D30

Transmission Line Protection


Line Distance
Protection System

Cost effective high-speed,


primary and backup distance protection
Key Benefits
• Cost effective, three zone quad or mho, phase and ground • Simplified teleprotection interfaces with Direct I/O
distance protection communications hardware for Transfer Trip and custom built
• Complete IEC 61850 Process Bus solution providing resource Pilot-Aided distance schemes
optimization and minimizing total P&C life cycle costs • Robust network security enabling Critical Infrastructure
• Programmable logic for building customized pilot schemes Protection through user command logging, and dual
permission access control
• Reduced relay to relay wiring and associated installation
costs through high-speed inter-relay communications • Application flexibility - Multiple I/O options, programmable
logic (FlexLogic™)
• Embedded IEC61850 Protocol
• Ambient temperature monitoring with alarming when outside
Applications temperature exceeds upper thresholds

• Overhead sub-transmission lines and underground cables • Circuits with in-zone power transformers
including series compensated lines. • Secure application with Capacitively-Coupled Voltage
• Circuits requiring three-pole autoreclosing and independent Transformers (CCVTs)
synchrocheck supervision • Backup protection for generators, transformers and reactors

Features
Protection and Control IEC 61850 Process Bus Interface
• Phase distance (three zones) with independent compensation • Robust communications with up to 8 HardFiber Bricks
settings for in-zone power transformers
• Seamless integration with existing D30 functions
• Ground distance (three zones) with independent self and
mutual zero sequence compensation • Redundant architecture for dependability and security
• Out-of-step tripping and power swing blocking Monitoring and Metering
• Line pickup • Metering - current, voltage, power, energy, frequency
• Directional overcurrent: Phase, neutral and negative sequence • Oscillography – analog and digital parameters at
• Synchronism check 64 samples/cycle
• Four-shot auto-recloser • Event Recorder - 1024 time tagged events with 0.5ms scan of
• VT fuse failure detector digital inputs
• Customize protection and control functions with FlexLogic™, • Data Logger - 16 channels with sampling rate up to
FlexCurves™, and FlexElements™ 1 sample / cycle
• Setting Security Audit Trail for tracking changes to D30
Communications configuration
• Networking interfaces – 100Mbit Fiber Optic Ethernet, RS485,
RS232, RS422, G.703, C37.94 EnerVista™ Software
• Multiple Protocols - IEC61850, DNP 3.0 Level 2, Modbus RTU, • Graphical Logic Designer and Logic Monitor to simplify
Modbus TCP/IP, IEC60870-5-104, Ethernet Global Data (EGD) designing and testing procedures
• Direct I/O – secure high-speed exchange of data between • Document and software archiving toolset to ensure
URs for Direct Transfer Trip and Pilot-aided distance schemes reference material and device utilities are up-to-date
• Embedded Managed Ethernet Switch with 4 - 100 Mbit Fiber • EnerVista™ Integrator providing easy integration of data in
optic ports and 2 copper ports

g
the D30 into new or existing monitoring and control systems

Multilin
189
D30 Line Distance Protection System

Protection and Control D30 - Protection, Metering, Monitoring and Control


The D30 is a cost effective distance
protection relay intended for protecting
sub-transmission lines and underground
cables of different voltage levels. Part
of the Universal Relay family, the D30
Transmission Line Protection

comes with a variety of versatile features


truly integrating protection, monitoring,
metering, communication and control in
one easy-to-use device. The Universal Relay
family offers higher degree of modularity
in its design and functionality providing
superior performance in protection and
control meeting the toughest requirements
of the marketplace.

Distance Protection
The core of the D30 relay is the distance The D30 is the single point for protection, control, metering, and monitoring in one integrated device that
function providing high degree of can be easily connected directly to HMI or SCADA monitoring and control systems.
sensitivity and selectivity for all types of
faults. The D30 comes with three zones suit for different power system conditions. In-Zone Transformer Compensation
of phase distance and ground distance The advanced comparator based distance Phase distance elements in the D30
providing the user maximum flexibility to elements provide utmost security, can be used to detect faults through
cater for different applications, including sensitivity and selectivity for different different types of three-phase wye/delta
primary sub-transmission line protection types of faults. Superior digital filtering transformers, allowing application of the
and back-up protection for busbars, EHV techniques provide secure and optimum D30 for backup protection on generators.
and HV transmission lines, generators, reach accuracy even under worst- VTs and CTs can be installed independently
transformers and reactors. The relay case CVT transients. Secure directional on either side of the power transformer.
can be applied to power systems with discrimination is achieved by using positive The relay automatically compensates for
different earthing conditions, lines with in- sequence memory voltage polarization transformer connections, to guarantee
zone transformers or tapped transformer providing reliable directionality for worst- accurate reach for any type of fault.
feeders, and overhead lines with series case close-in faults. An additional voltage
compensation. Each zone element for monitoring function provides extra security Load Encroachment
the phase and ground distance can to the distance element, which can be The load encroachment feature offers
be independently set as Quad or Mho used to block the distance elements under discrimination between line loading and
characteristics with the flexibility of voltage source fuse failure conditions. fault conditions, especially for long lines
designing different characteristic shapes to

Functional Block Diagram ANSI Device Numbers & Functions


Device
Number Function
21G Ground Distance
52 21P Phase Distance
25 Synchronism Check
CLOSE TRIP 27P Phase Undervoltage
Monitoring
27X Auxiliary Undervoltage
59X 27X 25 50DD Current Disturbance Detector
79 50G Ground Instantaneous Overcurrent
50N Neutral Instantaneous Overcurrent
50P Phase Instantaneous Overcurrent
50DD 50P 50_2 51P 51_2 21P 67P 67_2 68 78 50N 51N 67N/G 21G 50_2 Negative Sequence Instantaneous Overcurrent
51G Ground Time Overcurrent
59P 51N Neutral Time Overcurrent
Metering Transducer
VTFF
Inputs 51P Phase Time Overcurrent
27P 51_2 Negative Sequence Time Overcurrent
50G 51G 52 AC Circuit Breaker
59N 59N Neutral Overvoltage
59P Phase Overvoltage
59X Auxiliary Overvoltage
D30 Line Distance Protection System 59_2 Negative Sequence Overvoltage
67N Neutral Directional Overcurrent
67P Phase Directional Overcurrent
ANSI DEVICE NUMBERS AND FUNCTIONS
67_2 Negative Sequence Directional Overcurrent
DEVICE DEVICE
NUMBER FUNCTION NUMBER FUNCTION 68 Power Swing Blocking
21G Ground Distance 51_2 Negative Sequence Time Overcurrent 78 Out-of-Step Tripping
21P Phase Distance 52 AC Circuit Breaker 79 Automatic Recloser
25 Synchrocheck 59N Neutral Overvoltage
27P Phase Undervoltage 59P Phase Overvoltage
27X Auxiliary Undervoltage 59X Auxiliary Overvoltage
50DD Current Disturbance Detector 59_2 Negative Sequence Overvoltage
50G Ground Instantaneous Overcurrent 67N Neutral Directional Overcurrent
50N Neutral Instantaneous Overcurrent 67P Phase Directional Overcurrent
190 50P
50_2
Phase Instantaneous Overcurrent
Negative Sequence Instantaneous Overcurrent
67_2
68
www.GEMultilin.com
Negative Sequence Directional Overcurrent
Power Swing Blocking
51G Ground Time Overcurrent 78 Out-of-Step Tripping
51N Neutral Time Overcurrent 79 Automatic Recloser
D30 Line Distance Protection System

identify a line that has been de-energized run parallel with distance protection or
(line end open). Three instantaneous can be programmed to provide primary
overcurrent elements are used to identify protection under conditions when distance
a previously de-energized line that has elements are blocked during fuse-failure
been closed on to a fault. conditions.

Power Swing Detection Autorecloser


Z3 Z1

Transmission Line Protection


Dynamic transients in the power system The D30 provides multi shot autoreclosing
Z1 looking through a transformer due to short-circuits, circuit switching, or for 3 pole autoreclose on all types of
load changes can travel across the power faults with independently settable dead
network as power swings characterized time for each shot. Autoreclosing also
by fluctuating currents and voltages. This can be dynamically blocked by user
can result in unwanted tripping since programmable logic. Four different
distance elements can respond to these autoreclose modes are available enabling
power swings as faults. The D30 swing the users to select the reclosing mode to
detection element provides both power suit specific applications.
Z3 Z1 swing blocking and out-of-step tripping
functions. The element measures the Synchronism Check
Z1 & Z3 looking through a transformer
positive sequence apparent impedance The D30 monitors voltage difference,
and traces its locus with respect to either phase angle difference and slip frequency
under heavy loads by supervising the a two or three step user selectable mho or to ensure proper breaker closure as per
distance elements or any overcurrent quad operating characteristics. user defined settings. The D30 provides
element. This prevents unwanted tripping additional enhancements in synchronizing
under heavy load conditions and enables Overvoltage and Undervoltage by checking dead source conditions
optimum operation of the line while Protection for synchronism bypass under these
meeting regulatory requirements for line Long lines under lightly loaded conditions conditions.
loading. or no-load may experience voltages
exceeding the rated insulation voltage
Fault Locator
level of the line. Use the phase overvoltage IEC 61850 Process Bus
The integrated fault locator provides element of the D30 to initiate a local trip The IEC 61850 Process Bus module is
distance to fault in km or miles. Parallel as well as a remote trip using Direct I/O. designed to interface with the GE Multilin
line zero-sequence current compensation The D30 also provides additional voltage HardFiber System, allowing bi-directional
and load current compensation enables functions including neutral overvoltage, IEC 61850 fiber optic communications.
the D30 to provide improved accuracy for negative sequence overvoltage and phase The HardFiber System is designed to
fault distance measurement . undervoltage integrate seamlessly with the existing
Universal Relay applications, including
Line Pickup (Switch-on-to-Fault) Overcurrent Functions protection functions, FlexLogic, metering
The Line Pickup feature uses a combination The D30 provides overcurrent functions and communications.
of undercurrent and undervoltage to for phase, neutral and ground which can
The GE Multilin HardFiber System offers
the following benefits:
• Communicates using open standard
IEC 61850 messaging
• Drastically reduces P&C design,
installation and testing labor by
eliminating individual copper
terminations
• Integrates with existing D30’s by
replacing traditional CT/VT inputs with
IEC 61850 Process Bus module
• Does not introduce new Cyber Security
concerns

Visit the HardFiber System product page


on the GE Multilin web site for more
details.
Distance relay quadrilateral characteristics supervised by Load Encroachment function

www.GEMultilin.com 191
D30 Line Distance Protection System

Advanced Automation Custom Programmable Logic Designer


The D30 incorporates advanced automation
features including powerful FlexLogic™
programmable logic, communication, and
SCADA capabilities that far surpass what
is found in the average line protection
Transmission Line Protection

relay used for subtransmission. The D30


integrates seamlessly with other UR relays
for complete system protection.

FlexLogic™
FlexLogic™ is the powerful UR-platform
programming logic engine that provides the
ability of creating customized protection
and control schemes thereby minimizing
the need, and the associated costs, of
auxiliary components and wiring.
Using FlexLogic™, the D30 can be
programmed to provide required tripping
logic along with custom scheme logic for
FlexLogicTM allows customizing the D30 for custom protection, control and automation allowing users
breaker control (including interlocking),
to build line protection schemes and applications for their equipment.
transfer tripping schemes for remote
breakers and dynamic setting group
changes. and voltage parameters are available Advanced Device Health Diagnostics
as total RMS magnitude, and as The D30 performs comprehensive device
Scalable Hardware fundamental frequency magnitude and health diagnostic tests during startup and
The D30 is available with a multitude of I/O angle. continuously at runtime to test its own
configurations to suit the most demanding
major functions and critical hardware. These
application needs. The expandable modular Fault and Disturbance Recording
diagnostic tests monitor for conditions that
design allows for easy configuration and The advanced disturbance and event could impact security and availability of
future upgrades. recording features within the D30 can protection, and present device status via
significantly reduce the time needed for SCADA communications and front panel
• Flexible, modular I/O covering a broad postmortem analysis of power system display. Providing continuous monitoring
range of input signals and tripping events and creation of regulatory reports. and early detection of possible issues helps
schemes Recording functions include: improve system uptime.
• Types of digital outputs include trip-
• Sequence of Event (SOE) • Comprehensive device health diagnostic
rated Form-A and Solid State Relay (SSR)
- 1024 time stamped events performed during startup
mechanically latching, and
Form-C outputs • Oscillography, • Monitors the CT/VT input circuitry to
• Form-A and SSR outputs available with - 64 digital & up to 40 Analog channels validate the integrity of all signals
optional circuit continuity monitoring • Data Logger, disturbance recording –
and current detection to verify 16 channels up to 1 sample / cycle /
continuity and health of the associated channel
Communications
circuitry • Fault Reports The D30 provides advanced commun-
• Mechanically latching outputs - Powerful summary report of pre-fault ications technologies for remote data and
can be used to develop secure and fault values engineering access, making it easy and
interlocking applications and replace flexible to use and integrate into new and
electromechanical lockout relays existing infrastructures. Direct support for
The very high sampling rate and large
fiber optic Ethernet provides high-bandwidth
amount of storage space available for
communications allowing for low-latency
data recording in the D30 can eliminate
Monitoring and Metering the need for installing costly standalone
controls and high-speed file transfers of
relay fault and event record information.
The D30 includes high accuracy metering recording equipment.
The available redundant Ethernet option
and recording for all AC signals. Voltage,
and the embedded managed Ethernet
current, and power metering are built into
the relay as a standard feature. Current

192 www.GEMultilin.com
D30 Line Distance Protection System

switch provide the means of creating fault Substation Monitoring


tolerant communication architectures in
an easy, cost-effective manner without
the need for intermediary communication
hardware.

The D30 supports the most popular industry

Transmission Line Protection


standard protocols enabling easy, direct
integration into DCS and SCADA systems.

• IEC61850
• DNP3.0
• IEC60870-5-104
• Modbus RTU, Modbus TCP/IP

Interoperability with Embedded


IEC61850
Use the D30 with integrated IEC61850
to lower costs associated with line
protection, control and automation. GE Monitor the status of your substation using the easy to use Viewpoint Monitoring HMI
Multilin’s leadership in IEC61850 comes
from thousands of installed devices and than strictly limited to simplistic point- UR relay, to carry out postmortem event
follows on seven years of development to-point configurations between two analysis to ensure proper protection
experience with UCA 2.0. devices system operation.
• Connect to standard DS0 channel banks
• Replace expensive copper wiring EnerVista™ Launchpad
through standard RS422, G.703 or IEEE
between devices with direct transfer of EnerVista™ Launchpad is a powerful
C37.94 interfaces or via direct fiber optic
data using GOOSE messaging software package that provides users
connections
• Configure systems based on IEC61850 with all of the setup and support tools
• No external or handheld tester
and also monitor and troubleshoot needed for configuring and maintaining GE
required to provide channel diagnostic
them in real-time with EnerVista™ Multilin products. The setup software within
information
Viewpoint Engineer Launchpad allows configuring devices in
• Integrate GE Multilin IEDs and generic real-time by communicating using serial,
Multi-Language
IEC61850-compliant devices seamlessly Ethernet, or modem connections, or offline
The D30 supports English, French, Russian, by creating setting files to be sent to
in EnerVista™ Viewpoint Monitoring
and Chinese languages on the front panel, devices at a later time.
EnerVista™ setup software, and product
Direct I/O Messaging
manual. Easily switch between English and Included in Launchpad is a document
Direct I/O allows for sharing of high-speed an additional language on the local displays archiving and management system
digital information between multiple UR without uploading new firmware. that ensures critical documentation is
relays via direct back-to-back connections
up-to-date and available when needed.
or multiplexed through a standard DS0
multiplexer channel bank. Regardless of EnerVistaTM Software Documents made available include:

the connection method, Direct I/O provides The EnerVista™ Suite is an industry-
• Manuals
continuous real-time channel monitoring leading set of software programs that
that supplies diagnostics information on • Application Notes
simplifies every aspect of using the D30
channel health. relay. The EnerVista™ suite provides all • Guideform Specifications
Direct I/O provides superior relay-to-relay the tools to monitor the status of the • Brochures
communications that can be used in protected asset, maintain the relay, and
advanced interlocking, and other special • Wiring Diagrams
integrate information measured by the D30
protection schemes. into DCS or SCADA monitoring systems. • FAQ’s
Convenient COMTRADE and Sequence of • Service Bulletins
• Communication with up to 16 UR relays Events viewers are an integral part of the
in single or redundant rings rather UR Setup software included with every

www.GEMultilin.com 193
D30 Line Distance Protection System

Viewpoint Monitoring • Graphical System Designer • Automatic Event Retrieval

Viewpoint Monitoring is a simple-to-use • Graphical Logic Monitor • Automatic Waveform Retrieval


and full-featured monitoring and data • Graphical System Monitor
recording software package for small
systems. Viewpoint Monitoring provides a Viewpoint Maintenance
User Interface
complete HMI package with the following The D30 front panel provides extensive
Viewpoint Maintenance provides tools that
Transmission Line Protection

functionality: local HMI capabilities. The local display


will create reports on the operating status
is used for monitoring, status messaging,
of the relay, simplify the steps to download
• Plug-&-Play Device Monitoring fault diagnosis, and device configuration.
fault and event data, and reduce the work
• System Single-Line Monitoring & Control User configurable messages that combine
required for cyber-security compliance
text with live data, can be displayed when
• Annunciator Alarm Screens audits. Tools available in Viewpoint
user-defined conditions are met.
Maintenance include:
• Trending Reports
• Automatic Event Retrieval
• Settings Security Audit Report
• Automatic Waveform Retrieval
• Device Health Report

Viewpoint Engineer • Single Click Fault Data Retrieval

Viewpoint Engineer is a set of powerful


EnerVista™ Integrator
tools that will allow the configuration and
testing of UR relays at a system level EnerVista™ Integrator is a toolkit that allows
in an easy-to-use graphical drag-and- seamless integration of GE Multilin devices
drop environment. Viewpoint Engineer into new or existing automation systems.
provides the following configuration and Included in EnerVista™ Integrator is:
commissioning utilities:
• OPC/DDE Server
• Graphical Logic Designer • GE Multilin Drivers

Power System Troubleshooting


The D30 contains many tools and reports that simplify and reduce the amount of time required for troubleshooting power system events.

Graphically view zone settings for ground


& phase distance elements for the
selected zones.
Analyze transmission line faults using system
voltage, current and appropriate pickup flags that
are measured & recorded up to 64 samples/cycle.

Record the operation of the internal D30 elements and external


connected devices with 1ms time-stamped accuracy to identify
the Sequence of Operation of station devices during faults and
disturbances.

194 www.GEMultilin.com
D30 Line Distance Protection System

Typical Wiring

B
52 52
C

A B C

Transmission Line Protection


CURRENT
POLARIZATION
SOURCE

F 1a

F 1b

F 2a

F 2b

F 3a

F 3b

F 4a

F 4b

F 5a

F 6a

F 7a

F 8a
F 1c

F 2c

F 3c

F 4c

F 5c

F 6c

F 7c

F 8c
VX
VB

VC
VA

VX
IG5

IG1

VB

VC
IG

VA
IA5

IA1

IB

IC
IA

IC5

IC1
IB5

IB1
H7a 6H I H1a TC 1
H7c H1 H1b
V
H8a H1c
H8c I H2a
H7b H2 H2b
V
H2c
H8b SURGE
I H3a
H3 H3b
V TC 2
H3c
I H4a
H4 H4b
Multilin V
H4c
I H5a
H5
D30 V
H5b
H5c
I H6a
H6 H6b
V
H6c
W5a 6A I W1a
W5c W1 W1b
V
W6a W1c
W6c I W2a
W5b W2 W2b
V
W2c
W7a
W3a
W7c
W3 W3b
W8a
W3c
W8c
W4a
W7b
W4 W4b
W8b SURGE W4c
P1a
6C

P1 P1b
P1c
P2a
P2 P2b
U1a P2c
6D

U1c P3a
U2a P3 P3b
U2c P3c
U1b P4a
P4 P4b
U3a
U3c P4c
P5a
U4a
P5 P5b
U4c
U3b P5c
P6a
U5a P6 P6b
U5c P6c
U6a P7a
U6c P7 P7b
U5b P7c
U7a P8a
U7c P8 P8b PERSONAL
COMPUTER
U8a P8c
U8c
M1a
6K

U7b M1 M1b
U8b SURGE
RS-232 M1c
M2a
DB-9 M2 CONNECTOR
B1b M2b CONNECTOR
CRITICAL
1

B1a (front) M2c 1 1 8


FAILURE
B2b M3a TXD 2 2 3 RXD
B3a M3 M3b 3 3 2 TXD
RXD
DC B3b OUTPUT M3c 4 4 20
B5b HI M4a SGND 5 5 7 SGND
CONTROL M4
B6b LO M4b 6 6 6
POWER
B6a M4c 7 7 4
B8a SURGE M5a 8 8 5
B8b FILTER M5 M5b 9 9 22
M5c
UR COMPUTER
M6a
M6 M6b
* Optic
Fibre Tx1 10BaseFL
NORMAL M6c
Rx1
M7a
Tx2 10BaseFL COM M7 M7b
ALTERNATE
Rx2 1
M7c
Shielded 10BaseT M8a
Remote M8 M8b
Device D1a M8c
RS485
D2a
D3a com
D4b
D4a IRIG-B
Input
Co-axial BNC

IRIG-B
Co-axial BNC Output

D30-H00-HCL-F8F-H6H-m6K-P6C-u6D-W6a
Minimum
X W V U T S R P N M L K J H G F D B
6 6 6 6 6 8 9 1
Inputs/ Inputs/ Inputs/ Inputs/
outputs outputs outputs outputs Inputs/ CT/VT CPU Power
* * * * outputs Supply
PROVIDED configurations.

www.GEMultilin.com 195
D30 Line Distance Protection System

Ordering
D30 - * ** - H * * - F ** - H ** - M ** - P ** - U ** - W** For Full Sized Horizontal Mount
Base Unit D30 Base Unit
CPU E RS485 + RS485 (IEC61850 option not available)
G RS485 + Multi-mode ST 10BaseF
H RS485 + Mutli-mode ST Redundant 10BaseF
J RS485 + Multi-mode ST 100BaseFX
K RS485 + Multi-mode ST Redundant 100BaseFX
N RS485 + 10/100 BaseT
S RS485 + 6 port, 100 Mbps, Managed Ethernet Switch
Software Options 00 No Software Options
03 IEC61850
Transmission Line Protection

Mount H Horizontal (19" rack) - Standard


A Horizontal (19" rack) - Harsh Chemical Environment Option
V Vertical (3/4 size) - Standard
B Vertical (3/4 size) - Harsh Chemical Environment Option
User Interface K Enhanced English Front Panel
L Enhanced English Front Panel with User-Programmable Pushbuttons
M Enhanced French Front Panel
N Enhanced French Front Panel with User-Programmable Pushbuttons
Q Enhanced Russian Front Panel
T Enhanced Russian Front Panel with User-Programmable Pushbuttons
U Enhanced Chinese Front Panel
V Enhanced Chinese Front Panel with User-Programmable Pushbuttons
F Vertical Front Panel with English display
Power Supply H 125 / 250 V AC/DC
H RH 125/250 V AC/DC with redundant 125/250 V AC/DC power supply
L 24 - 48 V (DC only)
CT/VT DSP 8L Standard 4CT/4VT w/ enhanced diagnostics
8M Sensitive Ground 4CT/4VT w/ enhanced diagnostics
IEC 61850 Process Bus 81 8 Port IEC 61850 Process Bus Module
Digital I/O XX XX XX XX XX No module
4A 4A 4A 4A 4A 4 Solid State (No Monitoring) MOSFET Outputs
4C 4C 4C 4C 4C 4 Solid State (Current w/opt Voltage) MOSFET Outputs
4D 4D 4D 4D 4D 16 Digital Inputs with Auto-Burnish
4L 4L 4L 4L 4L 14 Form-A (No Monitoring) Latchable Outputs
67 67 67 67 67 8 Form-A (No Monitoring) Outputs
6C 6C 6C 6C 6C 8 Form-C Outputs
6D 6D 6D 6D 6D 16 Digital Inputs
6E 6E 6E 6E 6E 4 Form-C Outputs, 8 Digital Inputs
6F 6F 6F 6F 6F 8 Fast Form-C Outputs
6K 6K 6K 6K 6K 4 Form-C & 4 Fast Form-C Outputs
6L 6L 6L 6L 6L 2 Form-A (Current w/ opt Voltage) & 2 Form-C Outputs, 8 Digital Inputs
6M 6M 6M 6M 6M 2 Form-A (Current w/ opt Voltage) & 4 Form-C Outputs, 4 Digital Inputs
6N 6N 6N 6N 6N 4 Form-A (Current w/ opt Voltage) Outputs, 8 Digital Inputs
6P 6P 6P 6P 6P 6 Form-A (Current w/ opt Voltage) Outputs, 4 Digital Inputs
6R 6R 6R 6R 6R 2 Form-A (No Monitoring) & 2 Form-C Outputs, 8 Digital Inputs
6S 6S 6S 6S 6S 2 Form-A (No Monitoring) & 4 Form-C Outputs, 4 Digital Inputs
6T 6T 6T 6T 6T 4 Form-A (No Monitoring) Outputs, 8 Digital Inputs
6U 6U 6U 6U 6U 6 Form-A (No Monitoring) Outputs, 4 Digital Inputs
6V 6V 6V 6V 6V 2 Form-A (Cur w/ opt Volt) 1 Form-C Output, 2 Latching Outputs, 8 Digital Inputs
Transducer I/O 5A 5A 5A 5A 5A 4 dcmA Inputs, 4 dcmA Outputs
5F 5F 5F 5F 5F 8 dcmA Inputs
Inter-Relay Communications 7A 820 nm, multi-mode, LED, 1 Channel
7B 1300 nm, multi-mode, LED, 1 Channel
7C 1300 nm, single-mode, ELED, 1 Channel
7H 820 nm, multi-mode, LED, 2 Channels
7I 1300 nm, multi-mode, LED, 2 Channels
7J 1300 nm, single-mode, ELED, 2 Channels
7S G.703, 2 Channels
7W RS422, 2 Channels
73 1550 nm, single-mode, LASER, 2 Channels
77 IEEE C37.94, 820 nm, multi-mode, LED, 2 Channel
2B IEEE C37.94SM, 1300nm Single mode, ELED, 2 Channel Single mode
2S 6 port, 100 Mbps, Managed Ethernet Switch, HI (125/250V AC/DC)
2T 6 port, 100 Mbps, Managed Ethernet Switch, LO (24-48 Vdc)

Accessories for the D30 Visit www.GEMultilin.com/D30 to:


  •  UR Applications I Learning CD TRCD-URA1-C-S-1   •  View Guideform specifications
  •  Multilink Ethernet Switch ML2400-F-HI-HI-A2-A2-A6-G1   •  Download the instruction manual
  •  Viewpoint Engineer VPE-1   •  Review applications Notes and support documents
  •  Viewpoint Maintenance VPM-1   •  Buy a D30 online
  •  Viewpoint Monitoring IEC61850 VP-1-61850   •  View the UR Family brochure

Ordering Note: To view the latest options available for the D30, or to order the UR Classic Front Panel, please visit our online store for more details.

080626-v1