5 Means Of Identifying Grounded Conductors (By NEC 200


Article)
Google+

5 Means Of Identifying Grounded Conductors By NEC 200 Article (photo credit: inspectorsjournal.com)

Determining grounded conductors // NEC 200


Latest NEC requirements state at least five means of identifying grounded conductors. So, let’s go through each of
them //

1. Sizes 6 AWG or smaller


2. Sizes 4 AWG or larger
3. Flexible cords
4. Grounded conductors of different systems
5. Grounded conductors of multiconductor cables
1. Sizes 6 AWG or Smaller

An insulated grounded conductor of 6 AWG or smaller must be identified by one of the following means //

1. A continuous white outer finish.


2. A continuous gray outer finish.
3. Three continuous white or gray stripes along the conductor’s entire length on other than green insulation.
4. Wires that have their outer covering finished to show a white or gray color but have colored tracer threads in
the braid identifying the source of manufacture must be considered as meeting the provisions of this section.
5. The grounded conductor of a mineral-insulated, metal-sheathed cable (Type MI) must be identified at the time
of installation by distinctive marking at its terminations.
6. A single-conductor, sunlight-resistant, outdoor-rated cable used as a grounded conductor in photovoltaic power
systems, as permitted by 690.31 (article about permitted wiring methods), must be identified at the time of
installation by distinctive white marking at all terminations.
7. Fixture wire must comply with the requirements for grounded conductor identification as specified in 402.8 (see
below)
8. For aerial cable, the identification must be as above, or by means of a ridge located on the exterior of the cable
so as to identify it.

Article 402.8 Grounded Conductor Identification – Fixture wires that are intended to be used as
grounded conductors must be identified by one or more continuous white stripes on other than green
insulation.

Go back to means list ↑

2. Sizes 4 AWG or Larger

An insulated grounded conductor 4 AWG or larger must be identified by one of the following means //

1. A continuous white outer finish.


2. A continuous gray outer finish.
3. Three continuous white or gray stripes along the conductor’s entire length on other than green insulation.
4. At the time of installation, by a distinctive white or gray marking at its terminations. This marking must encircle
the conductor or insulation.

Go back to means list ↑

3. Flexible Cords

An insulated conductor that is intended for use as a grounded conductor, where contained within a flexible cord, must
be identified by a white or gray outer finish or by methods permitted by 400.22.

400.22 – Grounded Conductor Identification // One conductor of flexible cords that is intended to be used as a
grounded circuit conductor must have a continuous marker that readily distinguishes it from the other conductor or
conductors. The identification must consist of one of the methods indicated in 400.22(1) through (6) as shown below //

1. Colored Braid
2. Tracer in Braid
3. Colored Insulation
4. Colored Separator
5. Tinned Conductors
6. Surface Marking

Go back to means list ↑

4. Grounded Conductors of Different Systems

Where grounded conductors of different systems are installed in the same raceway, cable, box, auxiliary gutter, or
other type of enclosure, each grounded conductor must be identified by system.

Identification that distinguishes each system grounded conductor must be permitted by one of the following
means //

1. One system grounded conductor must have an outer covering conforming to 200.6(A) or (B).
2. The grounded conductor(s) of other systems must have a different outer covering conforming to 200.6(A) or
200.6(B) or by an outer covering of white or gray with a readily distinguishable colored stripe other than
green running along the insulation.
3. Other and different means of identification as allowed by 200.6(A) or (B) that will distinguish each
system grounded conductor.

The means of identification must be documented in a manner that is readily available or must be
permanently posted where the conductors of different systems originate.

Go back to means list ↑

5. Grounded Conductors of Multiconductor Cables

The insulated grounded conductors in a multiconductor cable must be identified by a continuous white or gray
outer finish or by three continuous white or gray stripes on other than green insulation along its entire length.
Multiconductor flat cable 4 AWG or larger must be permitted to employ an external ridge on the grounded conductor.

Exception No. 1 // Where the conditions of maintenance and supervision ensure that only qualified persons service
the installation, grounded conductors in multiconductor cables must be permitted to be permanently identified at their
terminations at the time of installation by a distinctive white marking or other equally effective means.

Exception No. 2 // The grounded conductor of a multiconductor varnished-cloth-insulated cable must be permitted to
be identified at its terminations at the time of installation by a distinctive white marking or other equally effective
means.
Informational Note // The color gray may have been used in the past as an ungrounded conductor. Care should be
taken when working on existing systems.

Go back to means list ↑

Reference // NFPA 70: National Electrical Code (NEC), 2014 Edition ( Purchase Now )