You are on page 1of 2

1.

Location : AC Plant

Feeder Name : APG

2. Equipment Details:

3. General Inspection: OK

4. Service Settings:

Over Load 1.0xIn


6Ir Time 2.5 Sec
Short circuit 6.0x Ir
Time 100 Msec
Ground Fault 0.30xIn
Time 100 Msec
Thermal Memory ON
Default ON

5. Secondary Injection Test:


5.1. Over Load:

Ref Set Current(A) Injected Current(A) Set Time(S) Operating Time(S)

R 1.0 In 2.5 In --- 14.77


Y 1.0 In 4.5 In --- 4.46
B 1.0 In 6.5 In 2.5 Sec @6.0Ir 2.12
5.2. Short Circuit:

Ref Set Current(A) Injected Current(A) Set Time(S) Operating Time(S)

R 6.0 Ir 6.5 Ir 0.1 0.29


Y 8.0 Ir 9.5 Ir 0.3 0.49
B 10.0 Ir 11.0 Ir 0.6 0.78

5.3. Earth Fault:

Ref Set Current(A) Injected Current(A) Set Time(S) Operating Time(S)

R 0.30 0.35 0.1 0.28


Y 0.40 0.45 0.3 0.48
B 0.50 0.50 0.4 No Trip
B 0.5 0.55 0.4 0.51

5.4. Thermal Memory ON:

Ref Set Current(A) Injected Current(A) Set Time(S) Operating Time(S)

R 1.0 In 4.5 In --- 0.40

5.5. Thermal Memory OFF:


Ref Set Current(A) Injected Current(A) Set Time(S) Operating Time(S)

R 1.0 In 4.5 In --- 4.37

6. Functional checks: (Whether Operational Checks OK / Not OK / Not Applicable)

1 CT Wiring from TB to Relay checks OK


2 Correct operation of appropriate indication/All Output relay OK
3 Correct operation of alarm contacts Not OK
4 Correct circuit breaker tripping contacts OK
5 Relay cover properly fixing OK
6 Correct operating reset switch Not OK
7 Data Storage/ Fault data Record Not OK

7. Comments : 1.Query Switch Function not working.


2. Test Switch Function Not Working.
3. Clear Switch Function Not Working.
8. Remarks : Relay found Healthy.