You are on page 1of 12

This document is exclusive property of Simon Carves India Limited.

It is to be used only for the purpose which it is lent and must not be copied or used in any way detrimental to the interest DEPARTMENT PROCEDURE Page 1 of 12
FOR
POWER CALCULATION Rev. No. 0
Simon Carves India Limited

Document No. 06-WI-01-DP-15

DEPARTMENT PROCEDURE

FOR

POWER CALCULATION
of this company and subject to return on demand

0 12-02-08 Issued for Implementation ALB GSS GSS

Rev
Date Description of revision Prepared By Checked By Approved By
No.
This document is exclusive property of Simon Carves India Limited. It is to be used only for the purpose which it is lent and must not be copied or used in any way detrimental to the interest DEPARTMENT PROCEDURE Page 2 of 12
FOR
POWER CALCULATION Rev. No. 0
Simon Carves India Limited

Document No. 06-WI-01-DP-15

TABLE OF CONTENTS

Clause Description Page No.


No.

1 Purpose 3

2 Scope 3

3 Responsibility and Authority 3

4 Reference 3

5 Abbreviations 3

6 Procedure 3

7 Records 4

8 Flow chart 4

9 Enclosure 4
of this company and subject to return on demand
This document is exclusive property of Simon Carves India Limited. It is to be used only for the purpose which it is lent and must not be copied or used in any way detrimental to the interest DEPARTMENT PROCEDURE Page 3 of 12
FOR
POWER CALCULATION Rev. No. 0
Simon Carves India Limited

Document No. 06-WI-01-DP-15

1.0 Purpose

The purpose of this procedure is to provide guidelines for calculation of power


consumption for instrumentation items including DCS, PLC and field
instruments such as flow meters.

2.0 Scope

This document provides guidelines for estimating power consumption for


various instrument items including DCS, Analyser systems. This power
consumption shall be used for initial sizing of UPS for instrument items by
Electrical department. However this value must be cross checked with actual
power consumption after finalization of DCS and other Vendors.

3.0 Responsibility and Authority

Lead Engineers is responsible to thoroughly check and discuss with Vendors


any large variations from these estimates before taking any corrective actions
by informing to respective departments.

4.0 Reference

• SCIL-06-WI-01 Work instruction for Instrumentation &


Telecommunication
• SCIL-06-WI-02 Work instruction for Instrumentation Basic
Engineering
• SCIL-19-QSP-03 Quality system procedure for Control of
Records

Reference shall be made to the following standards and codes to the


applicable sections in addition to this specification requirement.

6-52-55 Standard Specifications of DCS


of this company and subject to return on demand

Latest edition of the above standards are applicable

5.0 Abbreviations

DCS Distributed control system


PLC Programmable Logic Controller
UPS Uninterrupted power supply

6.0 Procedure

6.1 The following estimations may be used to calculate maximum power


consumption/heat dissipation of various items being specified for DCS, PLC
This document is exclusive property of Simon Carves India Limited. It is to be used only for the purpose which it is lent and must not be copied or used in any way detrimental to the interest DEPARTMENT PROCEDURE Page 4 of 12
FOR
POWER CALCULATION Rev. No. 0
Simon Carves India Limited

Document No. 06-WI-01-DP-15

being located in control room. For items not listed, reputed vendor catalogues
may be considered.

6.2 This information is required by the Electrical Department for the procurement
of UPS.

6.3 In case UPS forms a part of DCS material requisition, same guidelines shall
be used for initial estimates. UPS sizing factor and surge current
requirements must be finalized with DCS/UPS Vendor before finalizing UPS
size.

7.0 Records
Documents are maintained as per Quality system Procedure for Control of
Records (SCIL-19-QSP-03)

8.0 Flow Chart


N/A

9.0 Enclosure

Annexure - 1 : Power Consumption for PLC System


Annexure - 2 : Power Consumption for SCADA System
Annexure - 3 : Power Consumption for DCS System
Annexure - 4 : Power Consumption for Package Units
Annexure - 5 : Power Consumption for Field Instruments
Annexure - 6 : Power Consumption for Other Instruments
Annexure - 7 : Power Consumption for Telecom
Annexure - 8 : Power Consumption for Tank Gauging System
of this company and subject to return on demand
This document is exclusive property of Simon Carves India Limited. It is to be used only for the purpose which it is lent and must not be copied or used in any way detrimental to the interest DEPARTMENT PROCEDURE Page 5 of 12
FOR
POWER CALCULATION Rev. No. 0
Simon Carves India Limited

Document No. 06-WI-01-DP-15

ANNEXURE – 1

POWER CONSUMPTION FOR PLC SYSTEM

UNIT POWER
S.NO INSTRUMENTS CONSUMPTION
(W)
1 PLC(Programmable logic controller)
1.1 Processor sub system
1.1.1 Single Processor 300
1.1.2 Dual Processor 675
1.1.3 Triple Modular Redundant 210
Operator/ Engineering Work station 300
1.2 I/O Sub System
1.2.1 I/P Module( 16 input) 4.5
1.2.2 O/P Module( 16 output) 4.5
1.3 PLC Console
1.3.1 CRT and Printer 1000
1.3.2 Serial I/O communication module (2) 70
1.3.3 Power Supplies 60
of this company and subject to return on demand
This document is exclusive property of Simon Carves India Limited. It is to be used only for the purpose which it is lent and must not be copied or used in any way detrimental to the interest DEPARTMENT PROCEDURE Page 6 of 12
FOR
POWER CALCULATION Rev. No. 0
Simon Carves India Limited

Document No. 06-WI-01-DP-15

ANNEXURE - 2:

POWER CONSUMPTION FOR SCADA SYSTEM

UNIT POWER
S.NO INSTRUMENTS CONSUMPTION
(W)
1 SCADA System
1.1 SCADA Servers 1440
1.2 SCADA Servers LCD Monitor 100
1.3 SCADA MMI W/S 500
1.4 MMI LCD Monitor 100
1.5 APPS Server 1000
1.6 APPS LCD Monitor 100
1.7 GPS 5
1.8 Web Server 500
1.9 Web Server LCD Monitor 100
1.10 Main Firewall Proxy PC 500
1.11 Ethernet Switch 30
1.12 Rear Projection System 1300
1.13 WAN Router 140
1.14 Firewall Router 140
1.15 Line Switching Unit 160
1.16 Terminal Servers 40
1.17 SCADA Cabinet 50
1.18 Power Distribution Cabinet 50
of this company and subject to return on demand

1.19 B/W LaserJet Printer 600


1.20 Color Laserjet Printer 1000
This document is exclusive property of Simon Carves India Limited. It is to be used only for the purpose which it is lent and must not be copied or used in any way detrimental to the interest DEPARTMENT PROCEDURE Page 7 of 12
FOR
POWER CALCULATION Rev. No. 0
Simon Carves India Limited

Document No. 06-WI-01-DP-15

ANNEXURE - 3:

POWER CONSUMPTION FOR DCS SYSTEM

UNIT POWER
S.NO INSTRUMENTS CONSUMPTION
(W)
1 DCS System
1.1 Controller sub system 1500
1.2 Console sub system
1.2.1 One operator console 1500
1.2.2 Two operator console 1750
1.2.3 Three operator console 1115
1.2.4 Four operator console 3158
1.3 Engineering console 1150
1.4 Network interface unit 500
1.5 Printer 75
1.6 Hard copier 686
1.7 Assignable recorder 45
1.8 Marshalling cabinet 800
of this company and subject to return on demand
This document is exclusive property of Simon Carves India Limited. It is to be used only for the purpose which it is lent and must not be copied or used in any way detrimental to the interest DEPARTMENT PROCEDURE Page 8 of 12
FOR
POWER CALCULATION Rev. No. 0
Simon Carves India Limited

Document No. 06-WI-01-DP-15

ANNEXURE - 4:

POWER CONSUMPTION FOR PACKAGE UNITS

UNIT POWER
S.NO INSTRUMENTS CONSUMPTION
(W)
1 Package Units
1.1 Air Compressors 750
1.2 Cooling Tower 500
1.3 DM Plant (with PLC) 3000
1.4 WWTP (Waste Water Treatment Plant) 1000
1.5 Air Separation Plant (with DCS) 11000
1.6 Fire Water system 500
1.7 Reciprocating Compressor 1000
1.8 Centrifugal Compressor 1500
1.9 Turbine compressor panel 1500
1.10 Instrument air dryer control panel 500
1.11 Fire Water System Control Panel 1100
1.12 HVAC Control Panel 1000
1.13 Turbine Generator Panel 1500
1.14 Load Shed Panel 1500
1.15 Aviation Obstruction Light 750
of this company and subject to return on demand
This document is exclusive property of Simon Carves India Limited. It is to be used only for the purpose which it is lent and must not be copied or used in any way detrimental to the interest DEPARTMENT PROCEDURE Page 9 of 12
FOR
POWER CALCULATION Rev. No. 0
Simon Carves India Limited

Document No. 06-WI-01-DP-15

ANNEXURE - 5:

POWER CONSUMPTION FOR FIELD INSTRUMENTS

UNIT POWER
S.NO INSTRUMENTS CONSUMPTION
(W)
1 Field Instruments
1.1 Magnetic Flow Meter 40
1.2 Mass Flow Meter 15
1.3 Load Cell 50
1.4 Servo Level Instrument 100
1.5 Turbine Meter 5
1.6 Batch Controller 160
of this company and subject to return on demand
This document is exclusive property of Simon Carves India Limited. It is to be used only for the purpose which it is lent and must not be copied or used in any way detrimental to the interest DEPARTMENT PROCEDURE Page 10 of 12
FOR
POWER CALCULATION Rev. No. 0
Simon Carves India Limited

Document No. 06-WI-01-DP-15

ANNEXURE - 6:

POWER CONSUMPTION FOR OTHER INSTRUMENTS

UNIT POWER
S.NO INSTRUMENTS CONSUMPTION
(W)
1 Other Instruments
1.1 RTD To Voltage Convertor 11
1.2 Alarm Unit 8
1.3 Distributor 14
1.4 Programmable Recorder(1 pen/1 pen/3 pen) 10/13/16
1.5 Hybrid Recorder 60
1.6 Gas Chromatograph 1100
1.7 Zirconium oxygen analyzer 860
1.8 ph Analyser 3
1.9 Turbidity transmitter 15
1.10 Chlorine analyzer 15
1.11 Operator station 710
1.12 Stacked operator station 850
1.13 Operator console 340
1.14 Stacked operator console 680
1.15 Engineering station 850
1.16 Terminal board cabinet 1760
1.17 Serial printer 350
1.18 Color hard copier 350
of this company and subject to return on demand

1.19 Duplexed field control station 1950


1.20 Communication gateway unit 500
1.21 Field gateway unit 100
1.22 Addressable Fire Alarm Panel 500
1.23 Condition Monitoring system panel 1500
1.24 Burner Management Panel 500
This document is exclusive property of Simon Carves India Limited. It is to be used only for the purpose which it is lent and must not be copied or used in any way detrimental to the interest DEPARTMENT PROCEDURE Page 11 of 12
FOR
POWER CALCULATION Rev. No. 0
Simon Carves India Limited

Document No. 06-WI-01-DP-15

ANNEXURE - 7:

POWER CONSUMPTION FOR TELECOM

UNIT POWER
S.NO INSTRUMENTS CONSUMPTION
(W)
1 Telecom
1.1 Trunk radio cabinet 1000
1.2 Telecom cabinet 1000
1.3 PABX cabinet 1000
1.4 Tropo radio cabinet 1000
1.5 VSAT Hub cabinet 1500
1.6 CCTV cabinet 1500
1.7 workstation 300
1.8 Server 300
1.9 Switch 50
1.10 multiplexer 60
1.11 Router 50
1.12 Modem 50
1.13 FO converter 50
1.14 Fiber to Coaxial converter for CCTV 50
1.15 Outdoor telephone 5
1.16 Inter com telephone 3
1.17 CCTV camera 100
of this company and subject to return on demand
This document is exclusive property of Simon Carves India Limited. It is to be used only for the purpose which it is lent and must not be copied or used in any way detrimental to the interest DEPARTMENT PROCEDURE Page 12 of 12
FOR
POWER CALCULATION Rev. No. 0
Simon Carves India Limited

Document No. 06-WI-01-DP-15

ANNEXURE - 8:

POWER CONSUMPTION FOR TANK GAUGING SYSTEM

UNIT POWER
S.NO INSTRUMENTS CONSUMPTION
(W)
1 Tank gauging system
1.1 Tank Gauging system cabinet 1000
1.2 Tank Gauging Work station 300
1.3 Metering System Cabinet 1500
1.4 Metering Work station 300
1.5 Metering Remote I/O Cabinet 500
1.6 Tank Gauging Radar Transmitter 100