You are on page 1of 6

Objective Methods to Interpret Partial-Discharge Data

on Rotating-Machine Stator Windings


Greg C. Stone, Fellow, IEEE, and Vicki Warren, Member, IEEE
From IEEE Transactions on Industry Applications Vol. 42, No. 1, January/February 2006
Pages (195–200)

Approved for publication in the


Abstract—Partial-discharge (PD) measurements have long been IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS
by the Pulp and Paper Industry Committee of
used to assess the condition of the electrical insulation in motors the IEEE Industry Applications Society. Manuscript submitted
and generators rated 3.3 kV and above. There are many ways to for review June 23. 2005 and released for publication September
12,2005.
measure PDs during normal service of the motor or generator. The authors are with Iris Power Engineering Inc., Toronto, ON
M9C 1B2,
Unfortunately most of the measurement methods mix stator Canada (e-mail: gstone@irispower.com).
PD with electrical-interference signals from poor electrical Digital Object Identifier 10.1109/TIA.2005.861273
In general, for machines rated 3.3 kV and above, over 50 years
connections, power tool operation, corona from transmission of experience with PD testing in motors and generators has shown
lines, etc. The result can be false indications of stator-winding that months, if not years, of warning is often given before a winding
failure is likely to happen [I], [3].
problems, reducing confidence in PD measurements. Another
issue with online PD testing is interpretation, i.e., identifying There are many methods available to detect the PD activity in
which machines are in good condition and which machines operating motors and generators [1]. The electrical techniques rely
need maintenance. In the past decade, a database of over 60000 on monitoring the current or voltage pulse that is created whenever
test results has been assembled. In hundreds of machines, the a partial discharge occurs. The earliest methods measured the PD
condition of the insulation determined by a visual inspection pulse currents by means of a high-frequency current transformer
has been compared to the PD levels. The result is a table at the neutral point [2]. Others have used the leads from RTD
that provides an objective means of determining the stator- temperature sensors to serve as an antenna [4], [5], although
insulation condition relative to other similar machines. An organizations such as Electric Power Research Institute (EPRI) and
analysis of the results also shows that there are significant International Council on Large Electric Systems (CIGRE) have
differences in PD activity between manufacturers. This paper expressed reservations about the use of RTDs since the method
gives a review of the methods that can reduce the risk of false is controversial and interpretation is extremely subjective [6],[7].
indications, thus making the measurement less subjective. Today, the majority of machines that are routinely PD tested online
employ high-voltage capacitors as PD sensors [1].
Index Terms—Electrical insulation, partial discharge (PD), A key challenge with PD measurements is encountered when
stator winding. the motor or generator is monitored during normal operation.
Since the machine is connected to the power system, an electrical
I. INTRODUCTION interference (noise) is often present. Noise sources include corona
from the power system, slip ring/commutator sparking, sparking
PARTIAL discharges (PDs), sometimes also known as corona, are from poor electrical connections, arc welder operation, and/or
small electrical sparks that occur in deteriorated or poorly made power tool operation. This electrical noise masks the PD pulses
stator-winding insulation systems in motors and generators rated and may cause an inexperienced technician to conclude that a
3.3 kV and above. Over the past 15 years, online PD monitoring stator winding has high levels of PD, when it is actually the noise.
has become the most widely applied method to determine the The consequence is that a good winding is incorrectly assessed as
condition of the electrical insulation in such machines [l]-[3]. PD being defective, meaning that a false alarm is given suggesting that
testing detects most (but not all) of the common manufacturing and the winding is bad, when it is not.
deterioration problems in form-wound stator windings, including Such false alarms reduce the credibility of online PD tests; and
the following: even today, many feel that online PD testing is a “black art” best
left to specialists. This paper briefly describes objective methods
1) poor impregnation with epoxy; that separate a PD from the noise in motors and high-speed
2) poorly made semiconductive coatings; generators that are often associated with pulp and paper mills and
3) insufficient spacing between coils in the endwinding area; petrochemical plants.
4) loose coils in the slot;
5) overheating (long-term thermal deterioration);
6) winding contamination by moisture, oil, dirt, etc.;
7) load cycling problems;
8) poor electrical connections (although this is not strictly an
insulation problem).
A large number of PD results using the same test method (and
Paper PTD-05-12, presented at the 2005 IEEE Pulp and Paper Industry Conference, Jacksonville, FL
collected in an manner that the noise is suppressed) have been
accumulated in a single database. Towards the end of 2003, over
60 000 test results have been accumulated; and simple statistical
analysis has been applied to the database in order to extract
information to better interpret PD results. The main purpose of this
analysis is to help test users to objectively determine which motors
and generators have deteriorating stator insulation, allowing them
to plan appropriate maintenance. However, some interesting results
have emerged on the differences in PD activity as a function of
winding age, insulation type, and machine manufacturer. This
paper also presents these findings.

II. NOISE-SEPARATION METHODS

To enable automated statistical analysis of large quantities of PD


data (for example, from 60 000 measurements), one first needs the Fig. 1. Attenuation and dispersion of a pulse as it travels along a cross-linked
data to be purely stator PD and not a mixture of a PD and a noise. polyethylene power cable of different lengths.
If the PD and the noise are mixed together, then a human expert same capacitor used for the PD sensor.
is needed to review each test result and subjectively extract the
key PD data (for example, the peak PD magnitude—Qm) from the B. Surge-Impedance Mismatch
combined noise and PD signals. This clearly would be very time
consuming and subject to disagreements among experts. In many cases, a motor or a generator is fed by air-insulated bus
To date, PD detectors based on RTDs or radio frequency or has internal circuit ring buses. In general, such buses have a
current transducers (RFCTs) seem to require review by an expert characteristic (or surge) impedance of about 100 Ω.
to separate stator PD from all other signals [1]. Thus, the use of
automated statistical procedures to analyze vast quantities of PD In contrast, the surge impedance of a coil in a stator slot is much
data from such sensors is not practical. As a result, there are no lower—typically on the order of 30 Ohm. A noise pulse from the
simple criteria to help motor and generator owners assess if a PD power system that travels along the air-insulated bus sees a source
level is high or not when RTDs or RFCTs are used as PD sensors. impedance of 100 Ohm and then encounters the coil impedance of
Even with capacitive PD sensors, noise is sometimes mixed with 30 Ohm. Using the transmission-line theory, the first peak of a fast-
PD, preventing automated analysis. rise-time noise pulse is attenuated to about 25% of the original
Over 20 years ago, the North American utility industry sponsored magnitude. A PD pulse originating in the winding has a source
research to develop an objective online PD test for machines impedance of 30 Ohm, and then encounters the 100-Ohm impedance
that could be performed and interpreted by plant electrical staff of the air-insulated bus. From the transmission-line theory, a reflection
with a few days of training [1]. The PD test that was developed and a superposition occur, which results in the first peak of the
emphasized separating PD pulses from electrical-noise pulses. In PD pulse current being amplified by about 50%. The high-speed
fact, the techniques developed during this research depend on the traveling wave properties of the PD and noise pulses amplify the
following four separate noise-separation methods—since not one PD and suppress the external noise, enabling another method of
method was found to be completely effective on its own: increasing the SNR. To use this method, the noise and PD pulses
must be detected with their original rise times of < 5 ns, and the PD
1) frequency domain filtering; sensor must be within 1 m or so of the coils.
2) surge-impedance mismatch;
3) pulse-shape analysis: C. Pulse-Shape Analysis
4) time of noise and PD pulse arrival from a pair of sensors.
Practically, to reduce the risk of false indications to less A third method of separating a PD from a noise depends on the
than a few percent, at least three of the four methods are time-domain characteristics of the PD and noise pulses. Short
implemented simultaneously. In high noise environments, all rise-time current pulses, no matter what their source, are modified
four are implemented. as they travel along a power cable. There are two types of
modification: attenuation and dispersion, where the latter refers
A. Filtering to the frequency dependent attenuation of the pulse. The longer
the distance the pulse must travel, the greater is the attenuation
As part of the utility research project, surveys were performed of and dispersion encountered. Fig. 1 shows the effect of these two
the noise environment in typical plants. It was found that the noise properties as a voltage pulse propagates along a power cable. As
tended to produce the greatest signals at frequencies below 10 MHz the pulse propagates farther, the magnitude of the pulse decreases
or so. In contrast, when measured close to the stator winding, PD due to attenuation, and the rise time of the pulse lengthens due to
produces frequency components up to several hundred megahertz dispersion.
[8]. Thus, the highest PD signal-to-noise ratio (SNR) and thus the If a PD sensor is installed very close to the stator winding (say
lowest risk of false indications occurs if the PD is measured above less than 1 m), then any PD pulses from the stator winding will
about 40 MHz. A simple single-pole high-pass filter can be realized undergo negligible attenuation and dispersion as the PD pulse
with a 50-Ω input oscilloscope or a measurement instrument with travels to the sensor. However, if a noise pulse from the power
a high voltage capacitance of about 80 pf. The capacitor is the system first has to propagate through many meters of power cable,
Fig 2. Use of two capacitors per phase to separate a PD and a power-system noise based on the direction of pulse travel. Two sensors are only
needed if there is approximately less than 30 m of power cable between the switchgear and the motor.

then the noise pulse will be significantly reduced in magnitude, and the phase position with respect to the
magnitude and will have a longer rise time. By digitally 60-Hz ac cycle. Fig. 3 shows a typical plot of the PD
measuring the rise time, the PD can be separated from a from one phase of a motor stator winding. Consistent
noise on a pulse-by-pulse basis using rise time or pulse with international standards for PD testing of inductive
width [9]. Although intended to separate the PD from the apparatus (IEEE 1434 and IEC 60270), the pulse
noise that must travel along a power cable, pulse-shape magnitude is measured in the absolute units of millivolts
analysis is also effective in separating sparking sources (mV). From each test, two summary indicators are
on the machine rotor (for example, sparking from shaft extracted, representing all the PD pulse data collected.
ground brushes or slip-ring sparking in synchronous The peak positive and negative PD pulse magnitudes
machines), since such a noise tends to have a slower (+Qm and -Qm) represent the highest PD pulses
rise time when coupled to the stator winding. measured in mV with a minimum PD repetition rate of
ten pulses per second. Qm is a reasonable predictor of
D. Pulse Time of Arrival insulation condition at the most deteriorated location
in the winding. A high Qm measured in a winding
Where the connection to the power system is via air- compared to a lower Qm in another winding, usually
insulated bus or very short power cables and thus the implies that the former winding is more deteriorated.
pulse shape is not sufficiently different between a noise
and a PD, an additional noise-separation method based A. Database to the end of 2003
on using two sensors per phase has been implemented
(Fig. 2). If the sensors are at least two meters apart, a Since 1992, test results from portable test instruments
pulse from the power system will arrive at the “S” sensor were combined into a single database. This totaled to
before they are detected by the “M” sensor. Similarly, 60342 tests until the end of 2003 [10]. The database
if the pulse is due to stater-winding PD, the pulse will contains many repeat tests, sometimes performed over
first arrive at the “M” sensor before it arrives at the “S” many years. Also, many of the tests were done at different
sensor. With fast responding digital logic, the pulses can operating conditions. Machine operating conditions can
be classified as a noise or a PD, based on which sensor affect the PD activity and thus add additional variability
detects the signal first. to the analysis [1]. Therefore, the database was carefully
reduced such that the following applied.
III. PD DATA
1) Only online PD readings obtained when the
The noise-separation methods mentioned above, with machine was operating at or near full load at normal
the practical implementation using 80-pF capacitors operating temperature are included.
and appropriate digital instrumentation, has been 2) There is only one test result collected per sensor,
permanently installed on more than 6000 motors and thus, only the latest reading is extracted.
generators around the world. Some of the installations 3) Tests were discarded where there was reason to
were made over 20 years ago. As a result, a very believe the measurement was mislabeled.
large body of data has been collected where the PD is
essentially noise free. Once the PD is separated from The result of this culling is that to the end of
the noise, electronic instruments record the number, the 2003, there were 4828, 3953, and 2211 statistically
Fig. 3. Typical PD data from one phase are plotted with respect to the 60-Hz ac cycle. The vertical scale is the positive and negative PD magnitude in millivolts. The color
represents how many discharges are occurring per second at this magnitude and phase position. The higher the PD, the larger is the defect within the insulation. The peak
PD magnitude (Qm) for this phase is —400 mV and +200 mV.

independent test results for hydrogenerators, turbo generators, and operating voltage of a motor or generator increases, the 90% level
motors, respectively, in the database. also increases. Clearly, PD results from a 13.8-kV stator should not
be confused with those from a 6.9-kV stator. Statistical analysis
B. Statistical Distribution of PD Data (assuming the normal distribution) indicates that there is < 0.01
% chance that the voltage rating is not a key factor influencing the
The database was analyzed to determine the effect on Qm of Qm levels.
several different factors, including the following: With this table, it is now possible for motor and generator owners
to determine if the stator-winding insulation has a problem with
1) operating voltage of the stator winding; only an initial test. In addition, with some limitations, motor and
2) winding age: generator manufacturers can use this information as an indicator of
3) winding manufacturer. the relative quality of a new winding. If the PDs were higher than
that found on 90% of similar machines, then off-line tests and/
The range in Qm from all the tests for the particular operating or a visual inspection would be prudent. Continuous PD monitors
voltage was established for each set of the above factors. A would have their alarm levels set to the 90% level.
cumulative version of the statistical distribution is shown in Table
I. For example, for a 13.8-kV stator: 25% of tests had a Qm below C. Effect of Winding Age and Manufacturer
44 mV; 50% (the median) of the tests had a Qm below 123 mV;
75% -were below 246 mV; and 90% of tests yielded a Qm below An analysis of the statistical distribution of PDs for several
508 mV. Thus, if a Qm of 500 mV is obtained on a 13.8-kV motor, manufacturers was also performed. Fig. 4 shows the results
then it is likely that this stator will be deteriorated, since it has PD for 13-15-kV stators from 11 different original equipment
levels higher than 90% of similar machines. In fact, in over 200 manufacturers (OEMs) based around the world. Note that the data
machines where a stator was visually examined after registering a covers all ages of machines and all insulation systems made by
PD level greater than 90% of similar machines, significant stator- these manufacturers over the years. Clearly, there are differences
winding-insulation deterioration was always observed [11]. between the manufacturers. For example, OEMs D, E, H, and J
The effect of a particular factor on Qm was determined by have relatively low PDs on average, whereas manufacturer B has
comparing 90 percentile levels between the two data sets composed a relatively high PD for its fleet of machines. The cause of the
of, for example, 13.8-kV machines. It was concluded that this differences between manufacturers is unknown, but it may be due
factor is important in interpreting results if there was a significant to different manufacturing processes, electric-stress design levels,
difference in the average and 90% distribution levels of Qm for and assembly methods.
the two sets. From Table I, it is interesting to note that as the One surprising result from the statistical analysis of the database
Fig. 5. PD activity for nine motor and generator manufacturers as a function of the year the stator winding was built or rewound. The PD tests were done in 2003. For
some manufacturers, the PD activity for machines made in the past ten years is higher than machines they made more than ten years ago. 75th percentile of PD results by
manufacturer and year of installation (13-15-kV air-cooled machines with 80-pF sensors).

Pig. 4. Plot of PD magnitude versus cumulative probability of occurrence for 11 major motor and generator manufacturers. Manufacturer B has higher PD than most
other manufacturers of 13.8-kV motor and generator stator.

was the distribution of Qm as a function of winding, age. Fig. 5 recognized proven too] to help maintenance engineers identify
illustrates the PD results in the database from machines that were which stator windings need off-line testing, inspections, and/
one-year old to greater than 30 years old. There is no consistent or repairs.
trend—which is surprising since one would normally assume that 2) Objective separation of a PD and a noise is crucial if one is
older windings would be more deteriorated and thus have higher PD to automate the analysis of the huge volumes of data that can
levels. Fig. 5 implies that both older windings and new windings come from online PD tests. Four complimentary methods are
can have about the same high PD activity. In fact, four brands of described and were used for the data reported in this paper.
air-cooled windings manufactured in the past 10 years seem to have 3) With over 60 000 test results acquired with the same test
higher PD activity than older machines. This may reflect the fact that methods, what constitutes a winding with low, moderate,
modem windings tend to operate at higher thermal and electrical or high PD has been defined. Table I enables test users to
stresses than older machines [12], [13]. Other explanations for the objectively identify, with some certainty and without the need
inconsistent pattern of PD versus winding age may include the of an expert, which stators are likely to suffer from groundwall
observation that manufacturers of machines have a learning curve insulation deterioration.
to climb as they adopt new designs and manufacturing techniques 4) The practical importance of Table I is that if one applies
or that machine operators are continuously oscillating between PD sensors to a machine and one obtains a Qm that exceeds
proactive and breakdown maintenance strategies, depending on the 90 percentile of the relevant Qm distribution in the first
current management policies. measurement, then one should be concerned enough at the
high PD level to take action such as more frequent testing
IV. CONCLUSION and/or off-line tests and inspections at the next convenient
machine shutdown.
1) With thousands of machines monitored for as long as 15 5) Some machines made in the past decade exhibit higher
years with the same method, online PD testing has become a PD activity than machines that are considerably older. Newer
machines do not necessarily have more reliable insulation, Greg C. Stone (M’76-SM’88-F’93) received
implying that time-based maintenance practices may not be his Ph.D. degree in electrical engineering
optimal for large machines. from the University of Waterloo, Waterloo,
ON, Canada.
REFERENCES He has over 30 years experience in
the application and testing of large motor
[1] G. C. Stone, E. A. Boulter, I. Culbert, and H. Dhirani, Electrical and generator windings. He is the author or
Insulation for Rotating Machines. New York: IEEE Press, 2004. coauthor of almost 100 technical papers on
[2] J. Johnson and M. Warren, “Detection of slot discharges in HV motor and generator windings and testing.
stator windings during operation,” Trans. AIEE, vol. 70, pt. II, pp. Prior to joining Iris Power Engineering Inc.,
1993-1999, 1951. Toronto, ON, Canada, in 1990, he worked for the Canadian
[3] J. E. Timperly and E. K. Chambers, “Locating defects in large power utility Ontario Hydro.
rotating machines and associated systems through EMI diagnosis,” Dr. Stone has been involved in creating IEEE and International
presented at the International Council on Large Electric Systems Electrotechnical Commission (IEC) standards.
(CIGRE), Paris, France, Sep. 1992, Paper 11-311.
[4] I. Blokhintsev, M. Golovkov, A. Golubev, and C. Kane, “Field
experiences with the measurement of PD on rotating equipment,” Vicki Warren (S’93-M’95) received
IEEE Trans. Energy Corners., vol. 14, no. 4, pp. 930-938, Dec. the B.S. degree in electrical engineering
1999. from Tennessee Technological University,
[5] G. C. Stone, “Discussion of ‘Field experiences with the Cookeville.
measurement of PD on rotating equipment’,” IEEE Trans. Energy She was with the U.S. Army Corps of
Convers., vol. 16, no. 4, pp.380-381.Dec.2001. Engineers for 13 years prior to joining
[6] J. K. Nelson, “Assessment of partial discharge and Iris Power Engineering Inc., Toronto, ON,
electromagnetic interference on-line testing of turbine-driven Canada, where she is currently the Senior Field
generator stator winding insulation systems,” EPRI, Palo Alto, Services Engineer. While with the Corps, she
CA, EPRI Rep. 1007742, Mar. 2003. was responsible for the testing and maintenance of hydrogenerator
[7] Cigre Technical Brochure 258, Application of On-Line Partial windings, protection, and control devices; development of SCADA
Discharge Tests to Rotating Machines, 2004. software; and the installation of local area networks.
[8] G. C. Stone. “Importance of bandwidth in PD measurements
in operating motors and generators,” IEEE Trims. Dielectr. Electr.
Insul., vol. 7, no. 1, pp. 6-11, Feb. 2000.
[9] S. R. Campbell and H. G. Sedding, “Method and device for
distinguishing between PD and electrical noise.” U.S. Patent 5 475
312, Dec. 12, 1995.
[10] G. C. Stone and V. Warren, “Effect of manufacturer, winding
age and insulation type on stator winding PD levels,” IEEE Electr.
Insul. Mag., vol. 20, no. 5, pp. 13-17, Sep./Oct. 2004.
[11] C. Maughan, “Partial discharge as a stator winding evaluation
tool,” in Proc. Iris Rotating Machine Conf., Scottsdale, AZ, Jun.
2005, pp. 1-10.
[12] G. Griffith et al., “Problems with modem air-cooled generator
stator winding insulation,” IEEE Electr. Insul. Mag., vol. 16, no. 6,
pp. 6-10, Nov./Dec. 2000.
[13] J. Fealy, “Performance by design,” Power Eng., pp. 98-110,
Nov. 2004.

You might also like