You are on page 1of 32

0 1 2 3 4 5 6 7 8 9

FJ
EPLAN P8 2.3.5 7451

Revisions FJ
Person
responsible,
Revision Change EC-Number Remark Page
Entry date name,
index description
signature,
date

1 2 3 4 5 6 7

c 30.11.2015 Detail Überarbeitung Moll 131598 1

b 30.09.2015 Abschlusswiderstand DEIF Steuerung F.Jäger 129302 12


© MTU Friedrichshafen GmbH Refer to protection notice DIN 34! Any Aterations are subject to the approval of the design department

b 01.09.2015 Abschlusswiderstand DEIF Steuerung Florian Jäger 129302 10

a 01.09.2015 Textanpassung Deckblatt Florian Jäger 127217 1

- 01.09.2015 war kZ Florian Jäger 127088 1

1
Drawer 30.11.2015 Moll Circuit diagram Drawing number Revision overview == =
Approved 30.09.2015 Moll XZ54400000171 + 1:1
Norm 30.09.2015 Parchmann Material.No Order no. Page 0
Department EDF Koliwer X54434400107 of 32
0 1 2 3 4 5 6 7 8 9

FJ
EPLAN P8 2.3.5 7451

GENSET
© MTU Friedrichshafen GmbH Refer to protection notice DIN 34! Any Aterations are subject to the approval of the design department

Part list number


X54434400107

Drawing number
XZ54400000171

Description
CIRCUIT DIAGRAM GENSET
BR2000 BETA -> DEIF V2-V7 TCP/IP

0 2
Drawer 30.11.2015 Moll Circuit diagram Drawing number Cover sheet == =
- 01.09.2015 war kZ 127088 Florian JägerApproved 30.09.2015 Moll XZ54400000171 + 1:1
a 01.09.2015 Textanpassung Deckblatt 127217 Florian JägerNorm 30.09.2015 Parchmann Material.No Order no. Page 1
c 30.11.2015 Detail Überarbeitung 131598 Moll Department EDF Koliwer X54434400107 of 32
0 1 2 3 4 5 6 7 8 9

Table of contents
EPLAN P8 2.3.5 7451

Plant Location Page Page description Date Name X


0 Revision overview 30.11.2015 MMo Moll
1 Cover sheet 30.11.2015 MMo Moll
2 Electrical table of contents : /0 - /25.f 30.11.2015 MMo Moll
3 Switch-Cabinet Front outside 30.11.2015 MMo Moll
4 Switch-Cabinet Front outside 30.11.2015 MMo Moll
5 Mounting plate overview 30.11.2015 MMo Moll
6 Cabinet drilling diagram 01.09.2015 Jaegerf
7 Switch-cabinet rear outside 14.07.2015 mollmi
8 Legend panal 30.11.2015 MMo Moll
9 Clamp overview 30.11.2015 MMo Moll
10 Bus-overview DEIF AGC4 12.11.2015 MMo M.Moll
11 AGC 4 Digital Generator Controller 12.11.2015 MMo M.Moll
12 Generator Signal Automatic voltage regulator 12.11.2015 MMo M.Moll
© MTU Friedrichshafen GmbH Refer to protection notice DIN 34! Any Aterations are subject to the approval of the design department

13 Generator winding and bearing temperature 12.11.2015 MMo M.Moll


14 Power unit battery + starter 12.11.2015 MMo M.Moll
15 Water heater 3PH or 2PH 14.07.2015 mollmi
16 Fuel water separator 1-4 14.07.2015 mollmi
17 Engine control unit ADEC ECU9 Plug -X1 12.11.2015 MMo M.Moll
18 Supply 24VDC Charger 12.11.2015 MMo M.Moll
19 Supply 24VDC Charger 04.09.2015 Jaegerf
20 Remote control start & Emergency stop 30.09.2015 FJ F.Jäger
21 GCB-Generator circuit breaker 14.07.2015 mollmi
22 MCB-Mains circuit breaker 14.07.2015 mollmi
23 FAN-Engine fan 14.07.2015 mollmi
24 Spare terminal 03.09.2015 Jaegerf
25 Bill of material : RIT.1090009 - SIE.5ST3010 30.11.2015 MMo Moll
25.a Bill of material : SIE.5SY4120-7 - SCH.MTO 30.11.2015 MMo Moll
25.b Bill of material : SCH.MHR_3 - PHO.3212167 30.11.2015 MMo Moll
25.c Bill of material : PHO.3030857 - PHO.3030174 30.11.2015 MMo Moll
25.d Bill of material : PHO.3038558 - PHO.3038558 30.11.2015 MMo Moll
25.e Bill of material : PHO.3030747 - PHO.3038558 30.11.2015 MMo Moll
25.f Bill of material : PHO.3030747 - PHO.3031267 30.11.2015 MMo Moll

1 3
Drawer 30.11.2015 Moll Circuit diagram Drawing number Electrical table of contents : /0 - /25.f == =
Approved 30.09.2015 Moll XZ54400000171 + 1:1
Norm 30.09.2015 Parchmann Material.No Order no. Page 2
Department EDF Koliwer X54434400107 of 32
EPLAN P8 2.3.5 7451 0 1 2 3 4 5 6 7 8 9

Self check ok
Power
© MTU Friedrichshafen GmbH Refer to protection notice DIN 34! Any Aterations are subject to the approval of the design department

Lamp test

EMERGENCY STOP
ON

Load
ON
RUN

G
Alarm

2 4
Drawer 30.11.2015 Moll Circuit diagram Drawing number Switch-Cabinet Front == =
Approved 30.09.2015 Moll XZ54400000171 outside + 1:3
Norm 30.09.2015 Parchmann Material.No Order no. Page 3
Department EDF Koliwer X54434400107 of 32
EPLAN P8 2.3.5 7451 0 1 2 3 4 5 6 7 8 9

1000

219,5
© MTU Friedrichshafen GmbH Refer to protection notice DIN 34! Any Aterations are subject to the approval of the design department

Door cut-out

22,3
24,1

600
22,3

2,2
22,3

50,8
250

350

300
Frontdoor
96

204

20

18
173 66
239
241,5
400
500
3 5
Drawer 30.11.2015 Moll Circuit diagram Drawing number Switch-Cabinet Front == =
Approved 30.09.2015 Moll XZ54400000171 outside + 1:3
Norm 30.09.2015 Parchmann Material.No Order no. Page 4
Department EDF Koliwer X54434400107 of 32
© MTU Friedrichshafen GmbH Refer to protection notice DIN 34! Any Aterations are subject to the approval of the design department EPLAN P8 2.3.5 7451

4
+A300
0

20
42 24 25 27 29 40 33 35
6 5 4 3 2 1
TB2 21 C 11
O
M

N
O
MW 24 14
N
Mean Well O
24 14

+V Adj
SIEMENS SIEMENS SIEMENS SIEMENS SIEMENS SIEMENS
SIEMENS SIEMENS SIEMENS SIEMENS SIEMENS SIEMENS SIEMENS
LED 5SY_1 5SY_1 5SY_1 5SY_1 5SY_1 5SY_1 5SY_1

A2 C A1
O
I
L

TB1
1

26 28 30 32 34 36
3 2 1

39
6X01

1- Slot#1 14 15 28 29 Slot#2 36
10

37 Slot#3 50 51 64 65 Slot#4 72
2

Ethernet Service port Display


5X01
9

DEIF

73 Slot#5 78 79 Slot#5 84 85 Slot#5 89 90 Slot#6 97


8

4X01

Norm
Drawer
98 Slot#7 116 117 124 A1 A3 B1 B3 126 Slot#8 133

Approved
3X01
7
CABLE DUCT 80x40

2X01
6

Department EDF Koliwer


3

30.09.2015 Moll
30.11.2015 Moll
5

1X01

A2
24

24
21

I
C
N

L
O
C

N
O
O
M

30.09.2015 Parchmann
14

14
11

A1
Option

1
2
3
X1
POWER

955
Harness Door

CABLE DUCT 80x25


CABLE DUCT 80x40
4

871
Smart Connect
41

1
2
3
X2
RS485
X7
USB
17
CABLE DUCT 80x25

1
2
3
X3
CAN1

785
16

760
1
2
3
XMOD

CAN2
X4
X5
DIASYS
15

X07
5

1X02
14

Circuit diagram
MZ2
MZ1
4

MY2
3X03

MY1
555 MX2
MX1
M-
13

N
X06
3

L3
L2
3X02

X05

L1
12

N
6
X02

5
4
2
6

CABLE DUCT 80x25

Material.No
N
3
11
X02

X04

2
337

Drawing number 1
1

X54434400107
XZ54400000171

CABLE DUCT 80x80


7

130

overview
Order no.

162
Shield
Mounting plate
50

40
M8

M8

111
GCB
8

ECU
MCB

Geno
Geno

Spare
Engine

182
GND 6mm²

GND 6mm²

222
+
==

290
355
380
=
9

446
of

514
Page

539
1:3

32
5
6
EPLAN P8 2.3.5 7451 0 1 2 3 4 5 6 7 8 9

600 mm

Rubber cable grommets


2xM16/1xM25/1xM32
© MTU Friedrichshafen GmbH Refer to protection notice DIN 34! Any Aterations are subject to the approval of the design department

250
M16 M16 M25 M32

16 16 25 32

Rubber cable grommets M25 / NW=22 M25 / NW=22 M32 / NW=29 M32 / NW=29 Rubber cable grommets Rubber cable grommets
1xM20 1xM20 1xM20

7 6 5 4 3 2 1
M8 bolt M8 bolt

114
70
20 25 25 32 32 20 20
14 14
ECU Engine Geno Geno GCB MCB
Spare W001 W002 W003 W007 WTB4 WTB5

50 50 50 50 50 50
60

1. GCB Oelflex 14x1mm² 11,4mm


2. GCB Oelflex 2x2,5mm²
3. GENO W007 Harness NW29
4. GENO W003 Harness NW29
5. Engine W002 Harness NW22
6. ECU W001 Harness NW 22
7. MCB Oelflex 14x 1mm²

5 7
Drawer 01.09.2015 Florian Jäger Circuit diagram Drawing number Cabinet == =
Approved 30.09.2015 Moll XZ54400000171 drilling diagram + 1:2
Norm 30.09.2015 Parchmann Material.No Order no. Page 6
Department EDF Koliwer X54434400107 of 32
EPLAN P8 2.3.5 7451 0 1 2 3 4 5 6 7 8 9

1000

20 960 20

20
9 Hole 9mm 9
© MTU Friedrichshafen GmbH Refer to protection notice DIN 34! Any Aterations are subject to the approval of the design department

560

600
20
9 9

6 8
Drawer 14.07.2015 Michael Moll Circuit diagram Drawing number Switch-cabinet rear == =
Approved 30.09.2015 Moll XZ54400000171 outside + 1:3
Norm 30.09.2015 Parchmann Material.No Order no. Page 7
Department EDF Koliwer X54434400107 of 32
0 1 2 3 4 5 6 7 8 9

Legend panel
EPLAN P8 2.3.5 7451

Pos-Nr. item designation manufacturer No. manufacturer Designation


1 -X01
2 -X02
3 -3X02
4 -3X03
5 -1X01
6 -2X01
7 -3X01
8 -4X01
9 -5X01
10 -6X01
11 -X04
12 -X05
13 -X06
14 -1X02
15 -X07
16 -XMOD
17 -X03
20 -TB10 SDR-960-24 Mean Well Single-phase power supply 230V/ 24VDC/ 40A,
24 -FC1 5SY4106-7 Siemens AG Circuit-breaker C6A/10kVA 1pol
25 -FC2 5SY4110-7 Siemens AG Circuit-breaker C10A/10kVA 1pol
26 -FC2 5ST3010 Siemens AG Aux.current switch 1NO+1NC
27 -FC3 5SY4110-7 Siemens AG Circuit-breaker C10A/10kVA 1pol
© MTU Friedrichshafen GmbH Refer to protection notice DIN 34! Any Aterations are subject to the approval of the design department

28 -FC3 5ST3010 Siemens AG Aux.current switch 1NO+1NC


29 -FC4 5SY4106-7 Siemens AG Circuit-breaker C6A/10kVA 1pol
30 -FC4 5ST3010 Siemens AG Aux.current switch 1NO+1NC
32 -FC5 5ST3010 Siemens AG Aux.current switch 1NO+1NC
33 -FC6 5SY4125-7 Siemens AG Circuit-breaker C25A/10kVA 1pol
34 -FC6 5ST3010 Siemens AG Aux.current switch 1NO+1NC
35 -FC7 5SY4140-7 Siemens AG Circuit-breaker C40A/10kVA 1pol
36 -FC7 5ST3010 Siemens AG Aux.current switch 1NO+1NC
39 -AF20 X59434200202 Deif A/S Genset Controller V2-7 TCP/IP/CAN
40 -FC5 5SY4120-7 Siemens AG Circuit-breaker C20A/10kVA 1pol
41 -AF12 X00E50209782 MTU Friedrichshafen GmbH Smart Connect
42 -KF1 40.52.9.024.0000 Finder GmbH Relais 24V DC 2C 8A

7 9
Drawer 30.11.2015 Moll Circuit diagram Drawing number Legend panal == =
Approved 30.09.2015 Moll XZ54400000171 + 1:1
Norm 30.09.2015 Parchmann Material.No Order no. Page 8
Department EDF Koliwer X54434400107 of 32
© MTU Friedrichshafen GmbH Refer to protection notice DIN 34! Any Aterations are subject to the approval of the design department EPLAN P8 2.3.5 7451

8
3022218
3038532
0

3038516

6X01
3038558
3030747
3038532

5X01
1

3038558
3030747 3038532

3038516

4X01
3038558
3030747

3038516
2

3X01
3038558
3030747
3038516

3038558
2X01

Norm
Drawer
3030747

Approved
3038516

Department EDF Koliwer


3

1X01

3038558

30.09.2015 Moll
30.11.2015 Moll
3022218

30.09.2015 Parchmann
3022218

3031500

3036110
4

3036644

3031306

3030514
3036110
5

3030815

Circuit diagram
3022218 3031306
3030815
3031306
3031241 3030815
XMOD

3031306
3030815
3030488
3031306
3022218 3030815
3031306
6

3030514

Material.No
3022218 3036110
Drawing number 3036644
X07

X54434400107
XZ54400000171 3038558 3022218
3030747
3035980 3x
3038516 1201442
1X02

Prüfadapter sw
3038558 3212167
3022218 3035755 3035974 1x
Prüfadapter or
MZ2
3212139
7

MZ1
3022218
Order no.

MY2
3X03

3038532 MY1
Clamp overview

3030514 MX2
3031306
3030857 MX1
X06

3212167 M-
3038558 3038516
3030747 3212139
N
X05

3038516
3030174 L3
3030174 L2 3212154
3X02

3030857
L1
8

3212167
3038558
3030747 3212139
DANGER

N
6
+

3212154
==
X02

3030857 5
3038516 3212167 4
X04

3212139
N
=

3
9

3212154
X02

3030857 2
of

3030844 1 3031843
3038558
Page

3022218 1201442
1201468
1:1,5

32
9
10

3202575
0 1 2 3 4 5 6 7 8 9

Bus-overview
EPLAN P8 2.3.5 7451

DEIF AGC4
-AF20
/11.1 Automatic Genset Controller Engine CAN
PMS CAN Ethernet USB Memory Service port Display
AGC-4 Ethernet
Slot#8
CAN-BUS 1 CAN-BUS 2 CAN-BUS 3 CAN-BUS 4 USB

CAN_H1 COM CAN_L1 CAN_H2 COM CAN_L2 CAN_L COM CAN_H CAN_L COM CAN_H Power
/11.2 /11.2 /11.2 /11.2 /11.2 /11.2 /11.2 /11.2 /11.2 /11.2 /11.2 /11.2 Self check ok
Alarm inhibit
A1 A2 A3 B1 B2 B3 128 129 130 131 132 133

120Ω
120Ω 120Ω 120Ω

+A300
3 4 SH
WH BN SH
-XMOD
-WCAN_2
120Ω UNITRONIC
120Ω
2x0,34 mm²
*
© MTU Friedrichshafen GmbH Refer to protection notice DIN 34! Any Aterations are subject to the approval of the design department

-AF12 X7 X5
Smart connect
1 2 3 1 2 3
CAN1 GND

CAN2 GND
CAN1 (H)

CAN2 (H)
CAN1 (L)

CAN2 (L)
X1 X2 X3 X4

RS485 CAN1 CAN2


RS485 GND

CAN1 GND

CAN2 GND
RS485 (A)
RS485 (B)

CAN1 (H)

CAN2 (H)
CAN1 (L)

CAN2 (L) *

DIASYS
24VDC

0VDC
GND

USB
1 2 3 1 2 3 1 2 3 1 2 3 . X7:. Terminating resistor
X1 X2 X3 X4 X5
at the end of
1,5 mm²

the Bus system


GNYE

SH SH

GND

WH BK BN SH WH BK BN SH
18.2 / 0124
-WCAN_01 -WCAN_02
UNITRONIC UNITRONIC
GND

GND

3x0,34 mm² 3x0,34 mm²


SH

SH
LO

LO
HI

HI

18.2 / 0924
HI

LO

GND

SH

HI

LO

GND

SH

WH BK BN WH BK BN

Terminating resistor
120Ω

120Ω

included in the plug

+ENG X1 1 2 5 3 4 8
-KF3
CAN 1-Interface CAN 2-Interface
/17.0

Engine control unit


ADEC ECU9 Plug -X1

9 11
02.12.2015 Moll Drawer Circuit diagram Drawing number Bus-overview == =
Approved 30.09.2015 Moll XZ54400000171 DEIF AGC4 + 1:1
Norm 30.09.2015 Parchmann Material.No Order no. Page 10
b 01.09.2015 Abschlusswiderstand DEIF Steuerung 129302 Florian JägerDepartment EDF Koliwer X54434400107 of 32
0 1 2 3 4 5 6 7 8 9

Page - Page - Page - Page -


98 73 37 1
(+) 8-36VDC 18.2 / 0113 S1 (k) L1 AC current /12.7 /24.0 Active load sharing AGC4 / 18.1 Batt +
-AF20
EPLAN P8 2.3.5 7451

99 74 38 2
(-) COM for 118 18.4 / 0931
100
S2 (l) L1 AC current /12.7
75
AGC 4 /24.1
39
COM
3
0911 / 18.2 Batt -

MPU input S1 (k) L2 AC current /12.7 /24.2 Reactive load sharing /20.4 Status Relay

MPU GND
101 S2 (l) L2 AC current /12.7 76 Connection 40 Ext. kW / Hz set point /20.5 4 Status Relay

/13.3
102
103
S1 (k) L3 AC current /12.8 77
78
overview 41
42
COM /19.8 5
6
Horn
Winding temp 1A Ext. PF/VAr/V set point COM
/13.2 S2 (l) L3 AC current /12.7 0143 / 18.4
104 /21.2 43 GCB tripped 7 Relay 05
/13.2
105 /21.3 44 GCB charged /22.3 8 MCB open
/13.4
Winding temp 2A 106 /16.2 45 Fuel water separator 1 9 COM
/13.4
107 Generator sensing 79 /16.6 46 Fuel water separator 2 10 Relay 08
/13.4 /12.4
/13.6
108 80 C /24.3 47 Day tank no leakage /21.5 11 MCB close

SLOT3
SLOT5
Winding temp 3A 109 Generator sensing 81 /23.7 48 Auxilary CB Tripped 12 COM
/13.6 /12.4
110 82 49 13 Relay 11

SLOT1
/13.5 /20.1 Remote Start
111 83 50 14
COM 18.4 / 0943
112
Generator sensing /12.5 F /24.4 Spare /21.4 GCB open

/24.5 Generator sensing /12.5 84 51 Spare 15 COM


Safety System Override

SLOT7
113 52 Spare 16 Relay 14
Fixed load /24.6
114 53 Spare /22.3 17 GCB close
Floating load /24.7
115 54 Spare 18 COM
Blocking synch. Genset to Mains /24.7
Local genset release
116
Busbar/Mains sensing /24.0 85 B 55 Spare 19 Relay 17
117 56 20 Spare
External protection tripped /24.8 /24.0 86 0161 / 18.6 COM Only 10mA
118 57 Changeover switch starter 21 output Spare
© MTU Friedrichshafen GmbH Refer to protection notice DIN 34! Any Aterations are subject to the approval of the design department

Emergency stop /20.6 Busbar/Mains sensing /24.1 87 /14.7


119 58 22 COM
Engine stop /17.2 Busbar/Mains sensing /24.1 88 0141 / 18.4 COM
120 89 /23.5 59 Room fan on Louver /19.7 23 Auxalary CB tripped
Engine start prepare Busbar/Mains sensing /24.1
121 60 COM /22.1 24 MCB opened
Engine start /14.2
122 61 Coolant fan 1 25 MCB closed
COM 18.4 / 0142 /23.3 /22.1
123 62 COM /21.1 26 GCB opened
Spare
124 /23.3 63 Coolant fan 2 /21.1 27 GCB closed
Spare 90
COM /13.7
A1 64 COM 28 COM
CAN_H1 DEIF /10.1
Bearing (A) KS -DE temp /13.7 91 0152 / 18.6
CAN_GND 1 DEIF A2
COM /10.1 92
COM /13.8
CAN_L DEIF A3
CAN_L11 /10.2
SLOT6

Bearing (B) KGS -NDE /13.8 93 /12.1 65 Voltage-setpoint /23.2 29 Fuel transfer pump
CAN_H B1
CAN_H22 /10.2 94 66 30
COM /12.1 Spannungs Sollwert 0144 / 18.4 COM
CAN_GND 2 B2
COM /10.2 95 67 31
Day tank Not used /24.1 General fault red
CAN_L B3
CAN_L22 /10.2

SLOT2
96 68 32

SLOT4
COM COM
CAN_L 128
ECU /10.3 97 69 33
Room temp. /23.1 Fuel cooler /24.2 General alarm yellow
COM 129
ECU /10.3 70 34
0133 / 18.4 Relay 69 COM
130
SLOT8

CAN_H ECU /10.3 71 35


/15.3 Genset running /24.0 Daytank control
CAN_L 131
/10.4 72 36
Relay 71 COM
COM 132
/10.4
CAN_H 133
/10.4

No. Slot No. Slot

1 #1 Terminal 1-28 , Power supply 7 #7 Terminal 98-125 , Engine I/F

2 #2 Terminal 29-36 , Communication 8 #8 Terminal 126-133 , Engine communication , in- / outputs

3 #3 Terminal 37-64 , In- / outputs / load sharing 9 LED I/F

4 #4 Terminal 65-72 , Governor , AVR , in- / outputs

5 #5 Terminal 73-89 , AC measuring

6 #6 Terminal 90-97 , In- / outputs

10 12
Drawer 12.11.2015 M.Moll Circuit diagram Drawing number AGC 4 == =
Approved 30.09.2015 Moll XZ54400000171 Digital Generator Controller + 1:1
Norm 30.09.2015 Parchmann Material.No Order no. Page 11
Department EDF Koliwer X54434400107 of 32
EPLAN P8 2.3.5 7451 0 1 2 3 4 5 6 7 8 9

+GENO
/13.2

DVR Generator Generator


Control generator sensing output Current measurement
Auxiliary input negativ
Auxiliary input positiv

GND

IA+

IC+
IB+
IB-
IA-

IC-
L1

L2

L3

N
24VDC

0VDC
Geno
terminal box x x x x x x
Power supply -GENO
GND GND
x x x x x x x x x x x x x N
3X01:1 WH

3X01:2 WH

3X01:3 WH

3X01:4 WH

3X01:5 WH

3X01:6 WH

3X01:7 WH

3X01:8 WH

3X01:9 WH

3X01:10 WH
-W03/1

2,5² / 13AWG

2,5² / 13AWG

2,5² / 13AWG

2,5² / 13AWG
1 2 3 4 GNYE
1²/17AWG

1²/17AWG

1²/17AWG

1²/17AWG

1²/17AWG

1²/17AWG

1²/17AWG

1²/17AWG

1²/17AWG

1²/17AWG

MX2 WH

MX1 WH

MY1 WH

MZ1 WH
5x1,5² / AWG 15

W003 W003
© MTU Friedrichshafen GmbH Refer to protection notice DIN 34! Any Aterations are subject to the approval of the design department

-3X03 M-

MX2 WH

MY2 WH

MZ2 WH
Switching
jumper

-3X01 1 2 3 4 5 6 7 8

MX2

MX1

MY2

MY1

MZ2

MZ1
-3X02 -3X03

GND
1 2 3 N

*1
Ω

-AF20R

1² / 17AWG

1² / 17AWG

1² / 17AWG

1² / 17AWG
WH

WH

WH

WH
*2
+A300-X03:1.2:3

+A300-X03:9.2:3

GND
0123

0923

65 66 79 81 83 84 74 73 76 75 78 77
AOUT GEN VA IA- IA+ IB- IB+ IC- IC+
+A300-AF20
18.2 /

18.2 /

AGC4 AGC4 AGC4


/11.1
Voltage-setpoint Generator sensing voltage L1 S2 (l) L1 AC current

* Resistor
ATTENTION
*1 Installed by default
120 Ω Voltage-setpoint
For Generator regulator LS R449 ± 1V -> ± 10%

*2 D510 exchange the 120 Ω LS D510 ± 10V -> ± 10%


resistor to 470 Ω MA DVR ± 3V -> ± 30%

11 13
Drawer 30.11.2015 Moll Circuit diagram Drawing number Generator Signal Automatic == =
Approved 30.09.2015 Moll XZ54400000171 voltage regulator + 1:1
Norm 30.09.2015 Parchmann Material.No Order no. Page 12
b 30.09.2015 Abschlusswiderstand DEIF Steuerung 129302 F.Jäger Department EDF Koliwer X54434400107 of 32
0 1 2 3 4 5 6 7 8 9

+CUS
EPLAN P8 2.3.5 7451

Customer Winding
temp 1A
Winding
temp 2A
Winding
temp 3A
Bearing (A)
KS -DE temp /11.1
Bearing (B)
KGS -NDE temp /11.1
/11.1 /11.1 /11.1
Power AGC4 AGC4 AGC4 AGC4 AGC4
230V 1000W +A300-AF20 +A300-AF20 +A300-AF20 +A300-AF20 +A300-AF20

Fuse 16A/10kA
104 103 102 107 106 105 110 109 108 91 90 93 92
L N GND

DANGER
© MTU Friedrichshafen GmbH Refer to protection notice DIN 34! Any Aterations are subject to the approval of the design department

SH SH SH SH SH

-WBT01 -WBT02 -WBT03 -WBT08 -WBT07


Customer 3x2,5²/
13AWG
LIYCY
3x0,34²/22AWG WH BN GN
LIYCY
3x0,34²/22AWG WH BN GN
LIYCY
3x0,34²/22AWG WH BN GN
LIYCY
3x0,34²/22AWG WH BN GN
LIYCY
3x0,34²/22AWG WH BN GN

W007

x x +GENO x x x x x x x x x x x x x x x
/12.0
H1 H2
L1 L2 L3
Winding Winding Winding Bearing KS -DE Bearing KGS -ODE
temp. 1A temp. 2A temp. 3A temp temp
GENO-HEATER

+GEN-EB1

Option OPTION
DANGER
Power
230V - 500-1000W /
2,08-4,3 Amp.
Fuse C16A/10kA

12 14
Drawer 30.11.2015 Moll Circuit diagram Drawing number Generator winding and == =
Approved 30.09.2015 Moll XZ54400000171 bearing temperature + 1:1
Norm 30.09.2015 Parchmann Material.No Order no. Page 13
Department EDF Koliwer X54434400107 of 32
0 1 2 3 4 5 6 7 8 9

AGC4:121 Changeover switch


starter

WH

/11.1
x2 x1 AGC4
EPLAN P8 2.3.5 7451

0921 DBU / WH
1,5² / 15AWG
0921. / +A300-AF20
Engine start 11
+A300-V1
+A300-KF2 1N4007
/11.1 /14.7 12 14 57
AGC4
+A300-AF20

WH

WH

WH
+A300


2 3
121 -2X01 +A300-KF2
A1
+A300-KF2
* Option
24VDC A2 +A300-X03:9.3:2
0932 / 18.4

WH
Only at redundatem starter


14
11 /14.5
+A300-X03:9.2:1 12
* x2 x1 0921 DBU / WH
1,5² / 15AWG
0921 / 18.2 24
22
21
No start
+A300 2 3 +A300-V1
-2X01 1N4007

0912 / 18.2

0914 / 18.2

BAT+ / 18.0
© MTU Friedrichshafen GmbH Refer to protection notice DIN 34! Any Aterations are subject to the approval of the design department

BAT- / 18.0
W002
RD + 95² / 3/0AWG

BK - 95² / 3/0AWG

+ 95² / 3/0AWG

- 95² / 3/0AWG
RD

BK
WG2/1+ WG2/1-
1x95 mm² 1x95 mm²
2X01:3 WH

2X01:2 WH
1²/17AWG

1²/17AWG
1 mm² ws

1 mm² ws
6 mm²

6 mm²

6 mm²

6 mm²
0912

0914
GA+

GA+
C

C
A1 A2 1 2 2 1 A2 A1

29.013.12 + - 29.013.12
75A/18-32VDC 75A/18-32VDC
Pilot Relais (B) + - + - Pilot Relais (A)
+ENG-KF2 12V 12V +ENG-KF1

30 31 Battery 30 31
50 50
+ - + -
+ENG-GB1
M M

Engine start (B) B A Engine start (A)


+ENG-QA2 OPTION +ENG-QA1

13 15
Drawer 30.11.2015 Moll Circuit diagram Drawing number Power unit == =
Approved 30.09.2015 Moll XZ54400000171 battery + starter + 1:1
Norm 30.09.2015 Parchmann Material.No Order no. Page 14
Department EDF Koliwer X54434400107 of 32
0 1 2 3 4 5 6 7 8 9

Genset running
EPLAN P8 2.3.5 7451

+CUS /11.1
AGC4
+A300-AF20

Customer 71

1² / 17AWG
R2-A WH
+A300-V2 +A300-X03:9.2:2
x2 x1 0922 DBU / WH

+A300 1² / 17AWG
0922 / 18.2
1 1N4007
-2X01

/ 18.4
+A300-X03:9.4:4
L L L GND

0944
DANGER

0944 DBU / WH
1,5² / 15AWG
2X01:1 WH
1²/17AWG
0944
© MTU Friedrichshafen GmbH Refer to protection notice DIN 34! Any Aterations are subject to the approval of the design department

-XEB1
4 2
1 2
1 3

2X01:1
1,5² / 15AWG

1,5² / 15AWG

1,5² / 15AWG

1,5² / 15AWG

Customer

GND
L1 L2(N) L3(x) A1 A2

Water Heating - Cooling Water (B)

OPTION
+ENG-EB1
400V/50Hz

Power 1-PH.
DANGER 2500W 230V 10,8A Wire-Ölflex
Fuse C16A/10kA 3x2,5²/13AWG
max. 20m
Power 3-PH.
6000W 400V 8,6A Wire-Ölflex
Fuse C16A/10kA 4x2,5²/13AWG

14 16
Drawer 30.11.2015 Moll Circuit diagram Drawing number Water heater == =
Approved 30.09.2015 Moll XZ54400000171 3PH or 2PH + 1:1
Norm 30.09.2015 Parchmann Material.No Order no. Page 15
Department EDF Koliwer X54434400107 of 32
0 1 2 3 4 5 6 7 8 9

Fuel water Fuel water


EPLAN P8 2.3.5 7451

separator 1 separator 2
/11.1 /11.1
AGC4 AGC4
+A300-AF20 +A300-AF20

45 46

2X01:4 WH

2X01:5 WH
1² / 17AWG

1² / 17AWG
+A300 +A300
4 5
-2X01 -2X01

+A300-X03:9.6:2 +A300-X03:9.6:3
0962 / 18.6 0963 / 18.6

0162 / 18.6 0163 / 18.6


+A300-X03:1.6:2 +A300-X03:1.6:3
0962 DBU / WH

0963 DBU / WH
1,5² / 15AWG

1,5² / 15AWG

1,5² / 15AWG

1,5² / 15AWG
0162 DBU

0163 DBU
© MTU Friedrichshafen GmbH Refer to protection notice DIN 34! Any Aterations are subject to the approval of the design department

W002 W002
2X01:4 WH

2X01:5 WH
1²/17AWG

1²/17AWG
09xx
Pin 2

Bridge to pin 3

2 Pin 7
7
-XFWS1

-XFWS2
1 2 3 4 5 6 7 3 1 2 3 4 5 6 7
+ENG

1
2X01:4 6
2 5 7 -516- 4 2 5 7
5
3 4 6 Pin 4 01xx 3 4 6
Pin 5+6

2 5 7
2 5 7

3 4 6
3 4 6

5 2 7 6 3 4
5 2 7 6 3 4

+ - S + - S + - S + - S

Fuel water Fuel water Fuel water Fuel water


separator 1.1 separator 1.2 separator 2.1 separator 2.2
Minus switching Minus switching Minus switching Minus switching
PLCA 50DC PLCA 50DC PLCA 50DC PLCA 50DC

+ENG-BM1.1 +ENG-BM1.2 +ENG-BM2.1 +ENG-BM2.2

Option

15 17
Drawer 30.11.2015 Moll Circuit diagram Drawing number Fuel water separator 1-4 == =
Approved 30.09.2015 Moll XZ54400000171 + 1:1
Norm 30.09.2015 Parchmann Material.No Order no. Page 16
Department EDF Koliwer X54434400107 of 32
0 1 2 3 4 5 6 7 8 9

+A300-SF3
AGC4:119 *
EPLAN P8 2.3.5 7451

Option +A300
1

Only at redundatem starter -SF3 Cable harness W001 Engine control unit ECU
2
Injection
X1-1 CAN1_HI (HIGH)

Cable
interruption

1 6 X1-2 CAN1_LO (LOW)


Engine stop X1-5 CAN1_GND (GND)
/11.1
X1-3 CAN2_HI (HIGH)

Cable
AGC4 21
+A300-AF20 +A300 X1-4 CAN2_LO (LOW)

1² / 17AWG
WH X06:4
-SF1
119 /21.6
22 X1-8 CAN2_GND (GND)
E-Stop +A300
3 4 5
-X06
x
X1-34 START_ENGINE (IN_7) 1X01 1
+CUS Bridge X1-33 START_ENGINE (-GND) X03 9.8
-WSNA1 3

21
4
X1-30 SPEED - DOWN (IN_6) 1X01 2
+CUS X1-29 --------"-------- (-GND) X03 9.9
-SF2 Spare
* External customer
22
X1-26 SPEED - UP (IN_5) 1X01 3
SH
X1-25 --------"-------- (-GND) X03 9.8
-1X01 8 7 1 6 11 12 -1X02 1 2 3
X1-18 IDLE - MODE (IN_3) 1X01 4
X1-17 --------"-------- (-GND) X03 9.9
© MTU Friedrichshafen GmbH Refer to protection notice DIN 34! Any Aterations are subject to the approval of the design department

W001
X1-14 SWITCH - DROOP (IN_2) 1X01 5

1X01:11 WH

1X01:12 WH
1X01:8 WH

1X01:7 WH

1X01:1 WH

1X01:6 WH

-WECU_02
X1-13 --------"-------- (-GND) X03 9.9
1²/17AWG

1²/17AWG

1²/17AWG

1²/17AWG

1²/17AWG

1²/17AWG
CY WH BN GN
3x0,34 / 22AWG
X1-10 STOP ENGINE (IN_1) 1X01 6
X1-9 --------"-------- (-GND) X03 9.8
+ENG 46 42 34 10 31 32 39 43 35 40 44
-KF3 option input E-stop Analog out
X1-46 SPEED DEMAND VOLTAGE (AI1_U) 1X01 8
/10.2 X1-42 --------"-------- (-GND) 1X01 7
Engine control unit ECU9 Plug -X1 ECU 9 X1-19 STARTER ON (OUT4) 1X01 9
0V 24 V Pot.51 0V option Start X1-16 --------"-------- (-GND) 1X01 10
9 33 25 29 17 13 58 59 62 57 60 61 30 26 18 14 19 16 X1-39 BRIDGE
X1-43 BRIDGE
0981 DBU / WH

0983 DBU / WH

0984 DBU / WH

0994 DBU / WH

0992 DBU / WH

0993 DBU / WH

0971 DBU / WH

0972 DBU / WH

0973 DBU / WH
2,5² / 13AWG

2,5² / 13AWG

2,5² / 13AWG

2,5² / 13AWG

2,5² / 13AWG

2,5² / 13AWG

1X01:10 WH
1² / 17AWG

1² / 17AWG

1² / 17AWG

1² / 17AWG

1² / 17AWG

1² / 17AWG

1X01:2 WH

1X01:3 WH

1X01:4 WH

1X01:5 WH

1X01:9 WH
1²/17AWG

1²/17AWG

1²/17AWG

1²/17AWG

1²/17AWG

1²/17AWG
0511 DBU

0512 DBU

0513 DBU

X1-35 ANALOG LOW (-GND) 1X02 1

Cable
X1-40 ANALOG OUTPUT (AO1_OUT) 1X02 2
W001
X1-44 ANALOG OUTPUT (AO2_OUT) 1X02 3
0981

0983

0984

0994

0992

0993

0511

0512

0513

0971

0972

0973

X1-31 EMERGENCY STOP (IN) 1X01 11


+A300
2 3 4 5 9 10
X1-32 EMERGENCY STOP (+24V) 1X01 12
-1X01
-X1/2

-X3+

-X3-

Spare X1-58 BATTERY (+24V) X03 51


X1-59 BATTERY (+24V) X03 51
19.3

19.2

19.2

X1-62 BATTERY (+24V) X03 51


X1-57 BATTERY (-GND) X03 9.7
X1-60 BATTERY (-GND) X03 9.7
X1-61 BATTERY (-GND) X03 9.7

16 18
Drawer 30.11.2015 Moll Circuit diagram Drawing number Engine control unit == =
Approved 30.09.2015 Moll XZ54400000171 ADEC ECU9 Plug -X1 + 1:1
Norm 30.09.2015 Parchmann Material.No Order no. Page 17
Department EDF Koliwer X54434400107 of 32
0 1 2 3 4 5 6 7 8 9

Automatic
Genset
Controller General Digital output Digital input Generator Ciruit Breaker
EPLAN P8 2.3.5 7451

24V Fixed bridge


24V+ / 19.0
1 1 13 21 1 14 21 1 13 21 1 14 21
-FC1 -FC2 -FC3 -FC4 -FC5
C6A 2 C10A 2 14 22 C10A 2 13 22 C6A 2 14 22 C20A 2 13 22

/19.7

/19.7

/19.7

/19.7
2,5² / 16AWG

2,5² / 16AWG

2,5² / 16AWG
DBU

DBU

DBU
FC1

FC2

FC3
-X03 -X03 -X03 -X03
0133 / 11.6 / +A300-AF20:70 0153 / 21.0 / +GCB-TB4:1 TB4-14 / 21.8 / +GCB-TB4:14
1.1 0113 / 11.2 / +A300-AF20:98
1.3 1.5 0154 / 22.0 / +MCB-TB5:1
1.7
0132 / 20.3 / +A300-SF1:31 0152 / 11.7 / +A300-AF20:28
-X03 1+
10² -X03 -X03 0141 / 11.6 / +A300-AF20:58 -X03 0161 / 11.6 / +A300-AF20:56 -X03
0123 / 12.3 / +GENO:x 0143 / 11.7 / +A300-AF20:6 0163 / 16.7 / -XFWS2:5
BAT+ 1.2 0124 / 10.1 / +A300-AF12-X1:2
1.4 0144 / 11.7 / +A300-AF20:30
1.6 0164 / 23.0 / +FAN-TB6:1
1.8
6² / 9AWG
AGC4
RD 11.7 0142 / 11.2 / +A300-AF20:122 0162 / 16.3 / +ENG-XFWS1:5
© MTU Friedrichshafen GmbH Refer to protection notice DIN 34! Any Aterations are subject to the approval of the design department

14.9 / BAT+
14.9 / BAT-

-X03 9-
10²

0V
Fixed bridge

-X03 0921 / 14.3 / +A300-V1:x1 -X03 0941 / 19.8 / +A300-PJ1:x2 -X03


0923 / 12.3 / +GENO:x 0943 / 11.2 / +A300-AF20:111 0963 / 16.7 / -XFWS2:2
9.2 0924 / 10.1 / +A300-AF12-X1:3
9.4 0944 / 15.3 / -XEB1:2
9.6 0964 / 23.0 / +FAN-TB6:2
0922 / 15.4 / +A300-V2:x1 0962 / 16.3 / +ENG-XFWS1:2
1 0911 / 11.7 / +A300-AF20:2 0931 / 11.2 / +A300-AF20:99 TB4-15 / 21.8 / +GCB-TB4:15
BAT- -X03 -X03 -X03
6² / 9AWG 3 0913 / 19.7 / +A300-FC2:14 0953 / 21.0 / +GCB-TB4:2
BK 9.1 0914 / 14.9 / +ENG-KF1:A2
9.3 9.5 0954 / 22.0 / +MCB-TB5:2
0912 / 14.9 / +ENG-KF2:A2 0932 / 14.7 / +A300-KF2:A2 0952 / 20.1 / +A300-KF1:11
4
2 0V- / 19.0
Terminals legend

Mounting panel Front door


GND GND
-X03 9-
10²
4,0² / 11AWG

4,0² / 11AWG

6,0² / 9AWG

0V potential w/ with
GNYE

GNYE

GNYE

H05V-K 15AWG DBU-WH


-X03
GND GND GND
6,0² / 9AWG
6,0² / 9AWG

6,0² / 9AWG

GNYE
GNYE

GNYE

GND GND Shield


ground bolt ground bolt
SH
M8x25 M8x25

17 19
Drawer 30.11.2015 Moll Circuit diagram Drawing number Supply 24VDC Charger == =
Approved 30.09.2015 Moll XZ54400000171 + 1:1
Norm 30.09.2015 Parchmann Material.No Order no. Page 18
Department EDF Koliwer X54434400107 of 32
0 1 2 3 4 5 6 7 8 9

Auxalary CB tripped Horn


ECU
EPLAN P8 2.3.5 7451

/11.1 /11.1
18.8 / 24V+
24VDC Fixed bridge AGC4 AGC4
+A300-AF20 +A300-AF20

NO
1 13 21 1 14 21 23 5
-FC6 -FC7
C25A 2 14 22 C40A 2 13 22

/19.7

/19.7

FC7:14 WH

WH
1² / 17AWG

1² / 17AWG
2,5² / 13AWG
DBU

2005
FC6

19.2 / 0982
x1
14
-FC7 -PJ1

0991 DBU / WH

0991 DBU / WH

0982 DBU / WH
51

2,5² / 13AWG

2,5² / 13AWG

2,5² / 13AWG
/19.5 13 24V

6,0² / 9AWG
DBU
x2
13
-FC6

FC5

0941 DBU / WH
/19.1 14 Horn
Horn

1² / 17AWG
51 14
-TB10 -V -V +V +V -FC5
960W/24V/40A /18.7 13
2,5² / 13AWG

2,5² / 13AWG

2,5² / 13AWG

ADJ Range 26,7V 0V 24V


Mean Well 13
0512 DBU

0511 DBU

0513 DBU

+A300-X03:9.4:1
0941
© MTU Friedrichshafen GmbH Refer to protection notice DIN 34! Any Aterations are subject to the approval of the design department

SDR-960-24 -FC4
Battery Charger AC AC /18.6 14

18.4 /
W001 14
DANGER L N GND
-FC3
0512

0511

0513

/18.4 13
13
-FC2
X3+ -X01 L N GND /18.2 14
17.2

0913 DBU / WH
-X03

1² / 17AWG
9.9 3x1,5²/15 AWG

L1 N PE

+A300-X03:9.1:3
9.8

0913
0982 / 19.4 Customer

18.2 /
9.7 +GENO-CUS
0972 DBU / WH

0973 DBU / WH

0971 DBU / WH

0984 DBU / WH

0983 DBU / WH

0981 DBU / WH

0992 DBU / WH

0994 DBU / WH

0993 DBU / WH
2,5² / 13AWG

2,5² / 13AWG

2,5² / 13AWG

0VDC
18.8 / 0V-
1² / 17AWG

1² / 17AWG

1² / 17AWG

1² / 17AWG

1² / 17AWG

1² / 17AWG

Power 230VAC - 1,4A


-Fuse C16A/10kA
W001 - Wire 3x1,5²/15AWG
W001
0972

0973

0971

0984

0983

0981

0992

0994

0993

X3-
17.3
-X1/2
17.1

18 20
Drawer 30.11.2015 Moll Circuit diagram Drawing number Supply 24VDC Charger == =
Approved 30.09.2015 Moll XZ54400000171 + 1:1
Norm 30.09.2015 Parchmann Material.No Order no. Page 19
Department EDF Koliwer X54434400107 of 32
EPLAN P8 2.3.5 7451 0 1 2 3 4 5 6 7 8 9

Negativ signal required

Remote Start Status Relay Emergency stop

/11.1 /11.1 /11.1 /11.1


AGC4 AGC4 Closed if AGC4 AGC4

/ 18.6

/ 18.4
+A300-X03:9.5:2

+A300-X03:1.3:2
status I.O
+A300-AF20 +A300-AF20 +A300-AF20 +A300-AF20

COM NO IN
49 3 3 4 4 118
0952

0132
COM NO
WH KF1:31

1² / 17AWG
1² / 17AWG

0132 DBU
31
+A300
0952 DBU / WH

-SF1
1,5² / 15AWG

32
/21.6
© MTU Friedrichshafen GmbH Refer to protection notice DIN 34! Any Aterations are subject to the approval of the design department

E-Stop

1² / 17AWG

1² / 17AWG
WH X06:6

WH X06:7
12 14
+A300-KF1
/20.1 11
GND

+A300-KF1 +A300 6 7 GND


A1 A2 -X06 x
Bridge
24VDC

+A300 15 21
-X04 +CUS
-WSNA1 5 6 GND

31 GND
+CUS
Remote control start/ ATS start
-SF2 32

14 External customer
11 /20.1
12
24
21
22

19 21
Drawer 30.09.2015 F.Jäger Circuit diagram Drawing number Remote control start & Emergency stop == =
Approved 30.09.2015 Moll XZ54400000171 + 1:1
Norm 30.09.2015 Parchmann Material.No Order no. Page 20
Department EDF Koliwer X54434400107 of 32
EPLAN P8 2.3.5 7451 0 1 2 3 4 5 6 7 8 9

GCB closed GCB opened GCB tripped GCB charged GCB open MCB close

1² / 17AWG
WH X06:1
/11.1 /11.1 /11.1 /11.1 /11.1 /11.1
AGC4 AGC4 AGC4 AGC4 AGC4 AGC4 11
+A300-AF20 +A300-AF20 +A300-AF20 +A300-AF20 +A300-AF20 +A300-AF20 +A300
IN IN IN IN OUT OUT -SF1 12
27 26 43 44 14 11 /17.3
/20.3 +A300
E-Stop 1 2
-X06
x
+A300-X03:1.5:3

+A300-X03:9.5:3

1² / 17AWG
WH X06:8
Bridge
+CUS
-WSNA1 1 2

11

+A300-X03:9.5:1
+A300-X03:1.7:3
+CUS
-SF2
4X01:1 WH

4X01:2 WH

4X01:3 WH

4X01:4 WH

4X01:6 WH

4X01:7 WH
1² / 17AWG

1² / 17AWG

1² / 17AWG

1² / 17AWG

1² / 17AWG

1² / 17AWG
12
/ 18.6

/ 18.6

5X01-6 / 22.4

4X01-8 / 22.2
+A300

+A300-5X01:6

+A300-5X01:3
8
-X06 GND GND

1² / 17AWG
WH X06:2
External customer
© MTU Friedrichshafen GmbH Refer to protection notice DIN 34! Any Aterations are subject to the approval of the design department

0153

0953

1² / 17AWG
WH X06:8

/ 18.6
/ 18.7
TB4-14

TB4-15
+A300
0953 DBU / WH

1 2 3 4 5 6 7 8 9 10 11 12 GND GND
-4X01
1² / 17AWG

1² / 17AWG

Red bridge
0153 DBU

4X01: 7-8
Always bridge!
For option 3B
remove bridge.

-WTB4 1 2 3 4 5 6 7 8 9 10 11 12 13 GND 1 2 GND-WTB4.1


ÖLFLEX 110 ÖLFLEX 110
14G1,0 mm² 3G2,5 mm²

SPARE
+GCB NA
1 2 3 4 5 6 7 8 9 10 11 12 13 GND 14 15 GND
-TB4
21 22
Voltage Negativ signal required
0V (-)
Voltage GCB GCB GCB GCB GCB GCB Interlock Interlock E-stop E-stop Spare Only if
24V (+) closed opened tripped charged close open Motorized GCB

Control see generator Option


circuit breaker drawing GCB
20 22
Drawer 30.11.2015 Moll Circuit diagram Drawing number GCB-Generator circuit breaker == =
Approved 30.09.2015 Moll XZ54400000171 + 1:1
Norm 30.09.2015 Parchmann Material.No Order no. Page 21
Department EDF Koliwer X54434400107 of 32
EPLAN P8 2.3.5 7451 0 1 2 3 4 5 6 7 8 9

MCB closed MCB opened MCB open GCB close

/11.1 /11.1 /11.1 /11.1


AGC4 AGC4 AGC4 AGC4
+A300-AF20 +A300-AF20 +A300-AF20 +A300-AF20

IN IN OUT OUT
25 24 8 17
+A300-X03:1.5:4

+A300-X03:9.5:4

+A300-4X01:8

+A300-4X01:5
5X01:1 WH

5X01:2 WH

5X01:4 WH

5X01:5 WH
1² / 17AWG

1² / 17AWG

1² / 17AWG

1² / 17AWG
/ 18.6

/ 18.6

/ 21.5

/ 21.3
GND
4X01-8

5X01-6
© MTU Friedrichshafen GmbH Refer to protection notice DIN 34! Any Aterations are subject to the approval of the design department

0154

0954

+A300
0954 DBU / WH

1 2 3 4 5 6 7 8 9 10 11 12 GND
-5X01
1² / 17AWG

1² / 17AWG

Red bridge
0154 DBU

5X01: 5-6
Always bridge!
For option 3B
remove bridge.

-WTB5 1 2 3 4 5 6 7 8 9 10 11 GND
ÖLFLEX 110
12G1,0 mm²

+MCB 1 2 3 4 5 6 7 8 9 10 11 GND
-TB5
Voltage 21 22
0V (-) Negativ signal required

Voltage MCB MCB MCB MCB Interlock Interlock Spare Spare Spare Spare Spare Spare
24V (+) closed opened close open

Control see mains


circuit breaker drawing MCB Option
21 23
Drawer 30.11.2015 Moll Circuit diagram Drawing number MCB-Mains circuit breaker == =
Approved 30.09.2015 Moll XZ54400000171 + 1:1
Norm 30.09.2015 Parchmann Material.No Order no. Page 22
Department EDF Koliwer X54434400107 of 32
EPLAN P8 2.3.5 7451 0 1 2 3 4 5 6 7 8 9

Fuel cooler Fuel transfer pump Coolant fan 1 Coolant fan 2 Room fan on Auxilary CB Tripped
Louver
/11.1 /11.1 /11.1 /11.1 /11.1 /11.1
AGC4 AGC4 AGC4 AGC4 AGC4 AGC4
+A300-AF20 +A300-AF20 +A300-AF20 +A300-AF20 +A300-AF20 +A300-AF20

OUT OUT OUT OUT OUT IN


69 29 61 63 59 48
+A300-X03:1.6:4

+A300-X03:9.6:4

6X01:2 WH

6X01:3 WH

6X01:4 WH

6X01:5 WH

6X01:8 WH

6X01:10 WH
1² / 17AWG

1² / 17AWG

1² / 17AWG

1² / 17AWG

1² / 17AWG

1² / 17AWG
/ 18.6

/ 18.6

GND
© MTU Friedrichshafen GmbH Refer to protection notice DIN 34! Any Aterations are subject to the approval of the design department

0164

0964

+A300
1 2 3 4 5 6 7 8 9 10 11 12 GND
-6X01
0964 DBU / WH
1,5² / 15AWG

1,5² / 15AWG
0164 DBU

-WTB6 1 2 3 4 5 6 7 8 9 10 11 12 13 GND
ÖLFLEX 110
12G1,0 mm²

+FAN 1 2 3 4 5 6 7 8 9 10 11 12 13 GND
-TB6
Voltage
0V (-)
Voltage GENO Fuel cooler Fuel transfer Coolant Coolant fan 2 Coolant Coolant Room fan on Spare Auxilary CB Feedback Ground
24V (+) Heater pump fan 1 fan 3 Fan 4 Louver Tripped Coolant Fan
Failure

Control see power panel drawing


FAN Option
22 24
Drawer 30.11.2015 Moll Circuit diagram Drawing number FAN-Engine fan == =
Approved 30.09.2015 Moll XZ54400000171 + 1:1
Norm 30.09.2015 Parchmann Material.No Order no. Page 23
Department EDF Koliwer X54434400107 of 32
EPLAN P8 2.3.5 7451 0 1 2 3 4 5 6 7 8 9

-X02 1 2 N 3
GND
-X02
1² / 17AWG

1² / 17AWG

1² / 17AWG
4 5 6 N
2076 WH

2078 WH

2080 WH
GND

GND
-X04 1 2 3 4 5 6 10 11 13 22
85 86 87 88 89
VC

+A300-AF20
AGC4 /11.1 -X05 1 5 6 7 8 9 10 11 12 13 14
Busbar/Mains sensing voltage L1

-X07 1 2 3 4 5 6

0..20mA
Analog in

+A300
-XMOD
1 2
© MTU Friedrichshafen GmbH Refer to protection notice DIN 34! Any Aterations are subject to the approval of the design department

Negativ signal required


Active load sharing COM Reactive load Day tank no Spare Safety System Fixed load Floating load Blocking synch. External protection
sharing leakage Override Genset to Mains tripped
/11.1 /11.1 /11.1 /11.1 /11.1 /11.1 /11.1 /11.1 /11.1 /11.1
AGC4 AGC4 AGC4 AGC4 AGC4 AGC4 AGC4 AGC4 AGC4 AGC4
+A300-AF20 +A300-AF20 +A300-AF20 +A300-AF20 +A300-AF20 +A300-AF20 +A300-AF20 +A300-AF20 +A300-AF20 +A300-AF20

IN IN IN IN IN AN_IN AN_IN AN_IN AN_IN AN_IN


37 38 39 47 50 112 113 114 115 117
2038 DBU/WH

1² / 17AWG

1² / 17AWG

1² / 17AWG

1² / 17AWG

1² / 17AWG

1² / 17AWG

1² / 17AWG
2112 WH

2112 WH

2112 WH

2113 WH

2114 WH

2115 WH

2117 WH
1² / 17AWG

1² / 17AWG

1² / 17AWG
2037 WH

2039 WH

-X04 7 8 9 12 14 19 16 17 18 20

Daytank General fault General alarm


control red yellow
/11.1 /11.1 /11.1
AGC4 AGC4 AGC4
+A300-AF20 +A300-AF20 +A300-AF20

35 31 33

-X05 2 3 4

23 25
Drawer 03.09.2015 Florian Jäger Circuit diagram Drawing number Spare terminal == =
Approved 30.09.2015 Moll XZ54400000171 + 1:1
Norm 30.09.2015 Parchmann Material.No Order no. Page 24
Department EDF Koliwer X54434400107 of 32
0 1 2 3 4 5 6 7 8 9

Bill of material
EPLAN P8 2.3.5 7451

mmo

Device designation
Quantity Designation Order no. SAP-Order no. Manufacturer
Page / Position

1 AE Kompakt Schaltschrank Rittal GmbH & Co.KG


+A300 AE1090.009
Piece AE compact control cabinet
1840 Kabelkanal 80x30
+A300 TS8800.750 Rittal GmbH & Co.KG
mm Cable duct 80x30
1300 Kabelkanal 80x40 Rittal GmbH & Co.KG
+A300 TS8800.751
mm Cable duct 80x40
540 Kabelkanal 80x80 Rittal GmbH & Co.KG
+A300 TS8800.753
mm Cable duct 80x80
2430 Tragschiene TS35/7,5 Rittal GmbH & Co.KG
+A300 SZ2317.000
mm Support rail TS35/7,5
400 Sammelschiene Schirm 3x10 Phönix Contact GmbH & Co. KG
+A300 0402174
mm Bus bar shield 3x10
3 Auflageblock
+A300 0404428 Phönix Contact GmbH & Co. KG
Piece Support bracket
© MTU Friedrichshafen GmbH Refer to protection notice DIN 34! Any Aterations are subject to the approval of the design department

2 Anschlussklemme
+A300 0421029 Phönix Contact GmbH & Co. KG
Piece Terminal clamp
8 Schirmanschlussklemme
+A300 3025163 Phönix Contact GmbH & Co. KG
Piece Shield bus bar terimal
1 Datenschnittstelle
+A300-AF12 X00E50209782 MTU Friedrichshafen GmbH
Piece Smart Connect
1 Genset Controller V2-7 TCP/IP/CAN Deif A/S
+A300-AF20 X59434200202 X59434200202
Piece Genset Controller V2-7 TCP/IP/CAN
1 Widerstand 470 Ohm
+A300-AF20R Piece Resistor 470 Ohm
1 Leitungsschutzschalter C 6A/10kVA 1polig Siemens AG
+A300-FC1 5SY4106-7
Piece Circuit-breaker C6A/10kVA 1pol
1 Leitungsschutzschalter C10A/10kA 1polig Siemens AG
+A300-FC2 5SY4110-7
Piece Circuit-breaker C10A/10kVA 1pol
1 Hilfsstromschalter 1S+1OE für LS-Schalter Siemens AG
+A300-FC2 5ST3010
Piece Aux.current switch 1NO+1NC
1 Leitungsschutzschalter C10A/10kA 1polig
+A300-FC3 5SY4110-7 Siemens AG
Piece Circuit-breaker C10A/10kVA 1pol
1 Hilfsstromschalter 1S+1OE für LS-Schalter
+A300-FC3 5ST3010 Siemens AG
Piece Aux.current switch 1NO+1NC
1 Leitungsschutzschalter C 6A/10kVA 1polig
+A300-FC4 5SY4106-7 Siemens AG
Piece Circuit-breaker C6A/10kVA 1pol
1 Hilfsstromschalter 1S+1OE für LS-Schalter
+A300-FC4 5ST3010 Siemens AG
Piece Aux.current switch 1NO+1NC
MTU_25_Kunde_D_E

24 25.a
Drawer 30.11.2015 Moll Circuit diagram Drawing number Bill of material : RIT.1090009 - SIE.5ST3010 == =
Approved 30.09.2015 Moll XZ54400000171 + 1:1
Norm 30.09.2015 Parchmann Material.No Order no. Page 25
Department EDF Koliwer X54434400107 of 32
0 1 2 3 4 5 6 7 8 9

Bill of material
EPLAN P8 2.3.5 7451

mmo

Device designation
Quantity Designation Order no. SAP-Order no. Manufacturer
Page / Position

1 Leitungsschutzschalter C20A/10kA 1polig Siemens AG


+A300-FC5 5SY4120-7
Piece Circuit-breaker C20A/10kVA 1pol
1 Hilfsstromschalter 1S+1OE für LS-Schalter
+A300-FC5 5ST3010 Siemens AG
Piece Aux.current switch 1NO+1NC
1 Leitungsschutzschalter C25A/10kA 1polig Siemens AG
+A300-FC6 5SY4125-7
Piece Circuit-breaker C25A/10kVA 1pol
1 Hilfsstromschalter 1S+1OE für LS-Schalter Siemens AG
+A300-FC6 5ST3010
Piece Aux.current switch 1NO+1NC
1 Leitungsschutzschalter C40A/10kA 1polig Siemens AG
+A300-FC7 5SY4140-7
Piece Circuit-breaker C40A/10kVA 1pol
1 Hilfsstromschalter 1S+1OE für LS-Schalter Siemens AG
+A300-FC7 5ST3010
Piece Aux.current switch 1NO+1NC
1 Koppel-Relais 24V DC 2 Wechsler 8A
+A300-KF1 40.52.9.024.0000 X00059498 Finder GmbH
Piece Relais 24V DC 2C 8A
© MTU Friedrichshafen GmbH Refer to protection notice DIN 34! Any Aterations are subject to the approval of the design department

1 Schraubfassung für 40.52.


+A300-KF1 95.05 XP54442300012 Finder GmbH
Piece Relay socket to 40.52
1 Haltebügel für 40.52.
+A300-KF1 95.01 XP54442300013 Finder GmbH
Piece Retaining bracket for 40.52
1 Freilaufdiode 6-24VDC
+A300-KF1 99.02.9.024.99 93270511323 Finder GmbH
Piece Fly back diode 6-24VDC
0 Koppel-Relais 24V DC 2 Wechsler 8A Finder GmbH
+A300-KF2 40.52.9.024.0000 X00059498
Piece Relais 24V DC 2C 8A
0 Schraubfassung für 40.52.
+A300-KF2 95.05 XP54442300012 Finder GmbH
Piece Relay socket to 40.52
0 Haltebügel für 40.52. Finder GmbH
+A300-KF2 95.01 XP54442300013
Piece Retaining bracket for 40.52
0 Freilaufdiode 6-24VDC Finder GmbH
+A300-KF2 99.02.9.024.99 93270511323
Piece Fly back diode 6-24VDC
1 Akustikmelder IP40 Eaton GmbH
+A300-PJ1 229015
Piece Alarm horn IP40
1 Summer 18-30VDC - 83dB Dauerton
+A300-PJ1 229025 Eaton GmbH
Piece Alarm horn 18-30VDC - 83dB continuous tone
1 Blindstopfen grau
+A300-PJ1 216388 Eaton GmbH
Piece Blanking plug grey
1 NOT-AUS Pilzdrucktaster
+A300-SF1 RV356 SUR46024005 Schlegel GmbH & Co.KG
Piece Emerg.Stop push button
3 Tastkontaktgeber 1Ö
+A300-SF1 MTO SUR46024005_2 Schlegel GmbH & Co.KG
Piece Switch element 1NC
MTU_25_Kunde_D_E

25 25.b
Drawer 30.11.2015 Moll Circuit diagram Drawing number Bill of material : SIE.5SY4120-7 - SCH.MTO == =
Approved 30.09.2015 Moll XZ54400000171 + 1:1
Norm 30.09.2015 Parchmann Material.No Order no. Page 25.a
Department EDF Koliwer X54434400107 of 32
0 1 2 3 4 5 6 7 8 9

Bill of material
EPLAN P8 2.3.5 7451

mmo

Device designation
Quantity Designation Order no. SAP-Order no. Manufacturer
Page / Position

1 Modul-Halter 3 Elemente Schlegel GmbH & Co.KG


+A300-SF1 MHR_3 SUR46024005_1
Piece Module holder 3 elements
1 Unterlegschild für Not-Aus gelb
+A300-SF1 NAS22 SUR46601015 Schlegel GmbH & Co.KG
Piece Nameplates for emergency-off yellow
0 Drucktaster Schlegel GmbH & Co.KG
+A300-SF3 RT
Piece Push button
0 Tasterkappe Schlegel GmbH & Co.KG
+A300-SF3 TG22GWS
Piece Push button cap
0 Tastkontaktgeber 1Ö Schlegel GmbH & Co.KG
+A300-SF3 MTO SUR46024005_2
Piece Switch element 1NC
0 Modul-Halter 3 Elemente Schlegel GmbH & Co.KG
+A300-SF3 MHR_3 SUR46024005_1
Piece Module holder 3 elements
0 Schildträger
+A300-SF3 RABT Schlegel GmbH & Co.KG
Piece Tag holder
© MTU Friedrichshafen GmbH Refer to protection notice DIN 34! Any Aterations are subject to the approval of the design department

0 Bezeichnungsschild 19x27 gelasert


+A300-SF3 BZ23G Schlegel GmbH & Co.KG
Piece Label laser-cut 19x27
1 Einphasige Stromversorgung 230V/ 24VDC/ 40A,
+A300-TB10 SDR-960-24 Mean Well
Piece Single-phase power supply 230V/ 24VDC/ 40A,
1 Standard Diode 1000V/1,0A
+A300-V1 1N4007 93270510696 Diotec Semiconductor
Piece Standard diode 1000V/1,0A
1 Standard Diode 1000V/1,0A Diotec Semiconductor
+A300-V2 1N4007 93270510696
Piece Standard diode 1000V/1,0A
250 UNITRONIC LiYCY 2x0,34mm²
+A300-WCAN_2 0031068 Lapp GmbH
mm UNITRONIC LiYCY 2xAWG22
1 Schnellmontage-Endhalter, NS35/7 Phönix Contact GmbH & Co. KG
+A300-X01 1201442 SUR4-68-15352
Piece Snap-on end bracket, NS35/7
1 Abdeckhalter Phönix Contact GmbH & Co. KG
+A300-X01 1201468
Piece Cover holder
180 Abdeckprofil Phönix Contact GmbH & Co. KG
+A300-X01 3202575
Piece Cover profil
1 Abschlussdeckel D-STI /3
+A300-X01 3030844 Phönix Contact GmbH & Co. KG
Piece End cover D-STI /3
1 Trennplatte ATP-STI /3
+A300-X01 3030857 Phönix Contact GmbH & Co. KG
Piece Partition plate ATP-STI /3
1 Installationsklemme mit Zugfederanschluss STI 2,5
+A300-X01 3031843 Phönix Contact GmbH & Co. KG
Piece Installation level terminal block, Spring cage connection STI 2,5
2 Abschlussdeckel D-PTME 4
+A300-X02 3212167 Phönix Contact GmbH & Co. KG
Piece End cover D-PTME 4
MTU_25_Kunde_D_E

25.a 25.c
Drawer 30.11.2015 Moll Circuit diagram Drawing number Bill of material : SCH.MHR_3 - PHO.3212167 == =
Approved 30.09.2015 Moll XZ54400000171 + 1:1
Norm 30.09.2015 Parchmann Material.No Order no. Page 25.b
Department EDF Koliwer X54434400107 of 32
0 1 2 3 4 5 6 7 8 9

Bill of material
EPLAN P8 2.3.5 7451

mmo

Device designation
Quantity Designation Order no. SAP-Order no. Manufacturer
Page / Position

2 Trennplatte ATP-STI /3 Phönix Contact GmbH & Co. KG


+A300-X02 3030857
Piece Partition plate ATP-STI /3
8 Messwandler - Trennklemme
+A300-X02 3212139 Phönix Contact GmbH & Co. KG
Piece Measuring transformer - Disconnect terminal
2 Schutzleiterklemme mit Zugfederanschluss PTMED 4 PE Phönix Contact GmbH & Co. KG
+A300-X02 3212154
Piece Ground terminal blocks with spring-cage connection PTMED 4 PE
2 Schnellmontage-Endhalter, NS35/7 Phönix Contact GmbH & Co. KG
+A300-X03 3022218
Piece Snap-on end bracket, NS35/7
2 Deckel D-ST 10 Phönix Contact GmbH & Co. KG
+A300-X03 3036644
Piece Cover D-ST 10
5 Trennplatte ATP-ST Quattro Phönix Contact GmbH & Co. KG
+A300-X03 3030815
Piece Seperator plate ATP-ST quattro
2 Abschlussdeckel D-ST 2,5 Quattro
+A300-X03 3030514 Phönix Contact GmbH & Co. KG
Piece End cover D-ST 2,5 Quattro
© MTU Friedrichshafen GmbH Refer to protection notice DIN 34! Any Aterations are subject to the approval of the design department

5 Steckbrücke 2-fach
+A300-X03 3030161 Phönix Contact GmbH & Co. KG
Piece Two-point jumper
2 Reduzierbrücke ST 10-(2,5/4)
+A300-X03 3030873 Phönix Contact GmbH & Co. KG
Piece Reducing jumper ST 10-(2,5/4)
1 Steckbrücke 3-fach
+A300-X03 3030174 Phönix Contact GmbH & Co. KG
Piece Three-point jumper
2 Steckbrücke 4-fach Phönix Contact GmbH & Co. KG
+A300-X03 3030187
Piece Four-point jumper
3 Durchgangsklemme mit Zugfederanschluss ST10
+A300-X03 3036110 Phönix Contact GmbH & Co. KG
Piece Spring Cage Feed-Through Terminal Blocks
14 Zugfederanschlussklemme ST 2,5-Quattro 0,08-2,5²/ 28-12 AWG Phönix Contact GmbH & Co. KG
+A300-X03 3031306
Piece Bottom terminals ST 2,5-Quattro 0,08-2,5²/ 28-12 AWG
3 Schutzleiterklemme mit Zugfederanschluss ST6 PE Phönix Contact GmbH & Co. KG
+A300-X03 3031500 SUR4-68-15363
Piece Ground terminal blocks with spring-cage connection ST6 PE
1 Schnellmontage-Endhalter, NS35/7 Phönix Contact GmbH & Co. KG
+A300-X04 3022218
Piece Snap-on end bracket, NS35/7
1 Deckel D-STTBS 2,5 TWIN
+A300-X04 3038558 Phönix Contact GmbH & Co. KG
Piece Cover D-STTBS 2,5 TWIN
1 Trennplatte ATP-STTB 4
+A300-X04 3030747 Phönix Contact GmbH & Co. KG
Piece Partition plate ATP-STTB 4
11 Durchgangsklemme mit Zugfederanschluss STTB 2,5-TWIN
+A300-X04 3038516 Phönix Contact GmbH & Co. KG
Piece Spring Cage Feed-Through Terminal Blocks STTB 2,5-TWIN
2 Steckbrücke 3-fach
+A300-X05 3030174 Phönix Contact GmbH & Co. KG
Piece Three-point jumper
MTU_25_Kunde_D_E

25.b 25.d
Drawer 30.11.2015 Moll Circuit diagram Drawing number Bill of material : PHO.3030857 - PHO.3030174 == =
Approved 30.09.2015 Moll XZ54400000171 + 1:1
Norm 30.09.2015 Parchmann Material.No Order no. Page 25.c
Department EDF Koliwer X54434400107 of 32
0 1 2 3 4 5 6 7 8 9

Bill of material
EPLAN P8 2.3.5 7451

mmo

Device designation
Quantity Designation Order no. SAP-Order no. Manufacturer
Page / Position

1 Deckel D-STTBS 2,5 TWIN Phönix Contact GmbH & Co. KG


+A300-X05 3038558
Piece Cover D-STTBS 2,5 TWIN
1 Trennplatte ATP-STTB 4
+A300-X05 3030747 Phönix Contact GmbH & Co. KG
Piece Partition plate ATP-STTB 4
7 Durchgangsklemme mit Zugfederanschluss STTB 2,5-TWIN Phönix Contact GmbH & Co. KG
+A300-X05 3038516
Piece Spring Cage Feed-Through Terminal Blocks STTB 2,5-TWIN
1 Schnellmontage-Endhalter, NS35/7 Phönix Contact GmbH & Co. KG
+A300-X06 3022218
Piece Snap-on end bracket, NS35/7
1 Deckel D-STTBS 2,5 TWIN Phönix Contact GmbH & Co. KG
+A300-X06 3038558
Piece Cover D-STTBS 2,5 TWIN
4 Durchgangsklemme mit Zugfederanschluss STTB 2,5-TWIN Phönix Contact GmbH & Co. KG
+A300-X06 3038516
Piece Spring Cage Feed-Through Terminal Blocks STTB 2,5-TWIN
1 Schutzleiterklemme mit Zugfederanschluss STTB 2,5 TWIN PE
+A300-X06 3038532 Phönix Contact GmbH & Co. KG
Piece Ground terminal blocks with spring-cage connection STTB 2,5 TWIN
© MTU Friedrichshafen GmbH Refer to protection notice DIN 34! Any Aterations are subject to the approval of the design department

1 Schnellmontage-Endhalter, NS35/7
+A300-X07 3022218 Phönix Contact GmbH & Co. KG
Piece Snap-on end bracket, NS35/7
1 Deckel D-STTBS 2,5 TWIN
+A300-X07 3038558 Phönix Contact GmbH & Co. KG
Piece Cover D-STTBS 2,5 TWIN
3 Durchgangsklemme mit Zugfederanschluss STTB 2,5-TWIN
+A300-X07 3038516 Phönix Contact GmbH & Co. KG
Piece Spring Cage Feed-Through Terminal Blocks STTB 2,5-TWIN
1 Schnellmontage-Endhalter, NS35/7 Phönix Contact GmbH & Co. KG
+A300-1X01 3022218
Piece Snap-on end bracket, NS35/7
1 Deckel D-STTBS 2,5 TWIN
+A300-1X01 3038558 Phönix Contact GmbH & Co. KG
Piece Cover D-STTBS 2,5 TWIN
1 Trennplatte ATP-STTB 4 Phönix Contact GmbH & Co. KG
+A300-1X01 3030747
Piece Partition plate ATP-STTB 4
6 Durchgangsklemme mit Zugfederanschluss STTB 2,5-TWIN Phönix Contact GmbH & Co. KG
+A300-1X01 3038516
Piece Spring Cage Feed-Through Terminal Blocks STTB 2,5-TWIN
1 Schnellmontage-Endhalter, NS35/7 Phönix Contact GmbH & Co. KG
+A300-1X02 3022218
Piece Snap-on end bracket, NS35/7
1 Deckel D-STTBS 2,5 TWIN
+A300-1X02 3038558 Phönix Contact GmbH & Co. KG
Piece Cover D-STTBS 2,5 TWIN
1 Trennplatte ATP-STTB 4
+A300-1X02 3030747 Phönix Contact GmbH & Co. KG
Piece Partition plate ATP-STTB 4
2 Durchgangsklemme mit Zugfederanschluss STTB 2,5-TWIN
+A300-1X02 3038516 Phönix Contact GmbH & Co. KG
Piece Spring Cage Feed-Through Terminal Blocks STTB 2,5-TWIN
1 Deckel D-STTBS 2,5 TWIN
+A300-2X01 3038558 Phönix Contact GmbH & Co. KG
Piece Cover D-STTBS 2,5 TWIN
MTU_25_Kunde_D_E

25.c 25.e
Drawer 30.11.2015 Moll Circuit diagram Drawing number Bill of material : PHO.3038558 - PHO.3038558 == =
Approved 30.09.2015 Moll XZ54400000171 + 1:1
Norm 30.09.2015 Parchmann Material.No Order no. Page 25.d
Department EDF Koliwer X54434400107 of 32
0 1 2 3 4 5 6 7 8 9

Bill of material
EPLAN P8 2.3.5 7451

mmo

Device designation
Quantity Designation Order no. SAP-Order no. Manufacturer
Page / Position

1 Trennplatte ATP-STTB 4 Phönix Contact GmbH & Co. KG


+A300-2X01 3030747
Piece Partition plate ATP-STTB 4
3 Durchgangsklemme mit Zugfederanschluss STTB 2,5-TWIN
+A300-2X01 3038516 Phönix Contact GmbH & Co. KG
Piece Spring Cage Feed-Through Terminal Blocks STTB 2,5-TWIN
1 Deckel D-STTBS 2,5 TWIN Phönix Contact GmbH & Co. KG
+A300-3X01 3038558
Piece Cover D-STTBS 2,5 TWIN
1 Trennplatte ATP-STTB 4 Phönix Contact GmbH & Co. KG
+A300-3X01 3030747
Piece Partition plate ATP-STTB 4
0 Schnellmontage-Endhalter, NS35/7 Phönix Contact GmbH & Co. KG
+A300-3X01 1201442 SUR4-68-15352
Piece Snap-on end bracket, NS35/7
4 Durchgangsklemme mit Zugfederanschluss STTB 2,5-TWIN Phönix Contact GmbH & Co. KG
+A300-3X01 3038516
Piece Spring Cage Feed-Through Terminal Blocks STTB 2,5-TWIN
1 Abschlussdeckel D-PTME 4
+A300-3X02 3212167 Phönix Contact GmbH & Co. KG
Piece End cover D-PTME 4
© MTU Friedrichshafen GmbH Refer to protection notice DIN 34! Any Aterations are subject to the approval of the design department

1 Trennplatte ATP-STI /3
+A300-3X02 3030857 Phönix Contact GmbH & Co. KG
Piece Partition plate ATP-STI /3
4 Messwandler - Trennklemme
+A300-3X02 3212139 Phönix Contact GmbH & Co. KG
Piece Measuring transformer - Disconnect terminal
1 Schutzleiterklemme mit Zugfederanschluss PTMED 4 PE
+A300-3X02 3212154 Phönix Contact GmbH & Co. KG
Piece Ground terminal blocks with spring-cage connection PTMED 4 PE
1 Abschlussdeckel D-ST 2,5 Quattro Phönix Contact GmbH & Co. KG
+A300-3X03 3030514
Piece End cover D-ST 2,5 Quattro
1 Abschlussdeckel D-PTME 4
+A300-3X03 3212167 Phönix Contact GmbH & Co. KG
Piece End cover D-PTME 4
1 Schnellmontage-Endhalter, NS35/7 Phönix Contact GmbH & Co. KG
+A300-3X03 1201442 SUR4-68-15352
Piece Snap-on end bracket, NS35/7
3 Prüfadapter BK Phönix Contact GmbH & Co. KG
+A300-3X03 3035980
Piece Test adapter BK
1 Prüfadapter OG Phönix Contact GmbH & Co. KG
+A300-3X03 3035974
Piece Test adapter OG
3 Schaltbrücke
+A300-3X03 3035755 Phönix Contact GmbH & Co. KG
Piece Switching jumper
6 Messwandler - Trennklemme
+A300-3X03 3212139 Phönix Contact GmbH & Co. KG
Piece Measuring transformer - Disconnect terminal
1 Zugfederanschlussklemme ST 2,5-Quattro 0,08-2,5²/ 28-12 AWG
+A300-3X03 3031306 Phönix Contact GmbH & Co. KG
Piece Bottom terminals ST 2,5-Quattro 0,08-2,5²/ 28-12 AWG
1 Deckel D-STTBS 2,5 TWIN
+A300-4X01 3038558 Phönix Contact GmbH & Co. KG
Piece Cover D-STTBS 2,5 TWIN
MTU_25_Kunde_D_E

25.d 25.f
Drawer 30.11.2015 Moll Circuit diagram Drawing number Bill of material : PHO.3030747 - PHO.3038558 == =
Approved 30.09.2015 Moll XZ54400000171 + 1:1
Norm 30.09.2015 Parchmann Material.No Order no. Page 25.e
Department EDF Koliwer X54434400107 of 32
0 1 2 3 4 5 6 7 8 9

Bill of material
EPLAN P8 2.3.5 7451

mmo

Device designation
Quantity Designation Order no. SAP-Order no. Manufacturer
Page / Position

1 Trennplatte ATP-STTB 4 Phönix Contact GmbH & Co. KG


+A300-4X01 3030747
Piece Partition plate ATP-STTB 4
6 Durchgangsklemme mit Zugfederanschluss STTB 2,5-TWIN
+A300-4X01 3038516 Phönix Contact GmbH & Co. KG
Piece Spring Cage Feed-Through Terminal Blocks STTB 2,5-TWIN
2 Schutzleiterklemme mit Zugfederanschluss STTB 2,5 TWIN PE Phönix Contact GmbH & Co. KG
+A300-4X01 3038532
Piece Ground terminal blocks with spring-cage connection STTB 2,5 TWIN
1 Deckel D-STTBS 2,5 TWIN Phönix Contact GmbH & Co. KG
+A300-5X01 3038558
Piece Cover D-STTBS 2,5 TWIN
1 Trennplatte ATP-STTB 4 Phönix Contact GmbH & Co. KG
+A300-5X01 3030747
Piece Partition plate ATP-STTB 4
6 Durchgangsklemme mit Zugfederanschluss STTB 2,5-TWIN Phönix Contact GmbH & Co. KG
+A300-5X01 3038516
Piece Spring Cage Feed-Through Terminal Blocks STTB 2,5-TWIN
1 Schutzleiterklemme mit Zugfederanschluss STTB 2,5 TWIN PE
+A300-5X01 3038532 Phönix Contact GmbH & Co. KG
Piece Ground terminal blocks with spring-cage connection STTB 2,5 TWIN
© MTU Friedrichshafen GmbH Refer to protection notice DIN 34! Any Aterations are subject to the approval of the design department

1 Deckel D-STTBS 2,5 TWIN


+A300-6X01 3038558 Phönix Contact GmbH & Co. KG
Piece Cover D-STTBS 2,5 TWIN
1 Schnellmontage-Endhalter, NS35/7
+A300-6X01 3022218 Phönix Contact GmbH & Co. KG
Piece Snap-on end bracket, NS35/7
6 Durchgangsklemme mit Zugfederanschluss STTB 2,5-TWIN
+A300-6X01 3038516 Phönix Contact GmbH & Co. KG
Piece Spring Cage Feed-Through Terminal Blocks STTB 2,5-TWIN
1 Schutzleiterklemme mit Zugfederanschluss STTB 2,5 TWIN PE Phönix Contact GmbH & Co. KG
+A300-6X01 3038532
Piece Ground terminal blocks with spring-cage connection STTB 2,5 TWIN
2 Schnellmontage-Endhalter, NS35/7
+A300-XMOD 3022218 Phönix Contact GmbH & Co. KG
Piece Snap-on end bracket, NS35/7
1 Deckel D-ST 2,5 TWIN Phönix Contact GmbH & Co. KG
+A300-XMOD 3030488
Piece Cover D-ST 2,5 TWIN
4 Zugfederanschlussklemme ST 2,5-Twin Phönix Contact GmbH & Co. KG
+A300-XMOD 3031241
Piece Bottom terminals ST 2,5-Twin
2 Schutzleiter-Reihenklemme ST 2,5-Twin Phönix Contact GmbH & Co. KG
+A300-XMOD 3031267
Piece Ground terminal blocks with spring-cage connection ST 2,5-Twin

MTU_25_Kunde_D_E

25.e
Drawer 30.11.2015 Moll Circuit diagram Drawing number Bill of material : PHO.3030747 - PHO.3031267 == =
Approved 30.09.2015 Moll XZ54400000171 + 1:1
Norm 30.09.2015 Parchmann Material.No Order no. Page 25.f
Department EDF Koliwer X54434400107 of 32