You are on page 1of 12

TUTORIAL

RS-485: Still the Most Robust


Communication
Table of Contents

Abstract...........................................................................................................................1
RS-485 vs. RS-422..............................................................................................................................2
An In-Depth Look at RS-485...........................................................................................................3
Challenges of the Industrial Environment.....................................................................................5
Protecting Systems from Harsh Environments.........................................................................5
Conclusion......................................................................................................................10
References......................................................................................................................10
Abstract

Despite the rise in popularity of wireless networks, wired serial networks continue to
provide the most robust, reliable communication, especially in harsh environments. These
well-engineered networks provide effective communication in industrial and building
automation applications, which require immunity from noise, electrostatic discharge and
voltage faults, all resulting in increased uptime. This tutorial reviews the RS-485 protocol
and discusses why it is widely used in industrial applications and the common problems
it solves.

www.maximintegrated.com 1 of 10
RS-485 vs. RS-422
An examination of the characteristics that make RS-485 the
most popular interface protocol for use in harsh, industrial
environments.
The RS-485 transceiver is the most with factory automation can corrupt
popular interface for implementing data transmission or physically destroy
the physical layer in harsh industrial the network.
and building automation networks for
serial port communications. This serial There are many types of data interface
interface standard provides single-path protocols commonly used today.
differential signaling over a twisted Each was developed with a specific
pair of wires for long-distance and application in mind with a particular set
high-speed transmission needed for of protocol specifications and structure.
industrial applications. The RS-485 These interfaces include CAN, RS-
standard provides a robust interface 232, RS-485/RS-422, I2C, I2S, LIN, SPI
that can withstand harsh environments. and SMBus, to name a few. Of these,
One common problem with industrial RS-485 and RS-422 are still the most
and building applications is that large reliable, especially in harsh industrial,
electrical transients from fast switching electrical environments such as factory
inductive loads, electrostatic discharge, and building automation.
and frequent voltage surges associated

SLAVE SLAVE
R
R

MASTER
D
R

R
R

SLAVE SLAVE SLAVE

Figure 1. RS-422 multidrop bus

2 of 10 www.maximintegrated.com
Although RS-485 and RS-422 are under maximum load. With this
similar, they are not the same. There enhanced multidrop capability, you can
are some differences between these two create networks of devices connected to
standards that need to be noted when a single RS-485 serial port. The greater
designing a system. noise immunity and multidrop capability
make RS-485 the serial connection of
RS-422 is best suited for industrial choice in industrial applications that The RS-485
environments that require only one require multiple distributed devices transceiver is the
bus master (driver). It provides a networked to a PLC or other controllers most popular
mechanism for transmitting data up for data collection, HMI, or similar interface for
to 10Mbps. RS-422 sends each signal operations. RS-485 is a superset of RS- implementing
using a twisted pair of wires to increase 422; thus, all RS-422 devices may be the physical
noise immunity and improve baud rate controlled by RS-485. layer in harsh
and cable length. RS-422 is specified industrial
for multidrop applications where only Typical applications for RS-485 are and building
one transmitter is connected to, and similar to those of RS-422: process automation
transmits on, a bus of up to 10 receivers automation (chemicals, brewing, paper networks for
(Figure 1) according to TIA/EIA-422. mills), factory automation (automotive serial port
Typical applications include process and metal fabrication), HVAC, security, communications.
automation (chemicals, brewing, paper motor control, and motion control.
mills), factory automation (automotive Thus, RS-485 is the more commonly
and metal fabrication), HVAC, security, used between the two standards due to
motor control, and motion control. its enhanced capability.

RS-485 offers greater flexibility when


more than one bus master/driver is
An In-Depth Look at RS-485
needed. It is an improvement over RS- As mentioned earlier, TIA/EIA-485,
422 because it increases the number of commonly known as RS-485, is the
devices from 10 to 32 per TIA/EIA-485 most broadly used interface in industrial
and has a wider common mode (-7V applications. RS-485 can be used over
to +12V versus ±7V) and slightly lower long distances up to 4000 feet and high
differential voltage range (±1.5 versus speeds greater than 40 Mbps for shorter
±2V) to ensure adequate signal voltages disances. The differential nature of RS-

www.maximintegrated.com 3 of 10
VCC

RO RO
R A A R
RE RE

DE B B DE

DI DI
D D

MASTER A B A B SLAVE

D
R

R
RO RE DE DI RO RE DE DI
SLAVE SLAVE

Figure 2. Multidrop half-duplex transceiver system commonly used in industrial applications

485 will enable long runs, but it will slow operations with a two-pair bus (4-
down as the cable length increases. In wire). It can handle up to 32 drivers
addition to the distance, data rate will and up to 32 receivers in a half-duplex
be affected by the wire gauge and the multidrop configuration. New devices
number of nodes on the network. RS-485 have emerged that feature 1/4-unit-load,
with preempahsis like the MAX3291 can and even 1/8-unit-load receiver input
significantly improve on bandwidth and impedances, such as the MAX13448E,
distance for applications that require it. which allows 128 to 256 receivers on the
same bus. With this enhanced multidrop
The RS-485 interface can be used in capability, you can create networks of
half-duplex mode with a single-pair devices connected to a single RS-485
transmission bus or full-duplex mode serial port as shown in Figure 2.
for simultaneous transmit-and-receive

D +1.5V -1.5V +200mV -200mV R

Figure 3. RS-485 minimum bus signal levels

4 of 10 www.maximintegrated.com
The receiver input sensitivity is ±200mV. in these systems are subject to harsh
This means that to recognize a 1 or a 0 electrical environments.
bit, the receiver must see signal levels
DC-DC converters used in industrial
greater than +200mV for zero and lower
applications include those with high
than -200mV for one (Figure 3). Noise
input voltages and isolated power
that falls in the range between ±200mV
outputs. Many applications use 24V Maxim’s
is essentially blocked. The differential
or 48V DC inputs to provide power to RS-485
format produces effective common-
distributed applications that are not transceiver ICs
mode noise cancellation. Minimum
line powered. Once down converted to feature internal
receiver input impedance is 12kΩ,
12V or 5V, point-of-load conversion can protection such
and the driver output voltage is ±1.5V
be applied. Applications that maintain as high ESD-
minimum, ±5V maximum.
communications with remote sensors immunity,
and actuators need protection against fault protection
Challenges of the Industrial the effects of transients, EMI, and against large
Environment differing ground potentials. voltage
spikes and hot-
Designers of industrial systems face Companies such as Maxim Integrated
swap capability
many difficult challenges to assure robust take great care in ensuring that
for error-free
operation in the face of environmental ICs for industrial applications are
data
conditions that may damage the robust and able to withstand harsh
transmission.
hardware or negatively affect the digital electrical environments. Maxim’s RS-
communications. 485 transceiver ICs feature internal
protection such as high ESD-immunity,
One example is automatic control fault protection against large voltage
of process machinery in factory spikes and hot-swap capability for error-
automation. A process controller free data transmission.
monitors and measures operational
and environmental variables and sends Protecting Systems
actuation commands out to control from Harsh Electrical
devices or alarms. The controllers are Environments
usually microcontroller-based machines
with architecture optimized to meet the The following are protection features
needs of the factory and the application. that may be incorporated into RS-485
Point-to-point data communication line transceivers.

www.maximintegrated.com 5 of 10
RUPTURED
PASSIVATION
DIELECTRIC FAILURE
& CONTACT SPIKING
ELECTROTHERMAL
MIGRATION

ESD is SPLATTERED
a serious ALUMINUM

industrial
problem Figure 4. ICs with inadequate ESD protection are subject to catastrophic failure
estimated
to cause Extended ESD annually. ESD events that occur in the
billions of Electrostatic discharge (ESD), an field can cause individual component
dollars in overvoltage event, occurs when two failure and sometimes catastrophic
materials with different electrical system failures.
damages
potentials make contact, transfer
annually.
stored static charges, and generate a External ESD diodes and other discreet
spark. ESD sparks are often produced components can be used to protect data
by the interaction of people with lines. Many IC devices integrate some
their surroundings. These inadvertent degree of ESD protection and require
sparks can change the properties of a no further external protection for the
semiconductor device, degrading or IC itself. Figure 5 shows a simplified
destroying it entirely. ESD can also functional diagram of a common
threaten an electronic system when integrated protection scheme. Voltage
someone replaces a cable or even touches spikes at the signal input/output (I/O)
an I/O port. Discharges that accompany are clamped to VCC or GND and protect
these routine events can disable the the internal circuitry. Many interface
port by destroying one or more of the products and analog switches integrate
interface ICs (Figure 4). Such failures ESD protection designed to comply with
can be expensive—they raise the cost IEC 61000-4-2 standards.
of warranty repairs while diminishing
the product’s perceived quality. ESD is Maxim Integrated has invested a
a serious industrial problem estimated substantial effort in developing ICs with
to cause billions of dollars in damages robust internal ESD protection. Starting

6 of 10 www.maximintegrated.com
addition, they are protected against
VCC
ESD strikes while powered up, powered
down, and in shutdown mode.
SIGNAL I/O

Fault Protection
GND The driver outputs/receiver inputs of
(OR NEGATIVE Faults, such as
VOLTAGE RAIL) IC RS-485 devices in industrial network
overvoltages,
applications often experience voltage
Figure 5. Simplified integrated ESD can be caused
faults resulting from stray voltage
protection circuitry by wiring
spikes. Faults are different from ESD
errors, loose
events. While ESD events occur within
with RS-232 and RS-485 interface ICs, connections,
a short time range less than 100ns,
Maxim has become a leader in ESD pinched or
faults generally occur over a sustained
protection for interface transceivers. faulty cables
period of approximately 200µs or
These devices withstand the application or even solder
longer. Faults, such as overvoltages,
of IEC 61000-4-2 and JEDEC JS-001 ESD debris that
can be caused by wiring errors, loose
events directly to their I/O pins. This causes the
connections, pinched or faulty cables,
approach is robust, readily available, powerline
or even solder debris that causes the
requires no external real estate, and to contact
powerline to contact the data connection
costs less than most alternatives. the data
on the PCB or in the connector, can be
All Maxim devices incorporate ESD-
connection
exposed to high voltages for seconds or
protected structures on all pins to
on the PCB
even minutes before failure. This can
protect against electrostatic discharges
or in the
be catastrophic since many industrial
encountered during handling and
connector.
power supplies exceed +24V. Any
assembly. Transceivers with high ESD contact with a data line ensures the
protection, such as the MAX3483AE/ destruction of a standard, unprotected
MAX3485AE family, feature ±20kV ESD RS-485 transceiver.
protection on their transmitter-output
and receiver-input pins. Not only will To protect against these faults, ordinary
these transceivers not be damaged by RS-485 devices require costly discrete
ESD strikes less than their rated value, external protection circuitry or devices.
but they will continue to work normally Fault-protected RS-485 transceivers
without the need to cycle power. In offer overvoltage protection as high

www.maximintegrated.com 7 of 10
as ±40V, ±60V, and even ±80V on and -200mV. This guaranteed logic-
communication bus lines. Maxim offers high is achieved by setting the receiver
many fault-protected RS-485/RS-422 threshold between -50mV and -200mV.
Fail-Safe
transceivers such as the MAX13442E– If the differential receiver input voltage
Receivers
MAX13444E that can survive high DC (VA - VB) is greater than or equal to
guarantee
voltages on the data pins. To reduce -50mV, RO is logic-high. If (VA - VB)
a logic-high
system complexity and the need for is less than or equal to -200mV, RO is
receiver when
external protection, the driver outputs logic-low. In the case of a terminated
the receiver
inputs are and receiver inputs of these fault- bus with all transmitters disabled, the
opened or if all protected devices can withstand voltage receiver’s differential input voltage is
transmitters on faults of up to ±80V with respect to pulled to ground by the termination.
a terminated ground without damage. Protection is This results in a logic-high with a 50mV
bus are guaranteed regardless of whether the minimum noise margin. Unlike previous
disabled. device is active, shut down, or without fail-safe devices, the -50mV to -200mV
power. This makes them the most threshold complies with the ±200mV
Hot-Swap robust transceivers in the industry and, EIA/TIA-485 standard.
Circuitry therefore, ideal for industrial applications.
eliminates These devices are designed to survive Hot-Swap Capability
false overvoltage faults such as direct shorts Hot-swap circuitry eliminates false
transitions to power supplies, miswiring faults, transitions on the data cable during
on the data connector failures, cable crushes, and circuit initialization or connection to a
cable during tool mis-applications. live backplane. Short-circuit current
initialization limiting and thermal-shutdown circuitry
or connection True Fail-Safe Receivers protect the driver against excessive
to a live An important feature of many RS-485 power dissipation.
backplane. transceivers is the true fail-safe circuitry,
which guarantees a logic-high receiver Inserting circuit boards into a hot, or
output when the receiver inputs are powered, backplane may cause voltage
opened or shortened, or if all transmitters transients on DE, DE/RE, RE, and
on a terminated bus are disabled (high receiver inputs A and B that can lead to
impedance). True fail-safe solved the data errors. For example, upon initial
problem of a collapsing bus by changing circuit board insertion, the processor
the receiver input threshold to a slightly undergoes a power-up sequence. During
negative differential voltage of -50mV this period, the high-impedance state of

8 of 10 www.maximintegrated.com
the output drivers makes them unable How does this internal hot-swap circuitry
to drive the transceiver enable inputs work? At the driver-enable input (DE),
to a defined logic level. Meanwhile, there are two nMOS devices, M1 and
leakage currents of up to 10µA from the M2 (Figure 6). When VCC ramps from
high-impedance output, or capacitively zero, an internal 15µs timer turns on M2
coupled noise from VCC or GND, could and sets the SR latch, which also turns
cause an input to drift to an incorrect on M1. Transistors M2, a 2mA current
logic state. To prevent such a condition sink, and M1, a 100µA current sink, pull
from occurring, devices such as the DE to GND through a 5.6kΩ resistor. M2
MAX3440E–MAX3443E feature hot- pulls DE to the disabled state against
swap input circuitry on DE, DE/RE, and an external parasitic capacitance up to
RE to guard against unwanted driver 100pF that may drive DE high. After
activation during hot-swap situations. 15µs, the timer deactivates M2 while
When VCC rises, an internal pulldown M1 remains on, holding DE low against
(or pullup for RE) circuit holds DE low three-state leakage currents that may
for at least 10µs and until the current drive DE high. M1 remains on until an
into DE exceeds 200µA. After the initial external current source overcomes the
power-up sequence, the pulldown circuit required input current. At this time,
becomes transparent, resetting the hot- the SR latch resets M1 and turns off.
swap tolerable input. When M1 turns off, DE reverts to a
standard, high-impedance CMOS input.
Whenever VCC drops below 1V, the input
VCC

15µs
is reset. A complementary circuit for RE
TIMER
uses two pMOS devices to pull RE to
TIMER
VCC.

DE 5.6kΩ
(HOT SWAP)

2mA
100µA

M1 M2

Figure 6. Simplified structure of the


driver enable pin (DE)

www.maximintegrated.com 9 of 10
Conclusion
Industrial system applications, such as factory automation, are subjected to harsh electrical
environments. It is vitally important for the system-level designer to take into account voltage
transients from several sources when developing the hardware that will withstand these conditions.
Most data communications networks rely on the robustness of the RS-485 protocol standard
along with special safety features incorporated into the transceiver ICs to withstand these effects.
Structures such as extended ESD protection, high-voltage fault protection, and hot-swap capability
safeguard against these events to help maintain system reliability.

References
1. Application note 4491, “Damage from a Lightning Bolt or a Spark—It Depends on How Tall You Are!”
2. Application note 5260, “Design Considerations for a Harsh Industrial Environment”
3. Application note 639, “Maxim Leads the Way in ESD Protection”

Learn more
For more information, visit:
www.maximintegrated.com

© 2017 Maxim Integrated Products, Inc. All rights reserved. Maxim Integrated and the Maxim Integrated logo are trademarks of Maxim Integrated Products, Inc., in the
United States and other jurisdictions throughout the world. All other company names may be trade names or trademarks of their respective owners.

10 of 10