You are on page 1of 6

Size of beam 0.45 0.

3
sizn of column 0.45 0.45
size of slab 0.125
unit weight of rc 25 KN/m3

Self Weight of beam and column


self weight of (/m) Total leangth of Self weight KN
No of
SN story column beam Beam column column beam
1 1 5.06 3.375 256.54 112.2 568.01 865.82
2 2 5.06 3.375 256.54 112.2 568.01 865.82
3 3 5.06 3.375 256.54 112.2 568.01 865.82
4 4 5.06 3.375 256.54 112.2 568.01 865.82
5 5 5.06 3.375 256.54 56.1 384.24 865.82
6 6 5.06 3.375 64.95 19.8 100.24 219.21

self weight of slab


weight in KN/m2 Total area
no of Total load of slab
Sn story self wt floor finishing water proffing in KN/m2 m2
1 1 3.125 1 0 4.125 465.39
2 2 3.125 1 0 4.125 465.39
3 3 3.125 1 0 4.125 465.39
4 4 3.125 1 0 4.125 465.39
5 5 3.125 1 2 6.125 465.39
6 6 3.125 1 0 4.125 83.36

wall load calculation

no of Different wall load KN/m different load in KN


SN story partition brick Galvanized curtain partition brick
1 1 3.91875 14.421 2.08725 0.495 630.840375 1171.7063
2 2 7.8375 14.421 4.1745 0.495 129.31875 1171.7063
3 3 3.91875 14.421 2.08725 0.495 630.840375 1171.7063
4 4 7.8375 14.421 0 0.495 1132.362 1171.7063
5 5 3.91875 11.5805 0 0.2475 566.181 940.91563
6 6 0 4.37 0 0 283.8315
Live load calculation
no. of live load area of slab total live load
SN story KN/m2 m2 (KN)
1 1 2 465.39 930.78
2 2 0.75 465.39 349.0425
3 3 0.75 465.39 349.0425
4 4 2 465.39 930.78
5 5 0.375 465.39 174.52125
6 6 0.375 83.36 31.26

SN Total load on all floors remarks


1 6548.11 W1
2 5731.980 W2 pa load 173.83632
3 5966.375 W3
4 6782.508 W4
5 6132.132 W5
6 1076.385 W6
32237.492
Tital seismic weight (W) = 32237.492

h = height of building 19.8

SNDescription calculation
M
Natural time period e
1 Ta =0.075h0.75 d 0.7040
i
u
2 Type of soil m

Spectral Acceleration
3 Coefficient(Sa/g) 1.52

4 Zone factor (Z) seismic Zone V = 0.36

5 Importance Factor I 1.5

6 Response reduction factor R 5


Horizontal acceleration
7 coefficient(Ah =ZISa/2Rg 0.08317

Design seismic Base Shear


8 VB=AhW 2681.33

Distribution of Design Force

Storey
forces Q= storey
V Shear
*Wih i/∑Wihi forces
2

Floor level i Wi (KN) hi (m) Wihi2 2 (Vi) KN


6 1076.38 19.8 421985.9509 270.75 270.75
5 6132.13 16.5 1669472.892 1071.17 1341.92
4 6782.508 13.2 1181784.168 758.26 2100.18
3 5966.375 9.9 584764.4119 375.20 2475.38
2 5731.980 6.6 249685.0319 160.20 2635.58
1 6548.112 3.3 71308.94492 45.75 2681.33
total ∑ 4179001.4

Basement slab Other slab


CS X'= 10.057 CS X'= 10.057
Y' 11.219 Y' 11.219
CM X1 10.29 CM X2 11.358
Y1 12.08 Y2 11.818
ex = -0.233 ex= -1.301
ey = -0.861 ey= -0.599

edi=1.5e+0.05b1 edix -0.7115


ediy 0.3415
Total load
on each
floor KN
1433.84
1433.84 427.62 37.77
1433.84
1433.84
1250.07
319.44

unit weight thickness


Partition wall 19 0.125 144.48

total load brick wall 19 0.23 81.25


1919.73 Galvanized wall 25.3 0.05 127.98
1919.73 Curtain wall 25 0.006 14.35
1919.73
1919.73
2850.51 16.5
343.85

19.975 39.95

different load in KN Total Wall


Galvanized curtain load KN
267.126255 7.10325 2076.7761
534.25251 7.10325 1842.3808
267.126255 7.10325 2076.7761
0 7.10325 2311.1715
0 3.551625 1510.6483
0 0 283.8315
live load 4 KN/m2 4

balkuni 16.549 38.993581

Remark

IS 1893(Part 1):2002
Cl.7.6.1

Given

IS 1893(Part 1):2002
Cl.6.4.4 Fg 2

IS 1893(Part 1):2002
cl.6.4.2 Table 2

IS 1893(Part 1):2002
cl.6.4..2 Table 6
IS 1893(Part 1):2002
cl.6.4.2 Table 7
cl.6.4.2

cl.7.5.3

3.125

mb 0.318 water tanl 98

5873.112 147.994

‘dl =
or e,i – 0.05 bi
whichever of these gives the more severe effect
the shear of any ’frame where