You are on page 1of 12

System components / Modules in the power section

Training objectives:
You are informed about

• the electrical design of the


powermodules

• the options for 4Q-operation

• the components for the modular


design of the device types:
- Booksize
- Chassis / Cabinet segments

• overload capability, cable lengths


and attainable output voltage

SINAMICS Date:
File:
06/03/2007
ABU DHABI: Page 2 - 1
SITRAIN Training for
Automation and Drives
Siemens AG 2007. All rights reserved.

System components / Modules in the power section


Content Page
Component overview, example SINAMICS S120............................................................................. 3
Motor Module (Combination Booksize/Chassis possible on same CU320)........................................ 4
Electrical design of the power modules............................................................................................. 5
Pulse frequency / Active Line Module, Motor Module........................................................................ 6
Overview of infeed units................................................................................................................... 7
Electrical design of the power module S150..................................................................................... 8
Active Line Module / Circuit design: Chassis.................................................................................... 9
Electrical design of the power modules G130, G150......................................................................... 10
Basic Line Module / Circuit design: Chassis..................................................................................... 11
Smart Line Module / Circuit design: Chassis..................................................................................... 12
DC-link components......................................................................................................................... 13
DC-link components......................................................................................................................... 14
DC-link connection........................................................................................................................... 15
Electronic draw-out unit for chassis / Cabinet................................................................................... 16
Current actual value sensing / Thermal model.................................................................................. 17
System components on the motor-side............................................................................................. 18
Overload capability of Booksize-units............................................................................................... 19
Overload capability of Chassis-units................................................................................................. 20
Multi-parallel operation of converters S120 / AIM,ALM + MoMo........................................................ 21
Cable lengths................................................................................................................................... 22
Overall cable lengths of Booksize-units (per motor).......................................................................... 23
Attainable output voltage.................................................................................................................. 24

SINAMICS Date:
File:
06/03/2007
ABU DHABI: Page 2 - 2
SITRAIN Training for
Automation and Drives
Siemens AG 2007. All rights reserved.
Component overview, example SINAMICS S120

• SINAMICS S120 solves


complex drive tasks for a
large range of industrial
applications and is
therefore designed as a
modular system.

• The user can choose from


many harmonized
components and functions
to create a solution that
best meets his
requirements.

SINAMICS Date:
File:
06/03/2007
ABU DHABI: Page 2 - 3
SITRAIN Training for
Automation and Drives
Siemens AG 2007. All rights reserved.

Motor Module (Combination Booksize/Chassis possible on same CU320)


Booksize Booksize Chassis 400V Chassis 690V
Single MM Double MM
1.6 – 107 kW 2x1.6 – 2x9.7 kW 110 – 1405 kW 85 – 1270 kW

Booksize / special features FS F FS G FS H FS J


„ Diagnostic LEDs
„ short circuit and earth fault proof sine filter dv/dt filter; VPL1 choke
„ integrated safety functions “Safe 90-200 kW (400V/4kHz/SVM) 75-1200 kW 75-1200 kW
standstill” and ”Safe brake control“
„ integrated motor brake control
(up to 132 A)

1 Voltage Peak Limiter

SINAMICS Date:
File:
06/03/2007
ABU DHABI: Page 2 - 4
SITRAIN Training for
Automation and Drives
Siemens AG 2007. All rights reserved.
Electrical design of the power modules

U, f = constant U, f = variable

U Udc U
AC - DC DC - AC

i.e. 3AC, 400V, 50 Hz depending on line voltage or controlled

Rectifier DC-link Inverter

U1 U2
V1 V2
W1 W2
depending on line module
M

Line Line Module DC-link Motor Module Motor

SINAMICS Date:
File:
06/03/2007
ABU DHABI: Page 2 - 5
SITRAIN Training for
Automation and Drives
Siemens AG 2007. All rights reserved.

Pulse frequency / Active Line Module, Motor Module

2 kHz --> 500 µs

Pulse width modulation / Active Line Module Pulse width modulation / Motor Module

Framesize Switching frequency Switching frequency Current contr.


Active Line Module Motor Module sample time
s
losse
F, G (400V) 4.0 kHz 2.0 kHz (.... 8.0 kHz) 250 μs hing
Switc forma
nce
F, G (690V) 4.0 kHz 1.25 kHz (.... 5.0 kHz) 400 μs
am ic per
Dyn
H, J (400V) 2.0 / 4.0 kHz 1.25 kHz (.... 5.0 kHz) 400 μs
1,25 pulse frequency (kHz) 8
Booksize 8.0 kHz 2.5 / 4.0 kHz (.... 16 kHz) 400 / 250 μs

SINAMICS Date:
File:
06/03/2007
ABU DHABI: Page 2 - 6
SITRAIN Training for
Automation and Drives
Siemens AG 2007. All rights reserved.
Overview of infeed units

Active • Active Interface Module (AIM)


Infeed = • Active Line Module (ALM)
Actively controlled IGBT rectifier

Infeed
Infeed Smart • Line connection with choke
AC
AC // DC
DC Infeed = • Smart Line Module (SLM)
Line commutated IGBT rectifier

Basic • Line connection with choke


= • Basic Line Module (BLM)
Infeed
Line commutated B6-circuit rectifier

Properties Basic Infeed Smart Infeed Active Infeed


Operating mode 1Q operation / 4Q operation, 4Q operation,
uncontrolled uncontrolled controlled
Line supply fluctuations influence V_DC influence V_DC are compensated
Line feedback no yes yes
Harmonics to be considered to be considered can be neglected
Reactive power compens. no no yes
available for G130, G150 S150
S120 (type-depending) S120 (type-depending) S120 (type-depending)

SINAMICS Date:
File:
06/03/2007
ABU DHABI: Page 2 - 7
SITRAIN Training for
Automation and Drives
Siemens AG 2007. All rights reserved.

Electrical design of the power module S150

U, f = constant U, f = variable

U Udc U
AC - DC DC - AC

i.e. 3AC, 400V, 50 Hz controlled to setpoint voltage

Pre-charging Rectifier DC-link Inverter

U1 U2
V1 V2
W1 W2

Line Motor

DC-link

SINAMICS Date:
File:
06/03/2007
ABU DHABI: Page 2 - 8
SITRAIN Training for
Automation and Drives
Siemens AG 2007. All rights reserved.
Active Line Module / Circuit design: Chassis

Main features: Booksize Chassis 400 / 690 V


ƒ Controlled rectifying / regenerating 16 - 120 kW 132-900 / 560-1400 kW
unit with IGBT technology
ƒ Unrestricted regenerative operation ƒ Power block with
ƒ Boost operation enables controlled IGBT‘s, DC caps
DC-link voltage and sinusoidal line
ƒ Current transformer
current
ƒ Power factor control to obtain ƒ Electronic draw-out
cos φ = 1 unit CIB, CU320
ƒ Fan

FS J

SINAMICS Date:
File:
06/03/2007
ABU DHABI: Page 2 - 9
SITRAIN Training for
Automation and Drives
Siemens AG 2007. All rights reserved.

Electrical design of the power modules G130, G150

U, f = constant U, f = variable

U Udc U
AC - DC DC - AC
constant

i.e. 3AC, 400V, 50 Hz appr. 1,35 * 400V = 540V DC

Pre-charging Rectifier DC-link Inverter

RVL
U1 U2
V1 V2
W1 W2

RVL

Line Motor

DC-link Braking Chopper

SINAMICS Date:
File:
06/03/2007
ABU DHABI: Page 2 - 10
SITRAIN Training for
Automation and Drives
Siemens AG 2007. All rights reserved.
Basic Line Module / Circuit design: Chassis

Main features: Booksize Chassis 400 / 690 V


ƒ Line commutated rectifier unit under prep. 200-710 / 250-1100 kW
with thyristor technology
(B6 circuit) ƒ Thyristors and
ƒ No line feedback possible Thyristor control
ƒ Power block
S120 chassis and cabinet
segments with pre-charging by ƒ Slot for CU320,
means of firing angle control. electronic draw-out unit
ƒ Fan
S120 Booksize and G130/G150
with pre-charging via diode rectifier ƒ Fan fuses
and pre-charging resistors. FS G

SINAMICS Date:
File:
06/03/2007
ABU DHABI: Page 2 - 11
SITRAIN Training for
Automation and Drives
Siemens AG 2007. All rights reserved.

Smart Line Module / Circuit design: Chassis

Line supply Smart Line Module


DC+

T1 D1 T2 D2 T3 D3
LN LN

u1
LN LN

u2 Cd
LN LN

u3
EMC basic suppression

(for T4 T5 T6
D4 D5 D6
3 AC bypass contactor
380-690V precharging DC-
50/60Hz line choke
line fuses)
Line connection

Main features: Booksize Chassis 400 / 690 V


ƒ Uncontrolled rectifying / 5, 10 kW 140-800 / 132-1400 kW
regenerating unit with IGBT
technology ƒ Power block with
ƒ The use of IGBT modules IGBTs, DC-capacitors
prevents commutation failure as ƒ Current transformer
consequence of line supply failure
ƒ Electronic draw-out unit
CIB, CU320
ƒ Fan

FS H from 06/2006

SINAMICS Date:
File:
06/03/2007
ABU DHABI: Page 2 - 12
SITRAIN Training for
Automation and Drives
Siemens AG 2007. All rights reserved.
DC-link components

Braking Module and Braking resistors


„ Module operates autonomously
„ When triggered, the DC-link energy is dissipated into heat via external braking
resistor.
„ Two braking resistors are available:
Booksize: 0,3 kW continuous braking power (25 kW peak braking power)
1,5 kW continuous braking power (100 kW peak braking power)

Chassis: 25 kW continuous braking power


(125 kW peak braking power)
50 kW continuous braking power
(250 kW peak braking power)

SINAMICS Date:
File:
06/03/2007
ABU DHABI: Page 2 - 13
SITRAIN Training for
Automation and Drives
Siemens AG 2007. All rights reserved.

DC-link components

Braking Module and Braking resistors


„ Module operates autonomously
„ When triggered, the DC-link energy is dissipated into heat via external
braking resistor.
„ Two braking resistors are available:
Booksize:
0,3 kW continuous braking power
(25 kW peak braking power)
1,5 kW continuous braking power
(100 kW peak braking power)
Chassis:
25 kW continuous braking power
(125 kW peak braking power)
50 kW continuous braking power
(250 kW peak braking power)
Capacitor Module
„ Increases the DC-link capacity to cover up for short time line supply
interruptions and to better tolerate regenerative operation

Control Supply Module


„ Generates the 24 VDC supply from the line or from the DC-link voltage

SINAMICS Date:
File:
06/03/2007
ABU DHABI: Page 2 - 14
SITRAIN Training for
Automation and Drives
Siemens AG 2007. All rights reserved.
DC-link connection

24V terminal adapter DC-connection


Direct DC-supply
24V
for chassis
DC-link
bus bar
2DC

Line Motor Motor


Module Module Module

Motor Module

DC connection for Chassis-units


3-stage isolator switch with two switch positions ( 0 / 1 )
0= Off isolator contacts are open
1= Pre charging pre charging resistor is switched on; pre
charging is completed after about 2.5 s
Operation with the on command for the Motor Module
the third switching position is automatically
activated

SINAMICS Date:
File:
06/03/2007
ABU DHABI: Page 2 - 15
SITRAIN Training for
Automation and Drives
Siemens AG 2007. All rights reserved.

Electronic draw-out unit for chassis / Cabinet


Fib
re-o
ptic

3a Power-
2 supply

3
3b

3 DRIVE-CLiQ Base plate


sockets
1

3 Communication Interface board CIB


3a Adaptation Interface board AIBO (shunts, limit value monitoring)
3b Power Stack Adapter PSA (generation of the inverter pulse pattern)

Extended functionality of the CIB-FW starting with V2.3 and CIB-MLFB ...-3 (starting with HW-version M):
edge triggered modulation / safe stop / parallel operation of power sections up to 4xLM and 4xMM per CU320

SINAMICS Date:
File:
06/03/2007
ABU DHABI: Page 2 - 16
SITRAIN Training for
Automation and Drives
Siemens AG 2007. All rights reserved.
Current actual value sensing / Thermal model

Current actual value sensing

ƒ Powerstacks of the SINAMICS Motor Modules


detect all three output phase currents
ƒ A fault current is detected through summation
(earth fault monitoring)
ƒ The current transformer (CT) calibration is
performed in the factory by means of shunt
resistors and powerstack data on the CIB
board.

Thermal model

ƒ The converter‘s thermal protection is activated when the rated current is exceeded
over a longer period of time or when the heat sink temperature becomes too high.
This leads to a failure shut down or to an automatic influence of the control (reduction
of pulse frequency or of current limit) to reduce the converter‘s thermal load.

SINAMICS Date:
File:
06/03/2007
ABU DHABI: Page 2 - 17
SITRAIN Training for
Automation and Drives
Siemens AG 2007. All rights reserved.

System components on the motor-side

Motor reactors „ Limiting of capacitive charging-, discharging currents


„ Reduction of voltage gradient dv/dt
„ Typical uk about 1,5 %
„ For Motor Modules of power ratings 75 – 1200 kW

dv/dt – filter „ Limiting of voltage gradient to values < 500 V/µs


„ Limiting of phase-to-phase voltage to the value of the
DC-link voltage
„ For Motor Modules of power ratings 75 – 1200 kW

Sine filter „ Provides near sinusoidal motor voltage


(voltage noise 5 – 7%)
„ Only for space vector modulation; in consequence only 90 %
motor voltage as compared to “no sine filter”
„ Required pulse frequency of the Motor Module: 4 kHz
„ For voltage range 660 – 690 V not available
„ For Motor Modules of power ratings 90 – 200 kW

SINAMICS Date:
File:
06/03/2007
ABU DHABI: Page 2 - 18
SITRAIN Training for
Automation and Drives
Siemens AG 2007. All rights reserved.
Overload capability of Booksize-units

S1 operation with overload S6 duty cycle with base load

Catalogue D21.2 / chapter 2

duty cycle without base load

SINAMICS Date:
File:
06/03/2007
ABU DHABI: Page 2 - 19
SITRAIN Training for
Automation and Drives
Siemens AG 2007. All rights reserved.

Overload capability of Chassis-units

Small overload at base load current IL High overload at base load current IH
150 % for 10 sec resp. 110 % for 60 sec 160 % for 10 sec resp. 150 % for 60 sec
Example
I L*150% ohne G1_kurz G1_lang G2_kurz G2_lang I *160%
H
(700A) Überlast 150% 110% 170% 150%
I_G, A 330 320 320 280 280I H*150%
Zeit_2, s 300 290 240 290 240
I_Max, A 0 480 352 476 420
Zeit_1, s 0 10 60 10 60
I L*110%
I_N, A 330 327 327 289 313
(500A)
I N_eff
IL
300 s 300 s IH

10 60 300 10 60 300 T [sec.]

without IL_short IL_long IH_short IH_long


overload 150% 110% 160% 150%
I_B, A 330 320 320 280 280
Values for IL and IH Time_2, s 300 290 240 290 240
taken from catalogue I_Max, A 0 480 352 448 420
Time_1, s 0 10 60 10 60
I_N, A 330 327 327 287 313

SINAMICS Date:
File:
06/03/2007
ABU DHABI: Page 2 - 20
SITRAIN Training for
Automation and Drives
Siemens AG 2007. All rights reserved.
Multi-parallel operation of converters S120 / AIM,ALM + MoMo

Infeed units
Active Infeeds AIM+ALM
Decoupling ƒ Current balance control is
reactors provided
ƒ Symmetrical wiring of power
Infeed 1 Infeed 2 Infeed 4 Infeed units
cables is recommended
in parallel
ƒ Decoupling by means of
reactors of the Clean Power
Filter rsp. motor reactors
Control ƒ Current derating in parallel
Unit
CU320
CU320
operation (5% as compared
to a single unit ALM)

MoMo 1 MoMo 2 MoMo 4 Motor Modules MoMo


Motor modules ƒ Current balance control is
In parallel
provided
Decoupling
reactors

Motor connection

690V / 5600 kW

SINAMICS Date:
File:
06/03/2007
ABU DHABI: Page 2 - 21
SITRAIN Training for
Automation and Drives
Siemens AG 2007. All rights reserved.

Cable lengths
DRIVE-CLiQ cables
ƒ Standard within the cabinet 70 m
ƒ MOTION-CONNECT 500 100 m
ƒ MOTION-CONNECT 800 50 m

Power cables Chassis / Cabinet


- Any combination
(without / with reactor; without / with sine-filter
without / with dv/dt-filter 1) )
ƒ screened 300 m (525 m) 2)
ƒ unscreened 450 m (785 m) 2)

Sensor cables
ƒ SMC10 - sensor: resolver 130 m for 2-pole resolvers:
50 m for multi pole resolvers:
ƒ SMC20 - sensor: Sin/Cos, absolute 100 m
ƒ SMC30 - sensor: HTL, TTL 100 m
HTL with A+/A- .. 300 m
1) with “dv/dt-filter + VPL” (Voltage Peak Limiter) as output filter
2) with two reactors in series; second reactor possible only outside the cabinet

SINAMICS Date:
File:
06/03/2007
ABU DHABI: Page 2 - 22
SITRAIN Training for
Automation and Drives
Siemens AG 2007. All rights reserved.
Overall cable lengths of Booksize-units (per motor)

Cable length
50 m 100 m 150 m 200 m >=250 m
Rated
current
3A, 5A always allowed use 9A module
9A always allowed use 18A module

max. 150% Irated not allowed


18A always allowed (continuous max.
95% Irated) use 30A module
use 30A module
max. 135% Irated max. 110% Irated
always allowed always allowed (continuous max. (continuous max.
30A 90% Irated) 85% Irated) not allowed
max. 175% Irated max. 150% Irated
always allowed always allowed (continuous max. (continuous max.
45A, 60A 90% Irated) 85% Irated)
max. 135% Irated max. 110% Irated
always allowed always allowed (continuous max. (continuous max.
85A, 132A 95% Irated) 90% Irated)
max. 125% Irated max. 110% Irated
always allowed always allowed (continuous max. (continuous max.
200A 95% Irated) 90% Irated)

With Active Line Module and high efficiency line reactor: overall length of all power cables = 1000 m

SINAMICS Date:
File:
06/03/2007
ABU DHABI: Page 2 - 23
SITRAIN Training for
Automation and Drives
Siemens AG 2007. All rights reserved.

Attainable output voltage

ƒ The maximum output voltage is defined by the DC-link voltage and the inverter modulation depth.

ƒ The DC-link voltage level depends on the Line Module used in the application.

ƒ For Basic Line Module and Smart Line Module and for G130/G150 :
V.DC = 1.32...1.41 * V.Line with p0210 = 380 – 480 VAC
ƒ For Active Line Module / Booksize :
V.DC = 600 VDC with p0210 = 380 – 400 VAC / Active Mode [V.DCÆp3510]
V.DC = 625 VDC with p0210 = 401 – 415 VAC / Active Mode [V.DCÆp3510]
V.DC = 1.32...1.41 * U.Line with p0210 = 416 – 480 VAC / Smart Mode
p3510 = 1.42 up to 2.0 * p0210
ƒ For Active Line Module / Chassis and for S150 :
V.DC = 1.5 * V.Line with p0210 = 380 – 480 VAC / p3510 = 1.42 up to 1.6 * p0210

ƒ The maximum modulation depth that can be set is defined by the “operation type” of the Motor Module.
ƒ For “operation type” Servo (S120 / only space vector modulation)
V.out max.rms = 0.67 * V.DC
ƒ For “operation type” Vector (S120, G150, S150 / space vector mod. and edge triggered mod.)
V.out max.rms = 0.72 * V.DC > FW V2.3 and CIB-MLFB ….-3 (HW-version > M)

SINAMICS Date:
File:
06/03/2007
ABU DHABI: Page 2 - 24
SITRAIN Training for
Automation and Drives
Siemens AG 2007. All rights reserved.