Professional Documents
Culture Documents
Pounding
6.1 Introduction
Building pounding issues can arise when structures are built in close
proximity. This becomes a particularly important factor when considering
older existing buildings where setback requirements may not have been in
force at the time of construction and developments maximized the use of the
property.
Damage from adjacency and pounding has been observed in many different
earthquakes and regions. Buildings have been subject to moderate to severe
damage and collapse, causing concern that this type of effect needs to be
better identified as a consideration during rapid visual evaluations.
A number of resources were used to help define and develop the criteria for
pounding in the third edition ofFEMA P-154. The literature available is
relatively new and due to the complexity of the issue sometimes
contradictory. There are, however, sorne basic parameters that can be used to
identify potential problems caused by adjacent buildings pounding together,
such as building separation, alignment of floor and roof levels, height
differences, and end-of-row considerations.
The first edition ofFEMA 155 (FEMA, 1988b) noted that certain site
aspects, such as pounding, comer buildings, and adjacencies, had been used
as identifying criteria in the prior survey methods, and might be useful for
rapid visual screening procedure.
,. s. (pJo.Jd]:
: \ .
LLLU.
There are two basic configurations considered - floor alignments and
building height differences. These conditions, when met, generate factors D 1
and D2 that are further graded according to the severity of the deficiency.
The lesser of D 1 or D2 is then used in the computation of the final grade and
structural performance score.
The D 1 and D2 factors assume the building has a frame structure and allows
for reduction ofthese values if it is a stiff, or shear wall, structure. Figure
6-3 shows a page from the Assessment and Improvement of the Structural
Performance of Buildings in Earthquakes IEP screening form where
pounding is addressed.
The study revealed that there were several factors that appeared to
significantly increase the potential collapse rate including negligible building
separations and multiple adjacent buildings having low effective damping
and large mass. Conditions that appeared to have no discernible effect on
collapse rate included effective periods common to adjacent buildings in a
row and whether the adjacent buildings were modeled as rigid or flexible
diaphragms.
Comment
Factor si 1 0.4 max 0.7 1
Comment
Factor e! 1 0.4 max 0.7 1
Note:
Va/ues given assume the building has a frame structure. For stiff buildings ( eg with shear walls), the effect
of pounding may be reduced by taking the co-efficient to the right ofthe value applicable to frame buildings.
Factor D11 1
Table for Se/ection of Factor D1 Severe Significant lnsignificant
Separation O<Sep<.005H .005<Sep<.01H Sep>.01H
Alignment of Ftoors 1Mthin 20% of Storey Height O. 7 0.8 1
Alignment of Ftoors not 1Mthin 20% of Storey Height 0.4 0.7 0.8
Factor 021 1
Table for Selection of Factor D2 Severe Significant lnsignificant
O<Sep<.005H .005<Sep<.01H Sep>.01H
Height Difference > 4 Storeys 0.4 0.7 1
Height Difference 2 to 4 Storeys 0.7 0.9 1
Height Difference < 2 Storeys 1 1 1
Factor o_ ! ! =
(Set D lesser of D1 and D2 or..
=
set D 1.0 if no prospect of pounding)
3.5 Site Characteristics - (Stability, landslide threat, liquefaction etc)
Effect on Structural Performance Severe Significant lnsignificant
.....................................................................................................................................................................
3.7 Peñormance Achievement Ratio (PAR)
(equals A X B X e X D X E X F ) 1
o Very High seismicity: 1.50% for Level 2 (or 2 inches per story for
Level 1)
o High seismicity: 1.00% for Level 2 ( or 1-1/2 inches per story for
Level 1)
o Moderate seismicity: 0.25% for Level 2 ( or 1/2 inches per story for
Level 1)
o Low seismicity: 0.10% for Level 2 ( or 1/2 inches per story for Level
1)
Typical story heights are approximately 12 feet to 13 feet, but they can
be higher or as low as 9 feet. F or the 13 feet story height, the 1-1 /2" and
1/2" dimensions for Level 1 High and Moderate seismicity, respectively,
are approximately 1.0% and 0.3%. For the 9 feet story height, the 1-1/2"
and 1/2" dimensions are nearly 1.5% and 0.5%. For shallow story
heights, the Level 1 separation requirements are larger ( and more
conservative) than the Level 2 criteria. These values are considerably
smaller than the 4% separation recommendation in ASCE/SEI 41-13, but
somewhat in line with ASCE/SEI 41-13 drift limits for vertical building
elements at Collapse Prevention averaged for all building types for High
seismicity. The rationale for the reduction in Moderately High,
Moderate, and Low seismicity regions recognizes the lower expected
damage thresholds. See Section 6.3.1 for a more detailed explanation.
T < 0.4sec
(6-1)
T 2 0.4sec
where
T = 0.035H080 for FEMA Building Type SI
= 0.018H090 for FEMA Building Type Cl
(6-2)
= 0.032H055 for FEMA Building Types Wl, WlA, W2
Both buildings are assumed to be of the same height and period, but during
SA02 or SAlO shaking, the two buildings aren radians out-of-phase at the
point in time when they both experience maximum displacement (i.e., both
experience their spectral displacement response), and at the time of
maximum displacement they are moving toward each other rather than away.
The buildings can touch if the separation distance is less than or equal to
2Dmax·
In the worst case, the two buildings always reach their Dmax displacement at
the same time in every earthquake, and always in a direction toward each
other. Furthermore, in the worst case, for the two buildings merely to touch
at that moment aggravates collapse. In the best case, the two buildings must
have no initial gap between them for pounding to aggravate damage. Reality
almost certainly lies between these two extremes: the separation must be less
than sorne fraction,f where O <f < 1, of 2Dmax for pounding to occur and be
severe enough to aggravate damage. To estimatef properly, a series oftwo-
or three-dimensional nonlinear dynamic analyses could be performed of
various combinations ofbuildings to find the maximum value off where
pounding occurs and aggravates collapse. Based solely on the authors'
judgment,f is probably less than 0.5, so 0.5 is probably conservative,
meaning it will exaggerate the potential for pounding to aggravate collapse.
Thus, it is assumed here that the collapse probability only significantly
increases if D ::S o.:
H l 3 ft/story x 7 stories = 91 ft
3. They are exactly n radians out-of-phase and moving toward each other at
the moment of maximum displacement, and
4. They are located where SA02 or SAJO are the maximum value for their
seismicity level.
Table 6-2 Minimum Separation Distance for FEMA Building Types W1,
W1 A, W2 as a Percentage of H
Stories
1
Low
1
Mod
I Moderately
High I High
1
Very High
The results in Tables 6-2 through 6-5 indicate that to one significant figure,
the minimum separation distance is fairly independent of height. Thus, for
simplicity, a single threshold separation distance can be used, based on the
largest values shown above ( those of steel moment frame buildings, as
shown in Table 6-4), rounded to a nominal value, as shown in Table 6-6.
6.3.3 Validation
In the 2011 Tohoku earthquake, Okazaki et al. (2013) observed that two 11-
story steel reinforced concrete (SRC) buildings separated by a 1 O-cm gap
(approximately 0.4% separation) "pounded against each other. Despite the
cosmetic damage, the SRC buildings seemed to have suffered minimal
structural damage. At the time of investigation, many residents had retumed
to occupy the building." The buildings are located near Sendai, where Sa(l .O
second, 5%);::::; 0.7g at the nearby station DCRC No 23 was very close to the
high-seismicity value for SM1;::::; 0.8g. These buildings had much less than the
recommended 1.0% separation threshold, experienced motion very close to
the high-seismicity SM1, and survived with only cosmetic damage.