You are on page 1of 3

PROJECT POLGAHAWELA, POTHUHERA AND ALAWWA INTEGRATED WATER SUPPLY PROJECT

STRUCTURE INTAKE PUMP STATION ELEMENT RAFTER BEAM UKB 254x146x37 REF
CODES BS5950‐1:2000 DESIGNED BY KUSHAN CHECKED BY MAHESH 18/07/2017
Reference Calculations Output
11.1 DESIGN INFORMATION
Material Properties
2
Design strength of steel, py = 275 N/mm
2
Modulus of elasticity E = 205000 N/mm

Section Properties
Y D = 256 mm
T = 10.9 mm
B = 146.4 mm
b = 73.2 mm
d = 219 mm
X X t = 6.3 mm
b/T = 6.716
d/t = 34.762
rx = 108.4 mm
ry = 34.8 mm
Y A = 4.72E+03 mm2
3
Sx = 4.83E+05 mm
Sy = 1.19E+05 mm3
Zx = 4.33E+05 mm3
Zy = 7.80E+04 mm3

Lateral restraint
Distance between major axis restraints Lx = 6060 mm
Distance between minor axis restraints Ly = 1000 mm

Effective length factors


Effective length factor in major axis Kx  = 1
Effective length factor in minor axis Ky = 1
Effective length factor for lateral‐torsional buckling KLT = 1.4 Ly + 2 x D
= 1912 mm
 DESIGN FORCES
Load combination FC [kN] BM, Mx [kNm] SF, Fv [kN]
ENV(1.4DL+1.6LL+1.6CL) 18.64 22.04 25.86

SECTION CLASSIFICATION
T = 10.9 mm
2
Table 9 Design Strength, py = 275 N/mm
Parameter,
ε =
= 1.0
Table 11 Flange: Outstand Element of Compression Flange Rolled Section
b/T = 6.7
9ε = 9.0
b/T < 9ε Flange is Plastic
Web: Neutral Axis at Mid ‐ Depth
d/t = 34.8
80ε = 80.0
b/T < 80ε Web is Plastic
Hence, Section is Plastic Section is Plastic
Cl. 4.2.3 d/t < 70ε, and Hence Check for Shear Buckling is not required
PROJECT POLGAHAWELA, POTHUHERA AND ALAWWA INTEGRATED WATER SUPPLY PROJECT
STRUCTURE INTAKE PUMP STATION ELEMENT RAFTER BEAM UKB 254x146x37 REF
CODES BS5950‐1:2000 DESIGNED BY KUSHAN CHECKED BY MAHESH 18/07/2017
Reference Calculations Output
 SHEAR CAPACITY
Cl. 4.2.3 Design Shear Force, Fv = 25.9 kN
Shear Capacity, Pv =
= 266.1 kN
Hence, Section's Shear Capacity is Satisfactory Satisfactory

BENDING MOMENT CAPACITY
Cl. 4.2.5.2 Design Shear Force <<< 0.6 x Shear Capacity, Hence Low Shear Equation for
Bending is applied.
Design Bending Moment, Mx = 22.0 kNm
Cl. 4.2.5.3 Bending Moment Capacity, Mc = min(PySx,1.2pyZx)
= 132.9 kNm Mc = 132.9kNm
Hence, Section's Bending Moment Capacity is Satisfactory Satisfactory

 LATERAL TORSIONAL BUCKLING MOMENT CAPACITY
Table 13 Effective Length, LE = 1912.0 mm

λ =
Cl. 4.3.6.7 Slenderness,
= 55.0
Cl. 4.3.6.8 Buckling Parameter, u = 0.89
Torsional Index, x = 23.5
λ/x = 2.3
Flange Ratio for UB Sections, η = 0.5
Cl. 4.3.6.9 βw = 1.0
Therefore,
Table 19 Slenderness Factore, ν = 0.95
Cl. 4.3.6.7 Equivalent Slenderness, λLT =
Table 19 = 46.5
Table 16 Limiting Slenderness, λ LO = 34.3
Equivalent Slenderness > Limiting Slenderness, and Hence Check for Lateral
Torsional Buckling is Required.
Table 16 Buckling Resistance, pb = 245.2 N/mm2

Cl. 4.3.6.4 Buckling Resistance Moment Capacity, Mb =


= 118.5 kNm Mb = 118.5kNm
Design Bending Moment, Mx = 22.0 kNm
Therefore, = 118.5 kNm

Hence, Section's Buckling Moment Capacity is Satisfactory Satisfactory

COMPRESSION CAPACITY
Design compressive force Fc = 18.64 kN
Effective length for major axis buckling LEx = 6060 mm
Slenderness ratio λx = Lex/rx
= 55.93
Table 23 Struct curve = a
Table 24 Compressive strength pc = 244.105 N/mm2

Cl 4.7.4 Compressive resistance = Apcx


= 1152.18 kN
Hence, Section's Compressive Capacity is Satisfactory with respect to major axis Satisfactory
PROJECT POLGAHAWELA, POTHUHERA AND ALAWWA INTEGRATED WATER SUPPLY PROJECT
STRUCTURE INTAKE PUMP STATION ELEMENT RAFTER BEAM UKB 254x146x37 REF
CODES BS5950‐1:2000 DESIGNED BY KUSHAN CHECKED BY MAHESH 18/07/2017
Reference Calculations Output
Effective length for minor axis buckling Ley = 1000 mm
Slenderness ratio λy = Ley/ry
= 28.752
Table 23 Struct curve = b
Table 24 Compressive strength pc = 263.248 N/mm2

Cl 4.7.4 Compressive resistance = Apcx


= 1242.53 kN
Hence, Section's Compressive Capacity is Satisfactory with respect to minor axis Satisfactory

COMPRESSIVE MEMBERS WITH MOMENTS
Cl 4.8.3.2 Combined compression & bending check = Fc/(A x py) + M/Mc
= 0.18
Hence, Section's combined compression & bending is satisfactory Satisfactory

Cl 4.8.3.3 MEMBER BUCKLING RESISTANCE
Max major axis moment governing Mb MLT = Mx
= 22.04 kNm

mx = 1.0
my = 1.0
Cl 4.8.3.3.2 Buckling resistance check Fc/Pcx + mxM/Mc(1 + 0.5Fc/Pcx)

= 0.18

Fc/Pcy + mLTMLT/Mb

= 0.20

Hence, Section's member buckling resistance is satisfactory
Satisfactory

CHECK FOR DEFLECTION
Deflection due to Charateristic Imposed Loads ≤ LE

360

≤ 16.8 mm

From SAP2000 Actual Deflection due to Charateristic Imposed Loads = 2.8 mm


Hence, Deflection is Satisfactory Satisfactory