6Ir Time 2.5 Sec Short circuit 6.0x Ir Time 100 Msec Ground Fault 0.30xIn Time 100 Msec Thermal Memory ON Default ON
5. Secondary Injection Test:
5.1. Over Load:
Ref Set Current(A) Injected Current(A) Set Time(S) Operating Time(S)
R 1.0 In 2.5 In --- 14.77
Y 1.0 In 4.5 In --- 4.46 B 1.0 In 6.5 In 2.5 Sec @6.0Ir 2.12 5.2. Short Circuit:
Ref Set Current(A) Injected Current(A) Set Time(S) Operating Time(S)
R 6.0 Ir 6.5 Ir 0.1 0.29
Y 8.0 Ir 9.5 Ir 0.3 0.49 B 10.0 Ir 11.0 Ir 0.6 0.78
5.3. Earth Fault:
Ref Set Current(A) Injected Current(A) Set Time(S) Operating Time(S)
R 0.30 0.35 0.1 0.28
Y 0.40 0.45 0.3 0.48 B 0.50 0.50 0.4 No Trip B 0.5 0.55 0.4 0.51
5.4. Thermal Memory ON:
Ref Set Current(A) Injected Current(A) Set Time(S) Operating Time(S)
R 1.0 In 4.5 In --- 0.40
5.5. Thermal Memory OFF:
Ref Set Current(A) Injected Current(A) Set Time(S) Operating Time(S)
R 1.0 In 4.5 In --- 4.37
6. Functional checks: (Whether Operational Checks OK / Not OK / Not Applicable)
1 CT Wiring from TB to Relay checks OK
2 Correct operation of appropriate indication/All Output relay OK 3 Correct operation of alarm contacts Not OK 4 Correct circuit breaker tripping contacts OK 5 Relay cover properly fixing OK 6 Correct operating reset switch Not OK 7 Data Storage/ Fault data Record Not OK
7. Comments : 1.Query Switch Function not working.
2. Test Switch Function Not Working. 3. Clear Switch Function Not Working. 8. Remarks : Relay found Healthy.