Pad base bearing and stability subject to axial loading (EN1997-1:2004 and EN1992-1-1:2004)
Column properties:
Length of column Cl = 1.5 m
Width of column Cb = 1.5 m
Eccentricity in x-axis = 0m
Eccentricity in y-axis = 0m
Position in x-axis (relative to foundation edge) x = 2m
pos
Position in y-axis (relative to foundation edge) y = 1.5 m
pos
Soil properties:
Density of soil = 18 kN/m3
soil
Angle of friction = 25 Degrees
k
Effective Cohesion c' = 0 kN/m2
k
Angle of shear resistance ' = 35 Degrees
k
Loads:
Permanent load in z V = 100 kN
Gz
Note: load and moment variables are denoted by a label in the format X , where;
Yz
X - Represents load direction or moment. 'H', 'V' and 'M' represent Horizontal, Vertical and Moment respectively
Y - Represents load or moment type. 'G' and 'Q' represent Permanent and Variable respectively
z - Represents the axis
Moments:
No Moments added
(2) Partial Factors on Soil Parameters ( ), based on Table A-4 of EC7-1 Annex A
M
Material Property Symbol Set
M1 M2
Angle of Shearing Resistance (tan') 1.0 1.25
'
Effective Cohesion 1.0 1.25
c'
Undrained shear strength 1.0 1.4
cu
Weight Density 1.0 1.0
(3) Partial ResistanceFactors ( ) for shallow foundations, based on Table A-5 of EC7-1 Annex A
R
Resistance Symbol Set
R1 R2 R3
Bearing Capacity 1.0 1.4 1.0
R:v
Sliding Resistance 1.0 1.1 1.0
R:h
1.Horizontal action
Design horizontal action is calculated as the maximum action from applying all 4 combinations of favourable and unfavourable
PSF on permanent and variable horizontal actions.
a) If both the actions (permanent and variable) are negative value, then favourable PSF is considered.
b) If both the actions (permanent and variable) are positive value, then unfavourable PSF is considered.
c) If the (permanent action is positive and variable action is negative) or (vice versa), then favourable PSF is considered for
negative value and unfavourable PSF is considered for positive value.
3.Sliding resistance
Axial action is considered in calculating the resistance for sliding of foundation. We consider unfavourable PSF for negative
and favourable PSF for positive axial action.
Bearing resistance
Clause 6.3.2
Area of foundation
A = l*b
= 4*3
= 12 m2
Action in y-axis
H = 0
y
in Z-axis
V = *(A*(W +W )+V )+ *V
z G found soil Gz Qf Qz
= 1.35*(12*(50+18)+100)+0*0
= 1236.6 kN
Moments on foundation:
Moment in x-dir (about y-axis)
M = *(A*(W +W )*(l)/2+V *(x ))+ *M + *V *(x )+ *M +( *H + *H )*(h )
x G found soil Gz pos G Gx Q Qz pos Q Qx G Gx Q Qx 1
= 1.35*(12*(50+18)*(4)/2+100*(2))+1.35*0+1.5*0*(2)+1.5*0+(1.35*0+1.5*0)*(2)
= 2473.2 kNm
Moment in y-dir (about x-axis)
M = *(A*(W +W )*(b)/2+V *(y ))+ *M + *V *(y )+ *M +( *H + *H )*(h )
y G found soil Gz pos G Gy Q Qz pos Q Qy G Gy Q Qy 1
= 1.35*(12*(50+18)*(3)/2+100*(1.5))+1.35*0+1.5*0*(1.5)+1.5*0+(1.35*0+1.5*0)*(2)
= 1854.9 kNm
Eccentricity in y-axis
e = (M /V -(b)/2)
y y z
= (1854.9/1236.6-(3)/2)
= 2.22E-16 m
Effective width
b' = b-2*e
y
= 3-2*(2.22*10-16)
=3m
Effective area
A' = l'*b'
= 4*3
= 12 m2
Bearing pressure:
A known bearing pressure has been entered:
Bearing pressure
q =q
Ed Ed
= 200 kN/m2
check = q /q
Ed Rd
= 200/3517.85
= 0.057
In the absence of more detailed data, axially loaded pad footings may be designed and constructed as plain concrete,
provided that:
(0.85*h )/a >= SQR(9* /f )
F gd ctd
Where:
h = Depth of the foundation
f
a = Projection from column face
= Design value of ground pressure
gd
f = Design value of the concrete tensile strength
ctd
Material details
Concrete strength class
fck = 30 N/mm2
Coefficent
= 1
ct
Partial Factors for materials for ultimate limit states (Table 2.1N)
Design Situations for concrete
c
The design situation is assumed to be Persistent and Transient in this calculation, thus;
= 1.5
C
(0.85*h )/a >= SQR(9* /f ) Foundation Passes - The footing is structurally adequate for mass concrete base design.
F gd ctd
For conventional structures founded on clays, Eurocode 7 requires settlements to be calculated explicitly whenever the ratio of
the characteristic bearing capacity to the applied Serviceability loads is less than 3.
q <= q /
Ed Rd R,SLS
where q = the characteristic effects of actions, q = the characteristic resistance to those actions, and = a partial
Ed Rd R,SLS
resistance factor >= 3
check = q /(q / )
Ed Rd R,SLS
= 200/(3517.85/3)
= 0.17
Note: Any design must be built in accordance with Eurocode execution standards.