You are on page 1of 6

Medium Voltage Indoor metal Clad

Switchgear Switchgear Cubicle for 11KV


ABB Make SF6 - Type HPA

TRICOLITE
Pledged to Excellence Business Associates of
AIR INSULATED INDOOR SWITCHGEAR

The Cubicle is designed and type tested to meet requirements of IEC


298 & 694 / IS : 3427.
Fully compartmentalised construction with IP54 degree of protection.
2mm/3mm CRCA fully bolted construction.
Extendible at both ends.
Earthing Truck Extra (optional).
AIR INSULATED INDOOR SWITCHGEAR

BREAKER COMPARTMENT

Cassette mounted breaker with ‘isolated’ position on


cubicle front door.
Racking in/out of breaker from 'test' to 'service' position
and vice-versa with cubicle door closed only.
Mechanical interlock to prevent racking in/out of breaker,
when breaker is in closed position.
Live parts covered by automatic shutters when breaker is
racked out.
Multiple guides for safe, sure and enduring self alignment
of fixed and moving power contacts.

METERING COMPARTMENT

Metering compartment with numerical / static / electro-


magnetic relays, indicating meters, lamps and control
switches.
Protection and measuring apparatus customised as per
requirement.

CABLE & CT COMPARTMENT

Spacious compartment to accommodate 1 set of


CTs and 2 runs of cables.
Option of rear extension to accommodate extra CTs
or cables.
Adequate height for cable termination.
AIR INSULATED INDOOR SWITCHGEAR

PT COMPARTMENT

Withdrawable line PT provided in the breaker panel.


Removable fuses mounted on the PT.
Safety shutters between PT & cable compartment.

BUSBAR COMPARTMENT

Spacious busbar compartment for adequate air


clearances.
R,Y,B colour coded PVC sleeved busbars.
Busbar compartment separated from cable
compartment.

TECHNICAL DETAILS

Description Unit Rating


Rated Voltage kV 12
Rated Frequency Hz 50
Rated Busbar Current A 630-2500
Short Time Withstand Current (3sec) kA 40
kAp 100
Insulation Levels kVrms/kVp 28/75
Width X Depth X Height mm 800X1800X2375
Weight with Circuit Breaker (approx.) Kg 1000

Degree of Protection
Enclosure - IP54
CIRCUIT BREAKER Type HPA 12

SALIENT FEATURES

Sulphur Hexafluoride (SF6) used as


insulation and arc interruption medium.
Operationally safe and reliable in a wide
range of ambient temperatures (-500C to
400C).
Capable of Interrupting small magnetism
and capacitive currents.
O-C-O operation without recharging.
Closing spring charged by motor in less
than 15secs.
Electrical anti-pumping.
Provision for manual recharging.
Synchronization and fast auto reclosure
duty.

TECHNICAL DETAILS

Description Unit Rating


Rated Voltage kV 12

Insulation Levels kVrms/kVp 50

Normal Current A 1250, 1600, 2000, 2500

Breaking Capacity kA 40

Making Capacity kAp 100

Short Time Withstand Current kA 40(1sec):1250A


40(3sec):1600-2500A
Gas Pressure Bar 3-3.5

Opening Time Ms 36-45

Arcing Time Ms 15

Total Break Time Ms 60

Making Time Ms 75

Operating Sequence - 0-3min-CO-3min-CO/


0-0.3sec-CO-3min-CO
Weight (approx.) Kg 190-225
TRICOLITE
Pledged to Excellence
Plot No 5, Sector VI, IMT- Manesar,
Gurgaon – 122050 (Haryana)
Phone: +91124- 4367155- 159
Fax:+91124- 4367154
Email: sales@tricolite.com
Website: www.tricolite.com

•Regd. Office: 70, Najafgarh Road, New Delhi. Phone: +9111- 65477035, Fax:+9111- 25436393.

Works:
Plot No 5, Sector VI, IMT- Manesar, Gurgaon– 122050 (Haryana). Phone: +91124- 4367155- 159, Fax:+91124- 4367154.
Plot No. 142, Sector- V, IMT- Manesar, Gurgaon- 122050 (Haryana). Phone: +91124- 4367160.
18/1A, Site- IV, Industrial Area, Sahibabad, Ghaziabad- 201010. Phone: +91120- 2895101- 104, Fax:+91120- 2896111.