You are on page 1of 5

23rd International Conference on Electricity Distribution Lyon, 15-18 June 2015

Paper 0777

IMPACT OF OPERATING MECHANISM TYPE ON MV VACUUM CIRCUIT-


BREAKER RELIABILITY

Juan TOBIAS Jean-Marc BIASSE Philippe PICOT


Schneider Electric – France Schneider Electric – France Schneider Electric – France
juan.tobias@schneider-electric.com jean-marc.biasse@schneider-electric.com philippe.picot@schneider-electric.com

Denis PERRIN Marc BONJEAN Eduardo PUJADAS


Schneider Electric – France Schneider Electric – France Schneider Electric – France
denis.perrin@schneider-electric.com marc.bonjean@schneider-electric.com eduardo.pujadas@schneider-electric.com

ABSTRACT MV circuit-breakers have rated voltages between 1 kV


and 52 kV and are available with maximum ratings up to
Circuit-breakers main duty is to interrupt short-circuit 4000 A normal current and 63 kA rated short-circuit
current caused by a fault in the electrical network. As the current. In the 1970’s MV current interruption technology
circuit-breaker is the ultimate electrical safety device, evolved from oil to SF6 and vacuum. Over the past 20
reliable short-circuit current interruption in case of years vacuum circuit-breakers (VCB) have dominated the
market, as illustrated in Figure 1.
network fault is paramount. The operating mechanism is
a key sub-assembly that has direct impact on the circuit-
breaker reliability as well as its cost and size. This paper
describes the principle of operation of MV VCB
mechanisms, namely solenoid, spring and permanent
magnet actuators. It provides a synthesis of the
requirements imposed by IEC and ANSI standards for
MV circuit-breakers as well as an overview of the needs
of the main MV network applications regarding the
mechanisms. Reliability aspects are examined and it is
argued that MV VCB reliability in real operational
conditions is not linked to the rated number of
mechanical operation that a new VCB can do in a Figure 1. Historical evolution of MV circuit-breaker
laboratory interruption technology

INTRODUCTION STANDARDIZATION ASPECTS


Circuit-breakers are used for fast interruption of the General
short-circuit current to prevent damage to the rest of the
electrical installation. When the circuit-breaker is in MV switchgear global market is ruled by two main
closed position it can carry the rated normal current standardization bodies: International Electrotechnical
indefinitely as well as the rated short-circuit current for a Commission (IEC) and American National Standards
short time (< 3 seconds). Circuit-breakers can safely Institute (ANSI).
make and break several times short-circuit currents as There are significant differences in ratings and
well as all types of load currents. performances required by IEC and ANSI/IEEE circuit-
Circuit-breakers are always associated with a protection breaker standards. As a result global manufacturers
and control unit, also referred to as Intelligent Electronic usually have two different products. Over the past few
Device (IED). Current and voltage sensors supply low years IEC and IEEE standardization committees have
level signals to the IED that will constantly monitor the made progress towards convergence on type test
current and voltage in the circuit and issue a tripping or requirements for MV circuit-breaker standards.
closing command according to how it was programmed. All standards applicable to MV circuit-breakers consider
The circuit-breaker can also be opened or closed for the operating mechanism as a sub-assembly. They specify
control purposes either remotely via the IED or locally ratings and requirements for mechanical functionalities as
via mechanical push buttons. well as the test procedures to verify the mechanical and
Opening or closing the circuit-breaker contacts requires electrical performances. Ratings are defined in a coherent
some form of operating mechanism capable of storing the way with the real operational needs, particularly in terms
necessary energy to physically move the contacts. The of typical switching sequences and quantity of close-open
operating mechanism is a key sub-assembly that has (CO) cycles to be experienced by the circuit-breaker in its
direct impact on the circuit-breaker reliability. Its design lifetime.
requires considerations of many factors determined by Rated operating sequences are expressed as close (C) and
the type of interrupter technology used and performance open (O) operations followed by a time interval (t)
that has to be achieved. expressed in seconds or minutes. The requirements

CIRED 2015 1/5


23rd International Conference on Electricity Distribution Lyon, 15-18 June 2015

Paper 0777

defined in IEC or ANSI/IEEE standards for mechanical VCB MECHANISM DESIGN CONSTRAINTS
and switching operations, in terms of quantity of
operations and operating sequences reflect most of the Mechanisms for MV VCBs have specific requirements
needs found in the applications of circuit-breakers. that are related to the physical characteristics of vacuum
interrupters, which consist of a fixed and moving butt
IEC standard 62271-100 contacts kept under high vacuum inside a ceramic
This standard defines circuit-breaker mechanical envelope. The moving contact is attached to metallic
endurance ratings that impact mechanism designs. Two bellows that allow it to move to the open position,
types of mechanical endurance ratings are established : leaving a short gap of typically 10 to 20 mm. A typical
- Class M1 circuit-breakers require mechanical MV vacuum interrupter is illustrated in Figure 2.
endurance of 2,000 CO cycles; Butt contacts in closed position tend to be forced apart by
- Class M2 circuit-breaker have an extended the electromagnetic forces generated when the short-
mechanical endurance of 10,000 CO cycles. circuit current passes through them. This phenomenon,
For switching, normal duty circuit-breakers require either known as “contact popping” must be avoided as it leads
O – 3 min – CO – 3 min CO or CO – 15 s – CO operating to arcing, which causes contact surfaces to melt and
sequence. Circuit-breakers intended for rapid auto- subsequently to weld, making it impossible to separate
reclosing must perform O – 0.3 s – CO – t’ – CO where t’ them again.
can be 3 min, 1 min or 15 sec. To avoid “contact popping” the operating mechanism has
Mechanism designs used in normal duty and rapid auto- to provide a high compression force on the contacts in
reclosing duty MV circuit-breakers are quite different. closed position. In all cases this is provided by the “wipe
Meeting rapid auto-reclosing operating sequence is spring” located in the drive linkage, which is compressed
challenging as the mechanism must be capable to perform as the contacts close.
a closing operation 0.3 seconds after opening
ANSI/IEEE standards applicable to MV circuit-
breakers
ANSI/IEEE has three complementary standards that
impact the mechanism design.
- ANSI/IEEE standard C37.04 – Rating structure;
- ANSI/IEEE standard C37.06 – Preferred ratings;
- ANSI/IEEE standard C37.09 – Test procedures.
Manufacturers must choose the optimized ratings to
cover the target markets and carry out the circuit-breaker
type tests accordingly. Figure 2. Typical MV vacuum interrupter
The rated operating sequence defined for normal duty
circuit-breakers is O – 15 s– CO – 3 min CO while All MV circuit-breaker mechanisms must be able to
circuit-breakers intended for rapid auto-reclosing must achieve close-open operation on short-circuit. This means
perform O – 0.3 s – CO- 3min – CO. that when the circuit-breaker closes onto a fault, the
The rated interrupting times defined by ANSI/IEEE mechanism should have sufficient energy stored to be
C37.04 are expressed in terms of cycles of the power able to immediately open the interrupter and clear the
frequency: the most commonly used values are 3 cycles short-circuit current. The circuit-breaker must also be
(i.e. 50 ms at 60 Hz) and 5 cycles [1]. able to manage two simultaneous orders close and open
ANSI/IEEE C37.06 defines different values of operating (trip-free, as defined by IEV 441-16-31, and anti-
mechanical endurance capabilities for MV circuit- pumping features).
breakers, from 1,500 to 10,000 operations depending on For a class M2 circuit-breaker (10,000 CO cycles), the
ratings. vacuum interrupter itself is generally designed to achieve
a mechanical endurance between 20,000 to 30,000 CO
IEC 62271-111 and IEEE C37.60 standards for cycles. The limit comes from the metallic bellows that
automatic circuit-reclosers up to 38 kV eventually break under fatigue.
The preferred rated operating sequence for this special
type of circuit-breakers is: O – 0.5 s – CO – 2 s – CO – MECHANISM OPERATING PRINCIPLES
5 s – CO. Longer time intervals between C-O operations
may be used, depending on the application. Three types of operating mechanisms can be found in
This standard requires a minimum of 2,000 CO MV VCBs and auto-reclosers available in the global
operations to be done without maintenance, of which market today. These are classed by the type of technology
1,800 have to be done using the automatic circuit recloser used to store the energy needed to close and open the
integral protection and control unit. The remaining 200 vacuum interrupters.
operations shall be done by using the manual opening and Solenoid mechanism
closing mechanisms (when provided).
Solenoid mechanisms use a compressed spring to open
the interrupter and a solenoid to close it as well as
charging the opening spring. The energy required to
operate the solenoid is supplied by the DC or AC

CIRED 2015 2/5


23rd International Conference on Electricity Distribution Lyon, 15-18 June 2015

Paper 0777

auxiliary supply. Solenoids take a high current surge Energy for open and close operations is derived from two
when they are energized, which requires a stiff auxiliary separate electrolytic capacitors that are discharged into
power source (DC battery or LV AC) or a large capacitor the opening and closing coils. Manual trip in case of loss
discharge, and high rating auxiliary contacts. They are of DC supply is complex because it requires the
also bulkier and heavier than spring operated mechanism. application of a high force using a lever to “unstick” the
For this reason they are now rarely used in practice. armature from the permanent magnet latch and to provide
the opening energy.
Spring mechanism Mono-stable
stable PMA is often preferred to bi-stable for the
Spring mechanisms use separate charged springs to store following reasons :
energy for openinging and closing the interrupters. The - Eliminates risk of incomplete
inco opening (tripping
closing spring has sufficient energy to charge the opening energy is stored by charging the opening spring);
spring and is recharged either manually or by a small - Simpler manual and electrical tripping (only
motor supplied by the auxiliary supply.
supply There are two requires cancelling the permanent magnet flux to
basic types of VCB spring mechanisms: open the VCB).
- Mechanisms for VCBs that do not require fast
reclosing duty (e.g. O – 3 min – CO rated
operating sequence);
- Mechanisms for VCBs able to perform fast
reclosing duty (e.g. O – 0.3s – CO – 15 s – CO
rated operating sequence), as shown in Figure 3.

Figure 4. Single magnetic latch PMA mechanism

Electronic Control System


PMA mechanisms require an electronic control system
Figure 3. MV CB spring mechanism designed for fast that receives either DC or AC auxiliary power, provides
reclosing duty DC power to charge the electrolytic capacitors,
discharges the stored energy in the opening or closing
Two main principles are used in fast reclosing spring coils and disconnects the energy source once the VCB
mechanism designs: cam follower and four-bar
four linkage has reached the open or closed position. In most designs
[2]. Trip-free
free feature can be provided either by the the electronic control system is used to monitor the
intrinsic design of cam follower mechanism
mechan or by toggle condition of the capacitors and operating coils, giving
linkage systems [3]. alarms in case of anomalies.
The electrolytic capacitor is a key component as it stores
s
Permanent Magnet Actuator (PMA) mechanism the necessary electrical energy that will generate the
Permanent magnet actuator current pulse needed to operate the PMA. Typical
Permanent magnet actuator (PMA) mechanisms use capacitance of 100,000 µF charged at 80 V DC gives a
energy stored in electrolytic capacitor for closing stored energy of 320 Joules, sufficient to carry out a VCB
operation and permanent magnets to latch in closed fast reclosing sequence, including
uding short intervals between
position. PMA mechanisms were developed specifically CO operations.
to be used with MV VCBs [4].. First commercial models
were introduced in the market in the late 90’s [5] [6] but MV VCB NETWORK APPLICATIONS
uptake has been poor. There are two families of PMA
mechanisms : mono-stable (single magnetic latch) and bi-bi MV circuit-breaker mechanism performance
stable (double magnetic latch). requirements are dependent on the function they are
The principle of mono-stable PMA mechanism is similar intended to perform in the MV electrical distribution
to the solenoid one except that in closed position the network. There are four main types of MV networks :
mechanical latch is replaced by a permanent magnet latch - Electrical utility MV distribution networks;
networks
(see Figure 4). The closing force iss designed to keep the - Electro-intensive
intensive industrial sites;
sites
vacuum interrupter closed with the correct contact - Data centres and hospitals;
hospitals
pressure while charging the opening spring.
spring - Buildings,
uildings, infrastructure and light industry sites.
sites
In the bi-stable
stable PMA mechanisms, permanent magnets magne Utility MV distribution networks are specific to each
latch the armature in both closed and open position. To country, but they can be classified into urban
move the armature from one position
tion to the other a high underground cable network and rural r overhead line
magnetic flux is created by a DC current in i the opening networks. Utility
ity MV underground cable networks use
or closing coil. This reduces the magnetic latch strength
streng VCBs in MV transformer incomer, MV cable feeder or
and generates an opposing force in the other air gap. MV/LV transformer feeder applications. Faults in MV

CIRED 2015 3/5


23rd International Conference on Electricity Distribution Lyon, 15-18 June 2015

Paper 0777

cables and MV/LV transformers are rare, consequently require MV switchgear to operate for months or even
these VCBs remain in closed position for months or even years. Most operations are required to carry out planned
years, just carrying load current. In case of fault, the VCB maintenance.
will trip and remain open as all faults are permanent.
MV cables and MV/LV transformers are protected by OPERATING MECHANISM PERFORMANCE
time delayed overcurrent relays with operating time >
200 ms. Consequently, VCBs with rated operating REQUIREMENT BY APPLICATION
sequence O – 3 min – CO and opening times < 100 ms Selecting the VCB mechanism type for a particular MV
are perfectly fit for purpose. network application requires understanding of
MV utility networks supplying rural areas use overhead environmental constraints and switching duties in order
lines that are exposed to lightning strikes, birds and fallen to define rated mechanical and electrical endurance and
trees. Auto-reclosing duty is used in the overhead line operating sequence. The VCB expected operating life,
feeder VCB to minimize the impact of transient faults maintenance frequency and procedure are also important.
due to lightning strikes. The VCB is used to disconnect The selection criteria are summarized in Table 1.
the MV supply and reenergize the line after a few VCB Application Expected Rated Rated Expected Best
hundred milliseconds as it is very likely that the fault Type operations
per year
operating
sequence
mechanica
l
operating
life
adapted
VCB
disappears during the time that is de-energized. Utilities General Cable
endurance
M1
Mechanism

in certain countries like US, Australia and Brazil also purpose /transformer
feeder/incomer
< 30 O-3 min- CO 2,000 ops
30 years
Spring

install pole mounted automatic reclosers along long MV Capacitors


Motors O-0,3 s-CO- M2 Routine Spring
overhead lines to minimize the number of customers Frequent
switching
Generators
DRUPS < 300
15 s-CO
10,000 ops
ma intenanc
e every 3
(preferred)
or PMA
years
affected by transient faults. Reclosers are special circuit- Overhead feeder
Pole Mounted O-0,3s-CO-
breakers designed to perform several CO operations with recloser 2s-CO-5s-CO
10 years
PMA

short delay (< 5 sec) between them. Heavy Special Full


duty Arc furnace O-0,3 s-CO- ma intenanc PMA
< 3,000 15 s-CO 30,000 ops e required
MV electrical distribution networks used in oil and gas, every year

mining, steel, cement and paper industrial sites have very


large MV motors (> 3 MW). These installations are very Table 1. Mechanism requirements
dynamic. MV circuit-breakers perform many load
switching operations per day to change network For the vast majority of applications the performances of
configurations, shed loads and connect local generation. VCBs with spring mechanisms are perfectly adequate.
MV capacitor banks are often used to compensate lagging PMA mechanisms are recommended in special
power factor caused by the motor inductive loads. applications where the VCB has to perform a very high
Circuit-breakers used to control them also need to operate number of operations (e.g. arc furnace) or several
several times a day. consecutive fast reclosing cycles (e.g. pole mounted
The most demanding application for an MV circuit- recloser).
breaker is electric arc furnace (EAF) control in steel This selection criterion is reflected in the MV VCB
plants as the process requires several CO operations per global market data:
day switching high load current. To ensure high - Spring mechanism is the main technology for
reliability these special VCBs are subject to regular MV VCBs (> 90% market share);
maintenance. - PMA is the dominant mechanism technology for
pole mounted reclosers (> 90% market share);
MV electrical distribution networks for data centres and - PMA mechanisms are better adapted for niche
hospitals are designed for high supply availability. In applications requiring very precise “point on
case of a utility supply failure, critical loads (e.g. server wave” single pole switching [7].
rooms, operating theatres) are supplied by LV UPS for up
to 10 min, giving enough time to start back-up diesel
generators usually connected to the MV network via VCB RELIABILITY
circuit-breakers. Utility failures are indeed very rare, but The VCB rated mechanical endurance is generally
the back-up generation needs to be tested regularly, verified using a new device in a laboratory by performing
which requires MV circuit-breaker to perform regular CO repetitive uninterrupted sequence of CO operations that
operations with light load currents. Some data centres use stops when the VCB fails to open or close. This
diesel rotary UPS (DRUPS), which consist of an MV conventional test cannot represent all the situations and
generator driven by a flywheel and a diesel engine. In the real duties that the VCB will see in the field.
case of utility failure the critical load will be supplied by However, many consulting engineers and end users take
kinetic energy stored in the flywheel until the diesel the VCB rated mechanical endurance as an indicator of
generator gets up to right speed to take over the load. The operational reliability based on the belief that higher the
MV circuit-breaker connecting the DRUPS system to the mechanical endurance gives higher reliability.
utility supply could perform many CO operations with In fact, VCB reliability is more appropriately measured
light load current if the utility supply is poor. by its operational MTBF (Mean Time Between Failures).
In practice, operational MTBF of a new VCB operating
MV networks in commercial buildings, large mechanism design it is very difficult to estimate.
infrastructure and light industry sites consist mainly of Calculations must take into account the reliability of each
MV cable feeders and MV/LV transformer feeders. These component that takes part in the opening or closing of the
are static, very reliable MV cable network that do not VCB, as well as the stress factors and operating

CIRED 2015 4/5


23rd International Conference on Electricity Distribution Lyon, 15-18 June 2015

Paper 0777

conditions (often referred to as “the mission profile”). ageing. This undesirable condition will disappear after
Two simple reliability block diagrams (see Figure 5) the mechanism operates once [8]. This risk can be
show how component reliability contributes
butes to the overall reduced by performing a single CO operation every 3
reliability of spring and PMA VCB mechanisms.
mechanisms years or less.

CONCLUSION
Although spring mechanisms and PMA mechanisms are
based on different technologies, it is however seen that
both of them are suitable for most of MV VCB
applications.
Figure 5. Basic reliability model of spring and PMA VCB reliability is not linked to the maximum number of
mechanisms used for MTBF estimation. operations that a new device can perform in a laboratory.
The real parameter too consider is operational MTBF.
A quantitative comparison between both systems was Spring mechanism reliability is determined by
made using the following assumptions: mechanical system failure rates only while PMA
Failure rate of the mechanical parts (trip
trip coil, motorized mechanism reliability is determined by the combination
spring and PMA) is low at the beginning but bu increases of mechanical and electronic
ctronic failure rates.
with the number of operations due to wear. Periodic Although
ough spring mechanisms have a risk of performing a
maintenance can partially restore the condition of the “slow open” operation after long periods of inactivity, the
mechanism; risk can be reduced by carrying out periodical
p VCB
Failure rate of the electronic parts (control board and operation test.
electrolytic capacitors) is constant throughout the In summary, the author’ss logical arguments
argument challenge the
expected service lifefe of the operating mechanism but idea that VCBs with PMA mechanism with higher
considerably higher than that of the mechanical
mechanic parts at mechanical endurance are more reliable than VCBs with
early life stages; motorized spring operation.
Typical operational MTBF for mechanical systems was This qualitative analysis highlights just some aspects of
assumed to be > 1,000 years. This is based on field the impact of operating mechanism on VCB reliability,
failure data of spring-operated
operated LV and MV CBs CB in thus opening debate among the MV switchgear experts.
operation for over 15 years; Further work is required to achieve accurate VCB
Typical operational MTBF for PMA control board bo and reliability models.
electrolytic capacitor was assumed to be < 350 years. REFERENCES
This is based on operational reliability of Schneider [1] R. Catlett, J. Anderson, L. Chassereau, 2005, “Three-
Electric IEDs, which are considered to contain similar Cycle Breaker Applications”,
Applications IEEE INDUSTRY
technology. Actual reliability could
ould be worse (< 100 APPLICATIONS MAGAZINE • SEPT|OCT 2005, 2005 33-
years) [5];
43
Life expectancy of the
he electrolytic capacitor can decrease
dramatically at high operating temperatures. [2] A. Greenwood, 1994, Vacuum Switchgear, IEE,
Life expectancy for electromechanical systems (spring London, UK, 152-162.
mechanism and PMA) is > 30 years and does not [3] R.D. Garzon, 1997, High Voltage Circuit-breakers –
significantly depend on operating temperature. Design and Applications,
Applications Marcel Dekker, Inc.,
Another aspect to be considered for the comparison is the NewYork, USA, 214-219. 219.
result of a Failure Mode, Effects and Criticality
riticality Analysis [4] B.A.R. Mckean, C. Reuber, 1998, “Magnets &
(FMECA) of each mechanism design.. A summary of the Vacuum – The Perfect Match”, Match Trends in
main differences observed is provided in Table 2. Distribution Switchgear,
Switchgear Conference Publication
VCB failure mode and estimated risk No. 459, IEE
Inability to Incomplete Slow open on
VCB mechanism type open open operation trip order after [5] E. Dullni, H. Fink, C. Reuber, 1999, “A Vacuum
manually long inactivity
Motorized spring Low Negligible Medium Circuit-Breaker with Permanent
ermanent Magnetic Actuator
PMA Mono-stable Low Negligible Medium
Bi-stable Medium Medium Low and Electronic Control”,
ontrol”, Proceedings CIRED
conference
Table 2. VCB failure mode estimated risk [6] A.J.W. Lammers, P.P. Leufkens, G.C.
Schoonenberg,, 1998, “MV “M Vacuum Switchgear
The bi-stable
stable PMA has a non negligible risk of ending up Basedd on Magnetic Actuators”, Trends in
in an intermediate position between open and close as Distribution Switchgear,, Conference Publication No.
there is a natural position provided by the contact
459, IEE
pressure springs if they cannot be compressed up to the
final magnetic latch position. [7] C. Cereda, C. Gemme, C. Reuber, 1999,
In case that VCB has been inactive for many years “Synchronous Medium Voltage Circuit-breakers:
(normal situation in static MV networks), the spring and ABB Solution Based on Magnetic Drive and
mono-stable PMA mechanisms have a risk of opening Electronic Control”, Proceedings CIRED conference
with lower VI contact separation speed than required to [8] V. Kraynov, F. Pitis, V. Tchekhov, 2013, “Ageing
“ of
interrupt the fault current. This misoperation can
ca be due Mechanisms of Circuit-breakers”,
Circuit Proceedings
to increased friction between moving parts resulting from CIRED conference

CIRED 2015 5/5

You might also like