Professional Documents
Culture Documents
Absfract - The generator circuit-breaker (gen.c.b.) located The following considerations are being presented in
between the generator a n d the step-up transformer, is now this paper:
being applied world-wide. I t has become a recognized a) temporary overvoltages and power frequency
electrical component of power stations which is largely due voltage changes
to economical advantages and increased power station b) switching overvoltages
availability. c) lightning overvoltages transferred to the generator
Technical protection considerations for power stations have side.
always been the reason for discussion and the object of In general, lightning arresters and a high-voltage
improvement. With the use of a gen.c.b., some points of circuit-breaker are connected to the high-voltage side at
view need to be considered anew. Not only the protection or close to the transformer terminals. However, the
system in case of fault conditions will be influenced, but protection of the low-voltage side of the transformer and
also the insulation co-ordination philosophy . the generator is not always adequately ensured, so that
Below the results of some calculations concerning expected further measures are required. Some calculations are
overvoltages a r e presented. These calculations are based on intended to serve as a help in making decisions, as far as
a transformer rated 264/15.5kV, 22OMVA. But the results insulation co-ordination in a power station is concerned.
a r e transferable to other power plants.
Some measurements carried out on a transformer of the 2.STANDARDE E E C37.0 13-89 FOR GENERATOR CIRCUIT-
same rating complement the calculations. BREAKERS [8]
O u r findings may contribute to an improvement in
insulation co-ordination and protection of the electrical The initial installation of generator switchgear in
system generator - step-up transformer. nuclear power stations has presented some problems in
relation to national standards. The authorities responsible
1. INTRODUCTION for security in nuclear installations demanded that
equipment be fully tested in relation to standards which
Insulation co-ordination in high voltage networks has were either not yet in force for gen.c.b.s or only partially
been discussed in some detail in ANSI as well as in IEC relevant to them. In the USA the Nuclear Regulatory
Standards [ l , 2, 3, 41. Some of these recommendations Commission favoured the application of generator
may be used as a basis for judging the insulation co- circuit-breakers as a means of ensuring enhanced security
ordination in power stations with generator circuit- on the one hand, but on the other hand this organisation
breakers (gen.c.b.) between the generator and the impeded the import of electrical equipment without an
transformer. There are also some publications dealing USA-approval certificate.
with technical questions of protection against Therefore, a working group of the IEEE was
overvoltages in power stations [5, 6 , 71. established in the early 1970's in order to develop a
standard for generator circuit-breakers, including
94 SM 4L6-5 PWRD A paper recommended and approved recommendations for the type tests based on actual plant
by t h e IEEE Transmission and D i s t r i b u t i o n Committee requirements.
of t'ne IEEE Power Engineering S o c i e t y f o r p r e s e n t a t -
i o n a t t h e IEEE/PES 1994 Summer Meeting, San
This work was supported by the results of
Francisco, CA, J u l y 24 - 28, 1994. Manuscript sub- measurements and studies regarding transient recovery
mitted October 5 , 1993; made a v a i l a b l e f o r p r i n t i n g voltages of gen.c.b.s, published in [9, lo], and has now
May 17, 1994. been completed with the issue of an additional
application guide which matches the standard C37.0 13
first published in 1989.
Below, the withstand voltages to ground and across
the contacts for a gen.c.b. according to this standard are
given:
4.POWERFREQUENCY
VOLTAGE
CHANGES During closing or opening of a circuit-breaker one pole
of the three phases might fail, i.e. one pole does not open
Voltage fluctuations of a relatively long duration or of or does not close (stuck pole),
power frequency can be transferred to the low-voltage For an operating system common to the 3 poles of a
side of the transformer either as a result of switching gen.c.b. a malfunction of one pole is a very unlikely
operations, or due to a dielectric breakdown on the high- failure. However, such an event cannot be completely
voltage side. They might also be a result of non-linearity excluded and would not be signalled by the auxiliary
oscillations such as ferro-resonance. Power frequency switch.
voltage fluctuations across the open generator circuit- Fig. 2 shows the simulation results of a load rejection
breaker which result from non-synchronism must be at 100% load (a low probability contingency) combined
covered by the power frequency withstand voltage test. with a stuck pole in phase A. After having reached
approximate phase-opposition conditions, which would
4.1 Single phase-to-ground faults, steady state. take about OSsec, the max. phase-to-ground voltage at
The above mentioned conditions lead to 43p.u. phase-to- the transformer terminals would reach 2.9p.u. (1.2 + 43),
ground voltages in the unfaulted phases. Combined with see also phasor diagram Fig. 3, and at phase opposition
load rejection power frequency overvoltages of the maximum voltage across the open breaker contacts
(l.lt1.4)43p.u. to ground might be generated. [12] would amount to 3.8p.u. (43(1.2 + 1.0)). These are
extreme values which in practice are reduced by the
4.2 Overvoltages as a consequence of a mechanical voltage control of the generator and will take far more
failure in the operating mechanism . time to develop if the breaker is opened at no-load
conditions.
9-
-I L-G VOLT. GEN.
P
5
0 0.00
"
0.00
Gl
ARRESTER CURR.
m
m
4
zip
-h
"
0.; 140.0b bo.ob *;o.ob ito.ob 2bo.ob *i&
1388
_------
__----.
,/-
.*- --..
'. it indicates a normal fault-to-ground at the L.V. side of
the transformer which must not result in immediate
tripping of the H.V. c.b.
I A protection which detects a stuck pole and trips the
,: Ub-b H.V. c.b. could consist of a voltage relay connected to the
"\,. I .Y
.%' voltaic
voltage across contacts
open delta at the transformer-side P.T.s and a time relay
wired in series to it, released by a change of the position
of the gen.c.b. auxiliary switch and set to 20s. Such a
protection is feasible at low cost with existing
equipment.
Section 2 shows clearly that the test-voltages of the
gen.c.b. cover the maximum overvoltages to be expected
G-Generator at a stuck pole at any rate.
T-Transformer
4.3 Ferroresonance
Fig. 3 Phasor diagram: stuck pole close to phase opposition The phenomenon of "ferroresonance" or "relaxation
oscillations" is widely discussed in the relevant literature
Surge arresters at the transformer or generator [13, 141. These oscillations are characterized by the
terminals will not carry significant currents at those discharge of capacitances to ground via saturable P.T.
voltage levels (see Fig. 2) and, therefore, they will inductances causing periolc displacement of the system
neither have any influence nor be stressed in this case. neutral potential. A 3-phase system with an ungrounded
There is still a substantial safety margin, since the power neutral is a prerequisite and following additional
frequency withstand voltage to ground of the relevant conditions are to be fulfilled:
equipment is at least 3.5p.u. for a maximum operating - inductive P.T.s, single phase-to-ground
voltage of 27.5kV. - sytem capacitance to ground within certain limits
A critical situation can arise if a further contingency - luck-on event; normally a switching operation (trans-
is added, i.e. if a fault to ground occurs in one of the two former inrush, fault clearing causing asymmetry in the
phases, where the breaker has interrupted the load system).
current. If there is a fault on the generator side of the In order to remain stationary the oscillation of the
gen.c.b. the voltage to ground at the transformer side of neutral potential needs a periodic excitation by the 3-
the gen.c.b. rises to 3.7p.u. If a phase at the transformer phase system; in consequence, it will exhibit a harmonic
side of the gen.c.b. is grounded, the voltage at the or subharmonic frequency.
generator side of the gen.c.b. will reach a similar level. The following multiples of power frequency f are of
Transient overvoltages may be considerably higher (up to importance:
5.6p.u.) provided the fault occurs at the most - 3 times f: capacitance to ground very small, phase-to-
unfavourable instant. Surge arresters will be thermally ground voltages very high (3.5p.u.), easy to attenuate,
overloaded and, therefore, be destroyed under such rare
conditions. Anyhow, they would at least limit - 2 times f: capacitance to ground small, phase-to-ground
overvoltages for generator and transformer. voltages 2 + 3p.u., sometimes beat of oscillations, rare
Obviously, such a situation includes a certain amount - 1 time f: overvoltages appear in only 2 phases (1.3 +
of risk of damage and must, therefore, be avoided. The 3.5p.u.), therefore often mixed up with fault-to-
simplest and most efficient means is to open the H.V. c.b. ground, relatively frequent
in case of a stuck pole of gen. c.b. Analysis has shown - 0.5 times f, (second subharmonic): 1 + 1.7p.u.; with
that there are two criteria necessary and adequate for beat, in all phases, most frequent
detecting a stuck pole (without or with additional fault- - 0.33 times f, 0.25 times f, (third, fourth subharmonic):
to-ground): very rare, not stable
- there is always a voltage rise in the open delta winding For the second subharmonic oscillations, which are
of the P.T.s on the step-up transformer side of the gen. found frequently, overvoltages are modest and do not
c.b. (see Fig. 2), without or with additional fault-to- jeopardize the system; the problem is that the saturation
ground. currents may overheat and destroy the P.T.s which could
- this voltage rise appears within a certain period after result in short-circuits.
changing of breaker position, e.g. from 0 to about 20s According to the conditions mentioned above
after closing or opening of gen.c.b. If it appears later relaxation oscillations can only occur when the gen.c.b.
than about 20s after changing of breaker position then is open (generator neutral grounded via resistor).
1389
0
-
,Jfe,OfsE&,dt
80.00
1 . . I ,
200.00
, ,
240.00
, r
200.00
a ,
320.00
,
360.00
TABLE I
its clearing causes displacement of the voltages at the Transient overvoltages to ground in p.u. on the delta-winding of the step-
delta windings of the step-up transformer. However, up transformer at a single phase-to-groundfault in phase k
these effects are rather weak, which is shown by the
following results. Since the influence on the low voltage gen.c.b. closed gen.c.b. open
side is more pronounced if the gen.c.b. is open (due to a UB-G 2.2 2.0
small capacitive coupling of the delta winding of the UC-G 2.2 2.0
transformer to ground) only this case was analyzed. The
transformer was modelled three-phase by short-circuit
1390
6. ATMOSPHERIC
OVERVOLTAGES AND SURGE TRANSFER
1391
I I 1 I
low-voltage ride high-voltage ride
B -
-
T-LE I11
It is common practice to install surge arresters at the TRVs due to fault current interruption are amply
H.V. terminals of a transformer which is exposed to covered by the corresponding standards.
atmospheric overvoltages. According to IEC recom- Overvoltages at i n t e m p t i o n of magnetizing currents
mendations [4] the protective level should be at least ("current-chopping") are a special case and specific to
BIL/1.2 which would increase the safety margin for the gen.c.b. design. Experience shows that the maximum
L.V.-side, too. overvoltages to be expected are <3.5p.u. Arresters at
In our opinion, arresters at the low voltage side - in either side of the step-up transformer will further reduce
-
addition to the surge capacitors are not an absolute these values.
necessity. Since their maximum continuous operating The transfer of atmospheric overvoltages through the
voltage (MCOV) related to the nominal voltage is higher step-up transformer was measured and a simulation
(system with insulated neutral) than that of the H.V.-side scheme was developed based on these measurements
arresters, their protective effect is weaker. showing suffkient accuracy. It seems to the authors that
The influence of arresters at the L.V.-side is shown in the transformer model developed could also be applied to
Fig. 8b (otherwise same conditions as for Fig. 8a). The surge transfer calculations for other step-up transformers
overvoltage is reduced to about 80%. of similar rating. Those measurements and calculations
If arresters - in addition to the surge capacitors - are confirmed that a surge capacitor at the LV-side of the
installed, their location is of minor importance. As step-up transformer is highly recommendable, even if the
calculations have shown a distance of even 20m from the overvoltages to ground without surge capacitor are below
transformer to the arrester does not lower the the withstand voltage of the breaker. With a surge
effectiveness of the arrester. Obviously, this is due to the capacitor of 2125nF the steepness of the voltage surges is
rather low frequencies originated at the transformer LV- significantly reduced.
side. If arresters are installed at the H.V. side (usual case)
arresters at the L.V. side do not additionally improve
7. CONCLUSIONS the situation and may, therefore, be omitted.
The statements deduced from the analysis of a
In this paper insulation co-ordination aspects for a typical step-up transformer are applicable to the
power station with gen.c.b.s have been considered. conditions in other power stations under the assumption
By means of a typical power station configuration that with increasing voltage level at the HV-side also
with gen.c.b. the full scale of overvoltages (from power the generator operating voltage correspondingly grows.
frequency to atmospheric) has been analyzed.
The analysis consists of computer simulations and
measurements. 8. LITERATURE
As far as power frequency overvoltages are concerned
the situation is the same without and with gen.c.b. for ANSI C62.2-81: Guide for the Application of Valve
single phase faults to ground; the gen.c.b., however, Type Surge Arresters for A.C. Systems
allows selective protection in case of a fault. ANSI C92.1-1984: IEEE Standard for Surge
Ferroresonance overvoltages occurring when the step- Arresters for AC Power Circuits
up transformer is energized from the HV-side can easily ANSI C92.1-1982: American National Standard
be avoided by appropriate damping resistors in the delta Voltage Values for Preferred Transient Insulation
windings of the P.T.s. Levels
The consequences of faults of an extremely low IEC-Standard 7 1-2, 1976 Insulation Co-ordination,
probability as breakdown through the step-up transformer Part 2, Application Guide
may be mitigated by the gen.c.b.. Surge Transfer through Transformer-Generator
Another low probability occurrence, i.e. a mechanical Units, C.H. Hickling Proc. LEE Vol 116, No. 5 , May
failure in the gen.c.b., leading to a stuck pole condition 1969
will result in high power frequency overvoltages if there E.P. Dick, B.K. Gupta: Review of Generator Surge
is no adequate protection system. The criteria for such Protection Including Generator Breakers. IEEE
protection are given; the realization is feasible at low cost 1987, WM 216-5
with existing equipment. E.P. Dick, B.K. Gupta: Practical Design of
Switching overvoltages transferred from the HV-side Generator Surge Protection IEEE Vol 6, No. 2,
to the LV-side of the step-up transformer are modest. April 1991
Transients from a single phase to ground fault at the ANSIAEEE Standard C37.013-1993 with
LV-side rarely exceed 2.3p.u. and their frequency is Application Guide. Standard for AC High-Voltage
lowered by the surge capacitance .
1393
Generator Circuit-Breakers Rated on a Symmetrical Rated power 220MVA
Current Basis Connection YNd5
Electra No. 113, July 1987, pp. 43-50, "Generator Short-circuit reactance at rated voltage 12.30%
Circuit-Breaker. Transient Recovery Voltage in Tap changer, voltage change -5%/+5%
most Severe Short-circuit Conditions" X/Rratio 60
Electra No. 126, October 1989, pp. 555-63, BIL: Hv lO5DkVcrest
"Generator Circuit-Breaker. Transient Recovery LV 12SkVcrest
Voltages under Load Current and Out-of-Phase Power frequency, 50Hz, lmin 460kV
Conditions" no-load current at 0.92Ur 0.20%
Electromagnetic Transients Program (EMTP) 1.OOUr 0.34%
Rule Book, Bonneville Power Administration 1.06Ur 0.52%
Metal-Oxide Surge Arresters in AC Systems - Transformer capacitances:
CIGRE Brochure 60, April 1991 C1, low-voltage side to ground 8600pF
J.D. McCrumm: An Experimental Investigation of C2, high-voltage side to ground 2080pF
Subharmonic Currents, AIEE Transactions, 1942 c12, LV-Hv, 2870pF
Vol. 60, pp. 533-540 Losses, 3 phase, no-load 177kW
N. Germay et al.: Review of ferroresonance - Voltage transformer, 15.5kV
phenomena in h.v. power systems and presentation Type Pfiffner, VD2411 voltage factor 1.9130sec
of a voltage transformer model for predetermining 15.75kVl43; 0.1143; 0.1143; 0.113
them 130VA; 30VA; 1OOVA; 200VA, 8h
CIGRE 1974; Report 33-18 - System source short- circuit current on
Guidelines for Representation of Network Elements high-voltage side of transformer,3 ph. 26kA .
when Calculating Transients, by Working Group - Arrester, 15,5kV-side
33.02 (Internal Overvoltages), Type ABB MWA18,
CIGRE Brochure 1990 uc 18kV
M. Erche: Switching surges, Up (10kA) 52kVcrest
Book: Surges in High-Voltage Networks, edited by - Arrester 22OkV-side:
Klaus Ragaller, Plenum Press, New York 1980 Type: ABB MWL224
P. Glaninger: Das 'Schwingungsverhalten eines ein- uc 224kV
fachen Transformator-Ersatzschaltbildes Up (1OkA) 678kVcrest
ETZ-Archiv Bd. 5 , 1983 H. 11, S. 369-375 - Surge capacitor:
CIGRE Working Group 13.05: The Calculation of calculations based on values of: 125...250nF
Switching Surges
ELECTRA, NO. 32, pp. 17-42, 1974
9. ANNEX.
-
Data of generator, step-up transformer, voltage-trans-
former, high-voltage network and arresters used for the
analysis
- Power frequency 50Hz
- Generator data:
Rated power 228MVA
Rated voltage 15.5kV
BIL 125 kVcrest
Subtransient direct axis (xd") 0.141p.u.
Capacitance of armature winding to
ground all phases together 1 1.35pF
Generator grounding:
high resistance grounding (632.50, 16AIlOsec)
Inertia constant (H) 7.4sec