Professional Documents
Culture Documents
12-1-08 Page 20 5
12-1-08 Page 21 3
12-1-08 Page 22 4
12-1-08 Page 23 3
12-1-08 Page 24 3
12-1-08 Page 25 3
USER INTERFACE 8 – 10
Field Terminations 8
Front Panel Indicators 9
Power Connections 10
Front Panel Buttons 10
Battery Replacement 10
Enclosure 10
Cover Removal 10
Strain Relief Installation 10
Mounting 10
SYSTEM PLANNING 11 – 12
Hazard Identification 11
Pre-installation Guidelines 11 – 12
INSTALLATION 13 – 26
Installation Materials 13
Mounting Bracket Installation 13
Mounting to Existing CHECKFIRE SC Bracket 14
Manual/Automatic Actuator Installation 14
and Connection
Mounting Control Module 15
Remote High Level Alarm Installation 15
Shutdown Device Connection 16
Detection Wire Installation 16 – 18
Thermal Detector Installation 18 – 19
Optional Triple IR Flame Detector Installation 19 – 20
Pneumatic/Linear Detector Installation 21
Automatic Actuation Lead Connection 21
External Power Connection 22
Optional Pressure Switch/Electric Pull Station 22
Function Test 22 – 23
Placing the System in Service 24 – 26
SAFETY PRECAUTIONS
12-1-08 Page 1
REV. 1
SAFETY PRECAUTIONS
For the protection of personnel and equipment being installed, this
manual contains WARNING and CAUTION statements which are ! CAUTION
listed in the steps which they apply. These warnings and cautions
are also listed here so that the manual user can become familiar The fire suppression system will discharge dry chemical if the
with them before performing any procedures. cartridge is installed when operating the strike button. Do not
install cartridge unless puncture pin is fully retracted with ring
pin inserted and visual inspection seal installed.
! WARNING
! WARNING
! CAUTION
! CAUTION
! CAUTION
TOTAL SYSTEM DESCRIPTION The control module can be used as a self contained system,
The complete CHECKFIRE SC-N system is composed of compo- powered by its own internal lithium battery. This allows the detec-
nents which are combined to provide automatic fire detection and tion system to operate around-the-clock without use of external
actuation for equipment hazard areas. The electric detection and power. Optionally, external power can be connected to the control
actuation system is designed for use only with ANSUL fire module with the internal power also connected, which results in a
suppression systems requiring pneumatic input as a means of system with battery back-up. When connected to an external
actuation. In addition to the mechanical pneumatic means of oper- 12/24 VDC supply with the internal battery also connected, the
ating the suppression system, the CHECKFIRE SC-N also external power source becomes the primary supply, while the
provides an automatic and manual electric means to perform the internal power source is maintained in a stand-by mode of opera-
same function. tion.
The CHECKFIRE SC-N system is typically used with an ANSUL The control module may be installed where the ambient tempera-
A-101 Vehicle Fire Suppression system for 24-hour protection of ture is between –40 °F to 140 °F (–40 °C to 60 °C).
equipment. The system is particularly suited for the protection of The CHECKFIRE SC-N Detection and Actuation System is
equipment that is subjected to extreme environmental and physi- Approved by FM Approvals.
cal conditions such as vehicles used in forestry, mining, agricul-
ture, construction, public transportation, public utilities, land fill, Circuits
and waste disposal. The first initiating circuit is the supervised detection circuit
Some of its features include linear (wire) and/or spot (thermal), designed to be connected to linear (wire) and/or spot type thermal
flame detection, supervised circuitry, internally powered, detectors that provide a contact closure input to initiate a fire
adjustable shutdown and discharge time delays, auxiliary relays, detected condition. The second initiating circuit is designed to
and one-button operation. accept a contact closure type of actuating device such as an elec-
tric manual pull station or a pressure switch. The initiating circuits
CHECKFIRE SC-N Electric Detection and Actuation System are low impedance and designed to eliminate nuisance alarms
consists of the following components: associated with contact bounce.
1. Control Module
2. Manual/Automatic Actuator Two field programmable time delays provide timing of shutdown
3. Mounting Bracket and release functions associated with the operation of the detec-
4. Detection Wire tion and electric manual pull/ pressure switch initiation circuits.
5. Thermal Detectors 1) DETECTION INITIATING CIRCUIT
6. Pneumatic/Linear Detection
7. Triple IR (IR3) Flame Detector The detection circuit consists of two time delays:
8. Protracting Actuation Device ‘PAD’ (not shown) The first time delay is field programmed to assign the time
9. LT-10-R Cartridge between alarm (initiation of the detection circuit) and the oper-
10. Check Valve (not shown) ation of the shutdown relay. The first time delay is field
11. Remote High Level Alarm (not shown) programmable for 5, 10, 20, or 30 seconds.
12. Release Circuit Test Module (not shown) The second time delay is field programmed to assign the time
between the completion of the first time delay (when the shut-
2 down relay operates) and the operation of the release circuit.
The second time delay is field programmable for 0, 10, 20, or
30 seconds.
1
2) ELECTRIC MANUAL PULL/PRESSURE SWITCH FEED-
BACK INITIATING CIRCUIT
The second initiating circuit is field programmable to be used
3
as either an electric manual pull or pressure switch feedback
circuit. If selected as an electric manual pull circuit, its opera-
tion will override the first time delay function and initiate a
9 second time delay condition, causing the shutdown relay to
immediately operate and system release to occur upon
completion of the second time delay. Additionally, the control
module can be field programmed to shorten the second time
delay when a manual actuation occurs. The time delay options
available with the electric manual actuation are 0, 10, 20, and
4 30 seconds, with the condition that it can only be less than or
6
equal to the programmed time delay of the detection circuit.
5
Selection of the second initiating circuit as a pressure switch
feedback circuit will result in the operation of the alarm relay
002998
and shutdown relay immediately upon receiving the signal.
The release circuit will not be initiated from this feedback
7 circuit because the system will already have been pneumati-
cally actuated from the manual pneumatic actuator.
When this initiating circuit has operated, the Alarm and
Release LEDs, along with the audio sounder, will pulse until
the pressure switch is reset and then the control panel is reset.
SYSTEM COMPONENTS
12-1-08 Page 3
REV. 2
TOTAL SYSTEM DESCRIPTION (Continued) A 1/4 in. NPT street elbow is supplied with the actuator for conve-
Circuits (Continued) nient connection of the 1/4 in. actuation line to the fire suppression
system. See Figure 2.
3) A “DELAY” button is available for the operators use. Operation
SQUIB ACTUATOR,
of the “DELAY” button will restart the first time delay cycle if PART NO. 24479
STRIKE
initiated while the first time delay is active. Once the second BUTTON
time delay has started, operation of the “DELAY” button has RING
PIN
no affect. The “DELAY” button also serves the dual function of
silencing the auxiliary alarm relay. The silence function is only
effective 30 seconds or more after release or pressure switch
feedback operation has occurred.
FIGURE 2b
008220
LT-10-R CARTRIDGE
The LT-10-R cartridge is a pressure vessel that is factory-filled with
nitrogen to 1800 psi at 70 °F (124 bar at 21 °C). The cartridge is
installed in the manual/automatic actuator and provides the pres-
sure required to actuate the connected fire suppression system.
Cartridges requiring DOT (Department of Transportation) approval
only can be ordered as Part No. 13193. Cartridges requiring DOT
FIGURE 1 and TC (Transport Canada) approval can be ordered as Part No.
002755
423423. Following operation, the cartridge must be replaced. See
Figure 3.
MANUAL/AUTOMATIC ACTUATOR
The Manual/Automatic Actuator provides a manual and automatic SAFETY
SHIPPING CAP
means of fire suppression system actuation. There are two models
(Figure 2a and Figure 2b) used with the CHECKFIRE SC-N
Detection and Control System. In an automatic mode of operation,
the model shown in Figure 2a, Part No. 24479, uses a squib to
generate pressure to force the puncture pin down to puncture the CARTRIDGE
LT-10-R Actuation Cartridge. In an automatic mode of operation,
the model shown in Figure 2b, Part No. 435479, uses the mechan-
ical output of a protracting actuation device (PAD) to force the punc-
ture pin down. Manual actuation can be accomplished with either
model by pulling the ring pin and striking the red button. The system
is automatically actuated in either model by an electrical signal
from the CHECKFIRE SC-N Control Module. FIGURE 3
000851
SYSTEM COMPONENTS
12-1-08 Page 4
REV. 4
INSULATED
SPRING STEEL
CONDUCTORS
FIGURE 6
COMBINED BRACKET RETROFIT BRACKET 000855
PART NO. 423525 PART NO. 423531
002756 002757
THERMAL SPOT DETECTOR
Thermal detectors are normally open, contact closure devices. The
fixed temperature design of these detectors will cause the contacts
to close when the temperature of the surrounding air reaches the
set point temperature of the detector. See Figure 7.
CABLE CLAMP
WITHOUT PROTECTIVE
MOUNTING TUBING, PART NO.
BRACKET, 416762
PART NO. CABLE CLAMP WITH
416221 PROTECTIVE TUBING,
PART NO. 416214
SPLICING DEVICE
The In-Line Splice Kit, Part No. 428375, is required for detection
wire connection between the control module and the linear detec-
tion wire or between separate pieces of linear detection cable.
When the splicing device is used in the system, special sealing FIGURE 7
compound is required to make a proper seal. The kit consists of the 000856
necessary number of components to assemble 10 complete Thermal detectors are available in three preset temperatures as
assemblies. See Figure 5. shown below. Each temperature rating is stamped on the detector.
Rated Maximum
Operating Continuous
Temperature Use Temperature Detector
°F (°C) °F (°C) Color Part No.
270 (132) 234 (112) Blue 416218
325 (163) 280 (137) Red 416219
360 (182) 312 (155) Red 416220
SYSTEM COMPONENTS
4-1-07 Page 5
REV. 2
PNEUMATIC/LINEAR DETECTOR
The Pneumatic/Linear Detector, Part No. 416113, consists of 35 ft.
(10.7 m) of gas filled stainless steel tubing connected to a small BRACKET,
PART NO. 434116
pressure responder. When the gas in the tubing heats up, the
increase in pressure operates the responder, thus closing the
detection circuit of the control module. The pneumatic/linear detec-
tor will operate at a temperature of 900 °F (482 °C) over 12 in.
(31 cm) or 300 °F (149 °C) over the total length. The detector
assembly connects to the control module by means of a special
wire assembly which is supplied with the detector assembly. See
Figure 8.
TRIPLE IR (IR3) FLAME
DETECTOR, PART NO. 432035
OR PART NO. 434941
DETECTOR FIGURE 9
006829
TUBE
FIGURE 8
000857
! WARNING
END-OF-LINE RESISTOR
The End-Of-Line Resistor Assembly, Part No. 426520, is required RELEASE CIRCUIT TEST MODULE
for supervision of the external input circuits. The end-of-line resis- The release circuit test module, Part No. 423541, is used in place
tor assembly is available in a package of 10, Part No. 426461. of the Manual/Automatic Actuator during test procedures to simu-
Each package consists of 10 of the required components to late operation of the actuation device. The test module will provide
assemble 10 of the resistor assemblies. See Figure 16. The an indication of whether or not the release signal from the control
package contains an instruction sheet, Part No. 423542, detailing module is of adequate strength to automatically operate the
the assembly requirements. Manual/Automatic Actuator. See Figure 19. When using the
Manual/Automatic Actuator, Part No. 435479, a Protracting
Actuation Device (PAD) Test Adaptor, Part No. 436243, is required
to connect the Protracting Actuation Device to the test module.
LOCK This adaptor is included in the shipping package.
NUT
STRAIN RELIEF
CONNECTOR
TERMINAL BLOCK
WITH 4.7 K OHM
RESISTOR
CAP FIGURE 16
003050
CHECK VALVE
FIGURE 19
The 1/4 in. check valve, Part No. 25627, is installed in the actua- 003015
USER INTERFACE Shut Down Relay Circuit (Terminals No. 14, No. 15, and No. 16)
This section is designed to give the user overall information on all • Cable must be round jacketed, with an OD of 0.13 in. to 0.25 in.,
features and components pertaining to the CHECKFIRE SC-N suitable for the intended usage
Control Module itself. • 3 amp maximum load
• Relay specification: 4A 250VAC, 3A 30VDC resistive
FIELD TERMINATIONS • Normally open, normally closed set of contacts
External Power Circuit (Terminals No. 1 and No. 2) • Form “C” contact arrangement
• 12 to 24 VDC • Contacts shown in normal condition – No. 14 (NO), No. 15
(Common), No. 16 (NC)
• Polarity must be considered – Terminal No. 1 (+), Terminal No. 2
(–) Terminal Block
• 3 amp inline fuse must be used in the positive side • Terminal connections are sized for 12 - 24 AWG
• Cable must be round jacketed, with an OD of 0.13 in. to 0.25 in., • Terminal is labeled from left to right, No. 1 through No. 16
suitable for the intended usage
• The terminals are designed as follows:
Detection Circuit (Terminal No. 3 and No. 4) 1. + Ext. 12/24 VDC Battery
• Cable from splicing device must be round jacketed, with an OD 2. – Ext. 12/24 VDC Battery
of 0.13 in. to 0.25 in., suitable for the intended usage 3. + Detection Input
• Polarity need not be considered 4. – Detection Input
5. + Manual Input
Manual Pull/Pressure Switch Circuit (Terminals No. 5 and
No. 6) 6. – Manual Input
7. + Release Output
• Can be set up for either manual pull input or pressure switch
feedback input 8. – Release Output
• When set up for pressure switch feedback input, operation does 9. Trouble Common
not discharge system 10. Trouble NO
• Polarity need not be considered 11. Alarm NO
• Cable from splicing device must be round jacketed, with an OD 12. Alarm Common
of 0.13 to 0.25 in., suitable for the intended usage 13. Alarm NC
14. Shutdown NO
Release Circuit (Terminals No. 7 and No. 8)
15. Shutdown Common
• Polarity must be considered – Terminal No. 7 (+), Terminal No. 8 16. Shutdown NC
(–)
• 15 ft (4.6 m) maximum cable length between control module and
pneumatic actuator for squib actuation and 20 ft (6.1 m)
maximum cable length for PAD actuation
• Cable from splicing device must be round jacketed, with an OD
of 0.13 to 0.25 in., suitable for the intended usage
Alarm Relay Circuit (Terminals No. 11, No. 12, and No. 13)
• Cable must be round jacketed, with an OD of 0.13 in. to 0.25 in.,
suitable for the intended usage
• 3 amp maximum load
• Relay specification: 4A 250VAC, 3A 30VDC resistive
• Normally open, normally closed set of contacts
• Form “C” contact arrangement
• Contacts shown in non-alarm condition – No. 11 (NO), No. 12
(Common), No. 13 (NC)
USER INTERFACE
7-1-03 Page 9
REV. 1
Battery Trouble (Yellow) The Yellow Release LED and the audio will pulse at a rate of once
every 10 seconds when a trouble condition is detected in the
• LED pulses once every 10 seconds when indicating battery release circuit. The control module will return to normal when the
trouble trouble condition is cleared.
• The yellow battery trouble LED will pulse when a low power The Release Trouble will also pulse after the system has
condition is detected in either of the connected supplies (inter- completed a discharge cycle or a pressure switch feed back signal
nal or external). If only one power source is used, the control has been received. The trouble signal in this condition is used to
module will automatically ignore the unconnected circuit upon indicate a recharge of the fire suppression system is necessary. A
resetting the control module. If a power source is once Release Trouble under either of these conditions can only be
connected and recognized, a subsequent loss of that power cleared by resetting the control module.
source will be recognized as a Battery Trouble condition. If a
power source is once connected, recognized, and then discon- Detection Trouble (Yellow)
nected, the disconnected supply can be ignored by operating
The Yellow Detection Trouble LED and the audio pulse once every
the RESET button.
10 seconds when the control module detects a trouble in the
Power Normal (Green) detection circuit. The control module will automatically return to
normal when the trouble is cleared.
• LED pulses once every 3 seconds when indicating normal
power Sounder (Audio)
• The green Power Normal LED pulses “on” once every 3 seconds The sounder gives the audio indication for all alarm and trouble
indicating power is normal from both sources of input power. If outputs. The sounder will pulse at the same rate as the visual
the power drops below an acceptable level from either the inter- corresponding LED.
nal or external source of input power, the green Power LED will
be extinguished. If only one source of power is used, the green The sounder gives the audio indications of the various outputs.
Power LED will extinguish when the voltage level drops below an The sounder is rated at 85 dB at 2 ft (0.6 m).
acceptable level. The pulse rates are as follows:
per second.
After discharge, the LED and sounder will continue to pulse at GREEN
a rate of 4 times per second for 30 seconds. After that, it will YELLOW
switch to the trouble mode and pulse once every 10 seconds. RED
POWER CONNECTIONS
Internal
The 3.6 VDC internal lithium battery is connected to the control
module by a removable type plug. The battery must be replaced
annually or when the Yellow Battery LED and sounder are pulsing.
A label is attached near the battery mounting location for record-
ing the installation date.
! CAUTION
RESET
DELAY DELAY RESET
BUTTON
Discharged lithium batteries may contain significant amounts BUTTON
of unused energy and should be handled with care. Do not
compact for disposal. Before disposal, each battery must be
fully discharged and electrically isolated by enclosing in a
plastic bag and sealing the bag. Do not dispose of in fire.
Check applicable solid waste disposal regulations for proper
disposal of more than one battery.
FIGURE 22
0002760
External
The external power circuit can be between 12 to 24 VDC. The BATTERY REPLACEMENT
circuit must be fused at the source on the positive line. The exter- • While in use, the battery requires replacement every year or
nal power source is connected to the module terminal block on when the Yellow Battery LED and sounder are pulsing.
terminals No. 1 (+) and No. 2 (–). • The shelf life of the battery is eight (8) years.
Both power sources, internal and external, should be utilized • Control Module contains a label for recording battery replace-
whenever possible. This will always give the fire suppression ment date.
system a battery back-up when one of the sources are removed
for whatever reason. • Make certain used battery is disposed of properly.
HAZARD IDENTIFICATION
Before the CHECKFIRE SC-N Electric Detection and Actuation The CHECKFIRE SC-N control module contains 3 amp 30VDC
System is installed, the hazards to be protected must be identified. shutdown relay contacts to facilitate connection of shutdown
These hazard locations determine where the detection wire or devices recommended by the vehicle manufacturer. Example:
thermal detectors and the fire suppression system nozzles are opening or closing of coolant over-temperature alarm will bring
required. While the agent nozzles in existing fire suppression about properly sequenced engine shutdown on many vehicles.
systems will point out the hazard areas, the following information Consult vehicle manufacturer for details.
should still be reviewed to best determine detection requirements.
If an entire fire suppression/detection system is to be installed, this Alarm Application
information is vital in determining proper placement of discharge Even with an effective fire suppression/detection package, the
nozzles and detection devices. vehicle must be evacuated at the earliest possible moment to
assure passenger and operator safety. Most vehicles tend to be
Fire Hazard Definition very noisy, and on some, the operator cannot see the entire
A fire hazard is any area where an ignition source (high tempera- vehicle and often isn’t aware that a fire exists. Therefore, a high
ture or sparks) and fuel (flammable materials) may be found in decibel alarm should be provided near the operator to signal that
close proximity. the control module has received a detection signal.
Examples of ignition sources are engines, exhaust manifolds and
piping, turbochargers, battery compartments, electrical system PRE-INSTALLATION GUIDELINES
equipment, torque converters, transmissions, hydraulic pumps, Before installing the CHECKFIRE SC-N Electric Detection and
parking brakes, and friction from debris packed around parts. Actuation System, review all of the following information and plan
Occasionally other components may reach high temperatures due (sketch) the system layout. This will help to avoid any unforeseen
to malfunction. The potential danger from these components must installation problems. Once an acceptable layout has been deter-
also be examined during hazard identification. A parking brake left mined, record and keep it for future reference.
engaged is an example of a potential high temperature source. Control Module and Actuator Location
Temperatures in excess of the detection wire or thermal detector
ratings will cause the detection system to activate thereby actuat- 1. The control module and actuator must be mounted in full view
ing the fire suppression system. and accessible to the operator. They must be positioned within
arms reach of the operator to enable manual operation of the
The above mentioned heat sources can cause fire when they red strike button on the manual actuator as well as the “Delay”
come in contact with flammable materials such as leaking fuel: button (to extend time delay) on the front of the control
either broken fuel lines, slow leaks, broken hydraulic lines, or a module.
ruptured fuel tank. Type of Class A materials are part of the vehicle
itself such as electric wiring insulation, padding, plastic parts, the 2. The location must be suitable for bolting or welding if bolting is
packages on the vehicle, or debris due to poor maintenance. impractical. The mounting surface must be flat to avoid strain
These materials can contribute to the rapid buildup or spreading on the mounting bracket.
of fire. 3. There must be room enough to allow for proper wiring connec-
tion to the control module and to install the actuation line from
Other Considerations the fire suppression system to the manual/automatic actuator.
Be aware that the propagation of fire from one area to another Also, the module and actuator should be accessible for peri-
may cause a hazard to be larger than originally determined. Liquid odic inspection and maintenance. The components should be
fuel may spray, splash, or flow carrying the fire some distance from mounted in a location that will not interfere with normal equip-
the starting point. Radiation, sparks, or conduction through metal ment maintenance.
can carry heat to an area where the danger of fire wouldn’t NOTICE
normally exist. The ambient temperature in the mounting envi-
Also, consider the fire history of the equipment being protected or ronment must not fall below –40 °F (–40 °C) nor
of similar equipment. This information may be available through exceed 140 °F (60 °C).
company records or vehicle operators may have had first hand
experience enabling them to identify the locations of previous fires Linear Detection Wire Routing
as well as special hazards such as a hydraulic hose that frequently The preferred method for routing linear detection wire is to begin
ruptures. by connecting the detection wire directly to the CHECKFIRE SC-N
Each hazard that is identified must have both fire suppression control module.
system fixed nozzles and detection wire or thermal detectors. Because linear detection wire need only be routed through the
hazard area, another acceptable routing method is to use
Equipment Shutdown stranded 16 AWG jacketed wiring connected to the control module
Another factor to examine is equipment shutdown. Provisions and routed to the beginning of the hazard area(s). At that point, a
should be made to shut down any components that could possibly splicing device, Part No. 428375, can be used to make the proper
add to the intensity of the fire (fuel pumps, hydraulic pumps, connection between the stranded 16 AWG jacketed wire and the
engine, etc.) or any components that could possibly re-ignite the start of the linear detection wire. This method can only be used
fire once it has been suppressed (battery, electrical system). when the splicing device can be adequately protected from
Although a properly installed fire suppression/detection system is damage and moisture.
the primary means of protecting equipment from fire, an effective
fire protection package also includes provisions for equipment
shutdown.
SYSTEM PLANNING
6-30-05 Page 12
REV. 2
INSTALLATION
Before installing the detection and actuation system, the System
Planning portion of this manual should have been reviewed for
particular application resulting in a system layout sketch. Always
read the procedure before installing each component to become
familiar with the correct installation steps as they apply to the
particular application and sketch.
NOTICE
For ease of installation, the fire suppression
system should be installed before the detection
and actuation system.
INSTALLATION MATERIALS
All hardware and tools should be on hand before beginning the
installation. Check the Component Index, Pages 38-39, to make FIGURE 23
certain all necessary system components are available. 002761
Bolting
1. Using the bracket as a template, carefully mark the location of
the bracket mounting holes.
2. Center punch the premarked hole locations and drill 3/8 in.
(10 mm) holes through the mounting surface.
3. Secure the bracket to the mounting surface using appropriate
length of 5/16 in. (8 mm) bolts with flat washers, lockwashers,
and nuts. See Figure 23.
INSTALLATION
12-1-08 Page 14
REV. 2
ACTUATION
LINE OUTLET
JAM NUT
FIGURE 26b
008223
NUTS AND BOLTS INCLUDED Installing The Fire Suppression System Actuation Line
WITH RETROFIT BRACKET
FIGURE 25 Install 1/4 in. actuation hose from lower outlet on actuator to
002763 pneumatic actuator on fire suppression system using a check
valve at the intersection of each actuation device branch line. See
MANUAL/AUTOMATIC ACTUATOR INSTALLATION AND Figure 27.
CONNECTION The CHECKFIRE SC-N System output (using LT-10-R cartridge)
can pressurize up to 125 lineal ft (38.1 m) of 1/4 in. actuation line
Mounting
with up to eight tanks and/or accessories. Check valves are used
1. Remove jam nut from lower threads of actuator and slide actu- to protect against pressure loss if one or more actuator cartridges
ator through hole in mounting bracket. are removed or damaged; and by isolating each branch line, they
2. Rotate the Manual/Automatic Actuator so that the actuation reduce the overall lineal length of actuation line.
line outlet is accessible from the front.
With the actuation outlet accessible from the front, the squib ! CAUTION
inlet port on the Manual/Automatic Actuator, Part No. 24479
(see Figure 26a), or the terminal housing on Manual/Auto- The fire suppression system could be accidentally actuated
matic Actuator, Part No. 435479 (see Figure 26b), would be causing the release of agent if the Manual/Automatic Actuator
on the right side adjacent to the control module. and/or the nitrogen cartridge is installed before the appropriate
installation step is reached.
3. Reinstall jam nut and tighten firmly. (See Figure 26.)
4. Install ring pin but do not attach seal at this time.
DETECTION AND
ACTUATION
SYSTEM
100 FT
(30.5 m)
SQUIB PORT
ACTUATION
CHECK LINE
VALVES
PRESSURE
RELIEF
25 FT VALVE
ACTUATION LINE (7.6 m)
OUTLET
ACTUATION
JAM NUT LINE
100 FT
(30.5 m)
FIRE
MANUAL SUPPRESSION
ACTUATOR SYSTEM
FIGURE 26a
002764
FIGURE 27
002772
INSTALLATION
7-1-03 Page 15
REV. 1
FIGURE 28
000868
INSTALLATION
4-1-07 Page 16
REV. 4
FIGURE 30 ! CAUTION
000870
FIGURE 31
000871
CABLE TIE
(PART NO. 56991)
RUBBER SLEEVE
(PART NO. 56692)
FIGURE 32
006847
INSTALLATION
4-1-07 Page 17
REV. 4
DETECTION WIRE INSTALLATION (Continued) To properly install the thermal detector, complete the following:
Wiring (Continued) 1. Secure the mounting bracket(s) near the hazard. Make certain
2. Route the detection wire through a strain relief at the bottom the bracket does not shield the detector from the heat or
of the SC-N control module, to the terminal strip in the control flame.
module. Make certain wire is not exposed to damage. See 2. Attach the correct temperature range spot detector to the
Figure 34. bracket using (2) two flatwashers and (2) two 1/4-20 x 5/8 in.
3. On the terminal block at the control module, install the wires to socket head screws supplied in detector clamp package. See
terminals No. 3 and 4. See Figure 34. Note: It is not necessary Figure 35.
to be concerned about polarity when installing these wires. CABLE
CLAMP
DETECTION PROTECTIVE
CIRCUIT SHRINK SLEEVE
MOUNTING TUBING
RUBBER
BRACKET
SLEEVES
3 4
1/4-20 x 1/2
PINS SOCKET HEAD
SCREW
1/4-20 x 5/8
SOCKET HEAD
SCREW (2)
SPOT
DETECTOR
FIGURE 34 FIGURE 35
002765 000875
POSITION AFTER
SHRINK HEAT
TUBING TREATING
3/8 – 1/2 IN. 5 3/4 IN.
(0.9 – 1.3 cm) (14.6 cm)
FIGURE 36
000876
13. Complete this process on each detector in the system. (12) Ø .39 ON
3 7/8 IN. (9.5 cm)
14. Attach the ground wire to the vehicle ground. Do this by BOLT CENTER
mounting a sealed junction box in a convenient, protected EQUALLY SPACED
location. The box must be mounted to a rigid support. Run the
FIGURE 37a
detection circuit cable to the box and attach to grounding 007561
screw. See Figure 37.
15. Attach the end-of-line resistor assembly, Part No. 426520. See Mounting the Detector to the Bracket
Figure 37. See instruction sheet included with end-of-line The Triple IR flame detector is mounted to the bracket using 1/4-20
resistor shipping assembly for detailed assembly information. x 1 in. hex head bolts with lock nuts. The bolts and lock nuts are
Exception: If system design utilizes the Triple IR flame provided with the detector bracket assembly, Part No. 434116.
detection option, do not install the end of line resistor When looking directly at the face of the detector, the detector can
assembly. When detection wire installation is completed, be mounted with the connector facing either to the left, right, or
refer to “Triple IR Flame Detection System” installation down, whichever provides the least amount of strain on the
instructions. connector cable. Do not position the detector with the connec-
tor facing UP.
16. Run cable to the terminal strip at the control module. Make
certain cable is not subject to damage. Install cable to termi- Mounting the CHECKFIRE Detection Interface Module
nals 3 and 4. Assembly
The Interface Module Assembly, Part No. 434108, can be located
on any protected space on the vehicle. It can be mounted by
GROUND following the installation requirements of the SC-N module. The
WIRE
EOL RESISTOR following additional mounting requirements must also be followed:
ASSEMBLY, JUNCTION
PART NO. 426520 BOX • The Interface Module cannot be mounted with any of its
DETECTION threaded knockouts, plugged holes or cable inlets, in the UP
CIRCUIT
position.
GROUND
SCREW*
FIGURE 37
002766
INSTALLATION
12-1-08 Page 20
REV. 5
RELEASE OUTPUT
RELEASE OUTPUT
ALARM COMMON
SHUTDOWN NO
SHUTDOWN NC
MANUAL INPUT
MANUAL INPUT
BATTERY POWER
ALARM
CHECKFIRE
ALARM NO
ALARM NC
DETECTION
RELEASE
+
-
CIRCUIT
+
+
-
ALARM COMMON
SHUTDOWN COMMON
ALARM NO
TROUBLE COMMON
ALARM NC
SHUTDOWN NO
SHUTDOWN NC
TROUBLE NO
MANUAL INPUT
MANUAL INPUT
RELEASE OUTPUT
RELEASE OUTPUT
DETECTION INPUT
DETECTION INPUT
EXT 12/24VDC BAT
EXT 12/24VDC BAT
DETECTION 1 OUTPUT
DETECTION 1 OUTPUT
DETECTION 2 OUTPUT
DETECTION 2 OUTPUT
DETECTION 1 CIRCUIT
DETECTION 1 CIRCUIT
DETECTION 1 CIRCUIT
DETECTION 1 CIRCUIT
+ 24 VDC REG. OUTPUT
- 24 VDC REG. OUTPUT
DETECTION 2 INPUT
DETECTION 2 INPUT
+ 24 VDC EXTERNAL
- 24 VDC EXTERNAL
NOT USED
GROUND
SC-N MODULE
EXTERNAL POWER
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
(IF REQUIRED) TRIPLE IR (IR3)
INTERFACE MODULE
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
+
-
-
GROUND
NOT USED
DETECTION 1 OUTPUT
DETECTION 1 OUTPUT
DETECTION 2 OUTPUT
DETECTION 2 OUTPUT
DETECTION 1 CIRCUIT
DETECTION 1 CIRCUIT
DETECTION 1 CIRCUIT
DETECTION 1 CIRCUIT
DETECTION 2 INPUT
DETECTION 2 INPUT
24 VDC EXTERNAL
24 VDC EXTERNAL
TRIPLE IR (IR3)
END-OF-LINE
(EOL) CABLE
ASSEMBLY
BLUE
! CAUTION
GREEN
GREEN RED GREEN RED
BLUE ORANGE BLUE ORANGE
Do not attach actuation cable to actuator at this time. If
Manual/Automatic Actuator is connected, the system could be
A B C D A B C D A B C D
actuated accidentally during installation.
1. Route the cable from the actuator, through the strain relief, to
the terminal strip at the control module. See Figure 40.
2. Leaving a little slack, cut off excess cable.
3. Strip the internal wires approximately 1/4 in. (0.6 cm) and
808-DRV securely fasten the red/green leads to Terminal 7 and the
black/white leads to Terminal 8 on the control module. See
SINGLE DETECTOR Figure 40.
OUT
CONTROL
MODULE
TERMINAL BLOCK
EOL RESISTOR RELEASE CIRCUIT
3 4
ASSEMBLY,
PART NO. 426520 7 8
4.7 K, 1/8 W (SEE
ORANGE EOL RESISTOR
BLACK/WHITE
ASSEMBLY RED/
GREEN WIRE
INSTALLATION GREEN
RED BLUE INSTRUCTIONS, WIRE
PAGE 17)
A B C D
808-DRV
FIGURE 39 FIGURE 40
001059
002767
4. Attach the release circuit tester, Part No. 423541, at this time.
This will be required when performing the functional test,
starting at Page 22.
INSTALLATION
12-1-08 Page 22
REV. 4
DETECTION
CIRCUIT
WIRING
4.7 K OHM
EOL RESISTOR
ASSEMBLY, PART
NO. 426520
NOTE: ALL
CONNECTIONS MUST
BE WATERTIGHT.
PRESSURE SWITCH
NOTE: MAKE CERTAIN PRESSURE SWITCH EOL RESISTOR
CONNECTIONS ARE WATERPROOF.
FIGURE 43
FIGURE 42 002770
002769
Hold the wire on the terminals for a time which is shorter than
the time programmed in for the first time delay.
INSTALLATION
12-1-08 Page 23
REV. 3
PLACING THE SYSTEM IN SERVICE c. Remove test module from squib connector and firmly hand
After all testing has been successfully completed, the system may tighten squib connector unto squib. See Figure 46.
be placed in service. Note: Before connecting the squib to the CHECKFIRE
control module, make certain there are no alarms present.
! CAUTION
Squib
Note: If a Protracting Actuator, Part No. 435479, is being used,
skip this step and proceed to step 2.
1. Install squib by completing the following:
! CAUTION
a. Screw squib into upper-right inlet hole in actuator body and NOTICE
wrench tighten. See Figure 44. When the squib connector is removed from the
test module, the control module YELLOW
Release Trouble LED and Sounder will temporar-
ily pulse. This will stop when squib is connected.
SQUIB
! CAUTION
PLACING THE SYSTEM IN SERVICE (Continued) f. Thread the upper actuator body back into the lower body.
Protracting Actuation Device (Continued) See Figure 50.
b. Unscrew the upper portion of the actuator body to expose Note: Before connecting the PAD to the CHECKFIRE
the bore in the top of the puncture pin. See Figure 47. control module, make certain there are no alarms present.
g. Remove test module from actuator cable and mate the PAD
connector that is extending from the port in the actuator
body to the connector located on the inside of the Terminal
UPPER Housing and Cable Assembly, and using the two (2) captive
PORTION
OF BODY screws, re-attach the Terminal Housing and Cable
Assembly to the actuator body. See Figure 50.
SCREW
UPPER
PORTION
PORT
TERMINAL OF BODY
HOUSING
PUNCTURE SCREW
PIN BORE SCREW
STEP B STEP A
FIGURE 47 TERMINAL
008224
HOUSING
into the bore in the top of the pin, route the PAD connector
from the inside of the actuator to the outside of the actua-
tor through the port in the actuator body. Then, as the STEP F STEP G
connector is being pulled through the port, insert the PAD FIGURE 50
into the bore in the top of the actuation pin. See Figure 48. 008227
PROTRACTING h. Rotate the actuator so that the actuation line outlet is facing
ACTUATION the front and the Terminal Housing and Cable Assembly is
DEVICE (PAD)
facing to the right (facing the left side of the control module)
and tighten the jam nut firmly. See Figure 51.
TERMINAL
CONNECTOR HOUSING
ACTUATION
LINE OUTLET
FIGURE 48
008225
TIGHTEN
d. When the PAD is fully seated inside the bore in the actua- JAM NUT
tor pin, carefully pull on the PAD leads that are extending FIRMLY
outside the actuator body to take up the remaining slack in
the PAD lead wires. Note: Do not pull on the connector.
e. Position the upper body so that the slot in the stem base
straddles the PAD lead wires. See Figure 49.
FIGURE 51
008223
SLOT
PAD LEAD i. Install the ring pin, but do not attach the seal at this time.
WIRES
! CAUTION
a. Make certain puncture pin is fully retracted and insert ring 6. If a vehicle shutdown device is installed and the shutdown
pin through actuator body into puncture pin shaft. Note: time delay is being used, complete the following steps. See
The tip of the puncture pin of the PAD Actuator, Part No. Figure 54.
435479 only, should be retracted a distance slightly less a. Affix the “IN CASE OF FIRE” nameplate, Part No. 79060,
than 1/8 in. (3.2 mm) above the bottom of the actuator. See near the operator’s line of vision.
Figure 53.
b. Using Label No. 79404, cut along the dotted line to remove
b. Attach visual inspection seal, Part No. 197. the required number square.
c. Remove shipping cap and weigh cartridge before installing. c. Peel the protective backing from the number square to
Replace if weight is 1/4 ounce (7.1 g) or more below weight expose the adhesive.
stamped on LT-10-R cartridge.
d. Place the number square on the space provided in the third
d. Screw cartridge into actuator body and hand tighten. sentence of Label No. 79060: “THIS VEHICLE WILL AUTO-
MATICALLY SHUTDOWN AFTER_____SECONDS.”
SQUIB ACTUATOR,
PART NO. 24479
RING PINNED
AND SEALED
LT-10-R CARTRIDGE
FIGURE 52a
000885
PROTRACTING ACTUATOR,
PART NO. 435479
FIGURE 54
000886
FIGURE 55
000887
LT-10-R CARTRIDGE
FIGURE 52b
008228
IN CASE OF FIRE
12-1-08 Page 27
REV. 3
Read these precautions carefully until they are clearly understood. Manual System Actuation
All equipment operators or anyone who has any responsibility for The system can be actuated manually by pulling the ring pin and
the equipment should fully understand how the CHECKFIRE striking the red button on the manual/automatic actuator as shown
SC-N Detection and Actuation System operates. Every operator in Figure 56. Again, bring the equipment to a safe stop, shut off the
should be fully trained in these procedures. engine, manually actuate the system, move a safe distance from
1. When the system alarm sounds, bring the equipment to a safe the vehicle, and stand by with a hand portable extinguisher.
controlled stop, shut off the engine, and exit. (Equipment left
running may add fuel to the fire or reignite the fire with heat or
! CAUTION
sparks.)
Automatic Equipment Shutdown – The CHECKFIRE SC-N Manual actuation will result in immediate system discharge
system is equipped with a shutdown relay and time delay. If a which may obscure vision. Make certain vehicle is stopped
shutdown device is connected to the system, all responsible safely before manually actuating the system. Manual actuation
personnel should understand shutdown device operation and will bypass all auxiliary shutdown and alarm functions.
the length of the time delay (in seconds). If the DELAY button
(on the control module cover) is pushed and released before 2
the end of the shutdown time delay period, the time delay will
automatically repeat itself. This delay can be repeated (using STRIKE
BUTTON
the DELAY button) as many times as is necessary to stop the
vehicle safely before it shuts down. (The DELAY button can
also be held in indefinitely to delay shutdown – the shutdown
delay will then restart after the button is released.)
2. Move away from the equipment taking a hand portable extin- PULL RING
guisher along if possible. PIN
1
3.
! WARNING
1. Remove the four (4) screws holding the cover to the back box
and remove the cover.
BASE
2. Remove the battery from the back box and properly discard. OF STEM
LUBRICATE O-RING
Battery must be replaced after each discharge. If system WITH SILICONE GREASE
contains optional vehicle power, also disconnect the wire
leads at the vehicle battery. PUNCTURE PIN
NOTICE NOTICE
If the system was actuated manually and the When puncture pin is fully reset, cutting point of
squib was not actuated, cleaning is not neces- pin will be located approximately 1/16 in.
sary. (1.6 mm) below threads in lower actuator body.
i. Remove jam nut and slide actuator out of mounting 5. Protracting Actuator, Part No. 435479, Recharge Steps (see
bracket. Figure 57b):
ii. Unscrew upper portion of actuator body. Note: If the system was manually actuated – Proceed to
iii. Using a pencil eraser, apply pressure to the bottom of Step 6.
the puncture pin. This will force the puncture pin and a. Back out the two (2) screws holding the Terminal Housing
spring out of the actuator body. and Cable Assembly to the actuator body assembly,
iv. Thoroughly clean carbon deposits from base of stem, disconnect the actuation cable from the Protracting
puncture pin, spring, and inside surface of actuator Actuation Device (PAD) leads and remove the terminal
body. housing (the screws are captive screws and should remain
secured in the terminal housing cover).
v. After all components are clean and dry, liberally lubri-
cate O-rings with a good grade of extreme temperature b. Unscrew the upper portion of the actuator body to expose
silicone grease. the bore in the top of the puncture pin.
vi. Reassemble actuator, reinstall into bracket, and c. Remove the PAD from the actuator body by lifting the PAD
securely tighten jam nut. out of the puncture pin bore and actuator body, while
pulling the PAD leads back through the port in the side of
vii. Pull ring pin and push strike button several times to the actuator.
spread grease and ensure free movement of puncture
pin. d. After the PAD has been removed, tip the actuator body
upside down, being careful not to drop the actuator pin, to
viii. With strike button in the up position, insert ring pin remove the small brass septum that was ejected from the
through actuator body into puncture pin shaft. Install PAD during discharge.
visual inspection seal, Part No. 197.
e. Before inserting the new PAD into the bore in the top of the
pin, route the PAD connector from the inside of the actua-
tor to the outside of the actuator through the port in the
actuator body. Then, as the connector is being pulled
through the port, insert the PAD into the bore in the top of
the actuation pin.
f. When the PAD is fully seated inside the bore in the actua-
tor pin, carefully pull on the PAD leads that are extending
outside the actuator body to take up the remaining slack in
the PAD lead wires. Note: Do not pull on the connector.
g. Position the upper body so that the slot in the stem base
straddles the PAD lead wires.
RECHARGE
12-1-08 Page 29
REV. 3
RECHARGE (Continued)
5. Protracting Actuator, Part No. 435479, Recharge Steps:
(Continued)
h. Thread the upper actuator body back into the lower body.
i. Mate the PAD connector that is extending from the port in
the actuator body to the connector located on the inside of
the Terminal Housing and Cable Assembly, and using the
two (2) captive screws, re-attach the Terminal Housing and
Cable Assembly to the actuator body.
j. Rotate the actuator so that the gas outlet port is facing the
front and the Terminal Housing and Cable Assembly is
facing to the right (facing the left side of the control module)
and tighten the jam nut firmly.
UPPER
PORTION
OF BODY
BASE OF STEM
PROTRACTING
ACTUATION
DEVICE
PUNCTURE PIN
SPRING
ACTUATOR BODY
FIGURE 57b
008226
k. Install the ring pin, but do not attach seal at this time.
6. In the case of a fire, replace all linear detection wire and spot
detector cable. See Section III, Installation, for instructions.
a. Inspect all spot thermal detectors, if used, for damage, and
verify that each one has reset to its normal operational
mode. (With the detection wiring disconnected from the
detector, using a multimeter, check to verify that there is no
continuity between any of the detector pin connections.)
b. If Spectrex Model 20/20MI-32-A-F Triple IR (IR3) flame
detection is utilized, inspect detectors and verify they have
not been damaged. Make certain all detectors have been
reset to their normal operating condition. Refer to User and
Maintenance Manual (Ansul Part No. 432485) and follow
the detector maintenance instructions outlined on Page 18
in the manual to verify detector operation.
Note: The functional operation of the IR3 flame detectors
should result in an alarm condition in the CHECKFIRE SC-N
module.
7. Install new battery, Part No. 427308, in module. Record date
of installation.
8. Recharge the fire suppression system in accordance with the
corresponding manual.
9. Test the system and place into service by completing the
steps listed under “FUNCTIONAL TEST.”
10 Record date of recharge on a tag or in permanent record file.
Notify operating personnel that the system is back in service.
INSPECTION AND MAINTENANCE
12-1-08 Page 30
REV. 2
To ensure that the CHECKFIRE SC-N Electric Detection and 4. Five Year Protracting Actuation Device Replacement
Actuation System will operate as intended, proper inspection and a. The Protracting Actuation Device (PAD) must be replaced
maintenance procedures must be performed at the specified inter- after being in service for five years. (The month and year of
vals. manufacture is printed on the label located on the PAD
leads). Proper disposal of the PAD is accomplished by
DAILY INSPECTIONS actuating the PAD within the actuator body. If this is
The vehicle operator must check the system daily by visually veri- required, skip following steps b. through d. which deal with
fying that the GREEN power LED is flashing and no other LED is installing the test module in place of the PAD. By skipping
illuminated. Also, no audio alarm should be sounding. If any other steps b. through d., the PAD will be actuated during the
conditions exist, contact the local authorized ANSUL distributor or following test procedures.
whoever has been trained and authorized by ANSUL to perform
inspection and maintenance checks. ! CAUTION
MAINTENANCE (Continued) 14. Squib Replacement – Complete the following steps only if
10. Check first time delay – Alarm to Shutdown – Using a short the squib has been actuated. Otherwise, go to Step No. 15.
length of insulated wire stripped at both ends, hold one end of a. Unscrew the squib lead connector from the squib and
the wire to Terminal 3 and the other end to Terminal 4 on the remove the squib from the actuator body.
control module. See Figure 58. b. Clean manual/automatic actuator by referring to Step 4 on
DETECTION CIRCUIT Page 28 in Recharge Section.
TERMINALS 3 AND 4
c. Screw replacement squib into the upper-right hole in the
JUMPER
3 4 actuator body and wrench tighten.
d.
! CAUTION
MAINTENANCE (Continued)
18. Disconnect the actuation cable from the tester.
NOTICE
When actuation cable is removed from test
module, the YELLOW Release LED and the
audio alarm on the control module will temporar-
ily pulse. This will stop when PAD is connected.
19. Mate the PAD connector that is extending from the port in the
actuator body to the connector located on the inside of the
Terminal Housing and Cable Assembly, and using the two (2)
captive screws, re-attach the Terminal Housing and Cable
Assembly to the actuator body.
20. Rotate the actuator so that the actuation line outlet is facing
the front and the Terminal Housing and Cable Assembly is
facing to the right (facing the left side of the control module)
and tighten jam nut firmly.
21. Install the ring pin, but do not attach seal at this time.
22. Disconnect extender cable from backbox and cover, and rein-
stall cover onto module.
23. For both Squib and PAD Actuators – Push “RESET” button
on CHECKFIRE SC-N Control Module to reset system.
! CAUTION
24. Pull ring pin and push strike button on manual/automatic actu-
ator several times to ensure smooth movement.
NOTICE
If lever does not operate smoothly, clean and
lubricate internal components by completing
Step No. 4 on Page 28 in Recharge Section.
25. Yearly – Remove control module cover screws and replace
internal 3.6 VDC lithium battery, Part No. 427308. Record date
of new battery installation on label located near battery.
Reinstall control module cover and depress “RESET” button.
! CAUTION
The system must be in the trouble mode in order to display the Init Bad Log – This indicates that an error has been detected
diagnostics codes. in the datalog. If this occurs, the datalog is
automatically cleared and reset.
With the system in the trouble mode, depress the “DELAY” button.
With the “DELAY” button depressed, the trouble codes will be indi- Bad Checksum – Indicates that an error has been detected in
cated on the LEDs. the E-Prom. If this occurs, the factory default
program settings are restored.
LED Code
_________ Trouble
_______ Soft Reset – Indicates that the Reset button has been
depressed. The clock is not reset during a soft
Yellow Battery LED flashing Internal battery disconnected reset.
Yellow Battery LED flashing External battery disconnected +12 (24V) Low – Indicates that the external power input voltage
Red Alarm LED flashing has dropped below a “Normal” threshold level
and is in need of servicing.
Yellow Release LED flashing Release circuit is open
+12 (24V) Fault – Indicates external power input voltage has
Yellow Release LED flashing Release circuit has operated dropped below the minimum operating
Red Alarm LED flashing threshold or the external power has been
disconnected.
Yellow Detection LED flashing Detection circuit is open Int Batt Low – Indicates the internal battery voltage has
Yellow Detection LED flashing Electric manual pull station dropped below a “Normal” threshold level and
Red Alarm LED flashing circuit is open requires servicing.
Int Batt Fault – Indicates that the internal battery voltage has
HISTORY BUFFER dropped below the minimum operating
The CHECKFIRE SC-N control module is programmed to record threshold or the battery has been
faults, alarms, and programming changes in a numerical disconnected.
sequence. The module will store approximately 50 recorded Detection TD1 – Indicates that the Time Delay 1 sequence has
events. If the number of events exceeds 50, the earlier events will been initiated. This occurs as a result of oper-
be erased to make room for the later ones. ation of the detection circuit.
A sample History Buffer screen appears as follows: Detection TD2 – Indicates the start of the Time Delay 2
Event Number Event sequence as a result of a detection input.
0 Programmed Time (dddd:hh:mm:ss) Manual TD – Indicates the start of the time delay as a result
1 Detection TD1 0000:00:01:46 of the manual input circuit being initiated.
2 Delay Engaged 0000:00:01:52 Pressure Switch – Indicates activation of the pressure switch
3 Delay Released 0000:00:02:15 input circuit.
4 Detection TD2 0000:00:02:25 Delay Engaged – Indicates the delay button has been
5 Squib Release 0000:00:02:35 depressed during TD1 of an alarm condition.
6 Soft Reset 0000:00:05:10
7 All Clear 0000:00:05:13 Delay Released – Indicates the time the Delay button was
8 Int Batt Low 385:12:24:32 released after initiating.
9 Int Batt Fault 405:20:32:07 Detection Fault – Indicates an open circuit in the detection
The recorded event indicates which circuit had a fault or an alarm circuit.
recorded. Along with the type of fault or alarm, the history buffer Manual Fault – Indicates an open in the manual pull or pres-
also records the time, relative to the first event which is the power- sure switch circuit.
ing of the unit or restoration of power. New events are recorded by
days: hours: minutes: seconds that have transpired from the last Squib Fault – Indicates an open in the squib circuit or that
restoration of power. If power is removed and then restored, the the squib has fired.
counter starts over at 0000:00:00:00, however, previous history Squib Release – Indicates that the control module has fired the
will be retained in the buffer. squib.
Unknown – Indicates an unexplainable event in the
control module circuitry.
All Clear – Indicates alarm condition has been reset. This
indication occurs after TD2 clears.
TROUBLESHOOTING
12-1-08 Page 34
REV. 2
TROUBLESHOOTING TABLE
The following table designates normal operating and trouble conditions for the CHECKFIRE SC-N Detection and Actuation System.
Green Yellow Yellow Yellow
Power Power Red Detection Release Audio Alarm Shutdown Trouble Agent
Condition
________ Normal
______ Fault
_____ Alarm
_____ Fault
________ Fault
_______ Alarm
_____ Relay
_____ Relay
_________ Relay
_______ Release
_______
battery normal pulsing off off off off off normal normal normal off
module normal once every
external power 3 seconds
not used
battery normal pulsing off off pulsing off pulsing normal normal transferred off
detection fault once every once every once every
external power 3 seconds 10 seconds 10 seconds
not used
battery normal pulsing off off off pulsing pulsing normal normal transferred off
release fault once every once every
external power 10 seconds 10 seconds
not used
battery normal pulsing off off pulsing pulsing pulsing normal normal transferred off
detection fault once every once every once every
release fault 10 seconds 10 seconds 10 seconds
external power
not used
battery fault off pulsing off off off pulsing normal normal transferred off
external power normal once every once every
module normal 10 seconds 10 seconds
battery fault off pulsing off pulsing off pulsing normal normal transferred off
external power normal once every once every once every
detection fault 10 seconds 10 seconds 10 seconds
battery fault off pulsing off off pulsing pulsing normal normal transferred off
release fault once every once every once every
external power normal 10 seconds 10 seconds 10 seconds
battery fault off pulsing off pulsing pulsing pulsing normal normal transferred off
detection fault once every once every once every once every
release fault 10 seconds 10 seconds 10 seconds 10 seconds
external power normal
alarm detected pulsing off pulsing off off pulsing transferred normal normal off
alarm to shutdown once every twice twice every
period – TD1 3 seconds every second second
external power fault off pulsing off pulsing pulsing pulsing normal normal transferred off
detection fault once every once every once every once every
manual pull circuit fault 10 seconds 10 seconds 10 seconds 10 seconds
release fault
battery normal
battery fault off pulsing off off off pulsing normal normal transferred off
external power fault once every once every
10 seconds 10 seconds
battery fault off pulsing off pulsing off pulsing normal normal transferred off
external power fault once every once every once every
detection fault 10 seconds 10 seconds 10 seconds
TROUBLESHOOTING
12-1-08 Page 35
REV. 3
battery fault off pulsing off pulsing pulsing pulsing normal normal transferred off
external power fault once every once every once every once every
detection fault 10 seconds 10 seconds 10 seconds 10 seconds
manual pull circuit
fault
release fault
manual pull circuit pulsing off pulsing off off pulsing transferred transferred normal off
activated once every 4 times 4 times
pre release period 3 seconds per second per second
(manual release
time delay)
pressure switch pulsing off pulsing off off pulsing transferred transferred normal off
activated (0 to 30 once every 4 times 4 times
seconds 3 seconds per second per second
after activated)
pressure switch pulsing off pulsing off pulsing pulsing transferred transferred transferred off
activated once every once every once every once every
(post 30+ seconds 3 seconds 10 seconds 10 seconds 10 seconds
period)
shutdown to release pulsing off pulsing off off pulsing transferred transferred normal off
period once every 4 times 4 times
(2nd time delay) 3 seconds per second per second
0 - 30 seconds pulsing off pulsing off off* pulsing transferred transferred transferred fired
after release once every 4 times 4 times
3 seconds per second per second
30+ seconds pulsing off pulsing off pulsing pulsing transferred** transferred transferred fired
after release once every once every once every once every
3 seconds 10 seconds 10 seconds 10 seconds
manual pull pulsing off off pulsing off pulsing normal normal transferred off
circuit fault once every once every once every
battery normal 3 seconds 10 seconds 10 seconds
external power normal
manual pull pulsing off off pulsing off pulsing normal normal transferred off
circuit fault once every once every once every
detection fault 3 seconds 10 seconds 10 seconds
battery normal
external power normal
manual pull pulsing off off pulsing pulsing pulsing normal normal transferred off
circuit fault once every once every once every once every
detection fault 3 seconds 10 seconds 10 seconds 10 seconds
release fault
battery normal
TROUBLESHOOTING
12-1-08 Page 36
REV. 4
external power fault off pulsing off pulsing off pulsing normal normal transferred off
detection fault once every once every once every
battery normal 10 seconds 10 seconds 10 seconds
battery fault off pulsing off off off pulsing normal normal transferred off
no external power once every once every
module normal 30 seconds 30 seconds
battery fault off pulsing off pulsing off pulsing normal normal transferred off
detection fault once every once every once every
external power 10 seconds 10 seconds 10 seconds
not used
manual pull pulsing off pulsing off off* pulsing transferred transferred transferred fired
circuit activated once every 4 times 4 times
(0-30 seconds after 3 seconds per second per second
system activation)
pressure switch pulsing off pulsing pulsing pulsing pulsing transferred transferred transferred off
activated detection once every once every once every once every once every
fault (30+ seconds 3 seconds 10 seconds 10 seconds 10 seconds 10 seconds
after system
activation)
PROGRAMMING
The SC-N control module can be manually programmed by using Switch No. 1
the manual programming switch located on the control module PC If this switch is ON (Enable), it disables programming through a
board or it can be programmed from a PC through an RS232 inter- PC and enables the manual programming switch. If switch No. 1
face cable. is on, the operation of the control module will correspond to the
A number of settings can be programmed into the SC-N control settings of the other manual programming switches.
module: If this switch is OFF (Disable), the operation of the control
• Select initiating circuit No. 2 to operate as either an electric module will correspond to the settings of the PC program
manual pull circuit or pressure switch feedback circuit
Switch No. 2
• If selected as an electric manual pull circuit, it can be
programmed as either shutdown/immediate release or shut- This switch is used to select initiating circuit No. 2 to operate as
down/time delay/release either an electric manual pull or a pressure switch feedback
• Alarm to Shutdown (Time Delay 1) can be programmed for 5, ON = Pressure Switch Feedback
10, 20, 30 seconds OFF = Electric Manual Pull
• Shutdown to Release (Time Delay 2) can be programmed for 0,
10, 20, 30 seconds Switch No. 3
The SC-N control module is factory programmed with the follow- This switch is used to select either the shutdown/ time delay/
ing defaults: release or the shutdown/immediate release mode for the elec-
tric manual pull input
First time delay (Alarm to Shutdown) = 10 seconds
This switch is only active if the switch No. 2 is in the OFF posi-
Second time delay (Shutdown to Release) = 10 seconds tion
Manual Pull = Shutdown, Time Delay (10 seconds), Release
If switch No. 3 is set to ON, then operation of the electric manual
Manual Programming Switch = Disabled pull station will cause the control module to go through a shut-
If the factory defaults are acceptable, no additional programming down/ time delay/ release sequence. The time delay cycle will
is required. However, the factory program is only active if the be whatever is programmed on switches No. 6 and 7.
manual programming switch is disabled. If set to OFF, operation of the electric manual pull station will
Manual Programming Switch cause the control module to activate will go to the shutdown and
immediately operate the circuit
The manual programming switch is a PC board mounted, switch
package containing 7 switches. See Figure 59. To manually Switch No. 4 and 5
program the SC-N control module, each individual switch must be These two switches set the cycle time for time delay 1 (Alarm to
set in the correct position. Shutdown)
Switch No. 4 ON / Switch No. 5 ON = 5 seconds
Switch No. 4 OFF / Switch No. 5 ON = 10 seconds
RS-232 SERIAL Switch No. 4 ON / Switch No. 5 OFF = 20 seconds
INTERFACE CABLE
CONNECTION Switch No. 4 OFF / Switch No. 5 OFF = 30 seconds
FIGURE 59
002795
NOTICE
Do not remove see-through cover on switch.
Switch position(s) can be moved by using a
blunt, not sharp, object. Do not damage switch
cover.
PROGRAMMING
12-1-08 Page 38
REV. 3
PC PROGRAMMING Inputs
PC programming is another means of setting up the SC-N Control The program inputs will be explained individually.
Module to the required options.
Detection Setup
One advantage of using the PC programming approach versus the
manual programming switch feature is, with the PC, the module Time Delay 1: 10 seconds
can be programmed to have a shorter time delay period when Time Delay 2: 10 seconds
using the manual electric pull station than what is programmed
into the second time delay cycle of the detection circuit. When This input is to set the length of time for the time delays.
using the manual programming switch feature, the electric manual Time Delay 1 (Alarm to Shutdown cycle): This time delay can be
pull time delay will automatically correspond to the setting of the programmed for 5, 10, 20, or 30 seconds.
second time delay cycle of the detection circuit.
Time Delay 2 (Shutdown to Release cycle): This time delay can be
The control module is field programmed through a PC computer programmed for 0, 10, 20, or 30 seconds.
using an RS-232 serial interface cable. The interface cable kit is
available as Part No. 423524. Manual Release Setup
The internal 3.6 volt lithium battery must be installed in the Input selection: Manual pull
control module prior to programming. Time Delay before release: Shutdown, Time Delay, Release
Note: The following programming steps are instructions for Time Delay: 10 seconds
Windows 95 and 98 systems. See Ansul Bulletin No. 5030 (dated
October 25, 2005) for programming additional systems. This input allows for the selection of initiating circuit No. 2 to be
used as either manual pull or pressure switch input.
EXPLAINING THE MENU If choosing manual pull, two options are available: Shutdown/Time
When programming the CHECKFIRE SC-N control module, only Delay/Release option or Shutdown/Immediate Release. If choos-
one menu screen will appear on the computer. All programming ing the Shutdown/Time Delay/Release option, then the program
will be done using this screen. Before starting to program, the will not allow selection of a time delay that is greater than the time
menu setups and control options will be explained. delay selected for time delay No. 2 in the detection set-up. If choos-
ing the Shutdown/Immediate Release option, then no time delay
The following menu screen will appear when following the cycle is available.
programming steps: Note: The underlined letter or symbol repre-
sents the key to press to initiate the action. Programmable settings If choosing the pressure switch input, no options are available.
are shown as bold text.
Manual Programming Switch: Disabled
ANSUL CHECKFIRE SC-N Setup Program V0.43 When doing manual programming, the Manual Programming
Controller Model: CHECKFIRE SC-N V0.51 switch must be Enabled
Manual Programming Switch: Disabled When doing PC programming, the Manual Programming switch
must be Disabled
↓ Next
↑ Previous Command Keys
Detection Setup: ← → Change Command keys are used to select the different inputs to be
Time Delay 1: 10 seconds programmed and execute various computer operations. The
Time Delay 2: 10 seconds Upload Setup to Controller command keys are explained individually.
Download Setup to
Controller
↓Next
Manual Release Setup Verify Controller Setup
Input Selection: Manual Pull
Time Delay: Shutdown, The down arrow command key moves the cursor down to the next
Time Delay, Release input line. The input which the cursor is on will be highlighted.
Time Delay: 10 seconds
View Factory Defaults ↑Previous
Read Datalog From
Controller The up arrow command key moves the cursor up to the input line
Clear Datalog on above where it presently is. The input which the cursor is on will be
Controller highlighted.
Test Communications
Security Password
← →Change
Change
eXit
The right arrow and left arrow command keys allow for the selec-
tion of available settings on a particular input line. Example:
Changing the number of seconds of each time delay cycle;
Changing the Manual Release Input from Manual Pull to Pressure
Switch.
PROGRAMMING
12-1-08 Page 39
REV. 3
The D key is used to download the inputs from the control module Security password change
to the menu screen. This is mainly used to determine the settings
that are presently programmed in the control module. This will not The S key is used to change the user password. The program disc
change what is programmed in the controller. is factory programmed with a password of PESHTIGO. If a new
password is desired, type S. The status will indicate: Enter new
Verify controller setup password:
Type in the new password and press Enter. The new password will
The V key is used to determine the status of the control module now be saved in the program.
inputs. By pressing the V key, the program will verify if what is
shown on the menu screen is the same as what is programmed in
eXit
the control module. The status will indicate either verification
pass or verification fail. If verification fail is indicated, download
setup from controller to determine what is presently programmed The X key is used to exit out of the program. By pressing the X key,
in the control module. the computer will close the program.
Programming
View Factory default
Note: The internal 3.6 VDC battery must be plugged in to the
The F key is used to view what the default settings are from the control module before programming. Also, before PC
factory. By depressing this key, and viewing the settings, the programming, make certain the DIP Switch No. 1 is set to
module will not be changed from what is presently programmed. Disable (OFF).
In order to change the module back to the factory default, after While programming, with the cover assembly removed from the
viewing, depress the U key to upload the settings into the module. back box, it is normal for the sounder and the LEDs to pulse once
every 10 seconds. This will stop when the programming is
completed and the computer and internal battery is disconnected.
Read datalog from controller
Note: The internal battery can be disconnected without interfering
with the program in the module.
The history buffer datalog is a sequential listing of events that have
taken place over the life of the control module. The datalog will Step No. 1 – Attach the RS-232 interface cable between the
record events such as trouble, alarm, and programming. The list of computer and the CHECKFIRE SC-N control
history events that have taken place will be displayed on the module and turn on the computer.
screen. The history buffer will record approximately 50 events. If Step No. 2 – Insert programming disc in “A” disc drive and bring
more than 50 events take place, the oldest events will be erased up disc.
to make room for the most recent events.
Step No. 3 – Double click on the “A” drive icon.
The R key is used to download the events stored in the control
module to a file in the computer. To view the events, first, exit the Step No. 4 – On the next screen, double click on the “Setupsc”
menu screen by depressing X. The next screen will show three icon.
files, one being the datalog file. Double click on the datalog icon. Step No. 5 – The program screen will now ask for the password.
This will open the datalog file for viewing. Type in PESHTIGO and depress Enter. The pass-
word can be changed later by using the Security
password change input.
Clear datalog on controller
Step No. 6 – The program will ask for the correct communication
The C key is used to clear all the history events recorded in the port to address. Not knowing the type of computer
control module history buffer. After the C key is depressed, the being used, it is necessary to, by trial and error,
menu screen will indicate the datalog is cleared. From this point find the correct port. Type 1. If this is not the correct
on, all new events will start to be recorded. port, the program will respond with: Failure to
connect to comm port – Press 1 to retry or 2 to
Exit.
PROGRAMMING
12-1-08 Page 40
REV. 3
EXPLAINING THE MENU (Continued) Step No. 13 – Depress the ”RESET” button on the control
Programming (Continued) module.
Step No. 7 – Press 1 and then select another comport (2,3,4). Step No. 14 – At this point the programming is complete.
When the correct port is chosen, the program will Disconnect the RS-232 serial interface cable from
respond momentarily with, “Reading Settings From the control module. The module will continue to
Controller,” after which the main menu will appear pulse once every 10 seconds. Disconnecting the
on the screen. internal module battery will silence the module.
The internal programming will remain intact. The
module is now ready to be installed and wired.
ANSUL CHECKFIRE SC-N Setup Program V0.43
Controller Model: CHECKFIRE SC-N V0.51 Step No. 15 – If all programming is complete, the program can be
exited and the PC can be shutdown.
Manual Programming Switch: Disabled
↓ Next
↑ Previous
Detection Setup: ← → Change
Time Delay 1: 10 seconds
Time Delay 2: 10 seconds Upload Setup to Controller
Download Setup to
Controller
Manual Release Setup Verify Controller Setup
Input Selection: Manual Pull
Time Delay: Shutdown,
Time Delay, Release
Time Delay: 10 seconds
View Factory Defaults
Read Datalog From
Controller
Clear Datalog on
Controller
Test Communications
Security Password
Change
eXit
GAS
MOTOR
BATTERY
LOW
SQUIB
GAS CARTRIDGE/
SQUIB/
OFF SWITCH
FIGURE 60
003016
Operation is as follows:
1. The receptable on the tester mates with the connector on the
gas motor actuation cable, Part No. 416129, used with the
CHECKFIRE MP-N. A test adapter is provided for testing units
with actuator cables, Part No. 79062 or Part No. 422747, used
with the CHECKFIRE SC-N.
2. A three-position slide switch is located on the side of the
enclosure to select the type of output to test (squib, gas motor
and Protracting Actuation Device) and the third position is
“OFF.” The “SQUIB” setting should be used when testing a
CHECKFIRE SC-N model with either the Part No. 79062
cable or the Part No. 42247 cables. The gas motor setting is
used only for testing the CHECKFIRE MP-N model.
3. Steps for operation are:
a. With slide switch, select type of output to be tested. This will
also turn the unit on.
b. Press the reset button on the tester. This will illuminate the
“READY LED” if it is not already illuminated.
c. Connect to control unit actuator cable.
d. Proceed with activating output.
e. Once the unit activates, the unit tester will indicate a
“PASS” or “FAIL” status resulting from the test.
f. The tester can then be reset by pressing the RESET
button, which will prepare it for the next test.
APPENDIX
12-1-08 Page 42
COMPONENT INDEX
Part Shipping Weight
No. Assembly lb (kg)
Main Assemblies
436302 CHECKFIRE SC-N Electric Detection and Actuation 10 (4.5)
System includes:
423504 Control Module (module contains nuts and
washers for mounting to bracket)
435479 Manual/Automatic Actuator
423525 Combined Mounting Bracket
13193 Nitrogen Cartridge, LT-10-R
436026 Protracting Actuation Device 1/4 (0.1)
25627 1/4 in. Check Valve
79064 Label Package
53081 Owner’s Manual
436303 (Transport Canada) CHECKFIRE SC-N Electric Detection 10 (4.5)
and Actuation System includes:
(All of the standard shipping assembly components
except Nitrogen Cartridge, Part No. 13193, is replaced
with Nitrogen Cartridge, Part No. 423423)
427308 Battery Shipping Assembly (3.6 VDC) 1/4 (0.1)
426461 End-of-Line Resistor Assembly (Package of 10) 1/4 (0.1)
426520 End-of-Line Resistor Assembly (Single) 1/4 (0.1)
Accessory Equipment
423541 Release Circuit Test Module 1 (0.5)
436243 Protracting Actuation Device Test Adaptor 1/4 (0.5)
423525 Combined Bracket Shipping Assembly – 1 (0.5)
For mounting control module and actuator together
423528 Control Module Mounting Bracket – 1 (0.5)
For mounting control module separately
416726 Actuator Mounting Bracket – 1 (0.5)
For mounting actuator separately
423531 Control Module Retrofit Mounting Bracket – 1 (0.5)
For mounting control module to existing
CHECKFIRE SC mounting bracket
79559 Remote High Level Alarm 2 (0.9)
71820 Splicing Device 1/4 (0.1)
71230 356 °F (180 °C) Linear Detection Wire, 100 ft (30.4 m) 5 (2.3)
71231 356 °F (180 °C) Linear Detection Wire, 500 ft (152.4 m) 10 (4.5)
416218 270 °F (132 °C) Spot Detector 1/4 (0.1)
416219 325 °F (163 °C) Spot Detector 1/4 (0.1)
416220 360 °F (182 °C) Spot Detector 1/4 (0.1)
416213 Spot Detector Connector Package 1/4 (0.1)
416221 Spot Detector Bracket 1/4 (0.1)
416762 Spot Detector Cable Clamp Package (For Use 1/4 (0.1)
Without Protective Tubing)
416214 Spot Detector Cable Clamp Package (For Use 1/4 (0.1)
With Protective Tubing)
416215 Flex Non-Metallic Tubing 100 ft (30.4 m) 4 (1.8)
(For Spot Detectors)
416784 Crimp Tool (For Spot Detector) 1 (0.5)
416113 Pneumatic/Linear Detector, 35 ft (10.7 m) 1 (0.5)
(Model 808-DRV)
416216 Cable Assembly, 15 ft (4.6 m) (For Pneumatic/ 1/4 (0.1)
Linear Detector)
416378 Mounting Clips Package For Pneumatic/Linear 1/4 (0.1)
Detector Sensing Element (Includes 100 Clips)
417055 Wire, 392 °F (200 °C), 18 AWG-2 W/Shield and Drain Wire 10 (4.5)
500 ft (152 m)
APPENDIX
12-1-08 Page 43
RECHARGE EQUIPMENT
436026 Protracting Actuation Device 1/4 (0.1)
13193 LT-10-R Cartridge (DOT) 2 (0.9)
423423 LT-10-R Cartridge (DOT/TC) 2 (0.9)
427308 Battery Shipping Assembly (3.6 VDC) 1/4 (0.1)
423522 Installation, Maintenance, Recharge Manual 1/4 (0.1)
APPENDIX
12-1-08 Page 44
WARRANTY
The components of the Ansul CHECKFIRE SC-N Electric
Detection and Actuation System supplied by Ansul Incorporated,
(“ANSUL”) are warranted to you as the original purchaser for one
year from the date of delivery against defects in workmanship and
material. ANSUL will replace or repair any Ansul-supplied compo-
nent which, in its opinion, is defective and has not been tampered
with or subjected to misuse, abuse, exposed to highly corrosive
conditions or extreme high temperatures provided that written
notice of the alleged defect shall have been given to ANSUL within
30 days after discovery thereof and prior to the expiration of one
year after delivery, and further provided that if ANSUL so instructs,
such article or part thereof is promptly returned to ANSUL with
shipping charges prepaid.