1MRS752551-MTI EN

Technical Information Revision A


Date: 14.02.2003
Written by J.A
Checked by J.K
Approved by A.L

Operation Accuracy of under-and overvoltage protection functions in


REF 541 / 543 / 545 Feeder Protection Terminals and
REX 521 Feeder Protection Relay

This statement is written to clarify the measurement accuracies as stated in the Technical Reference
Manual, Standard Configurations (1MRS 751802-MUM) and Functional Block Descriptions: OV3_
(1MRS752322-MUM) and UV3_ 1MRS752333-MUM) regarding the 3-phase under- and overvoltage
protection in REX 521 and REF 54x feeder terminals.

OPERATION ACCURACIES
The operation accuracy is ± 2.5 % of the set value when Phase-to-Earth voltages are connected to the
terminal and Phase-to-Phase values are internally derived from these values in the terminal. (operation
Mode 3)

The operation accuracy is ± 1 % of the set value when Phase-to-Phase voltages are connected directly to
the terminal. (operaton Mode 1 or 2)

The above values apply when within the frequency range f/fn = 0.95...1.05

FURTHER INFORMATION
For further information please refer to the REX 521 Technical Reference Manual, Standard Configurations
(1MRS 751802-MUM) and Functional Block Descriptions: OV3_ (1MRS752322-MUM) and UV3_
1MRS752333-MUM) and/or contact your local ABB representative.

ABB Oy

Substation Automation Visiting Address Postal Address Telephone Internet


Automation Technology Strömberg Park, P.O. Box 699 +358 10 22 4000 www.abb.fi
Products Muottitie 2 A FIN-65101 Vaasa Telefax e-mail:
Business identity code: FIN-65100 Vaasa FINLAND +358 10 22 41599 first name.last name
0643134-6 FINLAND +358 10 22 41094 Sales @fi.abb.com
Domicile: Helsinki

You might also like