USER MANUAL

Underfloor Air Conditioning System


OfficeCool ® - LECU

Precision & Flexibility by DencoHappel


Controllers OfficeCool - LECU

Controller options
Handheld IR Controller When changing a setting on the LECU using the Hand-
held IR controller, ensure that it is pointing towards the IR
receiver in the LECU. A bleep will sound from the IR re-
ceiver to acknowledge the change. Note, there is no visu-
al indication of setting or temperature.
The IR receiver process following data:

Increase temperature setpoint


LED Illuminated Function
Increase/decrease fan speed No LED´s illuminated LECU switched off
Decrease temperature setpoint
Not used Green Fan operating
Not used
LECU On/Off
Amber Fan operating and LECU in
Select LECU on/off time.
heating mode
Press and hold for 5 seconds Green + Amber Fan operating and LECU in
Not used to set time cooling mode
Red Alarm

LCD Display Optional Carel LCD Display or Trend LCD Display

Legend:
1 - Actual set point or room temperature
2 - Actual fan speed
3 - Select fan speed
4 - Increase set point
5 - Decrease set point
6 - LECU On/Off
7 - Not used

Carel LCD Display

4
1
5
2

3 7 6

Trend LCD Display

1
2

5
6
4
3

2 PR-2013-0281-GB • Subject to modifications • R1-04/2016


OfficeCool - LECU Modes

Modes
Cooling mode If the room sensor detects that the local temperature is
too warm, it interrogates the underfloor sensor. If the un-
Return air sensor Raised modular derfloor temperature is below that of the room air, the
floor damper is modulated open to allow cooling to the space.
The damper is modulated sufficiently to offset the heat
Chosen temp

Independent
controller
gain to the space.

Heater
(optional)
Fan Fully modulating Floor void sensor
damper

Heating mode If the room sensor detects that the local temperature is
too cold, it interrogates the underfloor sensor. If the un-
Return air sensor Raised modular derfloor temperature is above that of the room air, the
floor damper is modulated open to allow heating to the space.
Chosen temp

Independent The damper is modulated sufficiently to offset the heat


controller
loss to the space.

Heater
(optional)
Fan Fully modulating
damper Floor void sensor

Recirculation mode When the room sensor detects that the local temperature
matches the set point, the damper will be closed and the
Return air sensor Raised modular unit will be in recirculation mode. An adjustable bleed
floor damper allows sufficient air from the floor void to provide
Independent the fresh air requirements for the space.
Chosen temp

controller

Heater
(optional)
Fan Fully modulating
damper Floor void sensor

Electric heater mode (optional) Under exceptional circumstances, if the room sensor de-
tect that the local temperature is too cold and upon inter-
Return air sensor Raised modular rogation of the underfloor sensor it is determinated that
floor there is insufficient heat available, the controller will mod-
Independent ulate the damper fully closed and initiate the electric heat-
Chosen temp

controller
er battery. The heater will be on until such time that either
the under floor temperature increases sufficiently to meet
the heating requirement, or the room temperature in-
creases to the set point.
Heater
(optional)
Fan Fully modulating
damper Floor void sensor

PR-2013-0281-GB • Subject to modifications • R1-04/2016 3