Relay Setting

Relay:
Location: NG/CENTRAL/9089/13.8kV/BUS - 1A/
NG/CEN Siemens/87BB1/7SJ6xx V4.7 - V4.9//
Device:
TRAL/90
Setting:
89/13.8k
V/BUS -
Date Setting: 4/18/2018 Setting Type: Proper In Service Since: Valid Until:
1A/
Active: Setting Status: Ready for operation In Service by:
Comment: #Issue No:18273 / RG

Parameter Set
Name: Parameter Set
Parameters
Device Configuration/Device Configuration
Name Description Value
0103 Setting Group Change Option Disabled
0104 Oscillographic Fault Records Enabled
0112 50/51 Definite Time only
0113 50N/51N Disabled
0117 Cold Load Pickup Disabled
0122 2nd Harmonic Inrush Restraint Disabled
0127 50 1Ph Disabled
0130 (sens.) Ground fault dir. characteristic cos phi / sin phi measurement (standard)
0131 (sensitive) Ground fault Disabled
0140 46 Negative Sequence Protection Disabled
0142 49 Thermal Overload Protection Disabled
0150 27, 59 Under/Overvoltage Protection Disabled
0154 81 Over/Underfrequency Protection Disabled
0155 Undervolt. / Q dir. con. Protection Disabled
0170 50BF Breaker Failure Protection Disabled
0172 52 Breaker Wear Monitoring Disabled
0182 74TC Trip Circuit Supervision Disabled
0190 External Temperature Input Disabled
0191 Ext. Temperature Input Connection Type 6 RTD simplex operation
Device, General Settings/General
Name Description Value
0610 Fault Display on LED / LCD Display Targets on every Pickup
0611 Spontaneous display of flt.annunciations NO
0617A T103-transfer limeted to 16 meas. values NO
0625A Minimum hold time of lachted LEDs 0 min
0700 GOOSE-Stop NO
Power System Data 1/Power System
Name Description Value
0201 CT Starpoint Towards busbar
0209 Phase Sequence L1 L2 L3
0213 VT Connection, three-phase U L1E, U L2E, U L3E
0214 Rated Frequency 60 Hz
0235A Storage of th. Replicas w/o Power Supply No
0240 VT Connection, single-phase NO
0250A 50, 51 Time Overcurrent with 2ph. prot. OFF
0251A CT Connection Ia, Ib, Ic, (IGnd)
0276 Unit of temperature measurement Degree Celsius
0280 Holmgreen-conn. (for fast sum-i-monit.) No
Power System Data 1/CT's
Name Description Value
0204 CT Rated Primary Current 3600 A
0205 CT Rated Secondary Current 1A
0217 Ignd-CT rated primary current 3600 A
0218 Ignd-CT rated secondary current 1A
Power System Data 1/VT's
Name Description Value

IPS v1.00 Printed: 4/18/2018 2:44:23 PM Page 1 of 2


Relay Setting
Relay:
Location: NG/CENTRAL/9089/13.8kV/BUS - 1A/
NG/CEN Siemens/87BB1/7SJ6xx V4.7 - V4.9//
Device:
TRAL/90
Power System Data 1/VT's
89/13.8k
V/BUS -
Name Description Value
1A/
0202 Rated Primary Voltage 13.8 kV
0203 Rated Secondary Voltage (L-L) 120 V
0206A Matching ratio Phase-VT To Open-Delta-VT 1.73
Power System Data 1/Breaker
Name Description Value
0210A Minimum TRIP Command Duration 0.15 s
0211A Maximum Close Command Duration 1s
0212 Closed Breaker Min. Current Threshold 0.04 A
Oscillographic Fault Records/Osc. Fault Rec.
Name Description Value
0401 Waveform Capture Save with Pickup
0402 Scope of Waveform Data Fault event
0403 Max. length of a Waveform Capture Record 2s
0404 Captured Waveform Prior to Trigger 0.25 s
0405 Captured Waveform after Event 0.1 s
0406 Capture Time via Binary Input 0.5 s
Power System Data 2/General
Name Description Value
1101 Measurem:FullScaleVoltage(Equipm.rating) 13.8 kV
1102 Measurem:FullScaleCurrent(Equipm.rating) 3600 A
1108 P,Q operational measured values sign not reversed
50/51 Phase/Ground Overcurrent/General
Name Description Value
1201 50, 51 Phase Time Overcurrent ON
1213A Manual Close Mode I>> instantaneously
1215A 50 Drop-Out Time Delay 0s
50/51 Phase/Ground Overcurrent/50
Name Description Value
1202 50-2 Pickup INF
1203 50-2 Time Delay 0s
1204 50-1 Pickup 0.1 A
Comment: The voltage setting - 110 volt
1205 50-1 Time Delay 0s
Comment: Series resistance - 1100 ohms
1214A 50-2 active Always
Comment: Shunt resistance - 384 ohms-To be adjusted at site.
1216A 50-3 active Always
Comment: Primary operating current - 1500 A
1217 50-3 Pickup INF
1218 50-3 Time Delay 0s
1219A 50-3 measurement of Fundamental component
1220A 50-2 measurement of Fundamental component
1221A 50-1 measurement of Fundamental component
Energy/Measurement
Name Description Value
8315 Meter resolution Standard