United Insulation, India

AN
NNEXURE
E-1
G
GUARANT
TEED TEC
CHNICAL PARTICUL
P LARS OF
AUXILIARY
A Y TRANSF
FORMERS
S.N. DESCRIPTION UNIT REQUIRED
R PA
ARAMETERS
S REMARKS
S
1 Generral details 20000kVA
1.1 Manuffacturer - United
U Insulaation
Industries
1.2 Place of manufactture - Vadodara
V
1.3 Type designations
s - Indoor (IIn metal
enclossure)
1.4 Appliccable standards IEC 660076
2 Main data
d
2.1 Numb ber of phases s - 3
2.2 Numb ber of windinggs - 2
2.3 Transformer rate ed voltages at rated
frequeency and no--load
high--voltage, prin
ncipal tappin g kV 133.8
high--voltage, extreme plus taapping kV 14.449
high--voltage extrreme minus ttapping kV 13. 11
low voltage
v kV 0.44
2.4 Numb ber of tap on HV-winding - 5 (includingg main tap)
2.5 Ratedd frequency Hz 500
2.6 Short duration se eparate sourrce power
frequeency withstannd voltage, 1 minute
HV winding
w kVrms 38kkV
LV winding
w kVrms 3kkV
2.7 Lightn
ning impulse withstand vvoltage for
HV wiinding kVpeak 95kkV
2.8 Power frequency withstand vvoltage for
HV wiinding kVrms 3kkV
2.9 Transformer con ntinuous th ree-phase
powerr rating on prrincipal tappiing kVA 20000kVA
3.0 Transformer no--load losse es (three
phasee) at rated d voltage, principal
kW 3.999kW
tappin
ng and rated d frequency with IEC
tolerance
3.1 Transformer load losses (75 5°C three-
phasee) at full looad and on n principal kW 15.6775kW
tappin
ng with IEC toolerance
3.2 Maximmum tempera ature rise in wwinding at
rated power, fre equency and d on tap
producing highestt losses (me asured by
°K 800
ance)
resista
3.3 Temperature class s of insulatio
on - Classs F
3.4 Perceent impedan nce voltage at rated
powerr, referred to 75°C and on n principal % 6%
tappin
ng
3.5 Vector group - Dynn11
3.6 Type of cooling - ANN
TKT-AT-03-DS-2702-A Page 2 of 3
S.N. DESCRIPTION UNIT REQUIRED PARAMETERS REMARKS
3.7 Class of insulation
 HV winding - F
 LV winding - F
3.8 Maximum sound pressure level dB(A) 75
3.9 Current Density of HV A/Sq.cm 2.7 A/Sq.cm
3.10 Current Density of LV A/Sq.cm 2.7 A/Sq.cm
3.11 Flux Density 1.69
3.12 CRGO core Grade M4 or better
4.0 Efficiency at rated voltage and rated % %
frequency at tap position with maximum
losses and unity power factor
4.1 At full load 98.98
4.2 at 75% of full load 99.11
4.3 at 50% of full load 99.17
4.4 at 25% of full load 98.96
5.0 Efficiency at rated voltage and rated % %
frequency at tap position with maximum
losses and unity power factor and at 0.8
lagging power factor
5.1 At full load 98.72
5.2 at 75% of full load 98.89
5.3 at 50% of full load 98.97
5.4 at 25% of full load 98.71
6.0 Load at which maximum efficiency % of full 50%
occurs load
7.0 Maximum efficiency at load % 99.17
8.0 Capacitance between windings
8.1 HV winding to earth (pF) (pF) 300 To 400pF(Appox)
8.2 LV winding to earth (pF) (pF)
9.0 Nominal currents at principle
tapping
HV winding A 83.67A
LV winding A 2886.75A
10 No-load current at rated voltage and A 1.6% - 2% of the rated
frequency current
11 Protection class for transformer IP IP 23
housing
12 Weight of complete transformer Kg As per GA drawing
including housing TKT-AT-03-GA-2703-A
13 Overall dimensions of transformer
housing (cubicle)
length mm
width mm
height mm
Note:
1. Wehaveconsideredoffcircuittaplinksinsteadofoffcircuittapchanger.
TKT-AT-03-DS-2702-A Page 3 of 3