You are on page 1of 9

IEEE Transactions on Power Delivery, Vol. 10.No.

3, July 1995 1385

Insulation Co-ordination Aspects for Power Stations


with Generator Circuit-Breakers
M. Sanders G. Koppl, Member, IEEE J. Kreuzer
ABB HV Technologies Ltd. KOEPPL POWER EXPERTS Consultant, Transformer Division
Zurich, Switzerland Lupfig, Switzerland ABB Secheron Ltd., Geneva, Switzerland

Absfract - The generator circuit-breaker (gen.c.b.) located The following considerations are being presented in
between the generator a n d the step-up transformer, is now this paper:
being applied world-wide. I t has become a recognized a) temporary overvoltages and power frequency
electrical component of power stations which is largely due voltage changes
to economical advantages and increased power station b) switching overvoltages
availability. c) lightning overvoltages transferred to the generator
Technical protection considerations for power stations have side.
always been the reason for discussion and the object of In general, lightning arresters and a high-voltage
improvement. With the use of a gen.c.b., some points of circuit-breaker are connected to the high-voltage side at
view need to be considered anew. Not only the protection or close to the transformer terminals. However, the
system in case of fault conditions will be influenced, but protection of the low-voltage side of the transformer and
also the insulation co-ordination philosophy . the generator is not always adequately ensured, so that
Below the results of some calculations concerning expected further measures are required. Some calculations are
overvoltages a r e presented. These calculations are based on intended to serve as a help in making decisions, as far as
a transformer rated 264/15.5kV, 22OMVA. But the results insulation co-ordination in a power station is concerned.
a r e transferable to other power plants.
Some measurements carried out on a transformer of the 2.STANDARDE E E C37.0 13-89 FOR GENERATOR CIRCUIT-
same rating complement the calculations. BREAKERS [8]
O u r findings may contribute to an improvement in
insulation co-ordination and protection of the electrical The initial installation of generator switchgear in
system generator - step-up transformer. nuclear power stations has presented some problems in
relation to national standards. The authorities responsible
1. INTRODUCTION for security in nuclear installations demanded that
equipment be fully tested in relation to standards which
Insulation co-ordination in high voltage networks has were either not yet in force for gen.c.b.s or only partially
been discussed in some detail in ANSI as well as in IEC relevant to them. In the USA the Nuclear Regulatory
Standards [ l , 2, 3, 41. Some of these recommendations Commission favoured the application of generator
may be used as a basis for judging the insulation co- circuit-breakers as a means of ensuring enhanced security
ordination in power stations with generator circuit- on the one hand, but on the other hand this organisation
breakers (gen.c.b.) between the generator and the impeded the import of electrical equipment without an
transformer. There are also some publications dealing USA-approval certificate.
with technical questions of protection against Therefore, a working group of the IEEE was
overvoltages in power stations [5, 6 , 71. established in the early 1970's in order to develop a
standard for generator circuit-breakers, including
94 SM 4L6-5 PWRD A paper recommended and approved recommendations for the type tests based on actual plant
by t h e IEEE Transmission and D i s t r i b u t i o n Committee requirements.
of t'ne IEEE Power Engineering S o c i e t y f o r p r e s e n t a t -
i o n a t t h e IEEE/PES 1994 Summer Meeting, San
This work was supported by the results of
Francisco, CA, J u l y 24 - 28, 1994. Manuscript sub- measurements and studies regarding transient recovery
mitted October 5 , 1993; made a v a i l a b l e f o r p r i n t i n g voltages of gen.c.b.s, published in [9, lo], and has now
May 17, 1994. been completed with the issue of an additional
application guide which matches the standard C37.0 13
first published in 1989.
Below, the withstand voltages to ground and across
the contacts for a gen.c.b. according to this standard are
given:

0885-8977/95/$04.00 0 1994 IEEE


1386

Circ. -break. Power frequ. Impulse withst.


rated max.volt. 60Hz, lmin. 1.2150psec
kV, rms Dry, kV, rms kV, crest
High-Voltage c.b.
15.8 and below 50 110
15.9 to 27.5 60 125
27.6 to 38 80 150
HI
The power-frequency type test is intended to cover the
Arrester
Transformer
A Step-up transformer
264155kV,220MVA
performance at operating voltage, at temporary over-
voltages and at switching overvoltages. Xt=12.2%
In addition to this, the gen.c.b. in open position must I[--/ Arrester
withstand 1.5 times the phase-opposition voltage at a
breaker-pressure of 1 bar i.e. 1.5~2Uror 3.67p.u. with
1p.u. = 0.817Ur, equal to the crest value of the phase
voltage, and Ur = rated line-to-line voltage. Gen.c.b.
The rated max. voltage of the gen.c.b. is equal to the
max. voltage of the generator in the power station. Sofar,
generators have had max. voltages up to 27.5kV. Based
on this voltage a dielectric withstand voltage to ground
and across the contacts of the gen.c.b. of 3.8p.u. (power
Generator @15.5kV
Xd=14.1%
p
(E)
frequency) or 5.6p.u. for lightning overvoltages is to be
proved. With lower generator voltages these p.u. values
are higher. Fig. 1. Single line diagram ofthe system modelled.
The gen.c.b. shall be tested under conditions of
"current interrupting", like terminal short circuit-current, two-winding transformer 264/15.5kV, YNd5, surge
out-of-phase current and excitation current at the arresters at the H.V. terminals and optionally at the
corresponding recovery voltage. According to [SI the 15.5kV terminals of the transformer. Phase-to-ground
max. switching overvoltage imposed on the generator and P.T.s were modelled at the transformer terminals, and a
transformer and resulting from a fault current H.V. system 264kV was supposed to provide a short-
interruption is <2.25p.u. or <50.5kV (based on 27.5kV). circuit current of 26kA three-phase, 2 1kA single-phase.
The interruption of the no-load transformer current The system data are given in the Annex in detail.
where Overvoltages >2.25p.u. may originate is a typical For stuck-pole simulations the type 59 generator
no-fault switchmg duty. model of EMTP was used; for all other calculations a
The ratio between the Switching Impulse Insulation simple source model for the generator with R, L, C
Withstand (BSL) and the Basic Impulse Insulation representation was considered to be adequate.
Withstand (BIL) could be assumed to be >0.70 i.e. the Due to the broad scope of different types and
switching impulse withstand voltage of a generator or frequencies of overvoltages different transformer models
transformer is >0.70x125kVcrest X37.5kVcrest or 3.9p.u. have been chosen in accordance with CIGRE guidelines
based on the max. generator voltage of 27.5kV. [15]. A 3-phase representation comprising a YNd-
The power frequency type test for a generator is to be connection, the correct vector group (YNdS), the turn
carried out with a withstand voltage equal to (2Ur+l)kV ratio and the power frequency values of short-circuit
or (2x27.5+1)=56kV or 3.5p.u., (see ANSI C50.1-65), reactance and series winding resistance were common to
which is considerably higher than the max. switching all models. Since mainly 3-legged transformers are used
impulse due to current interruption. as step-up transformers, the zero-sequence reactance of
-
the arrangement core air gap - tank seen from the HV
3. SYSTEM DATAUSED FOR SIMULATIONS. side and arranged parallel to the delta winding was also
taken into account by using in all cases the "three phase"
Fig. 1 shows the single line diagram of the system extension of the "EMTP Saturable Transformer
modelled. The simulations have been carried out by Component". Core saturation was considered for all
means of the EMTP [ 111. stationary and switching overvoltages (single phase fault,
The system consists of a typical power station ferroresonance, interruption of magnetizing current)
arrangement comprising a 228MVA synchronous basing on manufacturer voltage-current data (rms) which
generator 15.5kV, 50Hz, a generator circuit-breaker were transformed to flux-current values by means of the
equipped with capacitors to ground of 125nF, a 220MVA EMTP support routine "Convert".
1387

4.POWERFREQUENCY
VOLTAGE
CHANGES During closing or opening of a circuit-breaker one pole
of the three phases might fail, i.e. one pole does not open
Voltage fluctuations of a relatively long duration or of or does not close (stuck pole),
power frequency can be transferred to the low-voltage For an operating system common to the 3 poles of a
side of the transformer either as a result of switching gen.c.b. a malfunction of one pole is a very unlikely
operations, or due to a dielectric breakdown on the high- failure. However, such an event cannot be completely
voltage side. They might also be a result of non-linearity excluded and would not be signalled by the auxiliary
oscillations such as ferro-resonance. Power frequency switch.
voltage fluctuations across the open generator circuit- Fig. 2 shows the simulation results of a load rejection
breaker which result from non-synchronism must be at 100% load (a low probability contingency) combined
covered by the power frequency withstand voltage test. with a stuck pole in phase A. After having reached
approximate phase-opposition conditions, which would
4.1 Single phase-to-ground faults, steady state. take about OSsec, the max. phase-to-ground voltage at
The above mentioned conditions lead to 43p.u. phase-to- the transformer terminals would reach 2.9p.u. (1.2 + 43),
ground voltages in the unfaulted phases. Combined with see also phasor diagram Fig. 3, and at phase opposition
load rejection power frequency overvoltages of the maximum voltage across the open breaker contacts
(l.lt1.4)43p.u. to ground might be generated. [12] would amount to 3.8p.u. (43(1.2 + 1.0)). These are
extreme values which in practice are reduced by the
4.2 Overvoltages as a consequence of a mechanical voltage control of the generator and will take far more
failure in the operating mechanism . time to develop if the breaker is opened at no-load
conditions.

9-
-I L-G VOLT. GEN.

P
5
0 0.00
"

0.00

Gl

ARRESTER CURR.
m
m
4

zip
-h

"
0.; 140.0b bo.ob *;o.ob ito.ob 2bo.ob *i&
1388
_------
__----.
,/-
.*- --..
'. it indicates a normal fault-to-ground at the L.V. side of
the transformer which must not result in immediate
tripping of the H.V. c.b.
I A protection which detects a stuck pole and trips the
,: Ub-b H.V. c.b. could consist of a voltage relay connected to the
"\,. I .Y
.%' voltaic
voltage across contacts
open delta at the transformer-side P.T.s and a time relay
wired in series to it, released by a change of the position
of the gen.c.b. auxiliary switch and set to 20s. Such a
protection is feasible at low cost with existing
equipment.
Section 2 shows clearly that the test-voltages of the
gen.c.b. cover the maximum overvoltages to be expected
G-Generator at a stuck pole at any rate.
T-Transformer
4.3 Ferroresonance
Fig. 3 Phasor diagram: stuck pole close to phase opposition The phenomenon of "ferroresonance" or "relaxation
oscillations" is widely discussed in the relevant literature
Surge arresters at the transformer or generator [13, 141. These oscillations are characterized by the
terminals will not carry significant currents at those discharge of capacitances to ground via saturable P.T.
voltage levels (see Fig. 2) and, therefore, they will inductances causing periolc displacement of the system
neither have any influence nor be stressed in this case. neutral potential. A 3-phase system with an ungrounded
There is still a substantial safety margin, since the power neutral is a prerequisite and following additional
frequency withstand voltage to ground of the relevant conditions are to be fulfilled:
equipment is at least 3.5p.u. for a maximum operating - inductive P.T.s, single phase-to-ground
voltage of 27.5kV. - sytem capacitance to ground within certain limits
A critical situation can arise if a further contingency - luck-on event; normally a switching operation (trans-
is added, i.e. if a fault to ground occurs in one of the two former inrush, fault clearing causing asymmetry in the
phases, where the breaker has interrupted the load system).
current. If there is a fault on the generator side of the In order to remain stationary the oscillation of the
gen.c.b. the voltage to ground at the transformer side of neutral potential needs a periodic excitation by the 3-
the gen.c.b. rises to 3.7p.u. If a phase at the transformer phase system; in consequence, it will exhibit a harmonic
side of the gen.c.b. is grounded, the voltage at the or subharmonic frequency.
generator side of the gen.c.b. will reach a similar level. The following multiples of power frequency f are of
Transient overvoltages may be considerably higher (up to importance:
5.6p.u.) provided the fault occurs at the most - 3 times f: capacitance to ground very small, phase-to-
unfavourable instant. Surge arresters will be thermally ground voltages very high (3.5p.u.), easy to attenuate,
overloaded and, therefore, be destroyed under such rare
conditions. Anyhow, they would at least limit - 2 times f: capacitance to ground small, phase-to-ground
overvoltages for generator and transformer. voltages 2 + 3p.u., sometimes beat of oscillations, rare
Obviously, such a situation includes a certain amount - 1 time f: overvoltages appear in only 2 phases (1.3 +
of risk of damage and must, therefore, be avoided. The 3.5p.u.), therefore often mixed up with fault-to-
simplest and most efficient means is to open the H.V. c.b. ground, relatively frequent
in case of a stuck pole of gen. c.b. Analysis has shown - 0.5 times f, (second subharmonic): 1 + 1.7p.u.; with
that there are two criteria necessary and adequate for beat, in all phases, most frequent
detecting a stuck pole (without or with additional fault- - 0.33 times f, 0.25 times f, (third, fourth subharmonic):
to-ground): very rare, not stable
- there is always a voltage rise in the open delta winding For the second subharmonic oscillations, which are
of the P.T.s on the step-up transformer side of the gen. found frequently, overvoltages are modest and do not
c.b. (see Fig. 2), without or with additional fault-to- jeopardize the system; the problem is that the saturation
ground. currents may overheat and destroy the P.T.s which could
- this voltage rise appears within a certain period after result in short-circuits.
changing of breaker position, e.g. from 0 to about 20s According to the conditions mentioned above
after closing or opening of gen.c.b. If it appears later relaxation oscillations can only occur when the gen.c.b.
than about 20s after changing of breaker position then is open (generator neutral grounded via resistor).
1389

inductance, winding resistances, saturation charac-


X OPEN DELTA VOLT. p.’r.
teristics, coupling capacitances between H.V. and L.V.
windings and capacitances to ground according to the
recommendations given in [ 151. Fault initiation takes
0.00 place at the peak of phase-to-ground voltage. The
parameter was capacitance to ground at the low voltage
side i.e. existence and value of a surge capacitance.
OPEN DELTA VOLT. P.T. The results are shown in the following table.
b)

0
-
,Jfe,OfsE&,dt
80.00
1 . . I ,
200.00
, ,
240.00
, r
200.00
a ,
320.00
,
360.00
TABLE I

Overvoltages to ground in P.U. on the delta-winding of the transformer as


a consequence of a single phase short-circuit in the phase “A” of the high-
Fig. 4 Ferroresonance with P.T.s: voltage network.
a) without, b) with damping resistor in open delta winding at fault steady after current
inception state interruption
Fig. 4a shows the simulation results of a transformer surgecap. no yes no yes no yes
energization from the H.V. side and generated relaxation UA-G 1.4 1.0 1.3 0.7 1.4 1.2
oscillations. The second subharmonic is clearly visible in UB-G 1.0 1.0 0.8 1.0 1.0 1.0
the open delta voltage of the P.T.s. If an appropriate UC-G 1.0 1.0 0.9 0.6 1.8 1.2
damping resistor is inserted in the open delta the
oscillations disappear very quickly (Fig. 4b). We can, therefore draw the conclusion, that single
The following factors are important for avoiding phase-to-ground faults at the HV-side have only a minor
relaxation oscillations: influence on the voltage displacement at the LV-side and
selection of P.T.s with a high voltage factor (>1.9) that surge capacitors equalize and reduce transient and
ample VA rating of P.T.s and delta winding steady-state voltages. A larger surge capacitance (250nF)
damping resistor in open delta corresponding to VA did show only negligible improvements.
rating;
if not sufficient, time-controlled resistor (>VA rating of 5.2 Overvoltages due to single phase-to-ground faults
delta winding), or special P.T. designs . at the L.V.-side of the step-up transformer
Due to the high neutral-to-ground impedance the fault
4.4 Dielectric breakdown between H.V. and L.V. current is at any rate very small irrespective of the fact
windings of the transformer that the gen.c.b. is closed or open (resistive if the
A dielectric breakdown through the transformer with generator neutral is grounded via a resistor and gen.c.b.
partial transfer of the high voltage to the low voltage side closed, capacitive at open gen.c.b.). The natural
can be regarded as another low probability event. Surge frequency of the voltage oscillation in the unfaulted
arresters are likely to be destroyed in such an event, but phases is rather high. It is determined by subtransient
would keep away overvoltages from the generator in and short-circuit inductance and the small capacitances
combination with rapid tripping of the H.V. c.b and the to ground. As far as our calculations are concerned
gen.c.b., thus limiting further damages. 8.lkHz were reached at gen.c.b. closed and 10.3kHz at
gen.c.b. open, even with capacitors of 250nF at every side
5. SWITCHING
OVERVOLTAGES of the gen.c.b.. Over-voltages are modest and quickly
damped out, see following table.
5.1 Overvoltages due to single line-to-ground faults
in the H.V. system TABLE 11
A single line-to-ground fault in the H.V. system and ~ ~~~

its clearing causes displacement of the voltages at the Transient overvoltages to ground in p.u. on the delta-winding of the step-
delta windings of the step-up transformer. However, up transformer at a single phase-to-groundfault in phase k
these effects are rather weak, which is shown by the
following results. Since the influence on the low voltage gen.c.b. closed gen.c.b. open
side is more pronounced if the gen.c.b. is open (due to a UB-G 2.2 2.0
small capacitive coupling of the delta winding of the UC-G 2.2 2.0
transformer to ground) only this case was analyzed. The
transformer was modelled three-phase by short-circuit
1390

of a gen.c.b. is uncritical if arresters are connected to


either side of the transformer.

6. ATMOSPHERIC
OVERVOLTAGES AND SURGE TRANSFER

Since the analyses for power frequency and switching


overvoltages are based on proven models, the accuracy of
calculations rarely comes up for discussion. However, the
situation is different for atmospheric overvoltages with
steep fronts hitting a step-up transformer and being
transferred to the generator side. The practical
consequence of this is that the dimensioning of
corresponding counter-measures as surge capacitors and
arresters is carried out on the safe side (which is always
-
I ime Ge!2y td recommendable).
Obviously, the transformer is the crucial component.
Fig. J Inherent recovery voltage after short-circuit interruption There is some literature on how to model a transformer
for this problem [15, 171 indicating that coupling
5.3 Fault current interruption with the gen.c.b. capacitances and frequency dependent damping must be
The inherent recovery-voltage is shown in Fig. 5 correctly represented, but being of little help as far as the
(see "Application Guide" of Standard C37.013-93). After choice of values is concerned.
a short-circuit interruption the recovery-voltage appears Below, a rather simple approach is described. It
across the contacts of the first phase-to-clear with a rate- resulted in satisfactory conformity between measurements
of-rise of and simulations for a typical 220MVA two-winding step-
up transformer. The basis for this approach were
s = 1.5. (1/ 0.85)-2.& - lod U, *J2/3[kV/psec] measurements of the transformer (data see Annex) at
with y = 1.5 = amplitude factor of the inherent TFtV and various conditions and with various shapes of impulse
fo = natural frequency of the network. The maximum voltages. The transformer neutral was ungrounded and
voltage is the H.V. terminals A and B were grounded via resistors
of 500Q each representing the surge impedance of a
Ez = 1 . 5 - 1 . 5 - U r - m =1.84Ur ~ 2 . 2 5 p . u . transmission line. The impulse voltage, stemming from a
with lp.u.= U, = O.816Ur low-voltage impulse generator of 400V was applied to the
H.V. terminal C of the transformer. The chosen impulse
Ur = maximum line-to-line voltage of the generator.
voltage shapes were full wave 1/50ps, chopped wave
The voltage E2 appears also at the generator, transformer
terminals respectively in case of clearing a 3-phase fault- (1/50ps, 18ps) and wave 65/520ps.
to-ground. Fig. 6a and 6b show as an example the voltage
responses at the L.V.-side of the transformer (without,
5.4 Interruption of the transformer magnetizing respectively with surge capacitor), if a full-wave is
current applied at a H.V. terminal.
Due to instabilities of the arc between the breaker The same conditions (voltage shapes applied on H.V.
contacts premature current zeros at high frequencies terminal C, 500R resistors at the H.V. terminals A and
occur frequently when switching small inductive B, etc.) have been chosen for the simulation model. The
currents, leading to "current chopping". The "chopped" transformer was modelled according to Fig. 7, i.e. correct
current flowing in the no-load inductance can only winding ratio, vector group, total short-circuit
charge the transformer capacitances. This results in inductance, partitioned equally between the H.V. - and the
voltage oscillations of high amplitudes, occasionnally. L.V.-side. The frequency dependence of short-circuit
The tendency to chop a current also depends on the inductance and damping has been taken into account by
breaker-type, but various tests have shown, that the subdividing the short-circuit inductance on both voltage
maximum overvoltages to be expected are C3.5pu [16]. sides (La/Lb = 20/80) and inserting a parallel resistance
Arresters on either side of the transformer would to each inductance. Such a circuit with k elements has
reduce these overvoltages to less than 3p.u. The energies been shown in [ l j ] , without giving any proposal
to be absorbed by the arresters are extremely small. regarding the choice of values of inductances or
Therefore, switching a transformer at no-load by means resistances, however. In [ 181 there are time constants
~

1391

I I 1 I
low-voltage ride high-voltage ride
B -
-

Fig. 7 Transformer model for surge transfer simulations


(only one phase shown, without external connections)

The surge capacitance of 2 times 125nF decreases the


C natural frequency of the transformer at the L.V.-side
from 60kHz (without capacitance) to I7kHz, mitigating
the voltage rise. With regard to the voltage peak values to
ground there is also a difference of about 20% (100%
versus 82% with surge cap.).
It should be noted that at a full wave crest of 1050kV
(BIL) at the H.V. terminal of the step-up transformer,
with gen.c.b. in open position and without surge
Fig. 6 Measured voltage responses at L.V.-side of step-up transformer at capacitor, 63kV to ground would appear, i.e. 5.0.p.u.
full wave applied to H.V. terminal C w h c h is clearly below the withstand voltage of llOkV
a) without, b) with surge capacitor crest (8.7p.u. at max. operating voltage of 15.5kV).
However, a surge capacitance of 2125nF will prevent
given for transformers of various ratings and voltage spikes with steep fronts at the transformer L.V.-
corresponding preliminary values for these resistances side and lower the natural frequency of the transformer
have been chosen. By adjusting the resistances and considerably.
simulation results to the test results satisfactory ON
L-6 VOLT. [LVI
conformity was found, if
Ra = 7 * o 5 0 ~ z * L aand
Rb 2000 . o5OJ-j~* Lb.
Fig. 8a shows simulation results corresponding to
measurements of Fig. 6. The numerical results of the
simulations and the test-results, i.e. the crest values of
the transferred surges as a percentage of the applied
voltage, are given below.

T-LE I11

ulv/Uhv, in %, surge wave 1.2/5Ops

surge cap. no Yes


sim./measur. sim./measur.
ua-G - 1 3.4 0.3 I 0.5
Ub-G -1 6.0 4.91 4.5
uc-G -
- 1 5.4 - 4.8 I - 4.8
This transformer model for surge transfer calculations
seems to reproduce voltage responses adequately correct Fig. 8 Calculated voltage responses corresponding to Fig. 6b
with respect to insulation co-ordination purposes. a) without, b) with surge arrester at L.V.-side
1392

It is common practice to install surge arresters at the TRVs due to fault current interruption are amply
H.V. terminals of a transformer which is exposed to covered by the corresponding standards.
atmospheric overvoltages. According to IEC recom- Overvoltages at i n t e m p t i o n of magnetizing currents
mendations [4] the protective level should be at least ("current-chopping") are a special case and specific to
BIL/1.2 which would increase the safety margin for the gen.c.b. design. Experience shows that the maximum
L.V.-side, too. overvoltages to be expected are <3.5p.u. Arresters at
In our opinion, arresters at the low voltage side - in either side of the step-up transformer will further reduce
-
addition to the surge capacitors are not an absolute these values.
necessity. Since their maximum continuous operating The transfer of atmospheric overvoltages through the
voltage (MCOV) related to the nominal voltage is higher step-up transformer was measured and a simulation
(system with insulated neutral) than that of the H.V.-side scheme was developed based on these measurements
arresters, their protective effect is weaker. showing suffkient accuracy. It seems to the authors that
The influence of arresters at the L.V.-side is shown in the transformer model developed could also be applied to
Fig. 8b (otherwise same conditions as for Fig. 8a). The surge transfer calculations for other step-up transformers
overvoltage is reduced to about 80%. of similar rating. Those measurements and calculations
If arresters - in addition to the surge capacitors - are confirmed that a surge capacitor at the LV-side of the
installed, their location is of minor importance. As step-up transformer is highly recommendable, even if the
calculations have shown a distance of even 20m from the overvoltages to ground without surge capacitor are below
transformer to the arrester does not lower the the withstand voltage of the breaker. With a surge
effectiveness of the arrester. Obviously, this is due to the capacitor of 2125nF the steepness of the voltage surges is
rather low frequencies originated at the transformer LV- significantly reduced.
side. If arresters are installed at the H.V. side (usual case)
arresters at the L.V. side do not additionally improve
7. CONCLUSIONS the situation and may, therefore, be omitted.
The statements deduced from the analysis of a
In this paper insulation co-ordination aspects for a typical step-up transformer are applicable to the
power station with gen.c.b.s have been considered. conditions in other power stations under the assumption
By means of a typical power station configuration that with increasing voltage level at the HV-side also
with gen.c.b. the full scale of overvoltages (from power the generator operating voltage correspondingly grows.
frequency to atmospheric) has been analyzed.
The analysis consists of computer simulations and
measurements. 8. LITERATURE
As far as power frequency overvoltages are concerned
the situation is the same without and with gen.c.b. for ANSI C62.2-81: Guide for the Application of Valve
single phase faults to ground; the gen.c.b., however, Type Surge Arresters for A.C. Systems
allows selective protection in case of a fault. ANSI C92.1-1984: IEEE Standard for Surge
Ferroresonance overvoltages occurring when the step- Arresters for AC Power Circuits
up transformer is energized from the HV-side can easily ANSI C92.1-1982: American National Standard
be avoided by appropriate damping resistors in the delta Voltage Values for Preferred Transient Insulation
windings of the P.T.s. Levels
The consequences of faults of an extremely low IEC-Standard 7 1-2, 1976 Insulation Co-ordination,
probability as breakdown through the step-up transformer Part 2, Application Guide
may be mitigated by the gen.c.b.. Surge Transfer through Transformer-Generator
Another low probability occurrence, i.e. a mechanical Units, C.H. Hickling Proc. LEE Vol 116, No. 5 , May
failure in the gen.c.b., leading to a stuck pole condition 1969
will result in high power frequency overvoltages if there E.P. Dick, B.K. Gupta: Review of Generator Surge
is no adequate protection system. The criteria for such Protection Including Generator Breakers. IEEE
protection are given; the realization is feasible at low cost 1987, WM 216-5
with existing equipment. E.P. Dick, B.K. Gupta: Practical Design of
Switching overvoltages transferred from the HV-side Generator Surge Protection IEEE Vol 6, No. 2,
to the LV-side of the step-up transformer are modest. April 1991
Transients from a single phase to ground fault at the ANSIAEEE Standard C37.013-1993 with
LV-side rarely exceed 2.3p.u. and their frequency is Application Guide. Standard for AC High-Voltage
lowered by the surge capacitance .
1393
Generator Circuit-Breakers Rated on a Symmetrical Rated power 220MVA
Current Basis Connection YNd5
Electra No. 113, July 1987, pp. 43-50, "Generator Short-circuit reactance at rated voltage 12.30%
Circuit-Breaker. Transient Recovery Voltage in Tap changer, voltage change -5%/+5%
most Severe Short-circuit Conditions" X/Rratio 60
Electra No. 126, October 1989, pp. 555-63, BIL: Hv lO5DkVcrest
"Generator Circuit-Breaker. Transient Recovery LV 12SkVcrest
Voltages under Load Current and Out-of-Phase Power frequency, 50Hz, lmin 460kV
Conditions" no-load current at 0.92Ur 0.20%
Electromagnetic Transients Program (EMTP) 1.OOUr 0.34%
Rule Book, Bonneville Power Administration 1.06Ur 0.52%
Metal-Oxide Surge Arresters in AC Systems - Transformer capacitances:
CIGRE Brochure 60, April 1991 C1, low-voltage side to ground 8600pF
J.D. McCrumm: An Experimental Investigation of C2, high-voltage side to ground 2080pF
Subharmonic Currents, AIEE Transactions, 1942 c12, LV-Hv, 2870pF
Vol. 60, pp. 533-540 Losses, 3 phase, no-load 177kW
N. Germay et al.: Review of ferroresonance - Voltage transformer, 15.5kV
phenomena in h.v. power systems and presentation Type Pfiffner, VD2411 voltage factor 1.9130sec
of a voltage transformer model for predetermining 15.75kVl43; 0.1143; 0.1143; 0.113
them 130VA; 30VA; 1OOVA; 200VA, 8h
CIGRE 1974; Report 33-18 - System source short- circuit current on
Guidelines for Representation of Network Elements high-voltage side of transformer,3 ph. 26kA .
when Calculating Transients, by Working Group - Arrester, 15,5kV-side
33.02 (Internal Overvoltages), Type ABB MWA18,
CIGRE Brochure 1990 uc 18kV
M. Erche: Switching surges, Up (10kA) 52kVcrest
Book: Surges in High-Voltage Networks, edited by - Arrester 22OkV-side:
Klaus Ragaller, Plenum Press, New York 1980 Type: ABB MWL224
P. Glaninger: Das 'Schwingungsverhalten eines ein- uc 224kV
fachen Transformator-Ersatzschaltbildes Up (1OkA) 678kVcrest
ETZ-Archiv Bd. 5 , 1983 H. 11, S. 369-375 - Surge capacitor:
CIGRE Working Group 13.05: The Calculation of calculations based on values of: 125...250nF
Switching Surges
ELECTRA, NO. 32, pp. 17-42, 1974

9. ANNEX.

-
Data of generator, step-up transformer, voltage-trans-
former, high-voltage network and arresters used for the
analysis
- Power frequency 50Hz
- Generator data:
Rated power 228MVA
Rated voltage 15.5kV
BIL 125 kVcrest
Subtransient direct axis (xd") 0.141p.u.
Capacitance of armature winding to
ground all phases together 1 1.35pF
Generator grounding:
high resistance grounding (632.50, 16AIlOsec)
Inertia constant (H) 7.4sec

- Step-up transformer (rated values):


Rated voltage 264115.5kV

You might also like