Standards

What’s in a rating?
As a way of standardizing enclosure performance, organizations like
NEMA, UL, CSA, IEC, and VDE use rating systems to identify an
enclosure’s ability to resist external environmental influences.
Resistance to everything from dripping liquid to hose-down to total
submersion is defined by the ratings systems.While these ratings are
all intended to provide information to help you make a safer, more
informed product choice, there are differences among them.

In North America, NEMA, UL, and CSA are North American enclosure rating systems also
the commonly recognized organizations. include a 4X rating that indicates resistance to
Their ratings are based on similar application corrosion.This rating is based on the
descriptions and expected performance. UL enclosure’s ability to withstand prolonged
and CSA both require enclosure testing exposure to salt water spray.
by qualified evaluators in their labs.They also While a 4X rating is a good indicator that an
send site inspectors to make sure a enclosure can resist corrosion, it does not
manufacturer adheres to prescribed provide information on how a specific
manufacturing methods and material corrosive agent will affect a given enclosure
specifications. NEMA, on the other hand, does material. It is best to conduct a full analysis of
not require independent testing and leaves the specific application and environment to
compliance completely up to determine the best enclosure choice. (See
the manufacturer. Chemical Resistance Charts starting on page
A.20.)

A.02 Data subject to change without notice ☎ 763 422 2211 FAX 763 422 2600 ©2003 Hoffman Enclosures Inc.
A

Technical Information
Standards
In Europe, IEC ratings are based on IEC does not specify degrees of protection
performance criteria similar to NEMA. against risk of explosion or conditions
Nevertheless, there are differences in how such as moisture or corrosive vapors.
enclosure performance is interpreted. For NEMA, on the other hand, does specify
example, UL and CSA test requirements for most environmental conditions. For this
specify that an enclosure fails the watertight reason, and because the tests and evaluations
test if even a single drop of water enters the for other characteristics are not identical, the
enclosure. In the IEC standards for each IEC enclosure classification designations
protection level (IP), a certain amount of cannot be exactly equated with NEMA
water is allowed to enter the enclosure. enclosure Type numbers.

Data subject to change without notice ☎ 763 422 2211 FAX 763 422 2600 ©2003 Hoffman Enclosures Inc. A.03
Standards
CE and IEC Classifications

CE International Standards IP Protection


Classification
The CE Mark is a European Union (EU)
compliance symbol and acronym for IEC Publication 60529 Classification of Degrees
Conformité Européenne.The CE Mark of Protection by Enclosures provides a
indicates that a product complies with all system for specifying enclosures of electrical
European directives and essential harmonized equipment on the basis of the degree of
standards for health, safety, environment, and protection required. IEC 60529 does not
consumer protection that may apply specify degrees of protection against
to that product. In addition, the CE risk of explosions or conditions such
Mark promotes free trade movement as moisture (produced, for example,
from outside and within the EU. by condensation), corrosive vapors,
For industrial control equipment, the CE Mark fungus, or vermin. NEMA Standards
is not intended to be applied to empty Publication 250 does test for environmental
enclosures because such enclosures are inactive conditions such as corrosion, rust, icing, oil, and
components of a final assembly. The coolants. For this reason, and because the tests
responsibility of ensuring compliance with all and evaluations for other characteristics are
applicable EU directives and harmonized not identical, the IEC enclosure classification
standards belongs with the final equipment designations cannot be exactly equated with
manufacturer. NEMA enclosure Type numbers.
Hoffman enclosures are designed in compliance The table on page A.07 provides a cross-
with European standards and are eligible to reference from NEMA enclosure Type numbers
receive a Manufacturer’s Declaration of to IEC enclosure classification designations.
Conformity.The certificate assists the final This cross-reference is a Hoffman approximation
equipment manufacturer in obtaining the CE based on the most current available information
Mark. Contact Applications Engineering at on enclosure test performance and is not
(763) 422-2175 for further information. sanctioned by NEMA, IEC,VDE, or any affiliated
agency.
Hoffman enclosures meet the requirements
of the applicable European standards To use the table on page A.07, first find the
specified below. appropriate NEMA rating along the vertical
axis and then read across the horizontal axis
for the corresponding IP rating. Do not use
Applicable European Directives this table to convert IEC classification
73/23/EEC Low Voltage Directive for Electrical designations to NEMA Type numbers.
Equipment within Certain Voltage Limits
89/336/EEC EMC Directive Relating to
Electromagnetic Compatibility
98/37/EC Machinery Directive
Note: The EMC Directive is only secondarily
applicable since an empty enclosure does not
produce electromagnetic interference.

Applicable International Standards


IEC 60529 (IEC529) Degrees of Protection
Provided by Enclosures
IEC 60204 (IEC204) Electrical Equipment of
Industrial Machines
A.04 Data subject to change without notice ☎ 763 422 2211 FAX 763 422 2600 ©2003 Hoffman Enclosures Inc.
IP Rating Categories
First Numeral Second Numeral

IP

0
Protection
of Persons

No Protection
Protection
of Equipment IP

No Protection
0
Protection
of Equipment

No Protection
A

Technical Information
Protected against Protected against Protected against vertically
contact with large objects over falling drops of water,
areas of the body 50 mm in diameter e.g. condensation
(back of hand)

1 1

Protected against Protected against Protected against direct


contact with fingers solid objects over sprays of water up to 15
12mm in diameter from vertical
2 2

Protected against Protected against Protected against sprays to


tools and wires over solid objects over 60 from vertical
3 2.5 mm in diameter 2.5mm in diameter

Protected against Protected against Protected against water


4 tools and wires over
1 mm in diameter
solid objects over
1mm in diameter
sprayed from all directions
(limited ingress permitted)

Standards
Protected against Protected against Protected against low
tools and wires over dust (limited ingress, pressure jets of water
5 1mm in diameter no harmful deposit) from all directions
(limited ingress
5 permitted)

Protected against Totally protected Protected against


tools and wires over against dust strong jets of water
1mm in diameter
6
6

Protected against the


effects of immersion
7 between 15 cm and 1 m

Protected against long


8 periods of immersion under
pressure
CE IEC SYMBOLS

Example Rating
If 1st IP number is... and the 2nd IP number is... Then the IP rating
2 3 IP 2 3
(protection against solid objects) (protection against liquids) (An enclosure with this designation provies protection against touch with a finger and penetration of
solid objects greater than 12mm and against sprauying water.)

Data subject to change without notice ☎ 763 422 2211 FAX 763 422 2600 ©2003 Hoffman Enclosures Inc. A.05
Standards
NEMA, UL, and CSA Ratings

NEMA, UL, and CSA Ratings


NEMA, UL, and CSA are standard writing organizations commonly inspectors to make sure a manufacturer adheres to prescribed
recognized in North America.Their ratings are based on similar manufacturing methods and material specifications. NEMA, on the other
application descriptions and expected performance. UL and CSA both hand, does not require independent testing and leaves compliance
require enclosure testing by qualified evaluators.They also send site completely up to the manufacturer.

Enclosure Types Non-Hazardous Location


National Electrical Manufacturers Underwriters Laboratories Inc. Canadian Standards Association
Association (NEMA Standard 250) and (UL 50 and UL 508) (Standard C22.2 No. 94)
Enclosure Electrical and Electronic Mfg.
Rating Association of Canada (EEMAC)
Enclosures are intended for indoor use primarily to Indoor use primarily to provide protection against contact General purpose enclosure. Protects against accidental
provide a degree of protection against contact with the with the enclosed equipment and against a limited contact with live parts.
Type 1 enclosed equipment or locations where unusual service amount of falling dirt.
conditions do not exist.

Enclosures are intended for outdoor use primarily to Outdoor use to provide a degree of protection against Indoor or outdoor use; provides a degree of protection
provide a degree of protection against windblown dust, windblown dust and windblown rain; undamaged by the against rain, snow, and windblown dust; undamaged by
Type 3 rain, and sleet; undamaged by the formation of ice on the formation of ice on the enclosure. the external formation of ice on the enclosure.
enclosure.

Enclosures are intended for outdoor use primarily to Outdoor use to provide a degree of protection against Indoor or outdoor use; provides a degree of protection
a provide a degree of protection against falling rain and falling rain; undamaged by the formation of ice on against rain and snow; undamaged by the external
Type 3R sleet; undamaged by the formation of ice on the the enclosure. formation of ice on the enclosure.
enclosure.

Enclosures are intended for indoor or outdoor use Either indoor or outdoor use to provide a degree of Indoor or outdoor use; provides a degree of protection
primarily to provide a degree of protection against protection against falling rain, splashing water, and against rain, snow, windblown dust, splashing and
Type 4 windblown dust and rain, splashing water, and hose hose-directed water; undamaged by the formation of ice hose-directed water; undamaged by the external
directed water; undamaged by the formation of ice on on the enclosure. formation of ice on the enclosure.
the enclosure.
Enclosures are intended for indoor or outdoor use Either indoor or outdoor use to provide a degree of Indoor or outdoor use; provides a degree of protection
primarily to provide a degree of protection against protection against falling rain, splashing water, and against rain, snow, windblown dust, splashing and
Type 4X corrosion, windblown dust and rain, splashing water, and hose-directed water; undamaged by the formation of ice hose-directed water; undamaged by the external
hose-directed water; undamaged by the formation of ice on the enclosure; resists corrosion. formation of ice on the enclosure; resists corrosion.
on the enclosure.
Enclosures are intended for use indoors or outdoors Indoor or outdoor use to provide a degree of protection Indoor or outdoor use; provides a degree of protection
where occasional submersion is encountered. against entry of water during temporary submersion at a against the entry of water during temporary submersion
Type 6 limited depth; undamaged by the formation of ice on at a limited depth; undamaged by the external formation at a limited depth. Undamaged by the external formation
the enclosure. of ice on the enclosure. of ice on the enclosure; resists corrosion.

Enclosures are intended for indoor use primarily to Indoor use to provide a degree of protection against Indoor use; provides a degree of protection against
provide a degree of protection against dust, falling dirt, dust, dirt, fiber flyings, dripping water, and external circulating dust, lint, fibers, and flyings; dripping and light
Type 12 and dripping noncorrosive liquids. condensation of noncorrosive liquids. splashing of non-corrosive liquids; not provided with
knockouts.

Enclosures with knockouts are intended for indoor use Indoor use to provide a degree of protection against Indoor use: provides a degree of protection aganst
primarily to provide a degree of protection against dust, dust, dirt, fiber flyings, dripping water, and external circulating dust, lint, fibers and flyings; dripping and
Type 12K falling dirt, and dripping noncorrosive liquids. condensation of noncorrosive liquids. Knockouts located light splashing of non-corrosive liquids; provided with
in the top or bottom walls, or both. knockouts.

Enclosures are intended for indoor use primarily to Indoor use to provide a degree of protection against lint, Indoor use; provides a degree of protection against
Type 13 provide a degree of protection against dust, spraying of dust seepage, external condensation and spraying of circulating dust, lint, fibers, and flyings; seepage and
water, oil, and noncorrosive coolant. water, oil, and noncorrosive liquids. spraying of non-corrosive liquids, including oils and
coolants.

a NFPA 70 (National Electric Code) defines new Type 3RX as providing the same degree of protection as Type 3R, with the addition of protection against corrosive agents.

This material is reproduced with permission from NEMA. This material is reproduced with permission from This material is reproduced with permission from the
The preceding descriptions, however, are not intended to Underwriters Laboratories Inc. Enclosures for Electrical Canadian Standards Association.
be complete representations of National Electrical Equipment, UL 50, Copyright 1999 and Industrial
Manufacturers Association standards for enclosures nor Control Equipment, UL 508, Copyright 2001 by
those of the Electrical and Electronic Manufacturers Underwriters Laboratories Inc.
Association of Canada.
Underwriters Laboratories Inc. (UL) shall not be
responsible for the use of or reliance upon a UL
Standard by anyone. UL shall not incur any obligation or
liability for damages, including consequential damages,
arising out of or connection with the use, interpretation of,
or reliance upon a UL Standard.

A.06 Data subject to change without notice ☎ 763 422 2211 FAX 763 422 2600 ©2003 Hoffman Enclosures Inc.
Comparison of Specific Non-Hazardous Applications Outdoor Locations

A
Provides a Degree of Protection Against Type of Enclosure
the Following Environmental Conditions 3 3Ra 3RXa 4 4X 6
Incidental contact with the enclosed equipment • • • • • •
Rain, snow, and sleet b • • • • • •
Sleet c
Windblown dust • • • •
Hose-down • • •

Technical Information
Corrosive agents • •
Occasional temporary submersion •
a These enclosures may be ventilated.
b External operating mechanisms are not required to be operable when the enclosure is ice covered.
c External operating mechanisms are operable when the enclosure is ice covered.

Comparison of Specific Non-Hazardous Applications Indoor Locations


Provides a Degree of Protection Against Type of Enclosure
the Following Environmental Conditions 1a 4 4X 6 11 12 12K 13
Incidental contact with the enclosed equipment • • • • • • • •
Falling dirt • • • • • • • •
Falling liquids and light splashing • • • • • • •
Dust, lint, fibers, and flyings b • • • • • •
Hose-down and splashing water • • •
Oil and coolant seepage • • •
Oil or coolant spraying and splashing •
Corrosive agents • •
Occasional temporary submersion •
a These enclosures may be ventilated. However, Type 1 may not provide protection against small particles of falling dirt when ventilation is provided in the enclosure top.
Consult Hoffman for more information.
b These fibers and flyings are non-hazardous materials and are not considered Class II type ignitable fibers or combustible flyings. For Class III type ignitable fibers or combustible flyings

Standards
see the National Electrical Code Section 505.

The preceding tables are reproduced by permission of the National Electrical Manufacturers Association
from NEMA Standards Publication 250 “Enclosures for Electrical Equipment (1000 Volts Maximum),” copyright 1997 by NEMA.

Data subject to change without notice ☎ 763 422 2211 FAX 763 422 2600 ©2003 Hoffman Enclosures Inc. A.07
Industry Standards

Cross-Reference (Approximate) NEMA, UL, CSA, vs. IEC Enclosure Type


(Cannot be used to convert IEC Classifications to NEMA Type Numbers)
Enclosure
Rating IP20 IP22 IP55 IP64 IP65 IP66 IP67
Type 1 •
Type 3 •
Type 3R 3RX •
Type 4 •
Type 4X •
Type 6 •
Type 12, 12K •
Type 13 •
IEC 60529 has no equivalents to NEMA enclosure Types 7, 8, 9, 10, or 11.
• Indicates compliance.

Enclosure Type Rating vs. IP Rating


Electrical enclosures are rated by type (NEMA 250 / UL 50), and/or IP rated (IEC 60529) based on the degree of protection provided.
Type ratings and IP ratings have only the following in common:
1. A degree of protection for persons from hazardous components inside the enclosure
2. A degree of protection for equipment inside the enclosure from ingress of solid foreign objects, including dust
3. A degree of protection for equipment inside the enclosure from ingress of water

NEMA 250 and UL 50 type rating documentation defines additional requirements that a type-rated enclosure must meet.These include:
• Mechanical impact on enclosure walls
• Gasket aging and oil resistance
• Corrosion resistance
• Door and cover latching requirements
• Sheet metal gauge construction requirements (UL 50 only)

Electrical enclosures that carry only an IP rating have not been designed to the additional type-rating requirements.Therefore, a type rating cannot
be assigned to an enclosure that has been only IP-rated.

Electrical enclosures manufactured by Hoffman are tested for both type-rating and IP-rating and carry both type and IP ratings.

A.08 Data subject to change without notice ☎ 763 422 2211 FAX 763 422 2600 ©2003 Hoffman Enclosures Inc.
Glossary Terms Specifying Non-hazardous Environmental Conditions

A
Corrosion-Resistant Oil-Resistant Rain-tight
Constructed to provide a degree of Constructed so that oil will not interfere Constructed or protected so that exposure
protection against exposure to corrosive with successful operation of equipment. to beating rain will not result in water
agents such as salt spray.Type 4X enclosures Type 12 and 13 enclosures meet this entering the enclosure under specified test
meet this requirement. requirement. conditions.Type 3, 4, 4X, and 6 enclosures
meet this .
Dust-tight Oil-tight
Constructed so that circulating or airborne Constructed so that oil will not enter the Water-tight

Technical Information
dust will not enter the enclosure under enclosure under specified test conditions. Constructed so that moisture will not enter
specified test conditions.Type 3, 4, 4X, 12, Type 13 enclosures meet this requirement. the enclosure when it is subjected to a
12K, and 13 enclosures meet this stream of water under specified test
Outdoor conditions.Type 4, 4X, and 6 enclosures
requirement.
Constructed or protected so that exposure meet this requirement.
Drip-tight to the weather will not interfere with
Constructed so that falling moisture or dirt successful operation of equipment.Type 3, Weatherproof
does not enter the enclosure under specified 3R, 4, 4X, and 6 enclosures meet this Constructed or protected so that exposure
test conditions.Type 3, 4, 4X, 12, 12K, and 13 requirement. to the weather will not interfere with
enclosures meet this requirement. successful operation of the equipment.
Rainproof Rainproof, rain-tight, or water-tight
Indoor Constructed, protected, or treated to equipment can fulfill the requirements for
Not to be exposed to weather.Type 1, 3, 3R, prevent beating rain from interfering with weatherproof where varying weather
4, 4X, 6, 12, 12K, and 13 enclosures meet this the successful operation of the apparatus or conditions other than wetness, such as snow,
requirement. result in wetting of live parts and wiring ice, dust, or temperature extremes, are not a
within the enclosure under specified test factor.
conditions.Type 3R enclosures meet this
requirement. Wet Locations
See Rainproof.

Standards

Data subject to change without notice ☎ 763 422 2211 FAX 763 422 2600 ©2003 Hoffman Enclosures Inc. A.09