You are on page 1of 14

Dash et al.

Protection and Control of Modern Power Systems (2018) 3:8


https://doi.org/10.1186/s41601-018-0079-z
Protection and Control of
Modern Power Systems

ORIGINAL RESEARCH Open Access

Adaptive fractional integral terminal sliding


mode power control of UPFC in DFIG wind
farm penetrated multimachine power
system
P. K. Dash1*, R. K. Patnaik2 and S. P. Mishra1

Abstract
With an aim to improve the transient stability of a DFIG wind farm penetrated multimachine power system (MPN), an
adaptive fractional integral terminal sliding mode power control (AFITSMPC) strategy has been proposed for
the unified power flow controller (UPFC), which is compensating the MPN. The proposed AFITSMPC controls
the dq- axis series injected voltage, which controls the admittance model (AM) of the UPFC. As a result the
power output of the DFIG stabilizes which helps in maintaining the equilibrium between the electrical and
mechanical power of the nearby generators. Subsequently the rotor angular deviation of the respective generators
gets recovered, which significantly stabilizes the MPN. The proposed AFITSMPC for the admittance model of the UPFC
has been validated in a DFIG wind farm penetrated 2 area 4 machine power system in the MATLAB environment. The
robustness and efficacy of the proposed control strategy of the UPFC, in contrast to the conventional PI control is
vindicated under a number of intrinsic operating conditions, and the results analyzed are satisfactory.
Keywords: Adaptive fractional integral terminal sliding mode power control, Doubly fed induction generator,
Multimachine power network, Unified power flow controller

1 Introduction and reactive power flows across the ac transmission lines


The increase in the penetration of wind power, especially [4, 5]. A number of configurations of the UPFC used for
from doubly fed induction generator based wind farms the ac transmission lines in the last few decades have been
into the existing power grids, is although beneficial, but reviewed in [6]. Most of the models constitute a large
has significant pessimistic impacts [1] such as voltage and number of parameters involved and hence are computa-
frequency control, power transfer capability, transient sta- tionally more complex. On the contrary, a simple model
bility, etc. The employment of the power system stabilizers which is easier for deriving the controls has been pro-
(PSS) is helpful in stabilizing such power systems, but they posed in [7], where the voltage injected in the series por-
demonstrate an unreliable performance for the interarea tion of the UPFC is resolved into quadrature and phase
oscillations between the generators of the multimachine components, with respect to the current flowing along the
power systems [2]. In the process, the application of the line. These components are further used to effectively
Flexible AC Transmission System (FACTS) devices, such control the reactive and active power flow through the
as Unified Power Flow Controllers (UPFC) along with the transmission line, respectively.
PSS has illustrated excellent results, especially for improv- A review on some of the control systems for the
ing the oscillations exhibited by the power system compo- UPFC as well as their drawbacks has been discussed
nents [3]. Adding to it, they also control both the active in [8]. The proportional-integral (PI) control is one of
the effective conventional controller for the UPFC [9],
* Correspondence: pkdash.india@gmail.com but its performance is unreliable under some of the
1
Siksha O Anusandhan University, Khandagiri Square, Bhubaneswar, Odisha intermittent operating conditions (DFIG based wind
751030, India
Full list of author information is available at the end of the article
farms) [10]. In the due course of time some of the

© The Author(s). 2018 Open Access This article is distributed under the terms of the Creative Commons Attribution 4.0
International License (http://creativecommons.org/licenses/by/4.0/), which permits unrestricted use, distribution, and
reproduction in any medium, provided you give appropriate credit to the original author(s) and the source, provide a link to
the Creative Commons license, and indicate if changes were made.
Dash et al. Protection and Control of Modern Power Systems (2018) 3:8 Page 2 of 14

non-linear controls such as sliding mode control [10] experiences a realistic wind profile [17]. It is observed
(SMC), Neuro-SMC techniques [11] etc., have been that as compared to the conventional PI control, the
proposed for the control of the UPFC. The choice of proposed control strategy for the admittance model of
an ideal hyper plane that assures the asymptotic the UPFC is very much significant and robust in improv-
stability of the non- linear systems is very much ing the transient stability of the DFIG penetrated multi-
important for the controller design of the SMC. machine power system and exhibits the largest TCCL for
Adding to it, SMC is endowed with the well-known all most all the cases simulated in this paper. These out-
chattering phenomenon which makes it unreliable puts as illustrated in the simulation and results section
under certain operating conditions. Thus in order to are satisfactory and vindicate the real time application of
overcome the above mentioned problems, a fractional the proposed technique.
integral terminal sliding mode power control
(FITSMPC) has been investigated for the nonlinear
and dynamic systems [12] that shows a very much 2 Proposed admittance model of UPFC
promising result in terms of guaranteed finite time 2.1 Basic model of the UPFC
chatter free error convergence. Figure 1 illustrates the single line diagram of an
In view of the discussions made above, the major UPFC connected within the buses ‘m’ and ‘n’ (with
contributions of the paper are listed as follows: bus voltage magnitudes Vm∟δm and Vn∟δn, respect-
ively). As a generalized concept of the UPFC [7], it
(a) A FITSMPC is proposed to control the dq- axis comprises of a series transformer (Tsbt), a shunt
series injected voltage of the UPFC that exciter transformer (Tshet), a common dc link capaci-
subsequently controls the proposed admittance tor and two voltage source converters. In fact the bus
model of the UPFC. ‘n’ is very nearer to bus ‘m’, as compared to bus ‘o’
(b)The controller gains of the proposed FITSMPC for (with bus voltage magnitude Vo∟δo), as per the
the admittance model of the UPFC are made dynamic inequality relation “(xSE+ xTsbt) < <xTr. Line”, where xSE,
[13], such that they adjust with the intermittent xTsbt and xTr. Line are the reactance’s of the series
operating conditions. portion of UPFC, transformer Tsbt and the transmis-
(c)This subsequently controls the active power sion line between bus ‘n’ and ‘o’, respectively.
injection at the DFIG wind farm terminal, which Figure 2 shows the equivalent circuit of the UPFC
maintains the power balance of the nearby in terms of controlled current sources, where xSH
generators. As a result, the rotor angular oscillations represents the reactance’s across the shunt portions of
between the generators in the multimachine system the UPFC. ξSH and ξSE represent the susceptances of
gets recovered, which will help in improving the the shunt and series converter transformers of
power transfer capability of the associated respectively. Similarly, υ and υSH represent the angle
transmission lines (though this later portion has of the V Tsbt the UPFC, and V Tshet with respect toVm,
not been investigated in the current paper, but is respectively; δm and δn are the phase angle at buses
considered for future work). ‘m’ and ‘n’, respectively.
Motivated from [7], let us assume μα|Vm | and μβ|Vm |
The proposed controllers for the admittance model of be the induced voltage across Tsbt and Tshet, respectively,
the UPFC is installed in a standard 2-area 4-machine where μα and μβ are the voltage proportion level of the
system [7], which has been penetrated by a DFIG based series and shunt circuits of the UPFC, respectively. Thus
wind farm [14]. The overall model with their controllers expression for the injection of the active and reactive
have been simulated in the MATLAB/Editor environ- powers at buses ‘m’ and ‘n’ (Pm, Qm, Pn and Qn), respect-
ment following the necessary requirements for multima- ively, can be defined as:
chine simulation [15]. The size and location for
installation of the UPFC and DFIG based wind farm in 9
Pm ¼ μβ jV m j2 ξ SH sinðυSH Þ þ μα jV m j2 ξ SE sinðυÞ >
>
the multimachine power system has been followed as =
Qm ¼ μβ jV m j2 ξ SH cosðυSH Þ þ μα jV m j2 ξ SE cosðυÞ−jV m j2 ξ SH
per the references [7, 16], respectively. Critical Clearing Pn ¼ −μα jV m jjV n jξ SE sinðδ b þ υÞ >
>
;
Time (TCCL) [1], one of the key indicators of the transi- Qn ¼ −μα jV m jjV n jξ SE cosðδ b þ υÞ
ent stability index, has been taken as the basis for com-
ð1Þ
parison of the performance of the proposed controller
with the conventional PI control of the admittance
model of the UPFC installed in the DFIG wind farm It is further stated that, in order to attain a permissible
penetrated multimachine power system, and which is operation of the shunt converters, υSH ≈ 0. Thus we
subjected to three phase fault and the DFIG wind farm derive:
Dash et al. Protection and Control of Modern Power Systems (2018) 3:8 Page 3 of 14

  )
Y m ¼ Pm −jQm =jV m j2
  ð5Þ
Y n ¼ Pn −jQn =jV n j2

Substituting the expressions of Pm, Qm, Pn and Qn


from Eqs. (4), and (1) in Eq. (5), we derive,
 
Y m ¼ μα jV m j2 ξ SE sinðυÞ þ jV m jjI SH j− j μα jV m j2 ξ SE cosðυÞ =jV m j2
¼ μα ξ SE ½ sinðυÞ−j cosðυÞ þ jV m j−1 jI SH j
ð6Þ
Fig. 1 The single line diagram of an UPFC
Similarly,
2
μβ jV m j ξ SH sinðυSH Þ ≈ 0 and Y n ¼ −μα jV m jjV n jξ SE sinðδ b þ υÞ−jð−μα jV m jjV n jξ SE cosðδ b þ υÞÞ=jV n j2
2 2
μβ jV m j ξ SH cosðυSH Þ−jV m j ξ SH ≈ 0 ¼ −μα ξ SE ½ sinðδ n þ υÞ−j cosðδ n þ υÞjV n j−1 jV m j

ð2Þ ð7Þ

Consequently, it can be rewritten as: 2.3 Design of μα and υ


 Let us consider ϑζD and ϑζQ are the direct and quadra-
P m ¼ μα jV m j2 ξ SE sinðυÞ ture axis voltage injected in the series circuit of the
ð3Þ
Qm ¼ μα jV m j2 ξ SE cosðυÞ UPFC (ϑζ), i.e.
qffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi
It is to be noted that the autonomous control mechan- ϑζ ¼ ϑ2ζD þ ϑ2ζQ ð8Þ
ism of the shunt as well as the series converter of the
UPFC rarely leads to an exact balance of power between Now in order to attain a power flow control of the
them and hence some appropriate power injections must series inverter of the UPFC, ϑζ can be resolved (ϑζP and
be added to attain so. In accordance to it, the active ϑζQ) across the series current Iζ such that:
power at bus ‘m’ can be revisited as: 
ϑζP ¼ ϑζD sinðδ ξ Þ þ ϑζQ cosðδ ξ Þ
ð9Þ
Pm ¼ μα jV m j2 ξ SE sinðυÞ þ jV m jjI SH j ð4Þ ϑζR ¼ ϑζQ sinðδ ξ Þ−ϑζD cosðδ ξ Þ

where
where ISH corresponds to the real component of the
 
current across the shunt converter. δ ξ ¼ tan−1 iζD =iζQ ð10Þ

2.2 Admittance model of the UPFC and


Thus UPFC can be treated as admittances (Ym and Yn) qffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi
which can be expressed in terms of the active and react- iζ ¼ i2ζD þ i2ζQ ð11Þ
ive power across the two buses ‘m’ and ‘n’ (Pm, Qm, Pn
and Qn), respectively, as shown in Fig. 3. Where iζD and iζQ re the dq- axis component of the
Ym and Yn can be expressed mathematically as: series injected current Iζ.

Fig. 2 Equivalent circuit of the UPFC in terms of controller current sources


Dash et al. Protection and Control of Modern Power Systems (2018) 3:8 Page 4 of 14


ϑxD ¼ ϑςD þ V nD
ð16Þ
ϑxQ ¼ ϑςQ þ V nQ

Rearranging Eq. (16), we have:


h i9
ϑxD ¼ V mQ γ P þ V mD γ^Q = V 2mD −V 2mQ =
h i ð17Þ
ϑxQ ¼ V mD γ P þ V mQ γ^Q = V 2mD −V 2mQ ;
Fig. 3 Equivalent circuit of the proposed UPFC as
controllable admittances where
h i
The relation between the bus voltage ‘Vm’ and the γ^Q ¼ γ Q −V 2mD −V 2mQ ð18Þ
series injected voltage ‘ϑζ’ can be expressed in dq axis as:
 Finally the control objective is attained as:
ϑζD ¼ μα V mD cosðυÞ−μα V mQ sinðυÞ 
ð12Þ
ϑζR ¼ μα V mD sinðυÞ þ μα V mQ cosðυÞ ϑςD ¼ ϑxD −V nD
ð19Þ
ϑςQ ¼ ϑxQ −V nQ
Finally, the parameters μα and υ are designed as:
Thus γQ and γP are the target control terms which are
qffiffiffiffiffiffiffiffiffiffiffiffiffi
ϑ2ζP ϑ2ζQ    used to control the final dq- axis series injected voltages
iζD V mD ϑζP
μα ¼ and υ ¼ tan−1 þ tan−1 þ tan−1 (Eq. (34)), which subsequently control the proposed AM
Vm iζQ V mQ ϑζQ
of the UPFC, respectively.
ð13Þ

Thus UPFC has been modeled as controllable ad- 3.2 Proposed adaptive fractional integral terminal sliding
mittance loads as specified in Eqs. (6) and (7), re- mode power control (AFITSMPC) of UPFC
spectively. It is to be noted that the admittance Reformulating the dynamic power model of the series
across the loads Ym and Yn, can be controlled by μα SSSC of the UPFC (Eq. (17)):
and υ which are again controlled by ϑζP and ϑζQ, re-
spectively, which depends upon δξ, ϑζD and ϑζD, re- x_ ¼ Ax þ Bu ð20Þ
spectively. Thus the control of the UPFC as
where
controllable loads is achieved by controlling the series
−1
injected voltage, as shown in Eq. (22), which is the −ω 0 x 0 X1
A¼ ; B ¼ SE −1 ; x ¼
main contribution of this manuscript. Modelling of 0
ω 0
x SE X2
the dc link voltage is referred to [7]. pn γQ
¼ ; and u ¼ ð21Þ
qn γP

3 Methods The tracking error functions for the controller, in


3.1 The non- linear dynamic model of the UPFC terms of the active and reactive power of the SSSC of
The dynamic power model of the series SSSC of the the UPFC are defined as:
UPFC in form of a state- space representation can be 
defined as er1 p p
¼ n − n ð22Þ
er2 qn qn
p_ n ¼ −ωpn þ x−1
SE γ Q
ð14Þ Where pn and qn are the reference value of the active
q_ n ¼ ωqn þ x−1SE γ P
and reactive powers, which are evaluated in the initial
γQ and γP are the control terms associated with the solution.
non-linear dynamic Eq. (17), which are defined as: Taking the derivative of Eq. (22) with respect to time
on both sides, we derive:
h
 i )
γQ ¼ V 2mD þ V 2mQ − V mQ ϑxQ −V mD ϑxD
  ð15Þ e_ r1 ω 0 pn 0 x−1 γP
γ P ¼ V mD ϑxQ −V mQ ϑxD ¼ − −1 SE ð23Þ
e_ r2 0 −ω qn xSE 0 γQ

In the above Eq. (15), the terms ϑxD and ϑxQ are The fractional Integral terminal sliding surface (FITSS)
defined as: are defined as:
Dash et al. Protection and Control of Modern Power Systems (2018) 3:8 Page 5 of 14



σ r1 er1 α 0 eIr1 γ_ Prob γ ProbV β 0 γ Prob
¼ þ 1 ð24Þ ¼ − Prob
σ r2 er2 0 α2 eIIr2 γ_ Qrob γ QrobV 0 βQrob γ Qrob
ð35Þ
where
" β
# where
e_ Ir1 1 0 er11
¼ β ð25Þ " #
e_ IIr2 0 1 er22 γ ProbV ^
β 0 signðσ r2 Þ
¼ ProbV
^ ð36Þ
γ QrobV 0 β signðσ r1 Þ
With α1, α2 > 0, β1, β2 are fractional numbers satisfying QrobV

the relation 0 < [β1, β2] < 1.


Integrating the above Eq. (25), and replacing the re- " #
^_
β β 0 jσ r2 j
sultant in Eq. (23), the final expression for the FITSS ProbV
¼ − ProbA ð37Þ
in terms of the tracking error is defined as, ^_
β 0 βQrobA jσ r1 j
QrobV
2Z 3
β1
e
σ r1 e α 0 6 6Z
r1 7
7 In the above Eqs. (34)–(37), {βProbV, βQrobV, βProbA ,
¼ r1 þ 1 4 ð26Þ
σ r2 er2 0 α2 β 5 βQrobA} > 0, are the gains of the controller, whose initial
er22
values are mentioned in the Appendix. Eq. (37), which
makes the controller adaptive i.e., adjusts the controller
where (β1, β2) are the fractional powers of the tracking gains according to the varying operating conditions, is
errors (er1, er2) with initial values (−er1(0)/α1, −er1(0)/α1), defined as the fractional integral terminal sliding mode
respectively. adaptive law for the admittance model of the UPFC.
The derivative of the above Eq. (26) is defined as: Proof of convergence On the surface σ_ r1 ¼ 0 and
" β1 # σ_ r2 ¼ 0 we have,
σ_ r1 e_ r1 α1 0 er1
¼ þ ð27Þ 2 3
σ_ r2 e_ r2 0 α 2 eβ2 e_ r1
r2
" #
β 6 β 7
e_ r1 α1 er11 6 α1 er11 7 1
Replacing Eq. (23) in Eq. (27), we derive: ¼− ⇒ 6 7 ¼ − ð38Þ
e_ r1 β
α2 er22 4 e_ r2 5 1
" β
# β2
α2 er2
σ_ r1 ω 0 pn α 0 er11
⇒ ¼ þ 1
σ_ r2 0 −ω qn 0 α2 β
er22
Integrating the above Eq. (39), and then rearranging
0 x−1 γP the resultant term, the convergence time of the tracking
− −1 SE
xSE 0 γQ errors are derived as:
ð32Þ 2 3
2 3
jeIr1 j1−β1je j1−β1
Theorem 1 The tracking error functions as defined in 6 β 7 6 r1
6 α 1 ð1−β Þ 7 6 α1 ð1−β Þ 7
t r1
¼6 1 7 1 7
6 je j1−β2 7 ¼ 6 1−β 7 ð39Þ
Eq. (25) will converge to zero in a finite amount of time, 1

and the system will remain robust and stable if the


t r2 4 Ir2 5 4 jer2 j 2 5
β α2 ð1−β2 Þ
FITSS are chosen as in Eq. (32), and the control is de- α 2 ð1−β Þ
2 2
signed as follows:
Equation (39) guarantees a finite time convergence of
γP γ Pnom γ Prob the tracking error functions [12] as defined in Eq. (25).
¼ þ ð33Þ
γQ γ Qnom γ Qrob Proof of stability Let us consider the following Lyapu-
nov function:
where γPnom and γQnom are the nominal controls,
whereas γProb and γQrob are the robust controls, respect- 1 1 1
^_ ^
2
ively, as introduced by the terminal sliding mode con- V L ¼ σ 2r1 þ σ 2r2 þ β ProbV −β
2 2 β ProbA ProbV
cept and can be derived as follows:
1
^_ ^
2
þ βQrobV −β
γ Pnom 0 −ωxSE pn βQrobA QrobV
¼ ð34Þ
γ Qnom ωxSE 0 qn ð40Þ
" β #
0 α2 xSE er11
þ β Taking the derivative of the above Eq. (40) w.r.t time
α1 xSE 0 er22 on both sides, we derive:
Dash et al. Protection and Control of Modern Power Systems (2018) 3:8 Page 6 of 14


9
V_ L ¼ σ r1 σ_ r1 þ σ r2 σ_ r2 þ β^_ ^ ω_ rr ¼ 0:5  ðt ssh −t ee Þ=H gg >
>
ProbV −β ProbV jσ r2 j ð41Þ >
>

>
>
^_ ^ θtw ¼ ωee ðωtt −ωrr Þ >
>
þ β QrobV −βQrobV jσ r1 j >
>
>
>
ωtt ¼ 0:5  ðt mm −t sh Þ=H tt >
>
  >
>
E sd =
Lss −Lss >
>
E sd ¼ − þ ðωss −ωrr ÞE sq þ ωss I sq >
>
>
T rr T rr >
>
Substituting Eqs. (34)–(37) in eq. (32), we simplify as: =
−ωss K mrr V rq ¼ γ 1 −γ 3 V rq ð44Þ
  >
>
2n o n o3 >
>
^ E sq Lss −L=ss >
>
σ_ r1 ð1−hÞβQrob þ hβ signðσ r1 Þ E sq ¼ − −ðωss −ωrr ÞE sd −ωss I sd >
>
4 QrobV
o5 >
>
σ_ r2
¼ −x−1
SE   n T rr T rr >
>
^
ð1−hÞβ Prob þ hβ sign ð σ Þ >
>
ProbV r2 þωss K mrr V rd ¼ γ 2 þ γ 3 V rd >
>
>
>
ð42Þ >
>
P rr −Pii −ðωss −ωrr ÞP ss −Pii >
>
V dc ¼ ¼ >
;
C dc V dc C dc V dc

where h is the step length equal to 0.01. where ωrr, ωtt and ωss are the rotor, turbine and syn-
Now substituting Eq. (42) in Eq. (41), we derive: chronous speeds of the DFIG, respectively. Esd and Esq
denotes the voltage behind the transient reactance of the
DFIG. θtw represents the shaft twist angle. Cdc and Vdc
h  i are the capacitance and voltage components across the
V_ L ¼ − 1 þ hx−1 ^ ^_
SE βQrobV −βQrobV jσ r1 j dc terminal of the DFIG, respectively. The constants Hgg,
h  i Htt are represents the inertia constants of generator and
− 1 þ hx−1 ^
β − ^_
β
SE ProbV ProbV jσ r2 j turbine, respectively. Similarly, Lss, L/ss, Trr represent the
h
 i synchronous inductance, transient inductance and time
−x−1
SE σ r1 ð1−h Þβ Qrob þ σ r2 ð1−h Þβ Prob constant of DFIG respectively. Mathematically, L/ss = ωss
[L2mm/Lrr] and Trr = Lrr/rrr, where Lrr and rrr are the rotor
⇒ V_ L ≤0 for all σ r1 ≠0 and σ r2 ≠0:
self-inductance and resistance, respectively, and Lmm is
ð43Þ the mutual inductance between the stator and the rotor
terminals of the DFIG. tmm, tsh and tee are the mechan-
From Eq. (43), it is proved that as the value of V_ L ≤ 0
ical, shaft and electromechanical torque of the DFIG
for all σr1 ≠ 0 and σr2 ≠ 0, which guarantees the system
respectively.
stability. This completes the proof.
The total real and reactive power supplied by DFIG to
the network is simplified as:
4 DFIG wind farm model Pdf ¼ Pss þ P ii ¼ V sd I sd þ V sq I sq þ V rd I rd þ V rq I rq
Motivated from [1], the large off-shore [18] 100 MW
DFIGWF comprising 20 wind turbines rated at 5 MW ð45Þ
each is characterized by an equivalent amassed DFIG Qdf ¼ Qss þ Qii ¼ V sq I sd −V sd I sq ð46Þ
configuration, which is driven by an equivalent amassed
DFIG wind turbine (DFIGWT), via a matching gearbox where Ird, Irq, Isd, Isq, Iid, Iiq, Vrd, Vrq, Vsd, Vsq, Vid, and Viq,
mechanism, as shown in Fig. 4. Thus each of the wind are the dq-axis current and voltage quantities of the
turbines present in the wind farm model is assumed to RSC, stator, and GSC Terminals, respectively. Similarly,
be identical, and the resulting wind farm is an aggre- Prr, Pss, Pii, Pdf, Qrr, Qss, Qii, and Qdf are the active and
gated version of a number of wind turbines. The param- reactive power flows across the RSC, stator, GSC and
eters of a single DFIGWT are referred to [14]. As DFIG terminals respectively.
depicted from this figure, the DFIG stator terminals are The GSC operation has been restricted to unity power
directly connected to the low voltage side of the utility factor and hence, results in zero reactive power at the
transformer (LVSUT), whereas, the DFIG rotor termi- GSC terminal.
nals are connected to the same LVSUT via a back to
back, voltage source converter (VSC) based power elec- 5 Results
tronic circuit. Figure 5 illustrates the single line diagram of the test sys-
The synchronous dq reference frame based dy- tem i.e., the multimachine power system (2 area 4 ma-
namic model of the DFIG wind turbine is developed chine system [19]), with a 100 MW DFIG based wind
from its flux linkage model [16], and is represented farm [14] (comprising a lumped model of 20 number of
as: identical 5 MW DFIG based wind turbines) installed at
Dash et al. Protection and Control of Modern Power Systems (2018) 3:8 Page 7 of 14

Fig. 4 Single line diagram of the aggregated DFIG based Wind Farm

the bus ‘7’ and the 20 MVA equivalent admittance model of total power penetration capacity (TPPC) of the DFIG
of the UPFC [7] installed within the bus ‘m’ and ‘n’, re- wind farm, respectively [1].
spectively, (as has been explained in section II), and this As depicted in Fig. 6, number of operating conditions
model has been simulated in the MATLAB/Editor envir- that have been selected are ‘A (1.47 s, 8.38 m/s)’, ‘B
onment following the requirements for the multimachine (0.75 s, 7.30 m/s)’ and ‘C (2.5 s, 16.59 m/s)’, and ‘D
simulations [15]. The generators in the multimachine sys- (3.05 s, 12.52 m/s)’ which corresponds to lower and
tem are enabled with PSS, and the details regarding the higher wind speeds at positive and negative slopes, re-
concepts, modeling, parameterization and dynamics of the spectively. The penetration level of the DFIG wind
various network components (including generators, trans- power have been varied from (16.01–23.90) % of the
mission lines, transformers, PSS, DFIG based wind farm, TPPC [1], which corresponds to (0.51–0.76) p.u. of
UPFC, etc.) can be found in the literatures [14, 16, 19]. DFIG wind power penetration, and are denoted as the
For simulating the power system shown in Fig. 4, the base lower and higher penetration levels of the DFIG wind
MVA is chosen as 100. Further it is noted that the compu- power, respectively. It is to be noted that, a PI control
tational complexity associated with the dynamics of the strategy is incorporated to the control the DFIG wind
network components, i.e., transformers, exciters, trans- farm [13] converters. Figs. 6, 7, 8, 9, 10 and 11 illustrate
mission lines, converters, etc., is very much high for MPN the comparison of the cases where the STRATEGY A
simulation, and hence following the IEEE 1547 norms and (red line) involves the conventional PI control of the
[15], they have been neglected in this paper. A sporadic AM of the UPFC, whereas the STRATEGY B (black line)
wind profile [17], as shown in Fig. 5 is varying between involves the proposed AFITSMPC for the AM of the
0.11 m/s and 18.11 m/s, which matches to (0–80) % of UPFC. The gains of the PI controllers for the DFIG as
total power generation capacity (TPGC) and (0–25.31) % well as AM of UPFC are tuned through ITAE criterion

Fig. 5 Single line diagram of the test system


Dash et al. Protection and Control of Modern Power Systems (2018) 3:8 Page 8 of 14

5.1 Performance of the control strategies of the UPFC in


the DFIG wind farm penetrated two area four machine
system (Fig. 5) with the DFIG wind farm subjected to
fixed wind speed
In this particular case, a three phase fault is initiated
on bus 7 of the test system (Fig. 5) at the timing
instant ts = 2.11 s, where the DFIG wind farm is sub-
jected to fixed wind speed of 6.29 m/s. The perform-
ance of the controllers has been tested for both the
lower as well as higher level of penetration of the
Fig. 6 The sporadic wind profile DFIG wind farm, which are illustrated in Figs. 7 and
8, respectively. In order to evaluate the TCCL , the per-
formance of the proposed as well as conventional
controls of the AM of the UPFC is observed by re-
[20], with possible maximum wind power penetration. petitive simulations by increasing the duration of fault
The detailed values of the tuned gains for the PI control- ‘tf ’. It is observed that, the TCCL for the conventional
ler for the DFIG as well as AM of UPFC are mentioned PI control for this particular case is 249 ms and
in the Appendix. 161 ms for lower and higher penetration of DFIG
A three phase short-circuit fault is considered as the wind farm, respectively, at which the generators in
disturbance which has been simulated on one of the load the system losses synchronism (subplots (d)). On the
bus (bus ‘7’ in Fig. 5) for certain duration of time ‘tf ’ in contrary, for the same duration of fault (TCCL for PI
sec. The highest value of tf in the post fault region control), the proposed control of the AM of the
within which synchronism between the relative rotor an- UPFC is very much significant in improving the ‘Ym’
gles of the generators in a power system is maintained is and ‘Yn’ placed between the buses ‘m’ and ‘n’ as
defined as the critical clearing time denoted as TCCL [1]. shown in subfigures (a) and (b), respectively. Subse-
Thus it is very much significant that, for a given operat- quently, the power at the DFIG wind farm terminal
ing condition, the TCCL provides an exact clue of the (Pdg) is improved (subplot (c)), which is responsible
transient stability margin of the power system. for restraining the electrical and mechanical power

a STRATEGY A STRATEGY B
2
(p.u.)
ym

-2
-6
0 1 2 3 4 5 6 7 8
b
6
(p.u.)

2
yn

-2
0 1 2 3 4 5 6 7 8
c
1
(p.u.)
Pdg

0.5
0
0 1 2 3 4 5 6 7 8
d
2
(Rad/s)
dw 1-4

1
0
-1
0 1 2 3 4 5 6 7 8
Time (s)

Fig. 7 The response of the proposed and conventional controls of the admittance model of the UPFC for a three phase to ground
fault at time t = 2.11 s on the bus 7 of the test system as shown in Fig. 5, with a lower penetration of the DFIG wind farm which is
subjected to a fixed speed of 6.29 m/s, where, a the admittance of the UPFC at bus ‘m’ in p.u., b the admittance of the UPFC at bus
‘n’in p.u., c the active power injection of the DFIG (p.u.), and d the interarea oscillation between the generators ‘1′ and ‘4′
in Rad/s, respectively
Dash et al. Protection and Control of Modern Power Systems (2018) 3:8 Page 9 of 14

a STRATEGY A STRATEGY B
3

(p.u.)
ym
-1
-6
0 1 2 3 4 5 6 7 8
b
3
(p.u.)

1
yn

-4
0 1 2 3 4 5 6 7 8
c
1.5
(p.u.)

1
Pdg

0
0 1 2 3 4 5 6 7 8
d
1.8
(Rad/s)
dw1-4

-1
0 1 2 3 4 5 6 7 8
Time (s)

Fig. 8 The response of the proposed and conventional controls of the admittance model of the UPFC for a three phase to ground
fault at time t = 2.11 s on the bus 7 of the test system as shown in Fig. 5, with a higher penetration of the DFIG wind farm which is
subjected to a fixed speed of 6.29 m/s, where, a the admittance of the UPFC at bus ‘m’ in p.u., b the admittance of the UPFC at bus
‘n’in p.u., c the active power injection of the DFIG (p.u.), and d the interarea oscillation between the generators ‘1′ and ‘4′
in Rad/s, respectively

equilibrium of the nearby generators. This minimizes the TCCL for the proposed control strategies is found
the rotor angular deviation of the generators and out to be 266 ms and 181 ms, for lower and higher
hence stabilizes the MPN, which is reflected in the penetration of DFIG wind farm, which illustrates a
improvement on the interarea oscillation between 17 ms and 20 ms improvement in CCL, respectively,
generators 1 and 4, (DW 1–4 (Rad/s)) as illustrated for the proposed controller (STRATEGY B) in the
in subplot (d), in these figures, respectively. Further, fixed wind speed operation of the DFIG wind farm.

STRATEGY A STRATEGY B
a
4
(p.u.)
ym

-2
-8
0 1 2 3 4 5 6 7 8 9 10

b 8
(p.u.)

2
yn

-4
0 1 2 3 4 5 6 7 8 9 10

c
(p.u.)

1
Pdg

0
-1
0 1 2 3 4 5 6 7 8 9 10

d
2
(Rad/s)
dw1-4

0
-2
0 1 2 3 4 5 6 7 8 9 10
Time (s)

Fig. 9 The response of the proposed and conventional controls of the admittance model of the UPFC for a three phase to
ground fault at time t = 1.47 s (operating point ‘A’) on the bus 7 of the test system as shown in Fig. 5, with a lower penetration
of the DFIG wind farm which is subjected to a variable wind speed (Fig. 6), where, a the admittance of the UPFC at bus ‘m’ in
p.u., b the admittance of the UPFC at bus ‘n’in p.u., c the active power injection of the DFIG (p.u.), and d the interarea oscillation
between the generators ‘1′ and ‘4′ in Rad/s, respectively
Dash et al. Protection and Control of Modern Power Systems (2018) 3:8 Page 10 of 14

STRATEGY A STRATEGY B
a 5

(p.u.)
ym 0
-5
0 1 2 3 4 5 6 7 8
b
6
(p.u.)
yn

1
-5
0 1 2 3 4 5 6 7 8
c
2
(p.u.)
Pdg

1
0
-1
0 1 2 3 4 5 6 7 8
d
2
(Rad/s)
dw 1-4

0
-2
0 1 2 3 4 5 6 7 8
Time (s)

Fig. 10 The response of the proposed and conventional controls of the admittance model of the UPFC for a three phase to
ground fault at time t = 0.75 s (operating point ‘B’) on the bus 7 of the test system as shown in Fig. 5, with a lower penetration
of the DFIG wind farm which is subjected to a variable wind speed (Fig. 6), where, a the admittance of the UPFC at bus ‘m’ in
p.u., b the admittance of the UPFC at bus ‘n’in p.u., c the active power injection of the DFIG (p.u.), and d the interarea oscillation
between the generators ‘1′ and ‘4′ in Rad/s, respectively

5.2 Performance of the control strategies of the UPFC in verified for the stability enhancement of the MPN (Fig. 5)
the DFIG wind farm penetrated two area four machine under both the lower as well as higher level of penetra-
system (Fig. 5) with the DFIG wind farm subjected to tions of the DFIG wind farm, for a three phase fault ini-
variable wind speed tiated on bus 7 at the timing instants ‘A’, ‘B’ ‘C’ and ‘D’,
In this particular case, the robustness in performance of respectively, with a sporadic wind profile input to the
the proposed AFITSMPC for the AM of the UPFC is DFIG wind farm and the results are illustrated in Figs. 9,

STRATEGY A STRATEGY B
a
3
(p.u.)

0
ym

-6
0 1 2 3 4 5 6 7 8 9 10

b
6
(p.u.)

3
yn

-3
0 1 2 3 4 5 6 7 8 9 10
c
2
(p.u.)

1
Pdg

-1
0 1 2 3 4 5 6 7 8 9 10
d
1.8
(Rad/s)
dw1-4

0
-2
0 1 2 3 4 5 6 7 8 9 10
Time (s)

Fig. 11 The response of the proposed and conventional controls of the admittance model of the UPFC for a three phase to
ground fault at time t = 3.05 s (operating point ‘D’) on the bus 7 of the test system as shown in Fig. 5, with a higher penetration
of the DFIG wind farm which is subjected to a variable wind speed (Fig. 6), where, a the admittance of the UPFC at bus ‘m’ in
p.u., b the admittance of the UPFC at bus ‘n’in p.u., c the active power injection of the DFIG (p.u.), and d the interarea oscillation
between the generators ‘1′ and ‘4′ in Rad/s, respectively
Dash et al. Protection and Control of Modern Power Systems (2018) 3:8 Page 11 of 14

a STRATEGY A STRATEGY B
4

(p.u.)
ym
-1
-6
0 1 2 3 4 5 6 7 8 9 10
b
6
(p.u.)

1
yn

-4
0 1 2 3 4 5 6 7 8 9 10
c
2
(p.u.)

1
Pdg

0
-1
0 1 2 3 4 5 6 7 8 9 10
d
2
(Rad/s)
dw1-4

0
-2
0 1 2 3 4 5 6 7 8 9 10
Time (s)

Fig. 12 The response of the proposed and conventional controls of the admittance model of the UPFC for a three phase to
ground fault at time t = 2.5 s (operating point ‘C’) on the bus 7 of the test system as shown in Fig. 5, with a higher penetration
of the DFIG wind farm which is subjected to a variable wind speed (Fig. 6), where, a the admittance of the UPFC at bus ‘m’ in
p.u., b the admittance of the UPFC at bus ‘n’in p.u., c the active power injection of the DFIG (p.u.), and d the interarea oscillation
between the generators ‘1′ and ‘4′ in Rad/s, respectively

10, 11 and 12, respectively. Analogous to the previous enhancing the transient stability of the DFIG wind farm
section, in order to evaluate the TCCL (see Appendix for penetrated two area four machine power system have
details), the performance of the proposed as well as con- been illustrated in Tables 1 and 2 respectively. Form
ventional controls of the AM of the UPFC has been con- these tables, it illustrates the TCCL for both the conven-
stantly observed by gradually increasing the duration of tional and proposed controls as well as the improvement
fault’tf ’ for all the cases discussed in this case. Similar in the TCCL for the proposed control for all the cases dis-
observations as in case of previous case has been ob- cussed in this case, with the lower and higher penetra-
served in this case. For the particular cases illustrated in tion levels of the DFIG, respectively.
these figures, it is observed that for the fault duration re- The improvement in TCCL ranges between 9 ms −
sembling the TCCL for the conventional PI control (where 19 ms in the lower DFIG wind power penetration case,
the generators loose synchronism in the post fault region), where as it lies between 5 ms − 23 ms for the higher
the performance of the proposed AFITSMPC for the AM DFIG wind power penetration case. Thus as the
of the UPFC is very much stable there is drastic improve- proposed AFITSMPC for the AM of the UPFC illustrates
ment in the TCCL, which is evident in the subfigures (a) to an improved result in terms of damping out the
(d) in the Figs. 9, 10, 11 and 12, respectively. oscillations between the generators of the multimachine
A detailed quantitative analysis of the proposed power system for a number of intrinsic operating
STRATEGY B, i.e., Adaptive Fractional Integral terminal conditions, hence it guarantees the robustness of the
sliding mode Power control (AFITSMPC) for the AM of method and also the applicability of the method in real
the UPFC over the conventional STRATEGY A, for time applications (which is considered as a future work
demonstrating its (proposed controller) robustness in in this paper).

Table 1 Critical Clearing time for the conventional and proposed Table 2 Critical Clearing time for the conventional and proposed
controllers subjected to Lower penetration of DFIG Power controllers subjected to Higher penetration of DFIG Power
Operating TCCLfor STRATEGY A TCCLfor STRATEGY B Improvement in TCCL Operating TCCLfor STRATEGY A TCCLfor STRATEGY B Improvement in TCCL
Points in ms in ms for STRATEGY B in ms Points in ms in ms for STRATEGY B in ms
A 498 514 16 A 391 414 23
B 514 523 09 B 411 426 15
C 485 504 19 C 387 392 05
D 507 521 14 D 355 371 16
Dash et al. Protection and Control of Modern Power Systems (2018) 3:8 Page 12 of 14

6 Discussion the UPFC, in order to damp out the oscillation between


It is observed that from previous two subsections and the generators in a DFIG wind farm penetrated multi-
Figs. 7, 8, 9, 10, 11 and 12, that after the initiation of machine power system is proposed in this paper. Taking
disturbance, the simulation of the overall model (Fig. 5), the critical clearance time (TCCL) as the basis, the per-
illustrates some low frequency oscillations (as in case of formance of the conventional PI is compared with the
the interarea oscillation between the generators 1 and 4) proposed AFITSMPC for the AM of the UPFC. It is ob-
which is uncontrollable. On the contrary, the above served that the adaptive nature of the proposed strategy
simulation with the proposed AFITSMPC for the AM of B is very much significant in maintaining the synchron-
the UPFC, i.e., STRATEGY B, also exhibits some low ism between the generators in the multimachine system
frequency oscillation (as in case of the interarea oscilla- for a larger period of time (TCCL), which is evident by
tion between the generators 1 and 4), which deviates ap- improvement in TCCL for the proposed strategy for al-
proximately between − 2 and 2 Rad/S. But in spite of it, most all the case studies illustrated in the paper. It is
the active power or the reactive power based AFITSMPC also observed that the proposed AFITSMPC for the AM
control of an AM of the UPFC considerably damps out of the UPFC significantly stabilizes the active power out-
the respective inter-area low-frequency oscillations ex- put of the DFIG wind farm. This improves the electric
hibited by the network. In addition, the DFIG wind farm power of the nearby generators, which subsequently im-
is also equipped with the PI control mechanism on ac- proves (diminish) the irrespective rotor angle deviations
tive and reactive powers for both the rotor side as well and hence leads to the stability enhancement of the mul-
as grid side converters [21], which also boosts up in timachine power system. The proposed controllers for
damping the above low frequency interarea oscillations the UPFC has been tested for the stability enhancement
[22]. It is also observed that, [22] illustrates a method by of the MPN for higher and lower penetrations of the
which the low-frequency oscillation modes of the pre- DFIG power, at various operating points, where the
sented power system can be calculated through a low- DFIG wind farm has been subjected to a fixed as well as
frequency oscillation modal analysis combined with the a sporadic wind profile, respectively. It is observed that,
dynamic small signal mathematical models of DFIG with an increase in penetration level of the DFIG, the
wind turbines and synchronous generators, including oscillations shown by its active power in the post fault
their eigenvalues, oscillation frequencies, and damping region increases. In spite of this, the proposed controller
ratios. This is an important and interesting topic which for the AM of the UPFC has outperformed the conven-
will be given full consideration as a future work. tional one, by inheriting larger TCCL, for the DFIG pene-
In addition, the adaptive nature of the controller gains of trated multimachine system, under a number of intrinsic
the proposed AFITSMPC for the AM of the UPFC, is very operating conditions. This has been analyzed in the
much significant in quickly stabilizing the admittance simulation and result section, where the outputs shown
model of the UPFC where the DFIG wind farm in the mul- are satisfactory and vindicates the superiority of the pro-
timachine power system has been subjected to fixed as well posed controller.
as sporadic wind profile. In all the cases, there has been a
significant improvement in the interarea oscillations exhib- 8 Appendix
ited by the MPN by the strategy B, which is justified in sub-
figure (d) of the Figs. 6, 7, 8, 9, 10 and 11, respectively. The a) The dynamic model of the kth synchronous
TCCL for both the strategy A and B have been tabulated generator [19], (k = 1, 2, .., 6) is signified as:
which justifies its improvement for proposed STRATEGY
B for almost all the cases illustrated in this section. Further
it is observed that, with the increase in penetration level of 9
the DFIG wind farm, there is a significant increase in the δ_ k ¼ ωk −ωk0 >
>
>
=
maximum overshoots of the Pdg. In spite of this, the pro- ωk ¼ ξ 1 ½ph Mk −p

Ek  i
= = = ð47Þ
posed AFITSMPC for the AM of the UPFC, in comparison e_ Qk ¼ ξ 2 Δefdk − X dk −X dk I dk þ efdk0 −eqk > >
    >
;
to the conventional PI controller, is very much significant Δ_efdk ¼ ξ 3 K ek V tkref −V tk þ κ k −Δefdk
and robust to enhance the stability of the MPN, subjected
to both the higher and lower level DFIG wind farm pene- where ‘δk’ denotes the angular position of rotor, ‘ωk’ and
tration with fixed as well as sporadic wind profiles sub- ‘ωk0’ are the real and reference angular rotor speed, pMk
jected to different intrinsic operating conditions. and pEk are the mechanical and electrical power output
of the kth synchronous generator, respectively. Xdk , Xqk ,
7 Conclusion X/dk and X/qk denotes the dq- axis synchronous and tran-
An adaptive fractional integral terminal sliding mode sient reactance’s of the kth synchronous generator, re-
power control strategy of the admittance model (AM) of spectively. Efdi is the transient voltage, Vtkre fand Vtk are
Dash et al. Protection and Control of Modern Power Systems (2018) 3:8 Page 13 of 14

the reference and actual terminal voltage of the kth syn- and coordition of the various sections of the manuscript.. Author S.P.Mishra did
chronous generator, respectively. e/di, e/qi, I/di, and I/qi de- some simulations and provided data and took part in revising the paper.. All
authors read and approved the final manuscript.
notes the dq- axis terminal current and voltage of the kth
synchronous generator, respectively.
Competing interests
Main parameters of synchronous generator are as The authors declare that they have no competing interests.” Also no fund is
follows: received from any financial or non-financial organization.
Stator leakage reactance (× 1): 0.2 p.u., Stator re-
Author details
sistance (Rs): 1
Siksha O Anusandhan University, Khandagiri Square, Bhubaneswar, Odisha
0.0025 p.u., Synchronous reactance of d-axis (xd): 1.8 751030, India. 2GMR Institute of Technology, Rajam, Andhra Pradesh 532127,
p.u., Transient reactance of d-axis (x/d): 0.3 p.u., Sub India.
transient reactance of d-axis (x// d ):0.25 p.u., Synchronous Received: 22 August 2017 Accepted: 31 January 2018
reactance of q-axis (xq): 1.7 p.u., Transient reactance of
q-axis (x/q): 0.55 p.u., Sub-transient reactance of q-axis
/
(x//
q ):0.25 p.u., Transient time constant of d-axis (Td): 8 s, References
//
Sub-transient time constant of d-axis (Td ): 0.03 s, Tran- 1. Mitra, A., & Chatterjee, D. (2016). Active power control of DFIG-based wind
sient time constant of q-axis (T/q): 0.4 s, Sub-transient farm for improvement of transient stability of power systems. IEEE
Transactions on Power Systems, 31(1), 82–93.
time constant of q-axis (T// q ): 0.05 s. 2. Lei, X., Lerch, E. N., & Povh, D. (2001). Optimization and coordination of
Main parameters of the aggregated DFIG-based wind damping controls for improving system dynamic performance. IEEE
farm: Transactions on Power Systems, 16(3), 473–480.
3. Wang, H. (2000). A unified model for the analysis of FACTS devices in
Rated voltage: 690 V, Stator resistance Rs: 0.00706 damping power system oscillations. III. Unified power flow controller. IEEE
p.u., Stator leakage reactance Xs: 0.171 p.u., Rotor Transactions on Power Delivery, 15(3), 978–983.
resistance Rr 0.005 p.u., Rotor leakage reactance Xrl: 4. Noroozian, M., Angquist, L., Ghandhari, M., & Andersson, G. (1997).
Improving power system dynamics by series-connected FACTS devices. IEEE
0.156 p.u., Magnetizing reactance Xm: 2.9 p.u., Inertia Transactions on Power Delivery, 12(4), 1635–1641.
constant of equivalent generator Hg: 0.94 s, Inertia 5. Azbe, V., Gabrijel, U., Povh, D., & Mihalic, R. (2005). The energy function of a
constant of equivalent wind turbine Hw: 4.93 s, Tor- general multimachine system with a unified power flow controller. IEEE
Transactions on power systems, 20(3), 1478–1485.
sional stiffness of equivalent drive-train Ks: 0.5 p.u./ 6. Zadehbagheri, M., Ildarabadi, R., & Nejad, M. B. (2014). Review of the UPFC
el.rad. rI = 0.04, xI = 0.2, cdc = 0.1. different models in recent years. International Journal of Power Electronics
Wind Turbine data: ρair = 1.225 Kg/m3, rblade = 58.6 m, and Drive Systems, 4(3), 343–355.
7. Dash, P. K., Morris, S., & Mishra, S. (2004). Design of a nonlinear variable-gain
ωt = 0.8, ωS = 1, fuzzy controller for FACTS devices. IEEE transactions on control systems
technology, 12(3), 428–438.
μ2 μ2 μ9
cPP ¼ μ1  ½ − 8. Zhang, X. P., Rehtanz, C., & Pal, B. (2012). Flexible AC transmission systems:
λPP þ βAIR μ8 βAIR 3 þ 1 ð48Þ modelling and control. New York: Springer, Science & Business Media, ISBN:
μ2
μ5 978-3-642-28240-9.
−μ3 βAIR −μ4 βAIR ‐μ6   e λPP þβAIR μ8
þ μ10 9. Mishra, S., Dash, P. K., & Panda, G. (2000). TS-fuzzy controller for UPFC in a
multimachine power system. IET Gener Transm Distrib, 147(1), 15–22.
whereμ1 =0.22,μ2 =116,μ3 =0.4,μ4 =0,μ5 =0,μ6 =5,μ7 =12.5, 10. Nayeripour, M., Narimani, M. R., Niknam, T., & Jam, S. (2011). Design of
μ8 = 0.08,μ9 = 0.035andμ10 = 0. sliding mode controller for UPFC to improve power oscillation damping.
Applied Soft Computing, 11(8), 4766–4772.
11. Morris, S., Dash, P. K., & Morris, E. (2006). A PSO-based neuro-sliding mode
The values of the parameter of the proposed controller for the stability enhancement of power systems with UPFC 5th
controller: World Scientific and Engineering Academy and Society (WSEAS)
International Conference on Circuits, Systems, Electronics, Control & Signal
α1 ¼ 0:1; α2 ¼ 1:0; β1 ¼ 0:6; β2 ¼ 0:6; βProbV Processing (pp. 122–122).
12. Dadras, S., & Momeni, H. R. (2012). Fractional terminal sliding mode control
¼ 0:1; βQrobV ¼ 8; βProbA ¼ 0:1; βQrobA ¼ 10: design for a class of dynamical systems with uncertainty. Communications in
Nonlinear Science and Numerical Simulation, 17(1), 367–377.
The values of the parameter of conventional PI con- 13. Shotorbani, A. M., Ajami, A., Zadeh, S. G., Aghababa, M. P., & Mahboubi, B.
troller for DFIG: (2014). Robust terminal sliding mode power flow controller using unified
power flow controller with adaptive observer and local measurement. IET
Generation, Transmission & Distribution, 8(10), 1712–1723.
K Pdr ¼ 0:1; K Idr ¼ 150; K Pid ¼ 0:5; K Iiq ¼ 200: 14. Huang, H., & Chung, C. Y. (2012). Coordinated damping control design for
DFIG-based wind generation considering power output variation. IEEE
The values of the parameter of conventional PI con- Transactions on Power Systems, 27(4), 1916–1925.
troller for AM of UPFC: 15. Ghosh, S., Kamalasadan, S., Senroy, N., & Enslin, J. (2016). Doubly fed
induction generator (DFIG)-based wind farm control framework for primary
K Pym ¼ 1; K Iym ¼ 1150; K Pyn ¼ 4:35; K Iyn ¼ 1200: frequency and inertial response application. IEEE Transactions on Power
Systems, 31(3), 1861–1871.
16. Miao, Z., Fan, L., Osborn, D., & Yuvarajan, S. (2009). Control of DFIG-based
Authors’ contributions wind generation to improve interarea oscillation damping. IEEE Transactions
Author RKP designed the Adaptive fractional sliding mode algorithm for the on Energy Conversion, 24(2), 415–422.
DFIG wind farm with UPFC along with some simulations. Author P.K.Dash 17. Zhu, X., Genton, M. G., Gu, Y., & Xie, L. (2014). Space-time wind speed
conceived the original problem for detailed study along with results verification forecasting for improved power system dispatch. TEST, 23(1), 1–25.
Dash et al. Protection and Control of Modern Power Systems (2018) 3:8 Page 14 of 14

18. Pahn, T., Rolfes, R., & Jonkman, J. (2017). Inverse load calculation procedure
for offshore wind turbines and application to a 5-MW wind turbine support
structure. Wind Energy, 20(7), 1171–1186.
19. Kundur, P. (1994). In N. J. Balu & M. G. Lauby (Eds.), Power system stability
and control. New York: McGraw-hill.
20. Martins, F. G. (2005). Tuning PID controllers using the ITAE criterion.
International Journal of Engineering Education, 21(5), 867–873.
21. Patnaik, R. K., & Routray, S. K. (2015). Damping of interarea oscillations of a
wind farm based multimachine power system using an unified power flow
controller. Bhubaneswar: IEEE Power, Communication and Information
Technology Conference (PCITC) (pp. 458–464). IEEE.
22. Li, H., Liu, S., Ji, H., Yang, D., Yang, C., Chen, H., Zhao, B., Hu, Y., & Chen, Z.
(2014). Damping control strategies of inter-area low-frequency oscillation for
DFIG-based wind farms integrated into a power system. International
Journal of Electrical Power & Energy Systems, 61, 279–287.

You might also like