From zone + to zone – (each zone) 3.3 KOhms
From zone + to ground Infinity
From zone - to ground Infinity
Class A/Style D Initiating Device (Zone) Circuit
From zone + to zone – (each zone) Infinity
From zone + to ground Infinity
From zone - to ground Infinity
From zone + OUT to + IN Less than 25 Ohms
From zone - OUT to - IN Less than 25 Ohms
Class B/Style Y Notification Appliance Circuit (each signal circuit)
From + to ground Infinity
From - to ground Infinity

Resistance across circuit 10 KOhms


Class A/Style Z Notification Appliance Circuit (each signal circuit)
From + to ground Infinity
From - to ground Infinity
From B+ to A+ Less than 50 Ohms
From B- to A- Less than 50 Ohms

Resistance across circuit 10 KOhms


IDNET+ Loops (ZAMs and IAMs)
From IDNET+ “+” to ground Infinity
From IDNET+ “-” to ground Infinity

Note: Ground refers to Earth ground.

8-3
Earth Fault Diagnostics

Overview This section contains instructions on how to use the Earth Fault Search feature of the 4010ES
diagnostics menus. The minimum Earth Fault detection level for the 4010ES is 10 KOhms for
all circuits.
Earth Fault Search is a diagnostic search of external field wiring that assists in locating circuits
with earth faults. An earth fault occurs when an electrical circuit is shorted to ground. Although
most circuits operate with a single earth fault, multiple earth faults can disable communica-
tions. Because of this, earth faults must be located and repaired.
Earth Fault Search is conducted by the FACP. The diagnostic may be activated using either the
front panel interface or the Computer Port Protocol (CPP), via a service port.
The 4010ES supports two types of Earth Fault Searches:
• Location Search. Searches all circuits at a location, such as a transponder or the main
panel. For the purposes of Earth Fault Searching,
- A location is composed of a group of slaves connected to each other via 4010ES Comm
(local RUI).
- The main panel is defined as all slaves local to the Master CPU.
- A transponder denotes all slaves associated with a single Transponder Interface Card
(Remote InfoAlarm or 4009 TPS).
• IDNet Channel Search. Selectively enables channel isolators and repeaters to detect
which segment of the channel wiring has a fault. Earth faults are detected by one of the
following:
- A single designated power supply at a location. The power supply that detects the fault
is designated via a jumper setting on the power supply slave. For any given location,
only one power supply should detect earth faults.
- Each 4009 IDNet NAC Extender on an IDNet channel.

General Review the guidelines below before initiating an Earth Fault Search.
Guidelines • The Detect Earth Fault jumper (P3) must be installed at the MSS for earth fault detection
to occur. See Table 2-12 in Chapter 2 for details on that jumper.
• Only one power supply per location is configured to detect earth faults.
• For more reliable earth fault searching:
- Use IDNet channel isolators to isolate channel faults to a specific segment of channel
wiring.
- Set IDNet channel isolator addresses to the lowest IDNet device addresses, increasing
with communication distance from the IDNet card.
• If an earth fault is suspected on the IDNet channel with multiple isolators, start an IDNet
Channel Search before doing a Location Search. If the Location Search is done first, it
may not yield the correct location (this is a by-product of the extended amount of time
required for the IDNet channel to initialize during a Location Search).

Note: The 4009 IDNet NAC Extender has a common ground fault trouble that reports to the
panel without running the Earth Fault Search.

• Earth Fault Search detects only one fault at a time. Multiple faults require fixing the first
fault and then repeating the search.
• The FACP suspends normal operation for the duration of the Earth Fault Search.

Continued on next page

8-4
Earth Fault Diagnostics, Continued

General • Location Earth Fault Searches optionally allow exclusion of auxiliary power circuits from
Guidelines the search, so that modules connected to the 24 V auxiliary outputs can remain in
operation during the search.
• The option to exclude auxiliary power circuits does not apply to IDNet devices, because
the entire IDNet communication channel is isolated during each search.
• During the search, all related troubles are suppressed and a single trouble pseudo-point is
activated (P438).
• At the completion of the search, all slaves are restarted and normal panel operation
resumes.

IMPORTANT: The fire panel cannot provide fire protection during an Earth Fault
Search.

8-5
Earth Fault Searching from the Front Panel

Overview This section describes how to conduct an Earth Fault Search, from selecting the appropriate
access code to correcting the fault.

Access Level The panel must be at the appropriate access level (1, 2, 3, or 4) in order to run diagnostics. To
Selection get to the correct access level:
1. Press the Menu button. The following message comes up (press the Next or Previous
buttons, if necessary, to display it):
Press <NEXT> or <PREVIOUS> to scroll
Change Access Level?

2. Press the Enter button. Now you are prompted to log in or log out.
1=Login 2=Logout
CURRENT ACCESS LEVEL = x

3. Press the "1" key on the numeric keypad to log in, so that the passcode prompt comes up.
Enter a Passcode followed by <ENTER>

4. Enter the passcode and press the Enter button. ACCESS GRANTED displays briefly on the
LCD, and then the display goes back to:
1=Login 2=Logout
CURRENT ACCESS LEVEL = y

You can now open the diagnostic menu as described in the next topic.

Starting the Earth To start an Earth Fault Search:


Fault Search
1. If necessary, press the Menu button to access the menus.
2. Press the Previous or Next buttons until the diagnostic functions option appears:
Press <NEXT> or <PREVIOUS> to scroll
Diagnostic Functions?

3. Press the Enter button. Then press Next or Previous buttons until the Earth Fault Search
option appears:
Press <NEXT> or <PREVIOUS> to scroll
Earth Fault Search?

4. Press the Enter button. The following options become available when you press the Next and
Previous buttons:
Press <NEXT> or <PREVIOUS> to scroll
Location Search
Press <NEXT> or <PREVIOUS> to scroll
IDNet Channel Search

Press <NEXT> or <PREVIOUS> to scroll


Last Search Result

The search types are described below. When you have determined what kind of search to
initiate, display its option (one of the three shown above) and press the Enter button. Each
option is described below.

8-6
Earth Fault Searching from the Front Panel, Continued

Search Option A: • If you select the Location Search menu item, a list of cards to search becomes available.
Select Location Use the Next and Previous buttons to scroll through the list.
• If you find a card that you suspect is connected to a circuit with an earth ground, press the
Enter button when that circuit is shown.
• Before you can start the search, the Aux Power Select option comes up.
1=Exclude 2=Include
Exclude AUXPWR circuits from search?

• The number you select, 1 or 2, determines whether the auxiliary power circuit on the
selected board is searched for earth grounds. If you exclude the auxiliary power circuit
from the search, the circuit will continue to operate normally.
• Press 1 (or just press the Enter button) to exclude the card's auxiliary power circuits from
the search, or press 2 to remove auxiliary power circuits from normal operation and search
them for earth grounds.
• Now you are prompted to start the search. When the location you want to search is shown
and "Press <ENTER> to start search" displays, the search is ready to start. A sample is
shown below.
CARD 1, SYSTEM POWER SUPPLY
Press <ENTER> to start search

Note: The FACP suspends normal operation for the duration of the search.

• Press the Enter button to start the search.


• As the search progresses, watch the display for an indication of how much of the search
has been completed. The search can be aborted at any time if you press the Clear button.
Earth Search In-Progress, Please Wait...

Earth Search In-Progress, Please Wait...


40%

Skip ahead to "Completing the Search".

Search Option B: • If you select the IDNet Channel Search menu item, a list of IDNet channels to search
Select Location becomes available. Use the Next and Previous buttons to scroll through the list. When the
IDNet channel you want to search is shown and "Press <ENTER> to start search" displays,
the search is ready to start. A sample screen is shown below.
IDNET CHANNEL M12
Press <ENTER> to select for search

Note: The FACP suspends normal operation for the duration of the search.
• Press the Enter button to start the search.
• As the search progresses, watch the display for an indication of how much of the search
has been completed. The search can be aborted at any time if you press the Clear button.
Earth Search In-Progress, Please Wait...

Earth Search In-Progress, Please Wait...


40%

Skip ahead to "Completing the Search".

8-7
Earth Fault Searching from the Front Panel, Continued

Search Option C: This option simply displays the last Earth Fault Search result. If there has been no search since
Last Search the last system startup, or if the last search was aborted, the panel displays "RESULT NOT
Result AVAILABLE."

Completing the When a Location or IDNet Channel Search completes, all of the following occur:
Search
• All slaves automatically reset.
• The FACP turns off the Earth Fault Search trouble pseudo-point.
• The panel displays the specific fault information.

The panel can only return one Earth Fault Search result at a time. If another fault exists, it can
only be found via diagnostics after the first fault is cleared. Faults will continue to appear, one
by one, until each one has been found and corrected.

IMPORTANT: Once you have been directed to an earth ground fault and corrected it,
it is recommended that you restart the system (warm- or cold-start).

Continue to the next topic for a list of search results and their required actions.

8-8
Earth Fault Search Results

Overview There are several types of results that can display at the end of an Earth Fault Search. This
section covers all types of results.

IMPORTANT: Once you have been directed to an earth ground fault and
corrected it, it is recommended that you restart the system
(warm- or cold-start).

Non-Point Faults A non-point fault indicates a ground that cannot be traced to an addressable point (for example,
a shield).

Point Faults A point fault indicates a ground at a specific addressable point. Point faults can be found at any
point in the system that connects to field wiring.
Some IDNet channel point fault examples are illustrated below.
Fault not cleared. The message below shows that an IDNet channel that has been isolated for
fault detection still has the earth fault:
CARD 2, IDNET CARD (250 POINTS)
M1, EARTH FAULT SEARCH FAULT CLEAR FAIL

Fault between channel output and first isolator. The message below shows a fault between
the IDNet channel output and the first isolator on the line:
CARD 2, IDNET CARD (250 POINTS)
M1, CHANNEL OUTPUT EARTH FAULT

4009 IDNet NAC Extender/TrueAlert Addressable Controller faults. The message below
shows a fault detected on the 4009 IDNet NAC Extender before the repeater connected to that
circuit is turned on:
CARD 2, IDNET CARD (250 POINTS)
M1-18, 4009A NAC EARTH FAULT

Conversely, the following example shows a fault detected after the repeater connected to that
circuit is turned on:
CARD 2, IDNET CARD (250 POINTS)
M1-18, 4009A REPEATER EARTH FAULT

IDNet isolator fault. The message below shows a fault detected after the IDNet isolator was
turned on:
CARD 2, IDNET CARD (250 POINTS)
M1-3, IDNET ISOLATOR EARTH FAULT

8-9
Earth Fault Search Results, Continued

Fault Not Found If the message in the lower right corner of the LCD reads FAULT NOT FOUND (for a
Location Earth Fault Search) or FAULT CLEAR FAIL (for an IDNet Channel Earth Fault
Search), it means the search could not locate the fault, but it acknowledges that a fault exists.

There are five possible causes for this message:


• There are one or more internal wiring earth(s) in the system.
• There are system defects (hardware or software, such as a failed isolation circuit).
• An intermittent earth exists in the system (it occurs inconsistently and is therefore difficult
to track via diagnostics).
• The cable to the service port may be grounded due to the remote PC's 3-prong plug. Use a
non-grounded plug adapter to the remote PC to get rid of the earth ground.
• The fault is on an auxiliary output that was excluded from the search.

The problem may have to be found manually and then corrected in some of the above
scenarios.

No Fault If the message in the lower right corner of the LCD reads NO FAULT, it means the IDNet
channel search could not locate any earth faults on that channel.

Result Not If the message in the lower right corner of the LCD reads RESULT NOT AVAILABLE, it
Available means there is no result to view. This message comes up only when you have selected "Last
Search Result" on the menu.

8-10
Appendix A
ULC Programming Requirements
Introduction This appendix discusses the programming operations that must be met to comply with
Canadian Underwriter’s Laboratory (ULC) standards.

In this chapter This chapter covers the following topics:

Topic Page

Common Earth Fault Ground Indicator A-2

Simultaneous Alarm Display A-4

Setting Alarm Verification Timer to Canadian Operation A-7

Setting Alarm Reset / Inhibit Timer A-8

Alarm Cutout Timer A-9

A-1
Common Earth Fault Ground Indicator

Overview This application monitors a system pseudo (A112) that counts the number of ground faults that
occur on the system. Each time this counter increments (i.e., a ground fault occurs), a yellow
LED on the operator interface panel illuminates.

Step 1. Open CPU 1. Click on the Hardware Tab and expand the Unit 0, Box 1, Bay 1 icons to display the CPU
Card Properties Card. (Click on the + signs to the left of the Unit 0, Box 1, and Bay 1 icons to expand them.)
Dialog

Figure A-1. Selecting the CPU Card

2. Right click on the CPU card icon (it is highlighted in the example above) and select Proper-
ties. When the CPU card properties dialog appears, click on the Display tab as shown in the
example below.

Figure A-2. The Display Tab: Display Checkbox

A-2
Common Earth Fault Ground Indicator, Continued

Step 2. Program 1. Select one of the multicolor LEDs (0-5-11, 0-5-12, or 0-5-13) to program (Figure A-3).
the LED 2. Click on the Point Type drop down list box and select LEDYELLOW.
3. Click on the Mode drop down list box and select ON.
4. Enter A112 (no spaces) in the Reference Address field.

Figure A-3. The Display Tab: LEDs

A-3
Simultaneous Alarm Display

Overview ULC requires that every fire panel be capable of indicating the presence of up to eight
simultaneous alarms. The 48-LED Module supplied with some configurations of the 4010ES
panels is used for that purpose. Implementing this on the 4010ES is a two-step process, as
follows:

1. Create Annunciation Zone Lists. Divide the panel’s initiating devices into physical areas (by
floor, by department, etc.) Create a user-defined list for each zone and include all of the ini-
tiating devices for the zone in the list. See “Creating Annunciation Zone Lists” below for
information on doing this.
Note: Annunciation Zone Lists are only necessary if you are using addressable devices. If you
are using hardwired monitor zones, it is not necessary to create a list.
2. Program LED modes and reference addresses. This step associates the address of the zone
list with the LED and its mode.

Creating To create the annunciation zone lists – which are the lists containing the initiating devices for
Annunciation each zone – follow these steps.
Zone Lists
1. Click on the List Tab in the main ES Panel Programmer window.

2. Right click anywhere in the TagList dialog. A menu appears, containing a range of options.
Select Add List. A tag list, similar to the following, appears.

Figure A-4. The TagList Dialog

Continued on next page

A-4
Simultaneous Alarm Display, Continued

Creating 3. Select points for the list as follows.


Annunciation • Non-Adjacent Points. If the points required for the zone are not adjacent to one another,
Zone Lists select the points by holding down the shift key and then click the mouse cursor on each
point. When all of the non-adjacent points are selected, press the space key to select the
points and add them to the zone’s list. A >> symbol appears to the left of each point to
indicate that it is selected.
• Range of Adjacent Points. If the points required for the zone are adjacent to one another in
the tag list, highlight the first point then hold down the shift key and use the Up or Down
arrow key to highlight the points above or below the first point. When the full range of
points is highlighted, press the space key to select the points and add them to the zone’s
list. A >> symbol appears to the left of each point to indicate that it is selected.
4. Click the OK button in the TagList dialog. A labeling dialog appears, allowing you to spec-
ify the name for the list.

Figure A-5. The List Dialog


5. Enter a text name that uniquely identifies the zone (i.e., Floor1, Zone1, etc.). Click OK. The
list is added to the List Window. Repeat steps 1 through 5 for each annunciation zone list.

Programming the This section describes associating each pair of LEDs with the correct mode and reference
Address and address.
Mode for Each 1. Click on the Hardware Tab. Locate the icon for the 48 PLuggable LED Module (Door
LED Mount). Right click the mouse and select Properties. When the properties dialog for the card
appears, click on the Point Editing tab. A window similar to the following appears.

Figure A-6. The Point Editing Tab

Continued on next page

A-5
Simultaneous Alarm Display, Continued

Programming the 2. Do the following for each zone.


Address and a. Click on the line for a red LED.
Mode for Each
LED b. Click on the Mode drop down list box and select the FIRE mode.
c. Click on the Reference Address field and enter the identifier for one of the zone’s list
d. Click on the line for the yellow LED that is paired with the red LED you selected in Step
2a.
e. Click on the Mode drop down list box and select the TROUBLE mode.
f. Click on the Reference Address field and enter the identifier for the same list specified
in Step 2c.

The effect of this programming is that if any of the points within the zone’s list enters an alarm
state, the red LED illuminates. Likewise, if any of the points within the zone’s list enters a
trouble state, the yellow LED illuminates.

A-6
Setting Alarm Verification Timer to Canadian Operation

Introduction When you select Canadian operation for the alarm verification feature, the system operates as
follows:

• If a point specified within one of the alarm verification lists enters an alarm state, the
system delays the annunciation of the alarm for 15 seconds.
• When the 15-second timer expires, the system attempts to reset the initiating device for
five seconds.
• After the five-second timer expires, the system evaluates the state of the initiating device
for 10 additional seconds. After 10 seconds, if the device is still in alarm, the system
immediately annunciates the alarm.

Procedure 1. Click on the List tab to display the List window.


2. At the bottom of the List window, select the Alarm Verification tab.
3. Right Click on one of the lists and select Properties. The Alarm Verification Properties dia-
log shown below appears.
4. Click on the Alarm Verification tab.
5. Click on the drop down list box and select Canadian (ULC).

Setting this property for one alarm verification list sets it for all lists.

Figure A-7. Alarm Verification Properties: Alarm Verification Tab

A-7
Setting Alarm Reset / Inhibit Timer

Overview The Alarm Reset/Inhibit Timer system option disables the Alarm Silence and System Reset
keys for a user-definable duration that ranges from 1 to 60 minutes. The timer is activated only
by the first alarm (i.e., subsequent alarms do not reset the timer).

Note: The default setting is not enabled. This option must be enabled for Canadian jobs

Enabling Alarm To enable the Alarm Reset/Inhibit Timer, do the following:


Reset/Inhibit
Timer 1. Click on the Panel tab at the top of the programmer.
2. Click on the System Options tab at the bottom of the programmer. A screen similar to the
one shown below appears.
3. Click on the checkbox to the right of Alarm Silence/Reset Inhibit. Specify the timer value in
the Seconds box to the right of the checkbox.

Figure A-8. The Panel: System Options Tab

A-8
Alarm Cutout Timer

Overview The Alarm Cutout Timer allows you to set a duration (up to 10 minutes) that specifies how
long signals sound following an alarm. For example, with this option set at two minutes,
building signals sound for two minutes and then automatically stop. After the signals stop, the
alarm condition remains active at the panel.

Note: The default setting is not enabled. This option must be enabled for Canadian jobs

Enabling Alarm To enable the Alarm Cutout Timer, do the following:


Cutout Timer
1. Click on the Panel tab at the top of the programmer.
2. Click on the System Options tab at the bottom of the programmer. A screen similar to the
one shown below appears.
3. Click on the checkbox to the right of Alarm Cutout Timer. Specify the timer value in the
Seconds box to the right of the checkbox.

Figure A-9. System Options: Setting the Alarm Cutout Timer

A-9
Appendix B
UL Programming Requirements
Introduction This appendix identifies key UL programming requirements for the 4010ES FACP.

In this chapter This chapter covers the following topics:

Topic Page

Setting Alarm Verification to US Operation B-2

Alarm Cutout Timer B-3

Non-Steady Visual Evacuation System Option B-4

B-1
Setting Alarm Verification to US Operation

Overview When you select United States operation for the alarm verification feature, the system operates
as follows:

• If a point specified within one of the alarm verification lists enters an alarm state, the
system delays the annunciation of the alarm for 30 seconds.
• When the 15 second timer expires, the system attempts to reset the initiating device for
five seconds.
• After the five second timer expires, the system evaluates the state of the initiating device
for up to 120 additional seconds. If the device re-alarms during this time, the system
immediately annunciates the alarm.

Procedure 1. Click on the List tab to display the List window.


2. At the bottom of the List window, select the Alarm Verification tab.
3. Right Click on one of the lists and select Properties. The Alarm Verification Properties dia-
log shown below appears.
4. Click on the Alarm Verification tab.
5. Click on the drop down list box and select United States.

Setting this property for one alarm verification list sets it for all lists.

Figure B-1. Alarm Verification Properties: Alarm Verification Tab

B-2
Alarm Cutout Timer

Overview The Alarm Cutout Timer allows you to set a duration (up to 10 minutes) that specifies how
long signals sound following an alarm. For example, with this option set at two minutes,
building signals sound for two minutes and then automatically stop. After the signals stop, the
alarm condition remains active at the panel.

Note: The default setting is not enabled.

Enabling Alarm To enable the Alarm Cutout Timer, do the following:


Cutout Timer
1. Click on the Panel tab at the top of the programmer.
2. Click on the System Options tab at the bottom of the programmer. A screen similar to the
one shown below appears.
3. Click on the checkbooks to the right of Alarm Cutout Timer. Specify the timer value in the
Seconds box to the right of the checkbox.

Figure B-2. System Options: Setting the Alarm Cutout Timer

B-3
Non-Steady Visual Evacuation System Option

Overview When enabled, this option allows you to select the flash pattern output by Non-Steady Visual
Signals. The term Non-Steady Visual Signal refers to any visual notification appliance capable
of emitting a pattern of flashes (such as incandescent visuals).

The default setting for this option is not enabled.

When you enable this option, use the drop down list box to the right of the option to set the
flash pattern as follows:

• March Time. A coded signal that uses 120 beats per minute. Each beat consists of 1/4
second pulse on, 1/4 second off.
• Slow March Time. A coded signal that uses 60 beats per minute. Each beat consists of 1/2
second pulse on, 1/2 second off.
• Temporal. A five-pulse coding pattern consisting of five ½ second pulses, each separated
by a ½ second silence. Each three pulse group is separated by 1 ½ seconds of silence.

Note: This option cannot be used for public mode signaling as defined in Section 4-4 of
NFPA 72-99.

Figure B-3. System Options: Setting Non-Steady Visual Evacuation

B-4
Appendix C
Simplex Special Application NAC-Compatible
Notification Appliances and Accessories
Table C-1. Multi-Candela SmartSync (New Installations)

P/N Description Device Type

4906-9101 Visible Only 15/30/75/110cd Wall Mount Red Visible Only


4906-9103 Visible Only 15/30/75/110cd Wall Mount White Wall Mount

4906-9102 Visible Only 15/30/75/110cd Ceiling Mount Red Visible Only


4906-9104 Visible Only 15/30/75/110cd Ceiling Mount White Ceiling Mount

4906-9127 Audible Visible 15/30/75/110cd Wall Mount Red Audible Visible


4906-9129 Audible Visible 15/30/75/110cd Wall Mount White Wall Mount

4906-9128 Audible Visible 15/30/75/110cd Ceiling Mount Red Audible Visible


4906-9130 Audible Visible 15/30/75/110cd Ceiling Mount White Ceiling Mount

4906-9137 Audible Visible Multi-Tone Wall Mount Red Multitone Audible Visible
4906-9138 Audible Visible Multi-Tone Wall Mount White Wall Mount

4906-9133 Chime Visible Wall Mount Red Chime Visible


4906-9134 Chime Visible Wall Mount White Wall Mount

4906-9135 Chime Visible Ceiling Mount Red Chime Visible


4906-9136 Chime Visible Ceiling Mount White Ceiling Mount

4906-9151 Speaker Visible 15/30/75/110cd Wall Mount Red Speaker Visible


4906-9153 Speaker Visible 15/30/75/110cd Wall Mount White Wall Mount

Speaker Visible
4906-9154 Speaker Visible 15/30/75/110cd Ceiling Mount White
Ceiling Mount
4906-9109 Visible Only High Candela Wall Mount Red High Candela Visible Only
4906-9111 Visible Only High Candela Wall Mount White Wall Mount

4906-9110 Visible Only High Candela Ceiling Mount Red High Candela Visible Only
4906-9112 Visible Only High Candela Ceiling Mount White Ceiling Mount

4906-9139 Audible Visible High Candela Wall Mount Red High Candela Audible Visible
4906-9141 Audible Visible High Candela Wall Mount White Wall Mount

4906-9140 Audible Visible High Candela Ceiling Mount Red High Candela Audible Visible
4906-9142 Audible Visible High Candela Ceiling Mount White Ceiling Mount

4906-9105 Visible Only Weatherproof Wall Mount Red


Weatherproof Visible Only
4906-9106 Visible Only Weatherproof Wall Mount White
Wall Mount
4906-9113 Visible Only Weatherproof Wall Mount (CAN) Red
4906-9131 Audible Visible Weatherproof Wall Mount Red
Weatherproof Audible Visible
4906-9132 Audible Visible Weatherproof Wall Mount White
Wall Mount
4906-9143 Audible Visible Weatherproof Wall Mount (CAN) Red
4906-9107 Visible Only Non-Fire Emergency Alert Wall Mount White Non-Emergency Visible Only
4906-9108 Visible Only Non-Fire Emergency Alert Wall Mount Red Wall Mount

C-1
Special App. NAC-Compatible Notification App. and Acc., Continued

Table C-2. Audible Only Appliances

P/N Description Device Type

4901-9820 HORN 24VDC Red TrueAlert Non-Addressable (new installations) Audible Only
4901-9822 HORN 24VDC Red Audible Only Legacy Mount

Table C-3. Audible Visible and Speaker Visible Appliances

P/N Description Device Type


4903-9425 Audible Visible 15CD Red STD TrueAlert Non-Addressable
4903-9426 Audible Visible 75CD Red STD TrueAlert Non-Addressable
4903-9427 Audible Visible 110CD Red STD TrueAlert Non-Addressable Free Run or Sync
4903-9431 Audible Visible 15CD White STD TrueAlert Non-Addressable Audible Visible
4903-9432 Audible Visible 75CD White STD TrueAlert Non-Addressable
4903-9433 Audible Visible 110CD White STD TrueAlert Non-Addressable
4903-9356 Speaker Visible 15CD Red 25/70V TrueAlert Non-Addressable
4903-9357 Speaker Visible 75CD Red 25/70V TrueAlert Non-Addressable
4903-9358 Speaker Visible 110CD Red 25/70V TrueAlert Non-Addressable Free Run or Sync
4903-9359 Speaker Visible 15CD White 25/70V TrueAlert Non-Addressable Speaker Visible
4903-9360 Speaker Visible 75CD White 25/70V TrueAlert Non-Addressable
4903-9361 Speaker Visible 110CD White 25/70V TrueAlert Non-Addressable
4903-9196 Speaker Visible 15CD RND TrueALert Non-Addressable Free Run or Sync
4903-9197 Speaker Visible 30CD RND TrueAlert Non-Addressable Speaker Visible
4903-9198 Speaker Visible 110CD RND TrueAlert Non-Addressable Ceiling Mount

4903-9148 Speaker Visible 24VDC 30CD Red HORIZ Free Run or Sync
4903-9150 Speaker Visible 24VDC 15CD Red HORIZ Free Run or Sync Free Run or Sync
4903-9153 Speaker Visible 24VDC 15CD Red VER Free Run or Sync Speaker Visible
4903-9193 Speaker Visible 24VDC 15CD White HORIZ Free Run or Sync Legacy Housing

4903-9194 Speaker Visible 24VDC 30CD White HORIZ Free Run or Sync
4903-9252 Audible Visible 24VDC 15CD Red HOR Free Run or Sync
4903-9253 Audible Visible 24VDC 30CD Red HOR Free Run or Sync
4903-9254 Audible Visible 24VDC 110CD Red HOR Free Run or Sync Free Run or Sync
4903-9255 Audible Visible 24VDC 15CD Red VER Free Run or Sync Audible Visible
4903-9256 Audible Visible 24VDC 110CD Red VER Free Run or Sync Legacy Housing

4903-9257 Audible Visible 24VDC 15CD White HOR Free Run or Sync
4903-9258 Audible Visible 24VDC 30CD White HOR Free Run or Sync
4903-9417 Audible Visible 15CD Red SYNC TrueAlert Non-Addressable
4903-9418 Audible Visible 75CD Red SYNC TrueAlert Non-Addressable
4903-9419 Audible Visible 110CD Red SYNC TrueAlert Non-Addressable
Discontinued
4903-9428 Audible Visible 15CD White SYNC TrueAlert Non-Addressable
4903-9429 Audible Visible 75CD White SYNC TrueAlert Non-Addressable
4903-9430 Audible Visible 110CD White SYNC TrueAlert Non-Addressable

C-2
Special App. NAC-Compatible Notification App. and Acc., Continued

Table C-4. Visible Only Appliances (Retrofit)

P/N Description Device Type

4904-9174 Visible Only 24VDC 30CD Red VER Free Run or Sync
4904-9175 Visible Only 24VDC 110CD Red VER Free Run or Sync
4904-9176 Visible Only 24VDC 15CD Red VER Free Run or Sync
SmartSync Visible Only
4904-9177 Visible Only 24VDC 15CD White VER Free Run or Sync
Legacy Housing
4904-9178 Visible Only 24VDC 15CD Red HORIZ Free Run or Sync
4904-9180 Visible Only 24VDC 30CD Red HORIZ Free Run or Sync
4904-9181 Visible Only 24VDC 110CD White VER Free Run or Sync
4904-9182 Visible Only 24VDC 110CD Red HOR Free Run or Sync Discontinued
4904-9183 Visible Only 24VDC 15CD Red CEIL Free Run or Sync
4904-9184 Visible Only 24VDC 30CD Red CEIL Free Run or Sync
SmartSync Visible Only
4904-9185 Visible Only 24VDC 110CD Red CEIL Free Run or Sync
Ceiling Mount
4904-9345 Visible Only 24VDC 15CD White PLAIN Free Run or Sync
4904-9346 Visible Only 24VDC 30CD White PLAIN Free Run or Sync
4904-9168 Visible Only 15CD Red FREE-RUN TrueAlert Non-Addressable
4904-9169 Visible Only 75CD Red FREE-RUN TrueAlert Non-Addressable
4904-9170 Visible Only 110CD Red FREE-RUN TrueAlert Non-Addressable
Free-Run Visible Only
4904-9171 Visible Only 15CD White FREE-RUN TrueAlert Non-Addressable
4904-9172 Visible Only 75CD White FREE-RUN TrueAlert Non-Addressable
4904-9173 Visible Only 110CD White FREE-RUN TrueAlert Non-Addressable
4904-9331 Visible Only 15CD Red SYNC TrueAlert Non-Addressable
4904-9332 Visible Only 75CD Red SYNC TrueAlert Non-Addressable
4904-9333 Visible Only 110CD Red SYNC TrueAlert Non-Addressable
Discontinued
4904-9342 Visible Only 15CD White SYNC TrueAlert Non-Addressable
4904-9343 Visible Only 75CD White SYNC TrueAlert Non-Addressable
4904-9344 Visible Only 110CD White SYNC TrueAlert Non-Addressable

Table C-5. Miscellaneous

P/N Description

4090-9005 Suppression Release Peripheral (SRP)


4090-9006 Suppression Release Peripheral (SRP) w/ENCLOSURE
4905-9815 SMARTSYNC ADAPTER, TrueAlert Non-Addressable
4905-9938 SMARTSYNC CTL MODULE

C-3
Appendix D
Cooper Wheelock Appliances Compatible With 4010ES
Wheelock Protocol For Special Applications
Overview The tables in this appendix list Cooper Wheelock appliances compatible with 4010ES
Wheelock protocol for special applications.

Synchronizing
Horn Strobes Table D-1. Synchronizing Horn Strobes

Appliance Description
AS-241575W AS Series Horn Strobe. 24VDC, 15/75Cd, Wall Mount
AS-24MCW AS Series Horn Strobe. 24VDC, Multi-Cd, Wall Mount
AS-24MCC AS Series Horn Strobe. 24VDC, Multi-Cd, Ceiling Mount
AS-24MCWH AS Series Horn Strobe. 24VDC, Multi-High-Cd, Wall Mount
AS-24MCCH AS Series Horn Strobe. 24VDC, Multi-High-Cd, Ceiling Mount
ASWP-2475W, AS Series WP Horn Strobe. 24VDC, 30Cd, Wall or Ceiling Mount
ASWP-2475C
ASWP-24MCWH AS Series WP Horn Strobe. 24VDC, Multi-High-Cd, Wall Mount
ASWP-24MCCH AS Series WP Horn Strobe. 24VDC, Multi-High-Cd, Ceiling Mount
ASA-24MCW, AS Series Horn Strobe. 24VDC, Multi-Cd, Wall Mount. Amber/Blue
ASB-24MCW
ASA-24MCC, AS Series Horn Strobe. 24VDC, Multi-Cd, Ceiling Mount. Amber/Blue
ASB-24MCC
HSR HN STR, Red, 2-Wire, Wall, 12/24VDC, 3dB, 8CD, 5 Mount
HSRC HN STR, Red, 2-wire, Ceiling Mount, 12/24VDC, 3dB, 8 Cd, 5 Mount
HSRCS HN STR, Silver red, 2-wire, Ceiling Mount, 12/24VDC, 3dB, 8 Cd, 5 Mount
HSRS HN STR, Silver Red, 2-Wire, Wall, 12/24VDC, 3dB, 8CD, 5 Mount
HSW HN STR, White, 2-Wire, Wall, 12/24VDC, 3dB, 8CD, 5 Mount
HSWC HN STR, White, 2-wire, Ceiling Mount, 12/24VDC, 3dB, 8 Cd, 5 Mount
HSWCS HN STR, Silver white, 2-wire, Ceiling Mount, 12/24VDC, 3dB, 8 Cd, 5
Mount
HSWS HN STR, Silver White, 2-Wire, Wall, 12/24VDC, 3dB, 8CD, 5 Mount
HS4-241575W HS4 Series Horn Strobe. 24VDC, 15/75Cd, Wall Mount
HS4-24MCW HS4 Series Horn Strobe. 24VDC, Multi-Cd, Wall Mount
HS4-24MCWH HS4 Series Horn Strobe. 24VDC, Multi-High-Cd, Wall Mount
HS4-24MCC HS4 Series Horn Strobe. 24VDC, Multi-Cd, Ceiling Mount
NS-241575W NS Series Horn Strobe. 24VDC, 15/75Cd, Wall Mount
NS-24MCW NS Series Horn Strobe. 24VDC, Multi-Cd, Wall Mount
NS-24MCC NS Series Horn Strobe. 24VDC, Multi-Cd, Ceiling Mount
NS-24MCCH NS Series Horn Strobe. 24VDC, Multi-High-Cd, Ceiling Mount
ZNS-MCW ZNS Series Horn Strobe. 24VDC, Multi-Cd, Wall Mount
ZNS-MCWH ZNS Series Horn Strobe. 24VDC, Multi-High-Cd, Wall Mount
ZNS-24MCC ZNS Series Horn Strobe. 24VDC, Multi-Cd, Ceiling Mount
ZNS-24MCCH ZNS Series Horn Strobe. 24VDC, Multi-High-Cd, Ceiling Mount

D-1
Compatible Appliances, Continued

Synchronizing
Strobes
Table D-2. Synchronizing strobes

Appliance Description
RSS-241575W RSS Series Strobe. 24VDC, 15/75Cd, Wall Mount
RSSP-241575W RSSP Series Strobe. 12VDC or 24VDC, 15/75Cd, Wall Mount
RSS-24MCW, RSSP-24MCW RSS/RSSP Series Strobe. 24VDC, Multi-Cd, Wall Mount
RSS-24MCWH, RSSP-24MCWH RSS/RSSP Series Strobe. 24VDC, Multi-High-Cd, Wall Mount
RSS-24MCC, RSS-24MCCR RSS Series Strobe. 24VDC, Multi-Cd, Ceiling Mount (R=Round)
RSS-24MCCH, RSS-24MCCHR RSS Series Strobe. 24VDC, Multi-High-Cd, Ceiling Mount (R=Round)
RSSR-2415W, RSSR-2415C RSS Series Strobe. 24VDC, 15Cd, Red, Wall or Ceiling Mount
RSSR-2475W, RSSR-2475C RSS Series Strobe. 24VDC, 75Cd, Red, Wall or Ceiling Mount
RSSR-24110C RSS Series Strobe. 24VDC, 110Cd, Red, Ceiling Mount
RSSA-24110W, RSSB-24110W, RSS Series Strobe. 24VDC, 110Cd, Wall Mount. Amber/Blue/Green/
RSSG-24110W, RSSR-24110W Red.
RSSA-24MCC, RSSB-24MCC, RSS Series Strobe. 24VDC, Multi-Cd, Ceiling Mount. Amber/Blue/
RSSG-24MCC, RSSR-24MCC Green/Red.
RSSA-24MCCH, RSSB-24MCCH, RSS Series Strobe. 24VDC, Multi-High-Cd, Ceiling Mount. Amber/
RSSG-24MCCH, RSSR-24MCCH Blue/Green/Red.
RSSPA-24MCC RSSP Series Strobe. 24VDC, Multi-Cd, Ceiling Mount. Amber
RSSWPA-2475W RSS Series WP Strobe. 24VDC, Wall Mount. Amber
RSSWPA-24MCCH, RSSWPB-24MCCH, RSS Series WP Strobe. 24VDC, Multi-High-Cd, Ceiling Mount. Amber/
RSSWPG-24MCCH, RSSWPR-24MCCH Blue/Green/Red.
RSSWP-2475W, RSSWP-2475C RSS Series WP Strobe. 24VDC, 30Cd, Wall or Ceiling Mount
RSSWP-24MCWH RSS Series WP Strobe. 24VDC, Multi-High-Cd, Wall Mount
RSSWP-24MCCH RSS Series WP Strobe. 24VDC, Multi-High-Cd, Ceiling Mount
STR STR, Red, 2-Wire, Wall, 12/24VDC, 12/24VDC, 8CD, 5 Mount
STRC STR, Red, 2-wire, Ceiling Mount, 12/24VDC, 8 Cd, 5 Mount
STRCS STR, Silver red, 2-wire, Ceiling Mount, 12/24VDC, 8 Cd, 5 Mount
STRS STR, Silver Red, 2-Wire, Wall, 12/24VDC, 12/24VDC, 8CD, 5 Mount
STW STR, White, 2-Wire, Wall, 12/24VDC, 12/24VDC, 8CD, 5 Mount
STWC STR, White, 2-wire, Ceiling Mount, 12/24VDC, 8 Cd, 5 Mount
STWCS STR, Silver white, 2-wire, Ceiling Mount, 12/24VDC, 8 Cd, 5 Mount
STWS STR, Silver White, 2-Wire, Wall, 12/24VDC, 12/24VDC, 8CD, 5 Mount
ZRS-MCW ZRS Series Strobe. 24VDC, Multi-Cd, Wall Mount
ZRS-MCWH ZRS Series Strobe. 24VDC, Multi-High-Cd, Wall Mount
ZRS-24MCC ZRS Series Strobe. 24VDC, Multi-Cd, Ceiling Mount
ZRS-24MCCH ZRS Series Strobe. 24VDC, Multi-High-Cd, Ceiling Mount

D-2
Compatible Appliances, Continued

Appliances with
Synchronizing
Strobes
Table D-3. Appliances with synchronizing strobes

Appliance Description

(Only Strobe portion compatible with the 4008 Wheelock Protocol for Special Applications)
AMT-241575W, AMT Series Multi-Tone Horn Strobe. 24VDC, 15/75Cd, Wall Mount
AMT-241575W-NYC
AMT-24MCW AMT Series Multi-Tone Horn Strobe. 24VDC, Multi-Cd, Wall Mount
MT-241575W MT Series MT Horn Strobe. 24VDC, 15/75Cd, Wall Mount.
MT-24MCW MT Series Multi-Tone Horn Strobe. 24VDC, Multi-Cd, Wall Mount
MTWP-2475W, MTWP-2475C MTWP Series MT Horn Strobe. 24VDC, 30Cd, Wall or Ceiling Mount
MTWP-24MCWH MTWP Series MT Horn Strobe. 24VDC, Multi-High-Cd, Wall Mount
MTWP-24MCCH MTWP Series MT Horn Strobe. 24VDC, Multi-High-Cd, Ceiling
Mount
MTWPA-2475W, MTWPB-2475W MTWP Series Multi-Tone Horn Strobe. 24VDC, Wall Mount. Amber/
MTWPG-2475W, MTWPR-2475W Blue/Green/Red
MTA-24MCCH, MTB-24MCCH, MT Series Multi-Tone Horn Strobe. 24VDC, Multi-High-Cd, Wall
MTG-24MCCH, MTR-24MCCH Mount. Amber/Blue/Green/Red
MTWPA-24MCCH, MTWPB-24MCCH, MTWP Series Multi-Tone Horn Strobe. 24VDC, Multi-High-Cd, Wall
MTWPG-24MCCH,MTWPR-24MCCH Mount. Amber/Blue/Green/Red
ET70WP-2475W, ET70WP-2475C ET70WP Series Speaker Strobe. 24VDC, 30Cd, Wall or Ceiling
Mount
ET70WP-24185W ET70WP Series Speaker Strobe. 24VDC, 185Cd, Wall Mount
ET70WP-24177C ET70WP Series Speaker Strobe. 24VDC, 177Cd, Ceiling Mount
ET70WPA-2475 ET70WP Series Speaker Strobe. 24VDC, Wall or Ceiling Mt. Amber
CH70-241575W CH70 Series Chime Strobe. 24VDC, 15/75Cd, Wall Mount
CH70-24MCW CH70 Series Chime Strobe. 24VDC, Multi-Cd, Wall Mount
CH90-24MCC CH90 Series Chime Strobe. 24VDC, Multi-Cd, Ceiling Mount
CH70-24MCWH CH70 Series Chime Strobe. 24VDC, Multi-High-Cd, Wall Mount
CH90-24MCCH CH90 Series Chime Strobe. 24VDC, Multi-High-Cd, Ceiling Mount
E50-241575W E50 Series Speaker Strobe. 24VDC, 15/75Cd, Wall Mount
E50-24MCW E50 Series Speaker Strobe. 24VDC, Multi-Cd, Wall Mount
E50-24MCWH E50 Series Speaker Strobe. 24VDC, Multi-High-Cd, Wall Mount
E50A-24MCC, E50B-24MCC E50 Series Speaker Strobe. 24VDC, Multi-Cd, Ceiling Mt. Amber/
Blue
E60-24MCW E60 Series Speaker Strobe. 24VDC, Multi-Cd, Wall Mount
E60-24MCWH E60 Series Speaker Strobe. 24VDC, Multi-High-Cd, Wall Mount
E60-24MCC E60 Series Speaker Strobe. 24VDC, Multi-Cd, Ceiling Mount
E60-24MCCH E60 Series Speaker Strobe. 24VDC, Multi-High-Cd, Ceiling Mount
E70-241575W E70 Series Speaker Strobe. 24VDC, 15/75Cd, Wall Mount
E70-24MCW E70 Series Speaker Strobe. 24VDC, Multi-Cd, Wall Mount
E70-24MCWH E70 Series Speaker Strobe. 24VDC, Multi-High-Cd, Wall Mount
E70-24MCC, E90-24MCC E70/E90 Series Speaker Strobe. 24VDC, Multi-Cd, Ceiling Mount

Continued on next page

D-3
Compatible Appliances, Continued

Appliances with
Synchronizing
Strobes
Table D-3. Appliances with synchronizing strobes, Continued

Appliance Description

(Only Strobe portion compatible with the 4008 Wheelock Protocol for Special Applications)
E90-24MCCH E90 Series Speaker Strobe. 24VDC, Multi-High-Cd, Ceiling Mount
E60A-24MCC, E70A-24MCC, E60/E70/E90 Series Speaker Strobe. 24VDC, Multi-Cd, Ceiling
E70B-24MCC, E90A-24MCC, E90B-24MCC Mount. Amber/Blue
ET70-241575W, ET90-241575W ET70/ET90 Series Speaker Strobe. 24VDC, 15/75Cd, Wall Mount
ET70-24MCW ET70 Series Speaker Strobe. 24VDC, Multi-Cd, Wall Mount
ET70-24MCWH ET70 Series Speaker Strobe. 24VDC, Multi-High-Cd, Wall Mount
ET70-24MCC, ET90-24MCC ET70/ET90 Series Speaker Strobe. 24VDC, Multi-Cd, Ceiling Mount
ET70WPG-2475, ET70WPB-2475W ET70WP Series Speaker Strobe. 24VDC, Wall or Ceiling Mt. Green,
ET70WPG-2475W, ET70WPR-2475W Blue, Red
ET90-24MCCH ET90 Series Speaker Strobe. 24VDC, Multi-High-Cd, Ceiling Mount
ET80-241575W ET80 Series Speaker Strobe. 24VDC, 15/75Cd, Wall Mount
ET80-24MCW ET80 Series Speaker Strobe. 24VDC, Multi-Cd, Wall Mount
ET80-24MCWH ET80 Series Speaker Strobe. 24VDC, Multi-High-Cd, Wall Mount
S8-24MCC S8 Series Speaker Strobe. 24VDC, Multi-Cd, Ceiling Mount
S8-24MCCH S8 Series Speaker Strobe. 24VDC, Multi-High-Cd, Ceiling Mount
SA-S70-24MCW SA-S70 Series Amp-Speaker Strobe. 24VDC, Multi-Cd, Wall Mount
SA-S90-24MCC SA-S90 Series Amp-Speaker Strobe. 24VDC, Multi-Cd, Ceiling
Mount

Synchronizing
Horns
Table D-4. Synchronizing horns

Appliance Description
AH-24 AH Series Horn. 24VDC
AH-24WP AH Series Weatherproof Horn. 12VDC or 24VDC
HS-24 HS Series Horn. 24VDC
HNR Horn, Red, 2-Wire, Wall, 12/24VDC, 3dB, 5 Mount
HNRC Horn, Red, 2-wire, Ceiling Mount, 12/24V, 3dB, 5 Mount
HNRCS Horn, Silver red, 2-wire, Ceiling Mount, 12/24V, 3dB, 5 Mount
HNRS Horn, Silver Red, 2-Wire, Wall, 12/24VDC, 3dB, 5 Mount
HNW Horn, White, 2-Wire, Wall, 12/24VDC, 3dB, 5 Mount
HNWC Horn, White, 2-wire, Ceiling Mount, 12/24VDC, 3dB, 5 Mount
HNWCS Horn, Silver white, 2-wire, Ceiling Mount, 12/24VDC, 3dB, 5
Mount
HNWS Horn, Silver White, 2-Wire, Wall, 12/24VDC, 3dB, 5 Mount
MIZ-24S MIZ Series Horn. 24VDC
NH-12/24, NH-12/24R NH Series Horn. 12/24VDC (R=Round)
ZNH ZNH Series Horn. 12/24VDC

D-4
Compatible Appliances, Continued

Coded Audible
Appliances
Table D-5. Coded audible appliances

Appliance Description
AMT-12/24, AMT-12/24-NYC AMT Series Multi-Tone Horn. 12/24VDC, Wall or Ceiling
Mount
CH70, CH90 CH70/CH90 Series Chime. 24VDC, Wall or Ceiling Mount
CSX10-24-DC, CSXG10-24-DC CSX Series Bell. 24VDC, Wall Mount
MT-12/24, MT4-12/24 MT Series Multi-Tone Horn. 12/24VDC, Wall or Ceiling Mount

Non-
Synchronizing
Appliances
Table D-6. Non-synchronizing appliances

Appliance Description
MB-G6-24, MB-G10-24 MB Series Bell. 24V, Wall Mount

D-5
579-989
Rev. G

© 2011 - 2013 Tyco Fire Protection Products. Specifications and other information were current as of publication and are subject to change without notice.

You might also like