Super Solution

Air Circuit Breakers


Codes and Standards
UA Series are manufactured and tested in accordance
with the following standards Low-Voltage Power
Circuit Breaker
�ANSI C37.13
Contents
�ANSI C37.16
�ANSI C37.17 ● Overview 4
�ANSI C37.50 ● External configuration 14
�UL 1066 (cULus Listed)
● Internal configuration 16
�CSA C22.2 No.31-10
● Ordering 18
Note) Throughout this document, the phrase “ANSI Certified” means the product meets the
requirements of UL 1066 and ANSI C37 ● Ratings 22
● Trip relays 24
UL File Numbers:
● Accessories 50
Susol UA Series , 1600AF E326950 Vol.1 Sec.1
Susol UA Series , 3200AF E326951 Vol.1 Sec.2 ● Electrical diagram 76
Susol UA Series ,5000AF E326952 Vol.1 Sec.3 ● Dimensions 78
Premium Susol ACB meets your demands for high breaking capacity, fully line-up, and
optimized panel size.
Various accessories and connection methods realize user-friendly handling.

Susol ACB provides you with total solutions with an advanced trip relay for
measurement, diagnosis, analysis, and communication as well as protective functions for
absolute protective coordination and electric power monitoring system.

Super Solution

UL Listed/ANSI Certified
Low-Voltage Power Circuit Breaker UA series
LSIS Super Solution series

� Modular design
� High (130kA) Breaking Capacity Full Line-up to 5000A
� Satisfy the needs for a compact sized panels
� N-Phase conducting capacity 100%
� Interchangeable Trip unit and Rating plug

Safety
Monitor temperatures for safety (Optional)
�Careful selection of materials
�Arc space is zero
�Perform discriminations between upstream and
downstream levels
User convenience
various connection type for main circuit terminals
�Easy installation of accessories
�Interchangeable Trip unit and Rating plug
Intelligent Trip relay Susol Manual
Various and advanced functions Motor Starters
protection, measurement, diagnosis, analysis, communication
Susol Air Circuit Breakers

Susol Molded Circuit Breakers

Susol Magnetic Contactors &


Overload Relays
Full line-up & Compact
Up to 5000A, Susol ACB provides fully lined-up 3 frame.
For each frame, there is just one size, which is smaller and more compact.
It makes it possible for you to design the optimized volume panel.
H = 430mm

W = 334mm W = 412mm

85kA
UAS-08/16D
100kA
UAH-08~32E
08 800AF 08 800AF
16 1600AF 16 1600AF
85kA at 508Vac 20 2000AF
W=334(3p), 419(4p)mm 25 2500AF
32 3200AF
100kA at 508Vac
W=412(3p), 527(4p)mm
m
5m
37
=
D

W = 785mm

�The high breaking capacity:


130kA
UAH- 32~50G
85/100/130kA (at 508Vac) 32 3200AF
40 4000AF
�3 ampere frame sizes:
50 5000AF
1600/3200/5000AF 130kA at 508Vac
�N phase current conducting capacity: 100% W=785(3p), 1015(4p)mm
Trip Relay Trip relays are classified according to function.
Trip relays are classified according to their usages and functions to maximize
(OCR) customers’ satisfaction. Classified trip relays and easy installation.

�Protection: overload, short current, ground fault, earth leakage, under voltage, over voltage,
under frequency, over frequency, reverse power, unbalance, etc
�Measurement: voltage, ampere, power, energy, frequency, power factor, harmonics, etc.
�Event & fault recording: Max. 256 events & faults
�Communication: Modbus/RS-485, Profibus-DP

Susol ACB Trip Relay functioning world-best protection can be interlocked with mechanism.
It makes the breaking capacity of ACB improved and ACB’s life enhanced, and provides
advanced functions - measurement, diagnosis, analysis, and communication.
Susol ACB Trip relay
N type A type P/S type

�L/S/I/G/Thermal �L/S/I/G/Thermal �L/S/ I/G/Thermal(Continuous)


�ZSI �UV/OV/OF/UF/rP/Vun/Iun
�Self Power �Remote Reset �Measurement: V/A/W/Wh/F/PF
�RTC Timer mounted �Modbus/RS-485 �Harmonics (63th), Waveform (S Type)
�Fault information (LED) �Profibus-DP �ZSI
�Remote Reset
�Self Power �Modbus/RS-485
�AC/DC 100~250V �Profibus-DP
�DC 24~60V
�RTC Timer mounted �AC/DC 100~250V
�Fault Recording (10EA) �DC 24~60V
�RTC Timer mounted
�Event Recording (256EA)
�Fault Recording (256EA)
�Fault Wave (S Type)

Trip relays series


N Type (Normal) P Type (Power Meter)
N P
type �Self-power + Current protection type �A type + Power Meter +
Voltage / Frequency / Unbalance protection

A Type (Ammeter) S Type (Supreme)


A S
type �Current Meter + Current protection + type �P type + Harmonics analysis (63 th) +
DO control + Communication Fault wave recording
Accessories








ACB
� Trip Relay (OCR) � Auxiliary Switch (AX)
� Motor (M) � Key Lock (K1),
� Closing Coil (CC) Double Key Lock (K3)
� Shunt Coil (SHT) � Counter (C)
� Under Voltage Trip Device (UVT) � On/Off Button Lock (B)
� Door Interlock (DI) � Miss Insertion Preventing Device (MIP)
� MOC (Mechanically � Manual Reset Button (MRB)
Operated Cell Switch)
� Mechanical Interlock (MI)





� � �



Cradle Other
� Safety Shutter (ST) � Mechanical Interlock (MI) � Door Frame (DF)

� Zero Arc Space (ZAS) � Miss Insertion Prevent Device (MIP) � Dust Cover (DC)

� Cell Switch (CEL) � Safety Control Cover (SC) � Lifting Hook (LH)

� Door Interlock (DI) � Racking Interlock (RI) � UVT Time Delay Controller (UDC)

� MOC (Mechanical � Profibus-DP Communication module

Operated Cell switch) � Remote I/O


� Temperature Alarm
Connection
and Installation

Diversified terminal connection methods of the ACB main circuit for users.
Multiple connections
Various installation methods
Standard connection

Horizontal type Vertical type Front type

Mixed connection

Horizontal / Vertical type Vertical / Horizontal type Horizontal / Front type

Vertical / Front type Front / Horizontal type Front / Vertical type

�Front connection type is available to be connected regardless of the depth of main circuit terminal, and it is
suited for the panel required for limited installation space.
�The vertical and horizontal type terminal are module types which can easily compose the vertical and
horizontal terminals by rotating 90。 。

�Please refer to the rating lists (Page 22~25) because the installation method is various according to the rated current.
External configuration

Fixed type ACB


Terms
� � Trip relay
� Counter
� � OFF button
� � ON button
� � Series name
� � Charge handle


� Rated name plate
� Charge/Discharge indicator

� Closed/Open indicator

� Corporation logo
� � Arc cover (Zero Arc Space)
� � Safety control cover

� Cradle
� Draw-out handle
� � Position indicator
� Handle inserting hole

� Pad lock button
� Arc chute
� Control cover
� Fixed type bracket
� Rating plug

Draw-out ACB (Cradle)




� �








� �

14
Cradle (Internal) Cradle (Rear)



Terms

� � Safety control cover � Pad lock button
� � Draw-out handle � Connecting conductor (Line side)
� Position indicator � Connecting conductor (Load side)
� Handle inserting hole

Main nameplate
[Acronym explanation] [Secondary nameplate]
Explanation of terminologies
� Motor charge
Control power and
� Closing coil terminal No.
� Shunt tripping coil
� Auxiliary switches: Contact specification
and terminal No.
�Under voltage trip: UVT terminal No.
� OCR control source: Trip relay control power
� Alarm switch: Alarm and terminal No.
� Digital trip relay: Switching diagram
� Z.S.I: Input/Output terminal No.
� Reset: LED/LCD reset
� Communication: Communication and
terminal No.
� Voltage module: Phase voltage and symbol
� Earth/Leakage: Ground fault / Earth
leakage input terminal No.

15
Internal configuration

Terms

� Arc chute
� Aux. switch control terminal
� Control power supply terminal
� � � Trip relay control terminal
� � Carrying grip
� � Shunt coil or UVT coil
� Mechanism

� � Main body

� Counter

� Shunt coil

� � Closing coil
� Motor Ass’y
� � Aux. switch

� � � Closed button
� � Open button
� MTD base
� � Trip relay
� Front cover

16
� Terms
� � � � � � � � � Control circuit terminal block
� Control terminal
� � Auxiliary switches
� Closing, Shunt, UVT coil
� � Trip relay
� � Front cover
� Mechanism

� Charge handle
� Trip spring
� Closing spring
� � Draw-in/out device
� � Arc extinguishing part
� �
� Moving contact
� Fixed contact
� Conductor on line side

� Cradle finger
� Cradle
� Connecting conductor

� CT (Current transformer)
� Conductor on load side

17
Ordering

Breaker and Accessories

UAS 10 D 3 10 A

Frame Type Frame Size Phasing Poles Sensor Rating Mounting and Terminal
08 800AF 3/4P Standard 3 3P 04~08 400A~800A Mounting
D
16 1600AF RST(N) 4 4P 08~16 800A~1600A A Drawout
W 4P Reversed NRST Fixed
H Horizontal terminals
V Vertical terminals
Horizontal for line
M
Vertical for load
Vertical for line
N
Horizontal for load
P Front terminal
G Horizontal-con type
UAH 32 E 3 10
32 W Vertical-con type
* Terminals for P type must be
ordered separately
* G and W types can be applicable
to UAS-08D, UAS-16D only
Frame Type Frame Size Phasing Poles Sensor Rating * Front terminal is only available for
800~2000A
08 800AF 3/4P Standard 3 3P 04~08 400A~800A
E
16 1600AF RST(N) 4 4P 08~16 800A~1600A
20 2000AF X 4P Reversed NRST 10~20 1000A~2000A
25 2500AF 12~25 1200A~2500A
32 3200AF 16~32 1600A~3200A

32 3200AF 3/4P Standard 3 3P 16~32 1600A~3200A


G
40 4000AF RST(N) 4 4P 20~40 2000A~4000A
50 5000AF Z 4P Reversed NRST 25~50 2500A~5000A

UAA 16 D 3 10
00

Frame Type Frame Size Phasing Poles Sensor Rating


08 800AF 3/4P Standard 3 3P Not applied
D
16 1600AF RST(N) 4 4P
20 2000AF W 4P Reversed NRST
25 2500AF 3/4P Standard
E
32 3200AF RST(N)
40 4000AF X 4P Reversed NRST
50 5000AF 3/4P Standard
G
RST(N)
Z 4P Reversed NRST

18
M1 D1 D1 AX NG0 U1 AL C

Motor Operator Shunt Trip Trip relay Option


MA None (Manual operated) D0 None Refer to 21page
M1 AC/DC 100V~125V D1 AC/DC 100V~125V
M2 AC/DC 200V~250V D2 AC/DC 200V~250V
M3 DC 125V D3 DC 125V
M4 DC 24V~30V D4 DC 24V~30V
M5 DC 48V~60V D5 DC 48V~60V
M8 AC 48V D7 AC 48V

Closing Coil Charging/Auxiliary Switch UVT


D0 None AX Standard OFF charge/3a3b U0 None
D1 AC/DC 100V~125V AC Standard ON charge/3a3b U1 AC/DC 100V~125V
D2 AC/DC 200V~250V BX Standard OFF charge/5a5b U2 AC/DC 200V~250V
D3 DC 125V BC Standard ON charge/5a5b U3 DC 125V
D4 DC 24V~30V HX High capacity OFF charge/5a5b U4 DC 24V~30V
D5 DC 48V~60V HC High capacity ON charge/5a5b U5 DC 48V~60V
D7 AC 48V CC Standard ON charge/6a6b U6 AC 380V~480V
JC High capacity ON charge/6a6b U7 AC 48V

Code Description Code Description


AL AL1+MRB M MI Mechanical interlock
A1 AL1+MRB +RES(AC110~130V) *AC only D DI or MOC Door Interlock or MOC(Mechanism operated cell switch)
A2 AL1+AL2 +MRB K K1 Key Lock
A3 AL1+MRB +RES(DC110~125V) *DC only K2 K2 Key Interlock Set
A4 AL1+MRB +RES(AC200~250V) *AC only K3 K3 Key Interlock Double
A5 AL1+MRB +Auto Reset R RCS Ready to Close switch
A6 AL1+AL2 +MRB +Auto Reset T TM Temperature Monitoring
A7 AL1+MRB +RES(DC110~125V) +Auto Reset *DC only H1 AC/DC 100V ~125V, Double Shunt coil
A8 AL1+MRB +RES(AC200~250V) +Auto Reset *AC only H2 AC/DC 200V ~250V, Double Shunt coil
A9 AL1+MRB +RES(AC110~130V) +Auto Reset *AC only H3 SHT2 Note 2) DC 125V, Double Shunt coil
C C COUNTER H4 DC 24V ~30V, Double Shunt coil
S CS2 Charge switch communication H5 DC 48V ~60V, Double Shunt coil
B B On/Off Button lock H7 AC 48V, Double Shunt coil

A4 (AL1+MRB +RES(AC200~250V))+C(Counter)+B(ON/OFF Button Lock)+K(Key Lock)+R(Ready to Close switch)+M(Mechanic


N01
Interlock)+E(Spring Auto Release)
AL (AL1+MRB)+K(Key Lock(OFF Lock))+R(Ready to Close switch)+D(Door Interlock or MOC)+H1(AC/DC 100V ~ 130V, Double Shunt
N02
coil)+E(Spring Auto Release)
N03 C(Counter)+B(ON/OFF Button Lock)+K2(Key Interlock Set)+R(Ready to Close switch)+T(Temperature Monitoring)
N04 A4(AL1+MRB+RES(AC200~250V))+B(ON/OFF Button Lock)+K(Key Lock(OFF Lock))+M(Mechanical Interlock)+T(Temperature Monitoring)
A1(AL1+MRB+RES110~130V)+B(ON/OFF Button Lock)+K(Key Lock(OFF Lock))+R(Ready to Close switch)+M(Mechanical
N05
Interlock)+T(Temperature Monitoring)
N06 A2(AL1+AL2+MRB)+C(Counter)+K(Key Lock(OFF Lock))+R(Ready to Close switch)+T(Temperature Monitoring)
Note) * Codes for over 5 optional accessories are composed separately
**UVT and SHT2 can not be selected together. Select one of two.
19
Ordering

Product number structure

UAL N16D 3 A H E N

For UL ACB
Frame Size Number of poles Terminal configuration Shutter
Cradle type
3 3P H Horizontal type Without safety
S16D 1600AF E
4 4P V Vertical type shutter
Line: Horizontal With safety
S20E 2000AF M F
Load: Vertical shutter
Line: Vertical
S25E 2500AF N
Secondary Load: Horizontal
Other options
Connector type P Front type
S32E 3200AF
A Connector type G Horizontal-con type
S Arc cover
B Screw joint type W Vertical-con type
S40E 4000AF
C Spring tension type * Terminals for P type must be ordered separately
* G and W types can be applicable to S16D (1600AF) only.
S50G 5000AF

20
Trip relay

N G 0

OCR(Trip Unit) type Communication & Ground fault protection Control voltage & frequency

0 No OCR

N G 0
N Normal G Ground fault, No Communication 0 Self-power 60Hz
5 Self-power 50Hz

A G 0
A Ammeter G Ground fault, No Communication 0 No Control voltage 60Hz
C Ground fault and Communication 1 AC/DC 110V~250V 60Hz
E Ground fault(with external CT), No Communication 2 DC 24V~60V 60Hz
X Ground fault(with external CT) and Communication 5 No Control voltage 50Hz
6 AC/DC 110V~250V 50Hz
7 DC 24V~60V 50Hz

P C 1
P Power meter C Ground fault and Communication 1 AC/DC 110V~250V 60Hz
X Ground fault(with external CT) and Communication 2 DC 24V~60V 60Hz
6 AC/DC 110V~250V 50Hz
7 DC 24V~60V 50Hz

S C 1
S Supreme meter C Communication 1 AC/DC 110V~250V 60Hz
X Ground fault and Communication 2 DC 24V~60V 60Hz
6 AC/DC 110V~250V 50Hz
7 DC 24V~60V 50Hz

* Ground fault detection by current vector sum of 4 phase (R,S,T,N)


* Communication and output contacts for L,S,I,G do not work except OCR LED without control power supply.
* P and S types require Voltage Module to be ordered separately.
* LCD in trip unit can be display more than 10% of rated current.
* Currnet measuring value display more than 15% of rated current.

21
Ratings for UL Listed/ANSI Certified Susol UA Circuit Breakers

TYPE UAS-��D
AF 08 16
Rated current (In max) (A) at 40°C 800 1600
Rated current (A) at 40°C 800
400 1000
600 1200
630 1250
800 1600

Rated Maximum Voltage (V) 254V / 508V / 635V


Frequency (Hz) 50/60
Number of poles (P) 3P / 4P
Type of Trip relay (Electronic trip device) N, A, P, S (4 type)
Rated short circuit current (kA) With AC 635V 65
(Sym.) instantaneous 508V 85
UL 1066 254V 85
ANSI C37.13 Without AC 635V 65
instantaneous 508V 65
254V 65
Rated short Time current (kA) 65
Operating time (t) (ms) Maximum total breaking time 50ms
Maximum closing time 80ms
Life cycle ACB (time) Mechanical Without maintenance 12,500
With maintenance
Electrical Without maintenance 2,800
With maintenance
Weight lb (kg) Drawout type Main Body 3P 154 (70)
with Cradle 4P 187 (85)
Only Cradle 3P 71 (32)
4P 84 (38)
Fixed type Motor charging 3P 77 (35)
type 4P 99 (45)
External Draw-out type in (mm) H×W×D 3P 16.93×13.15×16.02
dimension (430×334×407)
4P 16.93×16.5×16.02
(430×419×407)
H
Fixed type in (mm) H×W×D 3P 11.81×11.81×11.61
D
W (300×300×295)
4P 11.81×15.16×11.61
(300×385×295)
Enclosure dimension in (mm) H×W×D 3P 19.69×15.75×13.39
(500×400×340)
4P 19.69×19.69×13.39
(500×500×340)

22
UAH-��E UAH-��G
08 16 20 25 32 32 40 50
800 1600 2000 2500 3200 3200 4000 5000
400 800 1000 1200 1600 1600 2000 2500
600 1000 1200 1250 2000 2000 2500 3000
630 1200 1250 1600 2500 2500 3000 3200
800 1250 1600 2000 3000 3000 3200 3600
1600 2000 2500 3200 3200 3600 4000
4000 5000
254V / 508V / 635V 254V / 508V / 635V
50/60 50/60
3P / 4P 3P / 4P
N, A, P, S (4 type) N, A, P, S (4 type)
85 100
100 130
100 130
85 100
85 100
85 100
85 100
50ms 50ms
80ms 90ms
12,500 5,000 5,000

2,800 1,000 1,000

214 (97) 245 (111) 326 (148) 489 (222)


269 (122) 309 (140) 414 (188) 626 (284)
99 (45) 123 (56) 205 (93) 276 (125)
121 (55) 152 (69) 256 (116) 355 (161)
101 (46) 110 (50) 196 (89) 227 (103)
126 (57) 137 (62) 249 (113) 287 (130)
16.93×16.22×16.02 18.11×30.91×16.02
(430×412×407) (460×785×407)
16.93×20.75×16.02 18.11×39.96×16.02
(430×527×407) (460×1015×407)
11.81×14.88×11.61 11.81×29.57×11.61
(300×378×295) (300×751×295)
11.81×19.41×11.61 11.81×38.62×11.61
(300×493×295) (300×981×295)
19.69×19.69×13.39 31.5×32.48×13.39
(500×500×340) (800×825×340)
19.69×24.21×13.39 31.5×41.54×13.39
(500×615×340) (800×1055×340)

23
Trip relay(OCR)
The trip relay of Susol ACB provides the additional protection functions for
voltage, frequency, unbalance, and others in addition to main protection
functions for over current, short-circuit, ground fault. It supports the
advanced measurement functions for voltage, current, power, electric energy,
harmonics, communication function, and others.
Analog trip function interlocked with mechanism enhanced a durability of
devices as well as the breaking capacity of ACB.
Zone selective interlocking function makes the protective coordination more
simple and thermal memory can be applied to various loads.

Contents
Trip relay types 25
N type:�Normal�
�type 26
A type:�Ammeter�
�type 28
P type:�Power meter�
�type 30
S type:�Supreme meter�
�type 32
Operation characteristic 34
Measurement function 36
Man machine interface 37
Protection element setting 38
Measurement element display 39
Characteristic curves 40
ZSI - Zone Selective Interlocking 45
Remote reset and digital I/O 46
Communication 47
Event & fault recording 48
System information 48
System block diagram 49
Trip relays

Trip relay types

Classification N type A type P type S type

Externals

Current �L / S / I / G �L / S / I / G / Thermal �L / S / I / G / Thermal(Continuous) �L / S / I / G / Thermal(Continuous)


protection �ZSI(Protective coordination) �ZSI(Protective coordination) �ZSI(Protective coordination)
� Earth leakage (Option) �Earth leakage(Option) �Earth leakage(Option)
�Over/Under current �Over/Under current
Other
- �Over/Under frequency �Over/Under frequency
protection
�Unbalance(Voltage/Current) �Unbalance(Voltage/Current)
�Reverse power �Reverse power
�Current (R / S / T / N) �3 Phase Voltage/Current RMS/Vector �3 Phase Voltage/Current RMS/Vector
�Power(P, Q, S), PF(3-Phase) �Power(P, Q, S), PF(3-Phase)
�Energy(Positive/Negative) �Energy(Positive/Negative)
Measurement
- �Frequency, Demand �Frequency, Demand
function
�Voltage/Current harmonics (1st~63th)
�3 Phase Waveforms
�THD, TDD, K-Factor
�Fine adjustment for long/short �Fine adjustment for long/short
Fine adjustment - -
time delay/instantaneous/ ground time delay/instantaneous/ ground
�Overload protection relays �Overload protection relays
Pre Trip Alarm - : DO (Alarm) (Ground fault is not : DO (Alarm) (Ground fault is not
available when using Pre trip alarm) available when using Pre trip alarm)
�3DO (Fixed) �3DO (Programmable) �3DO (Programmable)
Digital Output -
�L, S/I, G Alarm �Trip, Alarm, General �Trip, Alarm, General
�Compliance with IEC60255-3 �Compliance with IEC60255-3
IDMTL setting - -
SIT, VIT, EIT, DT SIT, VIT, EIT, DT
�Modbus/RS-485 �Modbus / RS-485 �Modbus / RS-485
Communication -
�Profibus-DP �Profibus-DP �Profibus-DP
�Self Power �Self Power �AC/DC 100~250V �AC/DC 100~250V
- Power shource - Power shource works �DC 24~60V �DC 24~60V
works over 20% of over 20% of load current.
Power supply load current. - External power source are Basic protection function(L / S / I / G)
required for comm. is still under normal operation
�AC/DC 100~250V without control power.
�DC 24~60V
RTC timer - �Available �Available �Available
�Long time delay �Long time delay �Long time delay �Long time delay
LED for
�Short time delay/Instantaneous �Short time delay/Instantaneous �Short time delay/Instantaneous �Short time delay/Instantaneous
trip info.
�Ground fault �Ground fault �Ground fault �Ground fault
�10 records �256 records �256 records
Fault recording -
(Fault/Current/Date and Time) (Fault/Current/Date and Time) �Last fault wave recording (3 Phase)
Event recording - - �256 records(Content, Status, Date) �256 records(Content, Status, Date)
Operating �Reset button �Reset, Menu �Reset, Menu �Reset, Menu
button Up/Down, Left/Right, Enter Up/Down, Left/Right, Enter Up/Down, Left/Right, Enter

25
Trip relays

N type:�Normal�
�type

■ Optimized protection function


■ OCR, OCGR function according IEC60947-2
■ Overload protection
- Long-time delay
- Thermal
■ Short-circuit protection
- Short-time delay / Instantaneous
- I2t On/Off optional (for short-time delay)
■ Ground fault protection
- I2t On/Off optional
■ Self-Power

① LED: Indication of trip info. and overload state

Isd
Alarm SP Ir Ii Ig

Ig: LED indicating ground-fault


Isd/Ii: LED indicating short-time or instantaneous tripping
Ir: LED indicating long-time delay
SP: Self-protection and battery test LED
Alarm: LED indicating an overload
(Turn on above 90%, Blink above 105%)

① ②
② Reset Key: Fault reset or battery check

③ Iu, Ir: Long-time current setting, tr: Long-time tripping delay setting

④ Isd: Short-time current setting, tsd: Short-time tripping delay setting

⑤ Ii: Instantaneous current setting


③ ⑥ Ig: Ground fault current setting, tg: Ground fault tripping delay setting

⑦ Test terminal: OCR test terminal (Connected with OCR tester)

⑧ Rating plug

⑤ - Rated current setting (45~100% of the AF)
- Frequency selectable(60Hz/50Hz)


26
Trip relays

Protection
Long time
t
Current setting (A) Iu = In×... 0.5 0.6 0.7 0.8 0.9 1.0 Ir
Ir = Iu×... 0.8 0.83 0.85 0.88 0.9 0.93 0.95 0.98 1.0
Time delay (s) tr@(1.5×lr) 12.5 25 50 100 200 300 400 500 Off tr

Accuracy: ±15% or below tr@(6.0×lr) 0.5 1 2 4 8 12 16 20 Off lsd


tsd
100ms tr@(7.2×lr) 0.34 0.69 1.38 2.7 5.5 8.3 11 13.8 Off
Ii
Short time
I
Current setting (A)
Isd = Ir×... 1.5 2 3 4 5 6 8 10 Off
Accuracy: ±10%
Time delay (s) I2t Off 0.05 0.1 0.2 0.3 0.4
tsd
@ 10×Ir I t On
2
0.1 0.2 0.3 0.4
Min. Trip
20 80 160 260 360
Time(ms)
(I t Off)
2

Max. Trip
80 140 240 340 440
Time(ms)
Instantaneous
Current setting (A) Ii = In×... 2 3 4 6 8 10 12 15 Off
Tripping time below 50ms
Ground fault
t
Pick-up (A)
Accuracy: ±10%(Ig�0.4In) Ig = In×... 0.2 0.3 0.4 0.5 0.6 0.7 0.8 1.0 Off
±20%(Ig≤0.4In) Ig

I t Off
2
0.05 0.1 0.2 0.3 0.4
tg tg
I2t On 0.1 0.2 0.3 0.4
Time delay (s) Min. Trip
20 80 160 260 360 I
@ 1×In Time(ms)
(I t Off)
2

Max. Trip
80 140 240 340 440
Time(ms)

27
Trip relays

A type:�Ammeter�
�type

■ Overload protection ■ Measurement and Display Function


- Long-time delay - High detailed measurement for current
- Thermal - character LCD type
■ Short-circuit protection ■ Fault recording
- Short-time delay / Instantaneous - Records Max. up to 10 fault information about fault type,
- I2t On/Off optional (for short-time delay) fault phase, fault data, occurrence time of fault
■ Ground fault protection ■ SBO (Select Before Operation)
- I2t On/Off optional - High reliability for control and setting change method
- Trip/Alarm selectable (need external power) ■ 3 DO(Digital Output)
- Blocking Time (0~60s) - Fixed
Do not ground fault detect during Blocking time ■ Communication
■ Realization of protective coordination by ZSI - Modbus/RS485
(Zone Selective Interlocking) - Profibus-DP
- Disable/Enable Selectable
■ High-performance and high-speed MCU built-in
- Accurate measurement with tolerance of 1.0%

① LCD: Indication of measurement and information

② LED: Indication of trip info. and overload state

Isd
Alarm SP Ir Ii Ig Comm

Ig: LED indicating ground-fault


Isd/Ii: LED indicating short-time or instantaneous tripping
Ir: LED indicating long-time delay
SP: Self-protection and battery test LED
Alarm: LED indicating an overload
(Turn on above 90%, Blink above 105%)

③ Key: Move to menu or reset



Reset
Esc

Reset/ESC: Fault reset or ESC from menu


④ Enter: Enter into secondary menu or setting input
Up/Down: Move the cursor up/down on screen or
increase/decrease a setting value
⑤ Right/Left: Move the cursor or setting right/left on screen
(Rotation)

Menu: Menu display ↔ Measurement display

⑦ ④ Iu, Ir: Long-time current setting, tr: Long-time tripping delay setting

⑤ Isd: Short-time current setting, tsd: Short-time tripping delay setting
⑥ Ii: Instantaneous current setting
⑦ Ig: Ground fault current setting, tg: Ground fault tripping delay setting

⑨ ⑧ Test terminal: OCR test terminal (Connected with OCR tester)


⑨ Rating plug
- Rated current setting (45~100% of the AF)
- Frequency selectable(60Hz/50Hz)

28
Trip relays

Protection
Long time t
Current setting (A) Iu = In×... 0.5 0.6 0.7 0.8 0.9 1.0 Ir

Ir = Iu×... 0.8 0.83 0.85 0.88 0.9 0.93 0.95 0.98 1.0
Time delay (s) tr@(1.5×lr) 12.5 25 50 100 200 300 400 500 Off tr

Accuracy: ±15% or below tr@(6.0×lr) 0.5 1 2 4 8 12 16 20 Off lsd


tsd
100ms tr@(7.2×lr) 0.34 0.69 1.38 2.7 5.5 8.3 11 13.8 Off
Ii
Short time
I
Current setting (A)
Isd = Ir×... 1.5 2 3 4 5 6 8 10 Off
Accuracy: ±10%
Time delay (s) I2t Off 0.05 0.1 0.2 0.3 0.4
tsd
@ 10×Ir I t On
2
0.1 0.2 0.3 0.4
Min. Trip
20 80 160 260 360
Time(ms)
(I t Off)
2

Max. Trip
80 140 240 340 440
Time(ms)
Instantaneous
Current setting (A) Ii = In×... 2 3 4 6 8 10 12 15 Off
Tripping time below 50ms
Ground fault t
Pick-up (A)
Accuracy: ±10%(Ig�0.4In) Ig = In×... 0.2 0.3 0.4 0.5 0.6 0.7 0.8 1.0 Off
±20%(Ig≤0.4In) Ig

I t Off
2
0.05 0.1 0.2 0.3 0.4
tg tg
I2t On 0.1 0.2 0.3 0.4
Time delay (s) Min. Trip I
20 80 160 260 360
@ 1×In Time(ms)
(I t Off)
2

Max. Trip
80 140 240 340 440
Time(ms)

Earth leakage (Option) t


Current setting (A) I△n 0.5 1 2 3 5 10 20 30 Off
Time delay (ms) Alarm
140 230 350 800 950
Accuracy: ±15% Time(ms) I n
△t
Trip
140 230 350 800 t
Time(ms)
Note) Current setting values are secondary current of the external CT.
Recommend : not to use current setting values more than 5A. I

29
Trip relays

P type:�Power meter�
�type
■ Overload protection ■ IDMTL setting (SIT, VIT, EIT, DT curve)
- Long-time delay - Basic setting : “None”. Thermal curve.
- Thermal ■ Measurement and Display Function
■ Short-circuit protection - High detailed measurement for 3 phase
- Short-time delay / Instantaneous current/Voltage/Power/Energy/Phase
- I2t On/Off optional (for short-time delay) angle/Frequency/PF/Demand
■ Ground fault protection - 128 x 128 Graphic LCD
- I2t On/Off optional - Indicates current/voltage Vector Diagram and Waveform
- Trip/Alarm selectable (need external power) ■ Fault recording
- Blocking Time (0~60s) - Records Max. up to 256 fault information about fault
Do not ground fault detect during Blocking time type, fault phase, fault value, occurrence time of fault
■ Protection for Over voltage/Under voltage/Over ■ Event recording
frequency/Under frequency/Unbalance/Reverse power - Records events of device related to setting change,
■ Realization of protective coordination by ZSI operation and state change. (Max. up to 256)
(Zone Selective Interlocking) ■ SBO (Select Before Operation)
- Disable/Enable Selectable - High reliability for control and setting change method
■ The fine-adjustable setting by knob and Key ■ 3 DO(Digital output)
- Programmable for alarm, trip and general DO
■ Communication
- Modbus/RS485
- Profibus-DP

① Graphic LCD: Indication of measurement and information

② LED: Indication of trip info. and overload state

Isd
Alarm SP Ir Ii Ig Comm

Comm: LED indicating comm. state (Blink when running)


Ig: LED indicating ground-fault
Isd/Ii: LED indicating short-time or instantaneous tripping
Ir: LED indicating long-time delay
SP: Self-protection and battery test LED
Alarm: LED indicating an overload
(Turn on above 90%, Blink above 105%)
③ Key: Move to menu or reset

Reset
Esc

Reset/ESC: Fault reset or ESC from menu


④ Enter: Enter into secondary menu or setting input
Up/Down: Move the cursor up/down on screen or
increase/decrease a setting value
Right/Left: Move the cursor or setting right/left on screen
⑤ (Rotation)
⑥ Menu: Menu display ↔ Measurement display

④ Ir: Long-time current setting, tr: Long-time tripping delay setting


⑦ ⑧
⑤ Isd: Short-time current setting, tsd: Short-time tripping delay setting
⑥ Ii: Instantaneous current setting
⑦ Ig: Ground fault current setting, tg: Ground fault tripping delay setting
⑨ ⑧ Test terminal: OCR test terminal (Connected with OCR tester)
⑨ Rating plug
- Rated current setting (45~100% of the AF)
- Frequency selectable(60Hz/50Hz)

30
Trip relays

Protection
Long time
t
Current setting (A) Ir = In×... 0.4 0.5 0.6 0.7 0.8 0.9 1.0 Ir
Time delay (s) tr@(1.5×lr) 12.5 25 50 100 200 300 400 500 Off
Accuracy: ±15% or below tr@(6.0×lr) 0.5 1 2 4 8 12 16 20 Off tr
100ms tr@(7.2×lr) 0.34 0.69 1.38 2.7 5.5 8.3 11 13.8 Off lsd
Short time tsd
Current setting (A) Ii
Isd = Ir×... 1.5 2 3 4 5 6 8 10 Off
Accuracy: ±10% I

Time delay (s) I2t Off 0.05 0.1 0.2 0.3 0.4
tsd
@ 10×Ir I2t On 0.1 0.2 0.3 0.4
Min. Trip
20 80 160 260 360
Time(ms)
(I2t Off)
Max. Trip
80 140 240 340 440
Time(ms)
Instantaneous
Current setting (A) Ii = In×... 2 3 4 6 8 10 12 15 Off
Tripping time below 50ms
Ground fault t
Pick-up (A)
Accuracy: ±10%(Ig�0.4In) Ig = In×... 0.2 0.3 0.4 0.5 0.6 0.7 0.8 1.0 Off
±20%(Ig≤0.4In) Ig
I2t Off 0.05 0.1 0.2 0.3 0.4
tg
I2t On 0.1 0.2 0.3 0.4 tg

Time delay (s) Min. Trip


20 80 160 260 360
@ 1×In Time(ms) I
(I2t Off)
Max. Trip
80 140 240 340 440
Time(ms)

Earth leakage (Option) t


Current setting (A) I△n 0.5 1 2 3 5 10 20 30 Off
Time delay (ms) Alarm
140 230 350 800 950
Accuracy: ±15% Time(ms) I n
△t
Trip
140 230 350 800
Time(ms) t
Note) Current setting values are secondary current of the external CT.
Recommend : not to use current setting values more than 5A.
I
PTA(Pre Trip Alarm)
Current setting (A) Ip = Ir x … 0.6 0.65 0.7 0.75 0.8 0.85 0.9 0.95 1
Time delay (s)
tp@(1.2×Ip) 1 5 10 15 20 25 30 35 Off
Accuracy: ±15%

Pick-up Time delay(s)


Other protection
Setting range Step Accuracy Setting range Step Accuracy
Under voltage 80V ~ 0V_Pick-up 1V ±5%
Over voltage UV_Pick-up ~ 980V 1V ±5% 1.2~40sec
Voltage unbalance 6% ~ 99% 1% ±2.5% or (*±10%)
Reverse power 10~500 kW 1kW ±10%
0.2~40sec
Over power 500~5000 kW 1kW ±10%
0.1sec ±0.1sec
Current unbalance 6% ~ 99% 1% ±2.5% or (*±10%)
Over 60Hz UF_Pick-up ~ 65 1Hz ±0.1Hz
frequency 50Hz UF_Pick-up ~ 55 1Hz ±0.1Hz 1.2~40sec
Under 60Hz 55Hz ~ OF_Pick-up 1Hz ±0.1Hz
frequency 50Hz 45Hz ~ OF_Pick-up 1Hz ±0.1Hz

31
Trip relays

S type:�Supreme meter�
�type
■ Overload protection - 128 x 128 Graphic LCD
- Long-time delay - Indicates current/voltage Vector Diagram and Waveform
- Thermal ■ Fault recording
■ Short-circuit protection - Records Max. up to 256 fault information about fault
- Short-time delay / Instantaneous type, fault phase, fault value, occurrence time of fault
- I2t On/Off optional (for short-time delay) - Fault wave recording: records the latest fault wave
■ Ground fault protection ■ Event recording
- I2t On/Off optional - Records events of device related to setting change,
- Trip/Alarm selectable (need external power) operation and state change. (Max. up to 256)
- Blocking Time (0~60s) ■ SBO (Select Before Operation)
Do not ground fault detect during Blocking time - High reliability for control and setting change method
■ Protection for Over voltage/Under voltage/Over ■ Power quality analysis
frequency/Under frequency/Unbalance/Reverse power - Measurement for 1st~63th harmonics
■ Realization of protective coordination by ZSI - THD, TDD, k-Factor
(Zone Selective Interlocking) - Voltage/current waveform capture
- Disable/Enable ■ 3 DO(Digital output)
■ The fine-adjustable setting by knob and Key - Programmable for alarm, trip and general DO
■ IDMTL setting (SIT, VIT, EIT, DT curve) ■ Communication
- Basic setting : “None”. Thermal curve. - Modbus/RS485
■ Measurement and Display Function - Profibus-DP
- High detailed measurement for 3 phase current/Voltage/
Power/Energy/Phase angle/Frequency/PF/Demand

① Graphic LCD: Indication of measurement and information


② LED: Indication of trip info. and overload state

Isd
Alarm SP Ir Ii Ig Comm

Comm: LED indicating comm. state (Blink when running)


Ig: LED indicating ground-fault
Isd/Ii: LED indicating short-time or instantaneous tripping
Ir: LED indicating long-time delay
SP: Self-protection LED and battery test LED
Alarm: LED indicating an overload
(Turn on above 90%, Blink above 105%)
③ Key: Move to menu or reset

② Reset
Esc

Reset/ESC: Fault reset or ESC from menu


Enter: Enter into secondary menu or setting input
④ Up/Down: Move the cursor up/down on screen or
increase/decrease a setting value
Right/Left: Move the cursor or setting right/left on screen
(Rotation)
⑤ Menu: Menu display ↔ Measurement display

④ Ir: Long-time current setting, tr: Long-time tripping delay setting
⑦ ⑧ ⑤ Isd: Short-time current setting, tsd: Short-time tripping delay setting
⑥ Ii: Instantaneous current setting
⑦ Ig: Ground fault current setting, tg: Ground fault tripping delay setting
⑧ Test terminal: OCR test terminal (Connected with OCR tester)
⑨ ⑨ Rating plug
- Rated current setting (45~100% of the AF)
- Frequency selectable(60Hz/50Hz)

32
Trip relays

Protection
Long time
t
Current setting (A) Iu = In×... 0.4 0.5 0.6 0.7 0.8 0.9 1.0 Ir
Time delay (s) tr@(1.5×lr) 12.5 25 50 100 200 300 400 500 Off
Accuracy: ±15% or below tr@(6.0×lr) 0.5 1 2 4 6 12 16 20 Off tr
100ms tr@(7.2×lr) 0.34 0.69 1.38 2.7 5.5 8.3 11 13.8 Off lsd
Short time tsd
Current setting (A) Ii
Isd = Ir×... 1.5 2 3 4 5 6 8 10 Off
Accuracy: ±10% I

Time delay (s) I2t Off 0.05 0.1 0.2 0.3 0.4
tsd
@ 10×Ir I2t On 0.1 0.2 0.3 0.4
Min. Trip
20 80 160 260 360
Time(ms)
(I2t Off)
Max. Trip
80 140 240 340 440
Time(ms)
Instantaneous
Current setting (A) Ii = In×... 2 3 4 6 8 10 12 15 Off
Tripping time below 50ms
Ground fault t
Pick-up (A)
Accuracy: ±10%(Ig�0.4In) Ig = In×... 0.2 0.3 0.4 0.5 0.6 0.7 0.8 1.0 Off
±20%(Ig≤0.4In) Ig
I2t Off 0.05 0.1 0.2 0.3 0.4
tg
I2t On 0.1 0.2 0.3 0.4 tg

Time delay (s) Min. Trip


20 80 160 260 360
@ 1×In Time(ms) I
(I2t Off)
Max. Trip
80 140 240 340 440
Time(ms)

Earth leakage (Option) t


Current setting (A) I△n 0.5 1 2 3 5 10 20 30 Off
Time delay (ms) Alarm
140 230 350 800 950
Accuracy: ±15% Time(ms) I n
△t
Trip
140 230 350 800
Time(ms) t
Note) Current setting values are secondary current of the external CT.
Recommend : not to use current setting values more than 5A.
I
PTA(Pre Trip Alarm)
Current setting (A) Ip = Ir x … 0.6 0.65 0.7 0.75 0.8 0.85 0.9 0.95 1
Time delay (s)
tp@(1.2×Ip) 1 5 10 15 20 25 30 35 Off
Accuracy: ±15%

Pick-up Time delay(s)


Other protection
Setting range Step Accuracy Setting range Step Accuracy
Under voltage 80V ~ 0V_Pick-up 1V ±5%
Over voltage UV_Pick-up ~ 980V 1V ±5% 1.2~40sec
Voltage unbalance 6% ~ 99% 1% ±2.5% or (*±10%)
Reverse power 10~500 kW 1kW ±10%
0.2~40sec
Over power 500~5000 kW 1kW ±10%
0.1sec ±0.1sec
Current unbalance 6% ~ 99% 1% ±2.5% or (*±10%)
Over 60Hz UF_Pick-up ~ 65 1Hz ±0.1Hz
frequency 50Hz UF_Pick-up ~ 55 1Hz ±0.1Hz 1.2~40sec
Under 60Hz 55Hz ~ OF_Pick-up 1Hz ±0.1Hz
frequency 50Hz 45Hz ~ OF_Pick-up 1Hz ±0.1Hz

33
Trip relays

Operation characteristics

Long-time delay (L)


The function for overload protection which has time delayed N, A type Iu
.8
.9
1
Ir
.88
.9
.93
tr
4
8
12
.7 .85 .95 2 16
characteristic in inverse ratio to fault current. .6 .83 .98 1 20
.5 .8 1 .5 off
Iong time
×In ×Iu @6 Ir
1. Standard current setting knob: Ir
1) Setting range in P type and S type: (0.4-0.5-0.6-0.7-0.8-0.9-1.0)×In P, S type
Ir
.7
.8
.9
tr
(S) 4
8
12
.6 1 2 16
2) Setting range in N type and A type: (0.4 ~1.0)×In .5 1 20
t .4 .5 off
- Iu: (0.5-0.6-0.7-0.8-0.9-1.0)×In Iong time

Ir ×In @6 Ir

- Ir: (0.8-0.83-0.85-0.88-0.9-0.93-0.95-0.98-1.0)×Iu
2. Time delay setting knob: tr
- Standard operating time is based on the time of 6×Ir tr
- Setting range: 0.5-1-2-4-8-12-16-20-Off sec (9 modes)
3. Relay pick-up current
- When current over (1.15)×Ir flows in, relay is picked up.
I
4. Relay operates basing on the largest load current among R/S/T/N phase.

Short-time delay (S)


The function for fault current (over current) protection which has definite
time characteristic and time delayed in inverse ratio to fault current. Isd
4
5
6
tsd
(S) .4
.4
.3
3 8 .3 .2
2 10 .2 .1
1. Standard current setting knob: Isd 1.5 off .1 .05
short time
- Setting range: (1.5-2-3-4-5-6-8-10-Off)×Ir ×Ir on 2 off
I t

t
2. Time delay setting knob: tsd
- Standard operating time is based on the time of 10×Ir.
- Inverse time (I2t On ): 0.1-0.2-0.3-0.4 sec
- Definite time (I2t Off): 0.05-0.1-0.2-0.3-0.4 sec Isd
3. Relay operates basing on the largest load current among R/S/T/N phase.
tsd
4. When ZSI function was set, the protection operation will take place instantaneously with input absence
by downstream devices. It is advised to disable its ZSI function on the last downstream device.
I

Instantaneous (I)
The function for breaking fault current above the setting value within
the shortest time to protect the circuit from short-circuit. Ii
6
8
10
4 12
15
1. Standard current setting knob: Ii 3
2 off
instantaneous
- Setting range: (2-3-4-6-8-10-12-15-Off)×In ×In

t
2. Relay operates basing on the largest load current among R/S/T/N phase.
3. Total breaking time is below 50ms.

Ii

34
Trip relays

Ground Fault (G)


The function for breaking ground fault current above setting value
after time-delay to protect the circuit from ground fault. Ig
.5
.6
.7
tg
(S) .4
.4
.3
.4 .8 .3 .2
.3 1 .2 .1
1. Standard setting current knob: Ig .2 off .1 .05
ground fault
on 2 off

- Setting range: (0.2-0.3-0.4-0.5-0.6-0.7-0.8-1.0-Off)×In ×In I t

t
2. Time delay setting knob: tg
- Inverse time (I2t On): 0.1-0.2-0.3-0.4 sec
- Definite time (I2t Off): 0.05-0.1-0.2-0.3-0.4 sec
Ig
3. Ground fault current is vector sum of each phase current. Therefore, 3Pole products may operate
under its phase-unbalance including ground fault situations.(R+S+T+(N) Phase)
tg
4. When ZSI function was set, the protection operation will take place instantaneously with input absence
by downstream devices. It is advised to disable its ZSI function on the last downstream device.
I
5. Ground-fault functions are basically provided with products equipped with a trip relay through its
internal CT that is embedded in each phase.(But, it can’t be used with earth-leakage protection
function at the same time)

Earth Leakage (G) - Option


The function for breaking earth leakage current above setting value after
time delay to protect the circuit from earth leakage. (A, P, S type) I n
3
5
10
t
(ms)
800
950
800
2 20 350 350
1 30 230 230
1. Standard setting current knob: I△n 0.5 off 140 140
earth leakage trip alarm
- Setting range: 0.5-1-2-3-5-10-20-30-Off (A)
t
2. Time delay setting knob: △t
- Trip time: 140-230-350-800 ms
- Alarm time: 140-230-350-800-950 ms
I n
3. Settings within its alarm range will prevent its breaker from tripping but activating its alarm.
4. This function is enabled and can be used only with private external CT(secondary output 5A)
t
selected by customers.
5. When ZSI function was set, the protection operation will take place instantaneously with input
I
absence by downstream devices. It is advised to disable its ZSI function on the last downstream
device.

※Use cautions with earth-leakage current settings R S T N


- When using other CT selected by customers, the setting range is from 0.5 to 5A based on its
secondary current.(Secondary output rating : 5A) ZCT or External
CT
Hence, under 100:5A CT, if trip relay is set to 0.5A, earth-leakage exceeding 10A will activate its
operation (0.5A×20 = 10A)

※Guideline for the external CT usage


A
- Earth-leakage protection characteristics using the standard CT which is installed inside of ACB can
protect currents from 20 to 100% range on its rated current.
- As rated currents on ACB increases, current that is covered by its standard CT increase as well.
This can not protect against small leakage currents.
ex) 400A ACB Min. Earth-leakage current 400A×20% =80A
4000A ACB Min. Earth-leakage current 4000A×20% =800A
- Therefore, customers are advised to install an external CT in accordance with its rated currents ZCT or External
CT
within its systems. And choose trip relay(E, X type) which is required with external CT usage in
order to provide earth-leakage functions.
B

35
Trip relays

Measurement function

Measurement
Class. Detailed element Unit Display range Accuracy
element
Line current Ia,Ib,Ic ±3%
Current Normal current I1 A 80A~65,535A
Reverse current I2
Line voltage Vab,Vbc,Vca ±1%
Phase voltage Va,Vb,Vc ±1%
Voltage V 60~690V
Normal voltage V1
Reverse voltage V2
Line-to-line ∠VabIa, ∠VabIb, ∠VabIc,
±1°
Line-to-current ∠VabVbc, ∠VabVca
Angle ° 0~360°
Phase-to-phase ∠VaVb,∠VaVc ±1°
Phase-to-current ∠VaIa, ∠VbIb, ∠VcIc ±1°
Active power Pa(ab), Pb(bc), Pc(ca), P kW 1kW~99,999kW ±3%
Power Reactive power Qa(ab), Qb(bc), Qc(ca), Q kVar 1kVar~99,999kVar ±3%
Apparent power Sa(ab), Sb(bc), Sc(ca), S kVA 1kVA~99,999kVA ±3%
WHa(ab), WHb(bc), kWh
Active energy 1kWh~9999.99MWh ±3%
WHc(ca), WH MWh
VARHa(ab), VARHb(bc), kVarh
Energy Reactive energy 1kVarh~9999.99MVarh ±3%
VARHc(ca), VARH Mvarh
Reverse active rWHa(ab), rWHb(bc), kWh
1kWh ~9999.99MWh ±3%
energy rWHc(ca), rWH MWh
Freq. Frequency F Hz 45~65Hz
Power factor Power factor(PF) PFa(ab), PFb(bc), PFc(ca), PF +: Lead, -: Lag
Unbalance Unbalance rate Iunalance, Vunbalance % 0.0~100.0
Active power
Peak demand kW 1kW~99999kW
Demand demand
Current demand Peak demand A 80A~65,535A
Voltage 1st~63th harmonics of
V 60~690V
harmonics Va(ab),Vb(bc),Vc(ca)
Harmonics Current harmonics 1st~63th harmonics of Ia,Ib,Ic A 80A~65,535A
THD, TDD % 0.0~100.0
K-Factor - 0.0~100.0

Voltage module
For P and S type Trip relay, separate voltage module is necessary
to measure other element besides current (Seperate purchase is needed)
- Voltage input range: AC 60~690V

Vr Vs Vt Vn Vr Vs Vt

1 13 V1 1 13 V1
2 14 V2 2 14 V2
3 15 V3 3 15 V3
4 16 Vn 4 16 Vn
5 17 5 17
6 Voltage 18 6 Voltage 18
7 module 19 7 module 19
8 20 8 20
9 9
10 10
11 11
12 12

3P4W wiring 3P3W wiring


36
Trip relays

Man machine interface

Initial display Measurement display


1000 A
M R S T N
Setting display
100%

50%
1. H/W set 2. Relay set 3. Events 4. Sys info 5. L/R (L)

1. Wiring 1. OCR 1. Event


Initial display
2. Comm 2. OCGR 2. Clear All

3. Password 3. OVR/UVR 3. Fault

4. Time-RTC 4. Unbal 4. Clear All

5. PT Ratio 5. rP/OPR

6. Demand 6. OFR/UFR

7. Data Rst

Max Power
Demand
Energy

CB Count
Run Time

8. DO Setup

9. Language

10. Option

An example of graphic LCD display

1000 A
1000 A Ir Ir =
R S T N
R S T N .7
.8
.9
.6 1
100%
.5
100%
50%
.4

50%
×In 1000 A
Ir adjustment
knob

Initial display Displayed screen when changing


Ir value into 1.0
(After 3 sec, return to initial display)

tg
(S) .4
.4
.3 Tg =
.3 .2
.2 .1
.1 .05 200 ms
on 2 off
I t [I2t](Off)
tg adjustment
knob
Displayed screen when changing
tg value into 0.2
(After 3sec, return to initial display)

37
Trip relays

Protection element setting

Initial display Setting display


M
1000 A 1.H/W Set 1.H/W Set
R S T N 2.Relay Set 2.Relay Set
100%
3.Events 3.Events
4.Sys Info 4.Sys Info
50%

5.L/R [L] 5.L/R [L]

PASSWORD 1.OCR
2.OCGR
3.OVR/UVR
4.Unbal
XXXX 5.rP/OPR
Password input Relay setting display

Find adjustment of protection setting current


Find adjustment of long-time delay �OCR and OCGR's current
OCR-L, S, I setting is basically controlled by
Select one IDTM characteristic knob's setting values.
800 A
curve among DT, SIT, VIT and EIT
EIT �The fine current that cannot
6400 A Find adjustment of short-time delay be controlled by knob is
I2T
[Off]
adjustable by using , key.
15000 A Find adjustment of Instantaneous �Fine adjustment is only
adjustable in the present knob
and next knob's setting range,
when moving knob, the
adjusted data becomes reset
state.
OCR-L, S, I OCR-L, S, I OCR-L, S, I
800 A 800 A 800 A
EIT EIT EIT
6400 A 6400 A 6401 A
I2T I2T I2T
[Off] [Off] [Off]
15000 A 15000 A 15000 A �The setting method of OCGR
is same with OCR's, fine
adjustment is available.
� �
1.OCR OVR/UVR Set 1.OCR Unbal V/I
Pick Up : 724 V Pick Up : 6%
2.OCGR Delay : 1.2 s
2.OCGR Delay : 10.0 s
3.OVR/UVR Action : None 3.OVR/UVR Action : D02
4.Unbal Pick Up : 150 V 4.Unbal Pick Up : 12 %
Delay : 1.2 s Delay : 10.0 s
5.rP/OPR Action : D01
5.rP/OPR Action : D03
Protection setting OVR/UVR setting Relay setting display Unbalance setting
display
� �
1.OCR rPower 6.OFR/UFR OFR/UFR Set
Pick Up :100 kW Pick Up : 65 Hz
2.OCGR Delay : 10.0 s Delay : 10.0 s
3.OVR/UVR Action : D02 Action : D01
4.Unbal Pick Up : 2400 kW Pick Up : 55 Hz
Delay : 0.2 s Delay : 10.0 s
5.rP/OPR Action : TRIP Action : None
Relay setting Reverse power setting Relay setting display Frequency setting
display

38
Trip relays

Measurement element display

Load current
1000 A
R S T N

100%

50%

��
Measurement Metering Overview Demand Current [A] Max Power [kW]
VR 220 V∠0.0 R : 1000 987
overview
IR 1000 A∠330.0 S : 1000 2007/05/14
P 986 kW T : 1000 10:00:00
Q 589 kVar Max Demand [kW]
PF 0.866 F 60.0 986
EP 56 kWh 2007/05/14
EQ 32 kVarh 11:15:00

��
Voltage/Current Vector Diagram VOLTGAE [V] V unbal 3Phase
vector diagram VR : 220∠ 0.0 Vpos : 220 V
It
VS : 220∠240.0 Vneg : 0 V
Vt
VT : 220∠120.0
Unbal : 0.0 %
CURRENT [A] I unbal 3Phase
Vr
Is IR : 1000∠330.0 Ipos : 1000 A
Ir
IS : 1000∠210.0
Vs Ineg : 0 A
IT : 1000∠ 90.0
IN : 0 Unbal : 0.0 %

��
Power and Power Diagram Active Power [kW] Apparent [kVA]
power factor P=986 R : 328 Total R : 379 Total
Q=589
S : 328 986 S : 379 1139
T : 328 T : 379
kW Reactive [kVar] Power Factor
R : 189 Total R : 0.87 Total
1000
S : 189 589 S : 0.87 0.866
kVar 2000 T : 189 T : 0.87
��
Energy Forward Energy Forward P [kWh] Reverse P [kWh]
P+ 1051 kWh R : 360 Total R : 0 Total

Q+
S : 360 1080 S : 0 0
607 kVarh
T : 360 T : 0
Reverse Energy Forward Q [kVarh] Reverse Q [kVarh]
P- 0 kWh R : 210 Total R : 0 Total

Q-
S : 210 630 S : 0 0
0 kVarh
T : 210 T : 0
��
Voltage/Current Volt Wave & FFT [%] S Volt Harmonics [V] S Volt Harmonics [V] S Volt Harmonics [V]
harmonics THD[S] : 25.0 H1 220 H8 0 H15 0 H22 0 H57 0
H2 0 H9 0 H16 0 H23 0 H58 0
(S type)
H3 55 H10 0 H17 55 H24 0 H59 0
H4 0 H11 0 H18 0 H25 0 H60 0
I H5 0 H12 0 H19 0 H26 0 H61 0
R
H6 0 H13 0 H20 0 H27 0 H62 0
S
H7 0 H14 0 H21 0 H28 0 H63 0
��
Curr Wave & FFT [%] R Curr Harmonics [A] R Curr Harmonics [A] R Curr Harmonics [A] TDD 3Phase
THD[R] : 3.0 H1 1000 H8 0 H15 1 H22 0 H57 0 R : 0.1 %
H2 0 H9 3 H16 0 H23 1 H58 0 S : 0.1 %
H3 15 H10 0 H17 1 H24 0 H59 0 T : 0.1 %
H4 0 H11 1 H18 0 H25 1 H60 0 Current K - Factor
T
H5 20 H12 0 H19 1 H26 0 H61 0 R : 1.2
R
H6 0 H13 1 H20 0 H27 1 H62 0 S : 1.2
S
H7 0 H14 0 H21 1 H28 0 H63 0 T : 1.3

39
Trip relays

Characteristics curves

Long-time delay (L) 5000


2000

Ir = 0.4...1 In
1000

500

200

100

50
40 tr = 0.5...20s
30
20
20
12
10
8

t(s) 5 4
4
3
2
2

1
1

0.5
0.4
0.3

0.2

0.1

0.05

0.02

0.01
0.5

0.7

10

20

× Ir

40
Trip relays

Short-time delay (S) 5000


2000

1000

500 Isd = 1.5...10 Ir

200

100

50
40
30
20
10

t(s) 5
4
3
2

0.4 0.4 I2t ON 0.4


0.3 0.3 0.3
0.2 0.2 0.2
I2t OFF

0.1 0.1 0.1

0.05
0.05

0.02

0.01
0.5

0.7

10

20

× Ir

41
Trip relays

Characteristics curves

Instantaneous (I) 100


Ground fault (G)

50
40
30

20

Ig = 0.2...1 In
10

5
4
3

t(s) 1
I2t ON

0.4 0.4 0.4

0.3
0.3 0.3

0.2 0.2 0.2

I2t OFF
0.1 0.1 0.1

0.05
0.05

Ii = 2...15 In

0.02

0.01
0.05
0.07
0.1

0.2

0.3
0.4
0.5

0.7

3
4
5

10

× In

42
Trip relays

IDMTL 10000

5000

2000

EIT
1000

500
VIT

200

100
SIT
t(s)
50

20
DT

10

0.05
0.5

0.7

10

20

× Ir

43
Trip relays

Characteristics curves

Pre Trip Alarm 500

200

100

50
40 35

30

20
15

10

5
5
4
3
t(s) 2

1
1

0.4
0.3

0.2

0.1

0.05

0.02

0.01
0.5

0.7

10

20

30

× Ip

44
Trip relays

ZSI - Zone Selective Interlocking (A, P, S type)

Zone-selective interlocking drops delay time that eliminates faults for breakers.
It minimizes the shock that all kinds of electric machineries get under
fault conditions.

1. In case of that short time-delay or ground fault accident occurs at ZSI built in system,
the breaker at accident site sends ZSI signal to halt upstream breaker’s operation.
2. To eliminate a breakdown, trip relay of ACB at accident site activates trip operation
without time delay.
3. The upstream breaker that received ZSI signal adhere to pre-set short time-delay or
ground fault time-delay for protective coordination in the system.
However upstream breaker that did not receive its signal will trip instantaneously.
4. For ordinary ZSI operation, it should arrange operation time accordingly so that downstream
circuit breakers will react before upstream ones under overcurrent/short time delay/
ground fault situations.
5. ZSI connecting line needs to be Max. 3m.

① Z4
Z3
Z2
ZSI input
Z1

Fault A


Z4
ZSI output
Z3
Z2
ZSI input
Z1

Fault B

Z4 Z4 Z4
Z3 Z3 Z3
Z2 Z2 Z2
Z1 Z1 Z1

1) Occurrence of fault A
- Only breaker ① performs instantaneous trip operation.
2) Occurrence of fault B
- Breaker ② performs instantaneous trip operation,
breaker ① performs trip operation after prearranged delay time
- But if breaker ② did not break the fault normally,
breaker ① performs instantaneous trip operation to protect system.

45
Trip relays

Remote reset and digital I/O (A, P, S type)

In case of that ACB operates due to accidents or over current,


Trip relay indicates the information of the accident through the LED and LCD.
Trip relay A, P and S type is possible to perform the remote reset by digital input,
and have 3 DO(Digital output).
1. Methods to reset Trip relay is to push the Reset button on the frontal side and to
use the remote reset.
2. Digital input
- [R11-R22] input: Remote reset
- [Z1-Z2] Input: ZSI input
- [E1-E2] Input: ZCT for earth leakage detection or external CT input
※All DI are dry contact that has 3.3V of recognition voltage. When inputting close by
SSR(Solid State Relay) or open-collector, connect collector(Drain) to R11.
3. Digital output 3a(524, 534, 544-513)
- Fault output: Long/Short time delay, Instantaneous, Ground fault, UVR, OVR, UFR,
OFR, rPower, Vunbal, Iunbal
(Maintains state as Latch form until user pushes reset.)
- General DO: when setting L/R as remote, it is available to control close/open
remotely by using communication.

Voltage module
ZSI output

Common
ZSI input

Power supply
Reset

ZCT
V1 V2 V3 Vn E1 Z3 Z1 485+ R11 R22 513 R2 R1

Trip relay

Z4 Z2 485- 544 534 524


GTD

LTD
S/I

Trip Digital Long Short Instantaneous Ground Overload OVR UVR rPower Vunbal Iunbal OFR UFR OPR Note
Relay Output time time Alarm
DO1(524) ● ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
P, S DO2(534) ○ ● ● ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ Programmable
type
DO3(544) ○ ○ ○ ● ○ ○ ○ ○ ○ ○ ○ ○ ○
DO1(524) ● × × ×
A type DO2(534) × ● ● × Not available Fixed
DO3(544) × × × ●

46
Trip relays

Communication

Modbus/RS-485
�Operation mode: Differential
�Distance: Max. 1.2km
�Cable : SCADA system
General RS-485 shielded twist
2-pair cable
�Baud rate : Modbus/RS-485
9600bps, 19200bps, 38400bps
�Transmission method: Half-Duplex
�Termination: 100Ω

Profibus-DP
�Profibus-DP module is installed
separately (Option) Ethernet/TCP/IP TCP/IP/Ethernet
Area
�Operation mode: Differential controller
�Distance: Max. 1.2km
TCP/IP
�Cable :
Profibus-DP shielded twist 2-pair cable
CNC
�Baud rate: 9600bps~12Mbps
�Transmission method: Half-Duplex
�Termination resistor: 100Ω Profibus-FMS
�Standard: EN 50170 / DIN 19245 PC
DCS

PLC

Profibus-DP

Profibus-DP Profibus-DP
communication module communication
(Option) module (Option) PLC

Modbus/RS-485

47
Trip relays

Event & fault recording (P, S type)

When there are events such as setting change, Info. change, error of self-diagnose,
state change, P and S type record Max. up to 256 information of the events in accordance with
time(ms). In addition, they can record Max. up to 256(up to 10 for A type) information of the faults
such as fault cause, fault phase, fault value and so on in accordance with time(ms).

Event information display


Password
Initial display Setting display input
M
1000 A 1.H/W Set 1.Event 1. Event-L 10. Event-L
R S T N 2.Relay Set 2.Clear All 2007/05/15 2007/04/15
100%
3.Events 20:29:41 10:11:24
4.Sys Info 3.Fault Sta Change Cfg Change
50%

5.L/R [L] 4.Clear All Power On Comm Set up

Fault information display


Password
Initial display Setting display input
M
1000 A 1.H/W Set 1.Event 1. Trip 9. Trip
R S T N 2.Relay Set 2.Clear All 2007/04/26 2007/04/11
100%
3.Events 08:35:52 09:11:32
4.Sys Info 3.Fault OCR-Short UVR
50%

5.L/R [L] 4.Clear All Phase T 930A Phase R OV

System information

P and S type can indicate information as followings with the information of the ACB.
- Present time: year/month/date/hour/minute/ms
- ACB current ratings
- N-phase current ratings: 100%
- Frequency information: 60Hz / 50Hz
- Closing numbers of breaker: CB ON numbers
- Trip relay operating time: OCR ON time
- ON time of breaker: CB ON time
- F/W ver. information

System information display


Password
Initial display Setting display input

M System Info System Info


1000 A 1.H/W Set Date Time Date Time
R S T N 2.Relay Set 2007/05/15 21:23:30 2007/05/15 21:23:30
Rating 1000 A Rating 1000 A
100%
3.Events Ex-Func 4POCGR Ex-Func 4POCGR
4.Sys Info Freq 60 Hz T-OPER 220 h
50%
CB ON# 23 T-CB ON 180 h
5.L/R [L] Ver-Arm 1.5 Ver-Msp 4.01A

48
Trip relays

System block diagram

R S T N

ACB Trip
ACB

Vcc/+9V/-9V Vcc +5V +24V

CN2-1
CN2-11
CPU Display
Output (LED, LCD) MTD
CN2-3 Filter
CN2-6
CN2-13 Amp. Power PCB Main PCB
Ass’y Ass’y Output
Signal CT CN2-5
CN2-15 CN2-8
Main PCB
CN2-7 Ass’y
CN2-16
CN2-14 Setting
part
GND 24

CN2-4
Vcc RY0 (K1)
Self CN4-2
+24V GTD contact
power
GND+24V RY1 (K2)
Power CT CN4-4
Main PCB +5V STD/INST contact
Ass’y
RY2 (K3)
-5V CN4-6
CN2-2 LTD contact

CN4-8
Trip relay

Common contact
Additional source CN4-9
AC/DC 100~250V
SMPS
CN4-10 Power PCB
DC 24~60V
Ass’y

CN1-1
ZSI output+ terminal
CN1-9 CN1-2
ZSI output- terminal
CN1-10 CN1-3
VDM ZSI input+ terminal
CN1-11 CN1-4
ZSI input- terminal
CN1-12

CN1-5
CN1-7 Remote reset+ terminal
Earth CN1-6
CN1-8 Remote reset- terminal

Input signal(R phase) CN3-2 CN1-7


Earth leakage+ terminal
Input signal(S phase) CN3-4
CN1-8
Input signal(T phase) CN3-6 Earth leakage- terminal

Input signal(N phase) CN3-8 Test


DC 24V CN3-5

UTXO CN3-1
Main PCB
Comm. CN4-1
URXO CN3-3 485+ terminal
Ass’y Power PCB
Ass’y CN4-3
GND 24V CN3-7/9
485- terminal
AD GND CN3-10

49
Accessories

AH
Mounting Accessories Page
Standard Option
SHT1 Shunt Coil ● 52
SHT2 Double Shunt Coil ○ 53
CC Closing Coil ● 54
M Motor ● 55
CS1 Charge Switch ● 55
CS2 Charge Switch Communication ** ○ 55
UVT Under Voltage Trip Device ○ 56
Internal
AL Trip Alarm Contact ** ○ 57
MRB Manual Reset Button ** ○ 57
RES Remote Reset Switch ○ 58
RCS Ready to Close Switch ○ 58
C Counter ● 65
AX Auxiliary Switch ○ 59
TM Temperature Alarm ** ○ 74
K1 Key Lock ○ 60
K2 Key Interlock Set ○ 60
K3 Double Key Lock ○ 61
B On/Off Button lock ○ 61
LH Lifting Hook ○ 62
External
CTD Condenser Trip Device * ○ 62
ATS Automatic Transfer Switch Controller * ○ 63
DC Dust Cover ○ 65
DF Door Frame ○ 68
OT OCR Tester * ○ 64
* Non UL Listed.
** Separate purchasing is not allowed. Each item should be purchased with the main body.

50
Accessories

AH
Mounting Accessories Page
Standard Option
N N type ○ 26
A A type ○ 28
Trip relay P P type ○ 30
S S type ○ 32
VM Voltage Module ○
SBC Shorting "b" Contact * ○
MI Mechanical Interlock ** ○ 67
ST Safety Shutter ○ 68
MIP Miss Insertion Prevent Device ○ 72
MOC Mechanical Operated Cell Switch ○ 66
Cradle CEL Cell Switch ○ 69
DI Door Interlock ○ 67
BSP Body Supporter ○ 70
RI Racking Interlock ○ 70
PL Pad Lock/ Position Lock ● 71
UDC UVT Time Delay Controller ○ 73
RCO Remote I/O ○ 75
Other
PC Profibus-DP comm. module ○

* Non UL Listed.
** Separate purchasing is not allowed. Each item should be purchased with the main body.
*** Voltage module should be purchased with P/S type trip relay.
**** It is available only when the control block is in the mode of auto-connection.
***** Trip unit P type & S type are under development, coming soon.

51
Accessories

Shunt Coil [SHT1]

�SHT1 is a control device which trips a


circuit breaker from remote place, when Shunt coil 1
applying voltage continuously or
instantaneously over 200ms to coil
terminals(C1, C2).
�When UVT coil is installed, its location
is changed.

1. Rated voltage and characteristics of Trip coil


Rated voltage [Vn] Power consumption (VA or W)
Operating voltage range [V] Trip time [ms]
DC [V] AC [V] Inrush Steady-state Opening
order
24~30 - 14 ~ 33
48~60 48 28 ~ 66 Less C1
100~125 100~125 70 ~ 140 200 5 than
200~250 200~250 140 ~ 280 40ms SHT1

- 380~480 * 266 ~ 528


C2
Note) Operating voltage range is the min. rated voltage standard for each rated voltage(Vn).
* Non UL Listed.

* 점선은
The dotted
Userline
배선임to
be made by the
2. Specification of the wire Wiring Diagram
customer
�Refer to the below table regarding the length and specification of wire when using trip coil with Wiring Diagram
DC 24~30[V] or DC/AC 48~60[V] of rated voltage.

The maximum wire length


Rated voltage [Vn]
DC 24~30 [V] DC/AC 48 [V]
#14 AWG #16 AWG #14 AWG #16 AWG
Wire type
(2.08mm2) (1.31mm2) (2.08mm2) (1.31mm2)
Operating 100% 95.7m 61m 457.8m 287.7m
voltage 85% 62.5m 38.4m 291.7m 183.2m

52
Accessories

Double Shunt Coil [SHT2]

�SHT2 is a control device which trips a


circuit breaker doubly from the outside. Shunt coil 1 Shunt coil 2
When SHT1 doesn’t operate normally, it
can trip a circuit breaker safely.
�Shunt coil 1: Install it at existing
location.
�Shunt coil 2: Install it on the right side of
the Shunt coil 1
�It is not available with UVT coil when
installing double shunt coil.

1. Rated voltage and characteristics of Trip coil


Rated voltage [Vn] Power consumption (VA or W)
Operating voltage range [V] Trip time [ms]
DC [V] AC [V] Inrush Steady-state Opening
order
24~30 - 14 ~ 33
48~60 48 28 ~ 66 Less C11

100~125 100~125 70 ~ 140 200 5 than


200~250 200~250 140 ~ 280 40ms SHT2

- 380~480 * 266 ~ 528


C12
Note) Operating voltage range is the min. rated voltage standard for each rated voltage(Vn).
* Non UL Listed.

* The dotted line to


be made by the
2. Specification of the wire customer
�Refer to the below table regarding the length and specification of wire when using trip coil with Wiring Diagram
DC 24~30[V] or DC/AC 48~60[V] of rated voltage.

The maximum wire length


Rated voltage [Vn]
DC 24~30 [V] DC/AC 48 [V]
#14 AWG #16 AWG #14 AWG #16 AWG
Wire type
(2.08mm2) (1.31mm2) (2.08mm2) (1.31mm2)
Operating 100% 95.7m 61m 457.8m 287.7m
voltage 85% 62.5m 38.4m 291.7m 183.2m

53
Accessories

Closing Coil [CC]

�It is a control device which closes a


circuit breaker, when the voltage is Closing coil
applied continuously or instantaneously
over 200ms to the coil terminals
(A1, A2).

1. Rated voltage and characteristics of Closing coil


Rated voltage [Vn] Power consumption (VA or W)
Close time
Operating voltage range [V]
DC [V] AC [V] Inrush Steady-state [ms] Closing
order
24~30 - 14 ~ 33
48~60 48 28 ~ 66 Less A1
100~125 100~125 70 ~ 140 200 5 than
200~250 200~250 140 ~ 280 80ms ** CC

- 380~480 * 266 ~ 528


Note) Operating voltage range is the min. rated standard for each rated voltage (Vh). A2
* Non UL Listed.
** Close time of G frame (3200~5000A) is less than 95ms.
* The dotted line to
be made by the
2. Specification of the wire customer
�Refer to the below table regarding the length and specification of wire when using trip coil with Wiring Diagram
DC 24~30[V] or DC/AC 48~60[V] of rated voltage.

The maximum wire length


Rated voltage [Vn]
DC 24~30 [V] DC/AC 48 [V]
#14 AWG #16 AWG #14 AWG #16 AWG
Wire type
(2.08mm2) (1.31mm2) (2.08mm2) (1.31mm2)
Operating 100% 95.7m 61m 457.8m 287.7m
voltage 85% 62.5m 38.4m 291.7m 183.2m

54
Accessories

Motor [M]

�Charge the closing spring of a Motor


circuit breaker by the external power
source. Without the external power
source, charge manually.
�Operating voltage range 85%~110%Vn
Gear

Main
axis

Input voltage(V) DC 24~30V AC/DC 48~60V AC/DC 100~130V AC/DC 200~250V AC 380V * AC 440~480V *
Load current(max.) 5A 3A 1A 0.5A 0.3A 0.3A
Starting current(Max.) 5 times of load current
Load rpm(Motor) 15000 ~ 19000 rpm
Charge time Less than 5sec.
Dielectric strength 2kV/min
Using temperature range -20。
~ 60。
Using humidity range Max. RH 80% (No dew condensation)
Endurance 15,000 cycle (Load connection, 2 times/min)
Charge switch 10A at 250VAC
* Non UL Listed.

Charge Switch [CS1]


Charge Switch Communication [CS2]

�It is a built-in contact which sends the signal to the outside, when motor charging is
completed. (2a)
�It has a “1a” contact for communication and the other “1a” contact for complete charging.
�When using an extra communication module (Remote I/O), the state of contacts
can be displayed through the network.
Classification Standard Remark
250/125 Vac 10 A
250 Vdc 0.3 A
Contactor
125 Vdc 0.6 A
Capacity
48 Vdc 3A
24 Vdc 5A

55
Accessories

Under Voltage Trip device [UVT]

�If the voltage of the main or the control


power is under voltage, UVT which is UVT coil Shunt coil
installed inside of the breaker breaks
the circuit automatically.
Please connect with UVT time-delay
device in order to present the time-
delay function because UVT is
technically instantaneous type.
�The closing of a circuit breaker is
Closing
impossible mechanically or electrically if coil
control power not supplied to UVT.
To close the circuit breaker, 65~85% of
rated voltage should be applied to both
terminals of UVT coil (D1, D2).

�When using UVT coil, the double trip


coil can not be used, and the location of
trip coil is changed.

1. Rated voltage and characteristics of UVT coil


Rated voltage [Vn] Operating voltage range [V] Power consumption (VA or W)
Trip time [ms]
DC [V] AC [V] Pick up Drop out Inrush Steady-state

24~30 -
48~60 48 Less
100~130 100~130 0.65~0.85 Vn 0.3~0.6 Vn 200 5 than
200~250 200~250 50ms
- 380~480
Note) Operating voltage range is the min. rated standard for each rated voltage (Vh).

2. Specification of the wire


�Refer to the below table regarding the length and specification of wire when using trip coil with
DC 24~30[V] or DC/AC 48~60[V] of rated voltage.

The maximum wire length


Rated voltage [Vn]
DC 24~30 [V] DC/AC 48 [V]
#14 AWG #16 AWG #14 AWG #16 AWG
Wire type
(2.08mm2) (1.31mm2) (2.08mm2) (1.31mm2)
Operating 100% 48.5m 30.5m 233.2m 143.9m
voltage 85% 13.4m 8.8m 62.5m 39.3m
Note) In case of using UVT coil, the location of Shunt coil is changed.

56
Accessories

Trip Alarm Contact [AL]

�When a circuit breaker is tripped by OCR which operates against the fault current
(Over Current Relay), Trip Alarm switch provides the information regarding the trip of circuit AL1, 1a
breaker by sending the electrical signal from the mechanical indicator on front cover of main AL2, 1a
circuit breaker or internal auxiliary switch. (Installed at the inside of circuit breaker)
�When a circuit breaker tripped by fault current, a mechanical trip indicator
(MRB, Manual Reset Button) pops out from the front cover and the switch (AL) which sends
control signal electrically is conducted to output the information occurred from fault circuit
breaker.
�MRB and AL can be operated only when tripping by OCR,
but doesn’t be operated by Off button and OFF operation of trip coil.
�To re-close a circuit breaker after a trip, press MRB to reset it for closing.
�2pcs of electrical trip switch (AL1, AL2, 1a) are provided (Option)
�Trip alarm contact and MRB(Manual reset bottom) need to be purchased together.

1. Electrical characteristics of trip alarm contact


Classification Standard Remark
250/125 Vac 10 A
250 Vdc 0.3 A
Contactor
125 Vdc 0.6 A
Capacity
48 Vdc 3A
24 Vdc 5A

Manual Reset Button [MRB]

�It is a function which resets a circuit


breaker manually when a circuit breaker is tripped by OCR.
�When a circuit breaker tripped by fault current, a mechanical trip indicator (MRB, Manual Reset
Button) pops out from the front cover and the switch(AL) which sends control signal electrically is
conducted to output the information occurred from fault circuit breaker.
�MRB can be operated only by OCR but not by OFF operation of circuit breaker. To re-close a
circuit breaker after a trip, press MRB to reset it for closing.

Manual
reset button

MRB reset lever


Note) The manual reset button is protruded in the event of trip.
Manual reset button

57
Accessories

Remote Reset Switch [RES]

�Following tripping, this function resets the "fault trip" alarm contacts(AL) and the mechanical
indicator(MRB) and enables circuit breaker closing.
Push button switch : AC 125V 10A, AC 250V 6A, DC 110V 2.2A, DC 220V 1.1A Resistive load
�In case of auto reset type circuit breaker
Following tripping, a reset of Manual Reset Button(MRB) or Remote Reset Switch(RES) is
no longer required to enable circuit breaker closing.
The mechanical indicator(MRB) and electrical indicator(AL) remain in fault position until the reset
button is pressed.
�AL2 and RES are alternative.

1. Rated voltage and rated current of RES


Rated voltage Operating current(Max.) Operating time Wire spec.
AC 6A
AC/DC 100~130V #14 AWG (2.08 mm2)
DC 5A
Less 40ms Reset
AC 3A order
AC/DC 200~250V #16 AWG (1.31 mm ) 2

DC 2.5A
183
Connect to inner
micro switch RES

184
Connect to
AL2 / RES

* The dotted line to


be made by the
customer

Wiring Diagram

Ready to Close Switch [RCS]

�It interlocks with mechanism of circuit


breaker.
�It indicates the status that the circuit
breaker is ready to do closing operation.
�When mechanism is in OFF position or
Ready to
in Charge, contact is output with “ON”
close switch
and it indicates that mechanism can be
closed.

Classification Standard Remark


250/125 Vac 10 A
250 Vdc 0.3 A “A” contact
Contactor
125 Vdc 0.6 A
Capacity
48 Vdc 3A Contact part
24 Vdc 5A

58
Accessories

Auxiliary switch [AX]

�It is a contact used to monitor


ON/OFF position of ACB from
remote place.

AUX. contact & charging types


AX Standard OFF charge 3a3b
AC Standard ON charge 3a3b
BX Standard OFF charge 5a5b
BC Standard ON charge 5a5b
HX High capacity OFF charge 5a5b
HC High capacity ON charge 5a5b
CC Standard ON charge 6a6b Standard High capacity
JC High capacity ON Charge 6a6b

Standard classification
Standard High capacity
2000, 5000AF 4000, 6300AF 2000, 5000AF 4000, 6300AF

Classification Standard High capacity Remark


250/125 Vac 10 A 250/125 Vac 10 A
250 Vdc 0.3 A 250 Vdc 3A
Contactor Capacity 125 Vdc 0.6 A 125 Vdc 5A
48 Vdc 3A 48 Vdc 10 A
24 Vdc 5A 24 Vdc 10 A
AX 3a3b - Standard
BX 5a5b - charging
HX - 5a5b type
No. of Contact AC 3a3b -
that can be used BC 5a5b - Rapid auto-
CC 6a6b - reclosing
HC - 5a5b charging type
JC - 6a6b

59
Accessories

Key Lock [K1]

�It is a device for locking which


prevents a certain circuit breaker from
being operated by user‘s discretion
when two or more circuit breakers are
used at the same time.
�K1: Preventing mechanical closing

K1

Key Interlock Set [K2]

�3 circuit breakers can be arranged for the continuous


power supply to the load side and be interlocked Wiring
mutually by using Key Lock embedded in each circuit
breaker.
Status
ACB-1 ACB-2 ACB-3
LOAD1 LOAD2
● ● ● OFF OFF
● ○ ○ ON ON
○ ● ○ ON ON
○ ○ ● ON ON
● ● ○ OFF OFF
● ○ ● OFF ON
○ ● ● ON OFF ACB1 ACB2
○: Release ●: Lock

ACB3

Load 1 Load 2

60
Accessories

Double Key Lock [K3]

�When only two keys are released at the


same time, circuit breakers operate.
Handling method is same as K1.

Key interlock double

ON/OFF Button Lock [B]

�It is to prevent manual operation of


ACB’s closing/tripping button due to
user’s wrong handling.

�It is not possible to handle ON/OFF


operation under the
“Button lock” status.

Note) Padlocks(∅5 ~ ∅6) are not supplied.

ON/OFF button lock

61
Accessories

Lifting Hook [LH]

�It is a device to
make an ACB easy to shift.
�Please hang it to both handles
of the arc cover.

Condenser Trip Device [CTD]


Ratings
�It gets a circuit breaker tripped Ratings Specification
electrically within regular time when Model CTD-100 CTD-200
control power supply is broken down and Rated input voltage (V) AC 100/110 AC 200/220
is used with Shunt coil, SHT. In case
there is no DC power, It can be used as ㎐)
Frequency (㎐ 50/60 50/60
the rectifier which supplies DC power to Rated charge voltage (V) 140/155 280/310
a circuit breaker by rectifying AC power. Charging time Within 5S Within 5S
Trip possible time Over 3 min. Over 2 min.
Range of Input voltage (%) 85~110 85~111
Condenser capacity ㎌
400㎌ ㎌
160㎌

External dimension Circuit diagram


131
118 7.5
15

AC input DC output

Side view 108


75
75

* Non UL Listed.

Rear view Front view

62
Accessories

Automatic Transfer Switch Controller [ATS]

Ratings
Model type ATSC-110 ATSC-220
Rated voltage AC 110V AC 220V
Voltage range AC 93.5(±5%) ~126.5V(±5%) AC 187(±5%) ~ 253V(±5%)
Frequency 50Hz/60Hz
Power consumption (apparent power) 15.4W
4-location switch (stop, N, R, Auto) � �
Test function � �
Generator control function � �
N power source setting (phase-to-phase/ 3phases) � �
Time setting (T1~T6) � �
Fault function (OCR/Circuit breaker trouble) � �
Output contact (Auto, Load burden) � �
Communication function (RS-485) - -

�T1: The delayed time from when UN (power supply of electric company) is tripped to when
generator start-up signal contact is closed. (t1: 0.2, 0.5, 1, 2, 4, 8, 15, 30, 40, 50secs)
�T2: The delayed time from when UN is closed to when ACB2 is tripped.
(t2: 0.2, 1, 2, 4, 8, 15, 30, 60, 120, 240secs)
�T3: The delayed time from when ACB1 is tripped to when ACB2 is closed.
(t3: 0.5, 1, 2, 5, 10, 15, 20, 25, 30, 40secs)
�T4: The delayed time from when ACB2 is tripped to when ACB1 is closed.
(t4: 0.5, 1, 2, 5, 10, 15, 20, 25, 30, 40secs)
�T5: The delayed time when ACB1 is closed to when generator start-up signal contact is
opened. (t5: 60, 120, 180, 240, 300, 360, 420, 480, 540, 600secs)
�Stop-mode: This mode is for compulsory trip of ACB1(electric power company) or
ACB2 (power station) when UN (power supply of electric power company) or UR (power supply
of power station) is available
*UN or UR should be kept in ON position
�N-mode: This mode is for compulsory closing of ACB1 when UN is available.
* it does not matter to be ON or OFF position of UR and if converting to N-mode while using UR,
generator start-up signal contact is opened.
�R-mode: This mode is for compulsory closing of ACB2 during the use of UR regardless of that
UN is available or not.
�Auto-mode: This mode is for transferring a circuit breaker automatically to available power
supply of UN or UR. In short, it trips the circuit breaker where power supply is not available and it
close the circuit breaker where power supply is available.
* Non UL Listed.

63
Accessories

OCR Tester [OT]

�It is a device which can test for the


operation of Trip Relay under no power
condition.

1. Maximum 17 times rated current


can be inputted.
2. It is possible to enter the current value
and phase on each of R/S/T/N
3. Frequency is adjustable.
4. It is available to test for long time
delay/short time delay/instantaneous
/ground fault.

OCR tester

Configuration

R S T N R, S, T, N phase signal input

Increase/Decrease signal input

ENT. ESC Signal setting/Delete

START STOP Waveform generation/Stop

50Hz 60Hz

Select frequency
Hz

* Non UL Listed.

64
Accessories

Dust Cover [DC]

�Attach it to the door frame.


�It protects the product against the dust
(IP5X) which may cause fault operation
and enhances the sealing degree by
being mounted to protrude type of
panel.
�It is transparent so that the front side of
ACB is visible and the Cover can be
opened/closed even if ACB is drawn out
to until TEST position.

Panel
door

Dust cover Door frame

Counter [C]

�It displays the total number of ON/OFF


operation of ACB.

Counter

65
Accessories

Mechanical Operated Cell Switch [MOC]

a1 a2 a3 a4 a5 b1 b2 b3 b4 b5 a1 a2 a3 a4 a5 b1 b2 b3 b4 b5

13 23 33 43 53 11 21 31 41 51 13 23 33 43 53 11 21 31 41 51

14 24 34 44 54 12 22 32 42 52 14 24 34 44 54 12 22 32 42 52

AUX S/W AUX S/W

�It is the contact (10a10b) which displays the ON/OFF condition of ACB.
It mechanically operates only when the breaker is “CONNECTED” position.
A standard type and a high capacity type is available.

�The contact capacity is as same as the ratings of aux. contacts.

�When MOC link is installed to cradle, MOC can be equipped with the inside of panel.

66
Accessories

Mechanical Interlock [MI]

�It is used to interlock closing and trip between two or three breakers mechanically
so as to prevent unintended operation at the same time.
�Wire type interlock can be applied upto 3 breakers

Door Interlock [DI]

�It is a safety device which


does not allow the panel
door to open when a
circuit breaker is in the
“ON” position.

Install on the door of panel

Install on the side plate of


ACB cradle

67
Accessories

Safety Shutter [ST]

�It is the automatic safety device to


protect the connectors of main circuit by
cutting off dangerous contact from
outside while the breaker is drawn out.
When the ACB is drawn in, the shutter is
automatically opened.

�There are 4 types of Safety Shutter and


they are divided as shown in figure below.
The types of safety shutter plate
1600AF, 3P 1600AF, 4P

3200AF, 3P 3200AF, 4P

Safety shutter

5000AF, 4P 5000AF, 4P

Door Frame [DF]

�When structuring the embedded type of


ACB panel, it protects the protrude front
of ACB and the cutting side of
panel door by attaching it to the panel
door.

Fixed type

Door frame Panel door


Draw-out type

68
Accessories

Cell Switch [CEL]

�It is a contact which indicates the


present position of ACB.(CONNECTED, Cell switch
TEST, DISCONNECTED)

<Contact configuration>
4C: 1Disconnected +1Test +2Connected
※ Contact configuration can be changeable if necessary.

ACB position DISCONNECTED CONNECTED

Draw-in and draw-out position DISCONNECTED TEST CONNECTED

CL-C ON
(Connected) OFF

Contact CL-T ON
OFF
operation (Test)
CL-D ON
OFF
(Disconnected)
Classification Standard
250/125 Vac 10 A
Contact 250 Vdc 0.3 A
capacity 125 Vdc 0.6 A
48 Vdc 3A
24 Vdc 5A
Contact number 4C

69
Accessories

Body Supporter [BSP]

�It interlocks the main body of circuit


breaker and cradle mechanically to fix
the former in connected position.
Therefore, all draw-in/outs are not
available.

Body supporter

* Non UL Listed.

Racking Interlock [RI]

Door plate

Handle inserting hole Racking interlock

�When panel door is opened, Draw in/out handle doesn’t be inserted.


Thus, panel handle can be inserted only when panel door is closed.

70
Accessories

Pad Lock / Position Lock [PL]

Draw-in button

Pad lock

ACB is subject to restriction regarding moving in connected, test, disconnected when drawing in or
out. If main body of ACB is placed in 3 positions, it is locked and stopped when drawing in or out.
�As shown in the figure, if draw-in/out button pops out, it means locking is operating.
�To continue Draw-in/out operation, release lock by pushing Draw-in/out button
�In case it is locked as shown in the figure above, main body of ACB can not be drawn in or
out into the cradle.
�For the lock device, user has to purchase it. (∅5 ~ ∅6)

71
Accessories

Miss Insertion Prevent Device [MIP]

1
A
2
B 3
C 4
D 5
E
F 6
G 7

Cradle ACB body

�When the main body of ACB is inserted to the cradle, if the ratings of ACB does not match with
cradle, it mechanically prevents ACB from being inserted into cradle of ACB.
�The installation method is variable according to ratings.

Cradle ACB Cradle ACB Cradle ACB Cradle ACB


ABCD 567 ADEF 237 ABEG 346 BCEG 146
ABCE 467 ADEG 236 ABFG 345 BDEF 137
ABCF 457 ADFG 235 ACDE 267 BDEG 136
ABCG 456 AEFG 234 ACDF 257 BDFG 135
ABDE 367 BCDE 167 ACDG 256 CDEF 127
ABDF 357 BCDF 157 ACEF 247 CDEG 126
ABDG 356 BCDG 156 ACEG 246 CEFG 124
ABEF 347 BCEF 147 ACFG 245 DEFG 123

72
Accessories

UVT Time Delay Controller [UDC]

�UVT is a device which makes ACB


tripped automatically to prevent the
accident on load side due to under
voltage or power breakdown.
There are two types, Instantaneous
type and time delay type.

�It can be installed on the rail or to the


cradle.

�Instantaneous type: only available with


UVT coil.

�Time delay type: available by


connecting UVT coil and UVT time
delay controller.

�Common use for the all types.

UVT time delay controller

1. The rated voltage and characteristic of UVT time delay controller


Rated voltage [Vn] Operating voltage range [V] Power consumption (VA or W)
Trip time[s]
DC [V] AC [V] Pick up Drop out Inrush Steady-state

48~60 48
100~130 100~130 0.5, 1,
0.65~0.85 Vn 0.4~0.6 5Vn 200 5
200~250 200~250 1.5, 3
- 380~480
Note) Operating voltage range is the min. rated standard for each rated voltage (Vh).

2. Wiring

1. Wiring for general type 2. Wiring for special type


Rated Rated
voltage voltage
(Vn) Delay trip (Vn)
function

5 7 5 7

14 16 14 16

Instantaneous
trip
function
D1 D2 D1 D2

ACB ACB
Rated Rated
voltage voltage
(Vn) (Vn)

* The wiring presented with red color should be set by uesers.

73
Accessories

Temperature Alarm [TM]

�Temperature Alarm Unit is a device to


show the temperature through a Temperature
alarm
sensor inside of ACB.
�The temperature sensor can be
installed up to 2 and the output is
connected to control terminal blocks.
�It displays the maximum temperature
of them and transmits through a
network.
�If the temperature is higher than a
standard, an alarm can occur.
�Temperature alarm unit
communicates with Modbus /
RS-485 basically, Profibus-DP need
to be purchased separately.
�Temperature alarm unit is installed
on the cradle or the inside of panel.

Control power 1 24V


13
24V GND
AC/DC 110/220V Power
2 5V
14
5V GND
3 15

4 16
Temperature alarm
Relay 3 17
5 Temperature Alarm(+)
DO control

6 18
Temperature Alarm(-)

8
Temp. Sensor input 1
9 RS-485(-) 19
Temp. Sensor input 2
10 RS-485(+)
*
20
Temp. Sensor input 3
11
Temp. Sensor input 4 MODBUS
12
RS-485 Profibus-DP
Temp_COM
*In case of using
Profibus-DP communication,
it needs to communicate with
ACB trip relay.

Temperature LED(℃): 10 ~150℃,


Warning
(Indicates the maximum value)

74
Accessories

Remote I/O Unit [RCO]

Control Power 1 24V Relay 0 13


CB close CB ON(+)
24V GND
AC/DC 110/220V Power
2 5V 14
CB ON(-)
5V GND
Relay 1 15
3
CB ON CB open CB OFF(+)
4 16
CB OFF CB OFF(-)
Remote I/O Unit
5
General DI 1
6
General DI 2

7
DI_COM

RS-485(-) 19
9

RS-485(+) 20
*
10

11
MODBUS
RS-485 Profibus-DP
12
*In case of using
Profibus-DP communication,
it needs to communicate with
ACB trip relay.

Classification Applied range Remarks


Contact switching capacity AC230V 16A / DC30V 16A
CB control
Max. switching capacity 3680VA, 480W
Contact switching capacity AC230V 6A / DC25V 6A Induction load
Alarm
Max. switching capacity 1880VA, 150W (cos∅=0.4, L/R=7ms)

�Remote I/O unit has the I/O contact which can


trip or close the ACB from the remote site by
communication.
�For the General DO, the output of DI1 or DI2 is
selectable.
�Remote I/O Unit communicates with Modbus /
RS-485 communication basically, Profibus-DP
need to be purchased separately.
�It supports SBO (Select Before Operation)
function and guarantees the control reliability.
�Remote I/O Unit can be installed on the cradle
of ACB or the inside of panel.
LED Status
- Baud rate setting
- Comm. address setting 1 DI1 Indicates digital Input #1condition
- Temperature setting
2 DI2 Indicates digital Input #2condition
3 DO ON Indicates temperature alarm output is ON
4 DO OFF Indicates temperature alarm output is OFF
5 CB ON Indicates circuit break close condition
6 CB OFF Indicates circuit break open condition
7 RUN LED Indicates unit run condition
Indicates circuit break terminal
8 CB ERROR
Disconnection / control Err condition

75
Electrical diagram

This diagram is based on “CONNECTED” position of a circuit breaker and Opening, Motor charging, Releasing of locking plate
should be normal condition.

Common
ZSI Output

ZSI Input
Voltage module Power supply

Reset

OFF

OFF

ON
ZCT
183
V1 V2 V3 VN E1 Z3 Z1 485+ R11 R22 513 R2 R1 251 83 /RES(+) D1 C11 C1 A1

Trip relay
UVT SHT2 SHT1 CC

or

184
E2 Z4 Z2 485- 544 534 524 252 84 /RES(-) D2 C12 C2 A2
STD/Inst

LTD
GTD

Digital trip relay Electric operatio


Main circuit Fault trip circuit

UVT
Secondary
Ready to close trip coil

Terminal code description


13 14 ~ 63 64 Auxiliary switch “a” D1 D2 Voltage input terminal of UVT
11 12 ~ 61 62 Auxiliary switch “b” 83 84 Alarm1 “a”
413 414 Charged signal 183 184 Alarm2 “a”
423 424 Charged signal communication 251 252 Ready to close switch
U1 U2 Motor charging R1 R2 Control power
A1 A2 Closing coil 513 ~ 544 Alarm contact
C1 C2 Shunt trip R11 R22 Alarm reset (Trip cause LED, Alarm contact)
C11 C12 2nd shunt trip 485+ 485- RS-485 communication

Note) 1. The diagram is shown with circuits de-energized, all devices open, connected and charged and relays in normal position
2. Relay is normal condition and charging type is "ON-Charging"
3. The standard of auxiliary contact is 3a3b. The auxiliary switch in above diagram is composed of 5a5b. See 48 page for more detail on auxiliary switches.
4. Option
- Ready to close contact, Trip alarm contact, UVT coil, Fully charged contact, secondary trip coil
- Cell switch, Temperature module, Voltage module, Remote close-open module, ZCT, ZSI
5. Please consult us for the use of ZSI (Zone selective Interlocking).
6. Refer to the page 33 for the connection of Trip relay and the page 43 for UVT.
7. For connecting RS-485 verify if the polarity is correct

76
Temperature
Module

U1 413 423 51 41 31 21 11 53 43 33 23 13 T1 TC1 T2 TC2 341 331 321 311


Axb

Temperature Temperature
Sensor-1 Sensor-2
Axb

Axb

Axb

Axb

Axb

Axa

Axa

Axa

Axa

Axa

CL

CL

CL

CL
M

U2 414 424 52 42 32 22 12 54 44 34 24 14 342 344 332 334 322 324 312 314
OFF

ON
Charged

Charged

Charge Thermal,
n completion communication
Auxiliary switch Cell switch
contact remote control module

Accessory code description


Z1 Z2 ZSI input Ax Auxiliary switch Internal wiring
Z3 Z4 ZSI output LTD Long time delay trip indicator External wiring
E1 E2 ZCT STD/Inst Short time delay/instantaneous (by customer)
VN ~ V3 Voltage module GTD Ground fault trip indicator Connector of the control
TC1 , TC2 ~ T1 , T2 Temperature module CL Cell switch circuit terminal of
311 ~ 344 Position switch M Motor drawout type
CC Closing coil
SHT1 Shunt tripping device 1
SHT2 Shunt tripping device 2
UVT UVT coil

77
Dimensions

Fixed type 800~1600A


(UAS-08/16D)
Front view Front view 11.81
(300)
15.16
(385)
Side view
11.02 11.02
(280) (280)
5.51 5.51
(140) (140) 2.56
(65)
Operating panel center Operating panel center

10.63

11.81
(270)

(300)

10.63

11.81
(270)

(300)

10.63
(270)
12.60
(320)

12.60
(320)

(320)
12.6
(133)
5.24
2.64
(67)

1.38
(35)
0.47 6.50 6.50 0.47 9.84 6.50
(12) (165) (165) (12) (250) (165) 2.83
0.79
(20)

0.79
(72)

(20)
13.94 17.28 1.46 6.5 3.35
(354) (439) (37) (165) (85)
13.52
(343.5)
3P 4P

Vertical Vertical Vertical-con


Operating panel center Operating panel center
type_3P Ø0.55(Ø14)
(Mounting Hole)
Ø0.55(Ø14)
(Mounting Hole)
Ø0.55(Ø14) Ø0.55(Ø14)
(Earthing Hole) (Earthing Hole)
(59.5)

(59.5)
2.34

2.34

(177.5)
(177.5)

6.99
6.99
0.98
(25)

3.19
(81)

0.98
(25)

(124)
4.88
0.59
(15)
3.15 3.35 3.35
(80) (85) (85) 0.59
(15)
3.15 3.35 3.35
6.50 6.50 (80) (85) (85)
(165) (165)
6.50 6.50
(165) (165)

Back view Side view


0.49
(12.5)

Ø0.55
(Ø14)
1.97
(50)
11.81
(300)

(133)
5.24

0.98
(25)
3.62
(92)

1.65
(42)

12.99 1.91
(330) (48.5)
0.79
(20)

13.94 13.52
(353.6) (343.5)

78
Dimensions

Vertical Vertical Vertical-con


Operating panel center Operating panel center
type_4P Ø0.55(Ø14)
(Mounting Hole)
Ø0.55(Ø14)
(Mounting Hole)
Ø0.55(Ø14) Ø0.55(Ø14)
(Earthing Hole) (Earthing Hole)

(59.5)
(59.5)

2.34
2.34

(177.5)
(177.5)

6.99
6.99

0.98
(25)
3.91
0.98
(25)

(81)

(124)
4.88
0.59
3.15 3.35 3.35 3.35 (15)
(80) (85) (85) (85) 0.59
3.15 3.35 3.35 3.35 (15)
6.50 9.84 (80) (85) (85) (85)
(165) (250)
6.50 9.84
(165) (250)

Back view Side view


0.49
(12.5)

Ø0.55
(Ø14)

1.97
(50)
11.83
(300)

(133)
5.24

0.98
(25)
3.62
(92)
3.62
(42)

16.34 1.91
0.79
(20)

(415) (48.5)
17.28 13.52
(438.6) (343.5)

Horizontal Horizontal
Operating panel center
Horizontal-con
Operating panel center

type_3P Ø0.55(Ø14)
(Mounting Hole)
Ø0.55(Ø14)
(Mounting Hole)
Ø0.55(Ø14) Ø0.55(Ø14)
(Earthing Hole) (Earthing Hole)
(59.5)

(2.34)
2.34

59.5

(177.5)
(177.5)

6.99
6.99
0.98

0.98
(25)

(25)
3.19
(81)

(124)
4.88

Ø0.55
(44.5)
1.75

(Ø14)
1.97 0.98
0.49
(12.5)

(50) (25)
2.66 3.35 3.35 1.77
0.75
(19)

(67.5) (85) (85) (45)


Ø0.55(Ø14)
6.50 6.50 3.15 3.35 3.35
(165) (165) (80) (85) (85)

6.50 6.50
(165) (165)

Back view Side view


0.59
(15)
11.81
(300)

(133)
5.24
2.64
(67)

12.99 1.91
0.79
(20)

(330) (48.5)
13.52
13.94 (343.5)
(353.6)

79
Dimensions

Fixed type 800~1600A


(UAS-08/16D)
Horizontal Horizontal Operating panel center
Ø0.55(Ø14)
Horizontal-con Operating panel center
Ø0.55(Ø14)
(Mounting Hole) (Mounting Hole)
type_4P Ø0.55(Ø14)
(Earthing Hole)
Ø0.55(Ø14)
(Earthing Hole)

(59.5)

(59.5)
2.34

2.34

(177.5)
(177.5)

6.99
6.99
0.98

0.98
(25)
(25)

3.19
(81)

(124)
4.88
Ø0.55

(44.5)
1.75
1.97 0.98 (Ø14)
(50) 0.49
(25) (12.5) Ø0.55
2.66 3.35 3.35 3.35 (Ø14) 1.77

0.75
(19)
(67.5) (85) (85) (85) (45)

6.50 9.84 3.15 3.35 3.35 3.35


(165) (250) (80) (85) (85) (85)
6.50 9.84
(165) (250)

Back view Side view

0.59
(15)
11.81
(300)

(133)
5.24
2.64
(67)

16.34 1.91
0.79
(20)

(415) (48.5)
13.52
17.28 (343.5)
(438.6)

Front Top view


Operating panel center Operating panel center
Ø0.55(Ø14)
connection (Mounting Hole) Ø0.55(Ø14)
(Mounting Hole)
Ø0.55(Ø14) Ø0.55(Ø14)
type (Earthing Hole) (Earthing Hole)
(59.5)

(59.5)
2.34

2.34

(177.5)
(177.5)

6.99
6.99

0.98
0.98

(25)
(25)

1.50
(38)

1.50
(38)

3.15 3.15
(80) (80)
6.50 6.50 6.50 9.84
(165) (165) (165) (250)

3P 4P

Side view
(234)
9.21
(505.5)
19.90

(202.5)
7.97

0.98
(25)
11.83
(300.5)

80
Dimensions

Draw-out type 800~1600A


(UAS-08/16D)
Front view Front view
Operating panel center Operating panel center

5.51 (140) 5.51 (140) 8.46(215) 5.51 (140)

16.93 (430)

16.93 (430)
10.63 (270)

10.63 (270)
2.56

2.56
(65)

(65)
10.24(260) 3.35(85) 10.24(260)

13.15(334) 16.50(419)

3P 4P

Vertical Bottom view Vertical-con


1.77 3.35 3.35
type_3P 1.77
(45)
3.35
(85)
3.35
(85)
(45) (85) (85) 0.59
(15)
0.59
(15)

(240.3)
9.45
(197.3)
7.76

(100)
(100)

3.94
3.94

(100)
(100)

3.94
3.94

10.24 Ø0.51(Ø13) 10.24 Ø0.51(Ø13)


(260) (Mounting Hole) (260) (Mounting Hole)

Back view Side view

0.49
(12.5)

Ø0.55(Ø14)
1.97
(50)

16.93
(430)
(133)
5.23

0.99
(25)
(122)
4.80

2.83
(72)

13.14 23.82
(334) (60.5) 18.39
(467.3)

81
Dimensions

Draw-out type 800~1600A


(UAS-08/16D)
Vertical Bottom view Vertical-con
3.35 3.35 3.35 3.35 3.35 3.35
type_4P 1.77
(45)
(85) (85) (85) 0.59
(15)
1.77
(45)
(85) (85) (85) 0.59
(15)

(240.3)
9.45
(197.3)
7.76

(100)
(100)

3.94
3.93

(100)
(100)

3.94
3.93

13.59 13.58
(345) Ø0.51(Ø13) (345) Ø0.51(Ø13)
(Mounting Hole) (Mounting Hole)

Back view Side view


0.49
(12.5)
Ø0.55(Ø14)
1.97
(50)

0.98
(25)

16.92
(430)
(133)
5.23
(122)
4.80

2.83
(72)

16.50 23.82
(60.5) 18.39
(419) (467.3)

Horizontal Bottom view


3.35 3.35
Vertical-con
(85) (85) 3.35 3.35
type_3P 1.28
(32.5)
1.97
(50)
0.98
(25)
1.77
(45)
(85) (85) 1.77
(45) Ø0.55(Ø14)
Ø0.55(Ø14)
(44.5)
0.75

1.77
(19)
(12.5)
0.49

(240.3)
9.45
(197.3)
7.76

(100)
(100)

3.94
3.94

(100)
(100)

3.94
3.94

10.24 10.24
(260) Ø0.51(Ø13) (260) Ø0.51(Ø13)
(Mounting Hole) (Mounting Hole)

Back view Side view


0.59
(15)

16.93
(430)
(133)
5.24
3.82
(97)

13.15 23.82
(334) (60.5) 18.39
(467.3)

82
Dimensions

Horizontal Botttom view


3.35 3.35 3.35
Vertical-con
3.35 3.35 3.35
(85) (85) (85) 1.77 (85) (85) (85)
type_4P 1.28
1.97
(50) (45) 1.77
(45)

0.75
(19)
(32.5) 0.98 Ø0.55(Ø14)
(25) Ø0.55(Ø14)

(44.5)
1.75
0.49
(12.5)

(240.3)
9.45
(197.3)
7.76

(100)
(100)

3.94
3.94

(100)
3.94
(100)
3.94

13.58 13.58
(345) Ø0.51(Ø13) (345) Ø0.51(Ø13)
(Mounting Hole) (Mounting Hole)

Back view Side view

0.60
(15)

16.93
(430)
(133)
5.23
3.81
(97)

16.50 23.82
(419) (60.5) 18.39
(467.3)

Front Bottom view


1.77(45) 1.77(45)
connection
type
(162.3)
(162)
6.38

6.38
(100)
(100)

3.94
3.94

(100)
3.94
(100)
3.94

10.24(260) 13.58(345)
Ø0.51(Ø13) Ø0.51(Ø13)
3P (Mounting Hole) 4P (Mounting Hole)

Back view Side view


1.26
(32)

(234)
9.21

16.93
(430)
(505.5)
19.90

(202.5)
7.97

Ø0.55(Ø14)
(73.5)
2.89
1.63
(41.5)

2.26
0.98 (57.5)
0.98
1.26
(32)

(25) (25) 17.00


1.77 (432.3)
(45)
3.35 3.35
(85) (85)
13.15(334)
83
Dimensions

Fixed type 800~2000A


(UAH-08~20E)
Front view 14.88
(378)
19.41
(493)
7.44 7.44 11.97 7.44
(189) (189) (304) (189)
11.02 11.02
(280) (280)

0.59
(15)
Operating panel center Operating panel center

10.63

10.63
11.81
10.63

(300)

(270)

(270)
11.81
(300)

(270)

12.60
12.60

(320)
(320)

1.38

1.38
1.38

(35)

(35)
(35)

0.79
0.79

(20)
(20)

8.03 8.03 12.56 8.03


(204) (204) (319) (204) 1.91 2.83
(56.5)

0.79
0.47

(20)
0.47 0.47 13.52 (72)
0.47 (12) (12)
(12) 17.01 (12) 21.54 (343.5)
(432) (547)

3P 4P Side view

Vertical Top view

type Operating panel center Operating panel center

Ø0.55 (Ø14) Ø0.55 (Ø14)

(59.5)
(59.5)

2.34
2.34

(177.5)
(177.5)

6.99
6.99
0.98
(25)

0.98
(25)

3.19
(81)
3.19
(81)

0.79 0.75
3.50 4.53 4.53 (20) 3.50 4.53 4.53 4.53 (20)
(89) (115) (115) (89) (115) (115) (115)

8.03 12.56
8.03 8.03 (204) (319)
(204) (204)

3P 4P

Side view
0.75
(19)

Ø0.55 (Ø14)
(44.5)
2.95

1.75
(75)
(133)
5.24
(104.5)
4.11

1.91
1.16
(29.5)

(48.5)
13.52
(343.5)

84
Dimensions

Horizontal Top view


Operating panel center Operating panel center

type
Ø0.55 (Ø14) Ø0.55 (Ø14)

(59.5)

(59.5)
2.34

2.34

(177.5)
(177.5)

6.99
6.99

0.98
(25)
0.98
(25)

0.75
(19)

3.19
3.19

(81)
(81)
2.64 2.95 1.75

0.75
(19)
2.95 1.75
(67) (75) (44.5) (75) (44.5)
4.53 4.53 2.64 4.53 4.53 4.53
(115) Ø0.55 (Ø14) (67) (115) (115) (115) Ø0.55 (Ø14)
(115)
8.03 8.03 8.03 12.56
(204) (204) (204) (319)

3P 4P

Side view
0.79
(20)
(133.5)
5.26
2.64
(67)

1.91
(48.5) 13.19
(343.5)

Front Top view


Operating panel center Operating panel center

connection
type Ø0.55(Ø14) Ø0.55(Ø14)

(59.5)
(59.5)

2.34
2.34

(177.5)

(177.5)
6.99

6.99
0.98
(25)
1.50
(38)
1.50
(38)

0.98
(25)

3.50 4.53 3.50


(89) (115) (89)
8.03 8.03 8.03 12.56
(204) (204) (204) (319)

3P 4P
Side view
(234)
9.21
19.92
(506)

(202.5)
7.97

0.98
(25) 11.83
(300.5)

85
Dimensions

Fixed type 2500A


(UAH-25E)
Vertical Top view Operating panel center Operating panel center

type
Ø0.55(Ø14) Ø0.55(Ø14)

(59.5)
(59.5)

2.34
2.34

(177.5)
(177.5)

6.99
6.99
0.98
(25)

0.98
(25)
(129)
5.08

(129)
5.08
0.79 0.79
3.50 4.53 4.53 (20) 3.50 4.53 4.53 4.53 (20)
(89) (115) (115) (89) (115) (115) (115)
8.03 8.03 8.03 12.56
(204) (204) (204) (319)

3P 4P

Back view
11.81

11.81
(300)

(300)
16.06 20.59

0.79
(20)
0.79
(20)

(408) (523)
17.01 21.54
(432) (547)

3P 4P

Side view
1.75
(44.5)

1.26
(32)

Ø0.55(Ø14)
(44.5)
2.95

1.75
(75)
(133.5)
5.26
(104.5)
4.11

1.16
(29.5)

3.80
(96.5)

15.41
(391.5)

86
Dimensions

Horizontal Top view Operating panel center Operating panel center

type
Ø0.55 (Ø14) Ø0.55 (Ø14)

(59.5)
(59.5)

2.34
2.34

(177.5)

(177.5)
6.99

6.99
0.98
(25)

0.98
(25)
(129)

(129)
5.08

5.08
(44.5)
(32) (44.5)

1.75
1.26 1.75
Ø0.55 (Ø14)

1.26
(32)
2.95 1.75 2.95 1.75
(75) (44.5) Ø0.55 (Ø14) (75) (44.5)
2.64 4.53 4.53 2.64 4.53 4.53 4.53
(67) (115) (115) (67) (115) (115) (115)
8.03 8.03 8.03 12.56
(204) (204) (204) (319)

3P 4P

Back view
11.81
(300)

11.81
(300)
16.06 20.59

0.79
(20)
0.79
(20)

(408) (523)

17.01 21.54
(432) (547)

3P 4P

Side view
0.79
(20)
(133.5)
5.26
2.64
(67)

3.80
(96.5)

15.41
(391.5)

87
Dimensions

Fixed type 3200A


(UAH-32E)
Vertical Top view
Operating panel center Operating panel center

type
Ø0.55 (Ø14) Ø0.55 (Ø14)

(59.5)

(59.5)
2.34

2.34
(177.5)

(177.5)
6.99

6.99
0.98
(25)

0.98
(25)

(225.5)
(225.5)

8.88
8.88
0.20 4.53 4.53 0.20 4.53 4.53 0.79
(5) (115) (115) 0.79 (5) (115) (115)
(20) (20)

8.03 8.03 8.03 12.56


(204) (204) (204) (319)
20.98
(533)

3P 4P

Back view

16.46 20.98
(418) (533)

3P 4P

Side view
1.75
(44.5)
0.44
(11.2)

Ø0.55 (Ø14)
(15.7)
0.62
(44.5)
1.75
(197)
7.76

3.07
(78)
(384.5)
15.14

Ø0.95(Ø19)
(44.8)
1.76
(130)
5.12

(44.5)
1.75

1.75
0.62
(15.7)

(44.5)
7.60
(193)
19.21
(488)

88
Dimensions

Draw-out type 800~2000A


(UAH-08~20E)
Front view Operating panel center Operating panel center
12.57
(319.3)
2.95
(75)
2.36
5.51 5.51 5.51 5.51 (60)
(140) (140) (140) (140) Disconnected
1.97 Disconnected & Test
(50)

16.93

16.93
(430)

(430)

10.63
(270)
10.63

10.63
(270)

(270)

(361.5)
14.23

(133)
5.243.82
(97)

2.56
(65)
2.56

2.56
(65)

(65)

1.85
(47)
7.87 2.36
10.24 9.65 5.12 (200) (60)
(260) (245) (130)
13.38
16.22 14.76 (339.8)
(412) (375)
20.75 17.65
(527) (448.3)

3P 4P Side view

Vertical Bottom view


4.53 4.53 4.53 4.53 4.53
type 0.59
(15)
(115) (115)
0.79
(20)
0.59
(15)
(115) (115) (115)
0.79
(20)
(207)

(207)
8.15

8.15
(100)
3.94
(100)
3.94

(100)
(100)

3.94
3.94

10.24 14.76
(260) Ø0.51 (Ø13) (375) Ø0.51 (Ø13)
3P 4P

Back view

16.22 20.75
(412) (527)

3P 4P

Side view
0.75
(19)

Ø0.55 (Ø14)
(44.5)
2.95

1.75
(75)

16.93
(430)
(133)
5.24

3.00
(75)
(134.5)
5.30

(59.5)
2.34

2.78
(70.5) 18.78
(477)

89
Dimensions

Draw-out type 800~2000A


(UAH-08~20E)
Horizontal Bottom view
4.53 4.53 4.53 4.53 4.53
type 0.29
(115) (115)
1.75 2.83
(115) (115) (115)
1.75
(7.3) 2.95 (44.5) (7.2) (44.5)
2.95
(75) (75)
Ø0.55 (Ø14)
Ø0.55 (Ø14)

0.75
(19)
0.75
(19)

(207)
(207)

8.15
8.15

(100)
(100)

3.94
3.94

(100)
3.94
(100)
3.94

10.24 14.76
(260) Ø0.51 (Ø13) (375) Ø0.51 (Ø13)

3P 4P

Back view

16.22 20.75
(412) (527)

3P 4P

Side view
0.79
(20)

16.93
(430)
(133)
5.24
3.82
(97)

2.78
(70.5)
18.78
(477)

90
Dimensions

Front Bottom view


0.59
0.59
connection (15) (15)

type

(164)
(164)

6.46
6.46

(100)
(100)

3.94
3.94

(100)
(100)

3.94
3.94

10.24 14.76
(260) Ø13(0.51) (375) Ø0.51(Ø13)
(Mounting Hole)

3P 4P

Back view Ø0.55 (Ø14) Ø0.55 (Ø14)


1.26
(32)

1.26
(32)

(505.5)
19.90
(41.5)

(41.5)
1.63

1.63
1.26
(32)
17.6 4.53 4.53 4.53
1.26
(32)

2.95
(75) (44.5) (115) (115) (115)

4.53 4.53 20.75


(115) (115) (527)
16.22
(412)

3P 4P

Side view
(234)
9.21

16.93
(430)
(505.5)
19.90

(202.5)
7.97

(73.5)
2.89

0.98
(25)
17.09
(434)

91
Dimensions

Draw-out type 2500A


(UAH-25E)
Vertical Bottom view
4.53 4.53 4.53 4.53 4.53
type 0.59
(15)
(115) (115) 0.79
(20) 0.59(15)
(115) (115) (115) 0.79
(20)

10.04
(255)

10.04
(255)
(100)
(100)

3.94
3.94
(100)

(100)
3.94

3.94
10.24 14.76
(260) Ø0.51 (Ø13) (375) Ø0.51 (Ø13)

3P 4P

Back view

16.22 20.75
(412) (527)

3P 4P

Side view
1.75 Ø0.55 (Ø14)
(44.5)
1.26
(32)
(44.5)
1.75
2.95
(75)

16.93
(430)
(133)
5.24
(134.5)
5.30

(59.5)
2.34

4.67
(118.5)
20.67
(525)

92
Dimensions

Horizontal Bottom view


4.53 4.53 4.53 4.53 4.53
type (115) (115) (115) (115) (115)

0.29 2.95 1.75 Ø0.55(Ø14) 0.29 2.95 1.75


(7.3) (75) (44.5) (7.3) (75) (44.5)

1.26
(32)
1.26
(32)
Ø0.55(Ø14)

1.75
(44.5)

1.75
(44.5)
10.04

10.04
(255)

(255)
(100)
(100)

3.94
3.94

(100)
(100)

3.94
3.94

10.24 14.76
(260) (375)
Ø0.51 (Ø13) Ø0.51 (Ø13)

3P 4P

Back view

16.22 20.75
(412) (527)

3P 4P

Side view
16.93
(430)
0.79
(20)
(133)
5.24
3.82
(97)

4.67
(118.5)
20.67
(525)

93
Dimensions

Draw-out type 3200A


(UAH-32E)
Vertical Bottom view

type 20.98
(533)
16.46 13.58
(418) (345)
3.13 9.06 0.79 3.11 4.53 0.79
(79.2) (230) (20) (79.2) (115) (20)

12.87
12.87

(327)
(327)

(100)
(100)

3.94
3.94

(100)
(100)

3.94
3.94

Ø0.51(Ø13) Ø0.51(Ø13)
10.24 (Mounting Hole) 14.76 (Mounting Hole)
(260) (375)

3P 4P

Back view

16.22 20.75
(412 ) (527)

3P 4P

Side view 2.11


(53.5)
Ø0.55(Ø14) 0.44
(11.2)
(15.7)
0.62
(78) (44.5)
3.07 1.75
(197)
7.76

16.93
(430)
15.31
(389)

Ø0.75(Ø19)
(44.8)
1.75
(135)
5.31

0.62
(15.7)
1.75
(44.5)

0.20
(5)

1.49
(38)
23.50
(597)

94
Dimensions

Fixed type 3200~5200A


(UAH-32~50G)
Front view
29.57(751) 38.62(981)
22.13(562) 7.44(189) 31.18(792) 7.44(189)
11.02(280) 11.02(280)
Operating panel center Operating panel center

11.81(300)
11.81(300)

10.63 (270)
12.60 (320)
12.60 (320)
10.63 (270)
1.38

1.38
(35)

(35)
0.79

0.79
(20)

(20)
22.72(577) 8.03(204) 31.77(807) 8.03(204)
0.47(12) 0.47(12) 0.47(12) 0.47(12)
31.69(805) 40.75(1035)

3P 4P

Vertical Top view


Operating panel center Operating panel center
type Ø0.55 (Ø14) Ø0.55 (Ø14)

(59.5)
(59.5)

2.34
2.34

(177.5)
(177.5)

6.99
6.99

0.98
0.98

(25)
(25)

(169)
(169)

6.65
6.65

2.99 0.79 2.99 0.79


(76) (20) (76) (20)
9.61 9.61 9.61 9.61 9.61
(244) (244) (244) (244) (244)

3P 4P

Back view
11.81

11.81
(300)

(300)

30.75 39.80
(781) (1011)
0.79
(20)

0.79
(20)

31.69 40.75
(805) (1035)

3P 4P

Side view 1.26 0.55


(32) (44.5)

Ø0.55 (Ø14)
(44.5)
2.95

1.75
(75)
(133)
5.24
(104.5)
4.11

5.37
1.16
(29.5)

(136.5)
16.99
(431.5)

95
Dimensions

Fixed type 3200~5200A


(UAH-32~50G)
Horizontal Top view Operating panel center Operating panel center
Ø0.55 (Ø14) Ø0.55 (Ø14)
type

(59.5)
(59.5)

2.34
2.34

(177.5)

(177.5)
6.99

6.99
0.98
0.98

(25)
(25)
(44.5)

(44.5)
1.75
1.75

(169)
6.65
(169)
6.65
1.75 5.95 1.25 1.75 5.94 1.25

1.26
(32)

1.26
(32)
(44.5) (151.2) (31.7) Ø0.55 (Ø14) (44.5) (151) (31.7)

9.61 9.61 Ø0.55 (Ø14) 9.61 9.61 9.61


(244) (244) (244) (244) (244)

3P 4P

Back view

11.81
(300)

11.81
(300)
30.75 39.80
(781) (1011)

0.79
(20)
0.79
(20)

31.77 40.75
(805) (1035)

3P 4P

Side view
0.79
(20)
(133)
5.24
2.64
(67)

5.37
(136.5)
16.99
(431.5)

96
Dimensions

Draw-out type 3200~5200A


(UAH-32~50G)
Front view Operating panel center Operating panel center

19.8 5.51 10.24 5.51


(503) (140) (733) (140)

18.11

18.11
(460)

(460)
10.24 4.45 10.24 10.24 13.5 10.24
(260) (113) (260) (260) (343) (260)

30.91 39.96
(785) (1015)

3P 4P

Vertical Bottom view


9.61(244) 9.61(244) 9.61(244) 9.61(244) 9.61(244)
type 0.79 3 0.79 2.99
(20) (76.2) (20) (76.2)
(275.3)

(275.3)
10.83

10.83
(200)

(200)
7.87

7.87
1.36 1.09
(34.6) 10.24 5.24 10.24 (27.6) 10.24 13.5 10.24
(260) (113) (260) (260) (343) (260)
Ø0.51(Ø13) Ø0.51(Ø13)
3P (Mounting Hole) 4P (Mounting Hole)

Back view

18.11
18.11

(460)
(460)

28.11 37.01
0.59
(15)

0.59
(15)

(714) (940)
30.91 39.96
(785) (1015)
Ø0.31(Ø8) Ø0.31(Ø8)
3P (Earthing Hole) 4P (Earthing Hole)

Side view
Ø0.55 (Ø14)

1.26 1.75
(32) (44.5)
(44.5)
1.75
17.05

(133)
(433)

5.24

2.95
(75)
(164.5)
6.48

(89.5)
3.52

5.45(138.5) 21.47
(545.3)

97
Dimensions

Draw-out type 3200~5200A


(UAH-32~50G)
Horizontal Bottom view
9.61 9.61 9.61 9.61 9.61
(244) (244) (244) (244) (244)
type 5.94(151.2)
Ø0.55(Ø14)
5.94(151.2)
3 1.25 1.75 3 1.25 1.75
(76.2) (44.5) (31.7) (44.5)

1.26
1.26
(31.7) (76.2)

(32)
(32)

1.75
(44.5)
(275.3)

(275.3)
10.83

10.83
(200)
7.87

(200)
7.87
1.36 1.09
(34.6) 10.24 5.24 10.24 (27.6) 10.24 13.50 10.24
(260) (113) (260) Ø0.51(Ø13) (260) (343) (260) Ø0.51(Ø13)
(Mounting Hole) (Mounting Hole)
3P 4P

Back view

18.11
18.11

(460)
(460)

28.11 37.01
0.59
(15)

0.59
(15)
(714) (940)
30.91 39.96
(785) Ø0.31(Ø8) (1015) Ø0.31(Ø8)
(Earthing Hole) (Earthing Hole)
3P 4P
Side view
0.79
(20)
17.05
(433)

(133)
5.24
(117)
4.61

5.45
(138.5)
21.56
(545.3)

98
� For your safety, please read user's manual thoroughly before operating.
� Contact the nearest authorized service facility for examination, repair, or adjustment.
� Please contact a qualified service technician when you need maintenance.
Do not disassemble or repair by yourself!
Safety Instructions � Any maintenance and inspection shall be performed by the personnel having expertise concerned.

ⓒ 2011.9 LSIS Co.,Ltd. All rights reserved. www.lsis.com

� HEAD OFFICE � Global Network


�LSIS (Middle East) FZE �
�Dubai, U.A.E.
LS-ro 127 (Hogye-dong) dongan-gu Anyang-si Address: LOB 19 JAFZA VIEW TOWER Room 205, Jebel Ali Freezone P.O. Box 114216, Dubai, United Arab Emirates
Gyeonggi-do Korea Tel: 971-4-886 5360 Fax: 971-4-886-5361 e-mail: dhleef@lsis.biz
�Dalian LSIS Co., Ltd. �
�Dalian, China
Tel. (82-2)2034-4887, 4873, 4918, 4148 Address: No.15, Liaohexi 3-Road, Economic and Technical Development zone, Dalian 116600, China
Tel: 86-411-8273-7777 Fax: 86-411-8730-7560 e-mail: tangyh@lsis.com.cn
Fax. (82-2)2034-4648 �LSIS (Wuxi) Co., Ltd. �
�Wuxi, China
Address: 102-A , National High & New Tech Industrial Development Area, Wuxi, Jiangsu, 214028, P.R.China
Tel: 86-510-8534-6666 Fax: 86-510-522-4078 e-mail: luw@lsis.com.cn
�LSIS-VINA Co., Ltd. �
�Hanoi, Vietnam
� CHEONG-JU PLANT Address: Nguyen Khe - Dong Anh - Ha Noi - Viet Nam
Tel: 84-4-882-0222 Fax: 84-4-882-0220 e-mail: sjbaik@lsis.biz
Cheong-Ju Plant #1, Song Jung Dong, Hung Duk Ku, �LSIS-VINA Co., Ltd. �
�Hochiminh , Vietnam
Cheong Ju, 361-720, Korea Address: 41 Nguyen Thi Minh Khai Str. Yoco Bldg 4th Floor, Hochiminh City, Vietnam
Tel: 84-8-3822-7941 Fax: 84-8-3822-7942 e-mail: hjchoid@lsis.biz
�LSIS Shanghai Office �
�Shanghai, China
Address: Room 32 floors of the Great Wall Building, No. 3000 North Zhongshan Road, Putuo District, Shanghai, China
Tel: 86-21-5237-9977 Fax: 89-21-5237-7189 e-mail: baijh@lsis.com.cn
�LSIS Beijing Office � �Beijing, China
Address: B-Tower 17FL.Beijing Global Trade Center B/D. No.36, BeiSanHuanDong-Lu, DongCheng-District,
Beijing 100013, P.R. China
Tel: 86-10-5825-6025,7 Fax: 86-10-5825-6026 e-mail: sunmj@lsis.com.cn
�LSIS Guangzhou Office �
�Guangzhou, China
Address: Room 1403, 14/F, New Poly Tower, No.2 Zhongshan Liu Road, Guangzhou 510180, P.R. China
Tel: 020-8326-6754 Fax: 020-8326-6287 e-mail: chenxs@lsis.com.cn
�LSIS Chengdu Office �
�Chengdu, China
Address: Room 1701 17Floor, huamin hanjun internationnal Building, No1 Fuxing Road Chengdu, 610016, P.R. China
Tel: 86-28-8670-3201 Fax: 86-28-8670-3203 e-mail: yangcf@lsis.com.cn
�LSIS Qingdao Office �
�Qingdao, China
Address: Room 2001,20/F,7B40, Galaxy Building, No.29 Shandong Road, Shinan District, Qingdao 266071, P.R. China
Tel: 86-532-8501-6058 Fax: 86-532-8501-6057 e-mail: wangzy@lsis.com.cn
�LSIS NETHERLANDS Co.Ltd �
�Schiphol-Rijk, Netherlands
Address: 1st. Floor, Tupolevlaan 48, 1119NZ,Schiphol-Rijk, The Netherlands
Tel: 31-20-654-1420 Fax: 31-20-654-1429 e-mail: junshickp@lsis.biz