ENGLISH Quick Start Guide - ATV212

S1A5382501
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Read and understand this quick start guide before performing any procedure with this drive.
• The user is responsible for compliance with all international and national electrical code requirements with respect to grounding of all
equipment.
• Many parts of this drive, including the printed circuit boards, operate at the line voltage. DO NOT TOUCH. Use only electrically insulated tools.
• DO NOT touch unshielded components or terminal strip screw connections with voltage present.
• DO NOT short across terminals PA/+ and PC/- or across the DC bus capacitors.
• Before servicing the drive:
- Disconnect all power, including external control power that may be present.
- Place a "DO NOT TURN ON" label on all power disconnects.
- Lock all power disconnects in the open position.
- WAIT 15 MINUTES to allow the DC bus capacitors to discharge.
- Measure the voltage of the DC bus between the PA/+ and PC/- terminals to ensure that the voltage is less than 42 Vdc.
- If the DC bus capacitors do not discharge completely, contact your local Schneider Electric representative. Do not repair or operate
the drive.
• Install and close all covers before applying power or starting and stopping the drive.
Failure to follow these instructions will result in death or serious injury.

Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider
Electric for any consequences arising out of the use of this product.

Information below is designed to use single drive connected to single motor with a motor cable length less than 50 meters (164 ft).
In any other case, consult the ATV212 installation manual and programming manual on www.schneider-electric.com.
Check your cables before connecting the drive with motor (length, power, shielded or unshielded). Motor cable length is _______(< 50 meters, 164 ft).

1 Check the delivery of the drive


• Remove ATV212 from the packaging and check that it has not been damaged.

WARNING
DAMAGED DRIVE EQUIPMENT
Do not operate or install any drive or drive accessory that appears damaged.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

• Check that the drive reference printed on the label is the same as that on the delivery note corresponding to the
purchase order. ATV212HU15N4
1.5KW - 2HP - 380 / 480V

Write the drive Model Reference: _____________ ___________and Serial Number: ____________________________

2 Check the line voltage compatibility


8B0915316127
• Check that the line voltage is compatible with the supply range of the drive.
Line voltage _______ Volts Drive voltage range _______ Volts
Drive range: ATV212 pppp M3X = 200 ... 240 V three-phase / ATV212 pppp N4p = 380 ... 480 V three-phase.

3 Mount the drive vertically


For a surrounding air temperature up to 40 °C (104 °F).
ATV212H ATV212W
(a)

(b)

(a) (a) (a) (a)

(c)
(a)

(b)

(a) 50 mm (2 in.) (b) 100 mm (4 in.) (c) 10 mm (0.4 in.)

See installation manual on www.schneider-electric.com for other thermal conditions.

www.schneider-electric.com 1/4 S1A53825 - 10/2010


4 Connect the drive: Power Connect the drive:
5
• Wire the drive to the ground.
• Check circuit breaker rating or fuse rating. Control choice
• Check that the motor voltage is compatible with the drive voltage.
Motor voltage ______Volts. [REMOTE configuration]
• Wire the drive to the motor. 5.1 (Control by external reference) 0,6 N.m
5.3 lb.in
• Wire the drive to the line supply.
• Wire the speed reference:

PP: Internal supply for ATV 2 12


analogue inputs
PP VIA CC
VIA: Analog/ logic input
CC: Common
200...240 V
2.2 to 10 kΩ
ATV212 M3X RUN
PRG
MON
%

Hz

Loc
Rem
MODE

ENT
• Wire the command:
RUN STOP

or Control command 2-wire:


380...400 V F: Run forward
ATV212 N4 ATV 2 12
R: Run reverse
Do: 6 + 7 + 8 + 9.1
P24: Internal supply F R P24
for logic inputs

Control command 3-wire:


F: Run forward ATV 212
R: Stop
RES: Run reverse F R RES P24 6 + 7 + 8 + 9.1
Do:
P24: internal supply
for logic inputs

Note: for ATV212H075ppp, ATV212HU15ppp, ATV212HU22ppp, to connect power,


open the door, remove the terminal board, connect R/L1, S/L2 ,T/L3 and fix again [LOCAL configuration]
the terminal board. 5.2 (control by internal reference). Do: 6 + 7 + 8 + 9.2

Loc
Rem

6 Apply power to the drive


• Check that used Logic Inputs are not active (see F, R, RES, P24, open circuit).
• Apply power to the drive.
Run
• At each power on , drive displays HELLO message, then run mode : mode
.0
0.
Hz

7 Set motor parameters


• See on the motor Nameplate to set the following parameters.
Customer
Menu Code Description Factory setting
setting
Pt [Mot cont. mode sel.]: Motor control mode
0 [Constant V/Hz]: Constant V/Hz
1 [Variable Torque]: Variable torque
1
2 [Cst V/Hz+Boost]: Constant V/Hz with automatic torque boost
AUF 3 [SVC]: Sensorless vector control
[QUICK MENU] 4 [Economy]: Energy saving
[Upper limit freq]:
uL 50.0
Nominal motor frequency on motor nameplate (Hz)
[Motor Rated Voltage]:
uLu drive rating
Nominal motor voltage on motor nameplate (V)
[Motor rated current]:
F415 drive rating
Nominal motor current on motor nameplate (A)
F--- [Motor rated speed]:
F417 drive rating
[EXTENDED MENU] Nominal motor speed on motor nameplate (rpm)
[Motor Current Limit]:
F601 110
Limit current during motoring or braking (%)

www.schneider-electric.com 2/4 S1A53825 - 10/2010


7 Set motor parameters (continued)
Customer
Menu Code Description Factory setting
setting
Set F400 [Auto-tuning drive] parameter to 2. The drive
F--- displays Atn1, the message disappears after a few seconds
F400 0
[EXTENDED MENU]
Auto-Tunning for uLu, uL, F415 and F417

DANGER WARNING
HAZARD OF ELECTRIC SHOCK OR ARC FLASH DAMAGED DRIVE EQUIPMENT
• During auto-tuning, the motor operates at rated • It is essential that the following parameters uLu, uL, F415 and
current. F417 are correctly configured before starting autotuning.
• Do not service the motor during auto-tuning. • When one or more of these parameters have been changed after auto-
tuning has been performed, F400 will return 0 and the procedure
Failure to follow these instructions will result in death will have to be repeated.
or serious injury.
Failure to follow these instructions can result in death, serious injury, or equip-
ment damage.

8 Set basic parameters


Menu Code Description Factory setting Customer
setting
AU1 [Auto ramp] Automatic ramp adaptation:
0 [Disabled] 1
1 [Enable] - (ACC) and (dEC)
2 [ACC only]
ACC [Acceleration time 1]:
Acceleration ramp and the time(s) ATV21 2 y 15KW = 10 s
AUF [Deceleration time 1]: ATV212 u 18KW = 30 s
dEC
[QUICK MENU] Deceleration ramp and the time (s)
[Low limit frequency]:
LL 0. 0
Motor frequency at minimum reference (Hz)
[High speed]:
UL 50.0
Motor frequency at maximum reference (Hz)
[Motor thermal prot.]:
tHr 100
Motor Rated Current Overload Setting (%)
[Switch. freq. level]
F--- Switching Frequency Level (kHz)
[EXTENDED F300 8 to12
MENU] Increasing the switching frequency may reduce audible motor noise.
See the derating curves in the ATV21 2Installation Manual.

9 Set control choice


9.1 [REMOTE configuration] 9.2 [LOCAL configuration]

Parameters factory settings:

2-wire control
Menu Code Setting RUN
%
_ CMOd [Command mode sel] 0 [Logic inputs] PRG
Hz
MON
F--- F111 [LI F selection] 2 [forward]
[EXTENDED
F112 [LI R selection] 3 [reverse] Loc
MENU] Rem
MODE

3-wire control
ENT
Menu Code Setting
_ CMOd [Command mode sel] 0 [Logic inputs]
F--- F111 [LI F selection] 2 [forward] STOP
[EXTENDED F112 [LI R selection] 49 [3-wire] RUN
RESET
MENU] F113 [LI RES selection] 3 [reverse]

10 Start the motor


www.schneider-electric.com 3/4 S1A53825 - 10/2010
Menus structure
Run Programming Monitoring
mode mode mode
RUN MODE MODE
0.
.0 PRG AUF Fr-F
Submenu
ENT MON MODE
Hz (1)

[Quick menu]
ATV212 Submenu
drive
GrU
[ALL PARAM CHANGE]
t0.10 [Drive run time 100h]
MODE AU1 [Auto ramp]
Power Up
Submenu
F--- Nbiii [Mdb com stat]
[EXTENDED MENU] ACC [Acceleration time 1]

Submenu
IO Niiii [Drive service alarm]
[I/O MENU] dEC [Deceleration time 1]

COM Submenu nErr [Past fault]


[COMMUNICATION MENU] LL [Low limit frequency]

MODE
Sr7 [Preset speed 7...1] n 50 [Comm. counter 1]
UL [Upper limit freq]

OLM [Motor overload prot] N 50 [Comm. counter 2]


tHr [Motor thermal prot.]

tHr [Motor thermal prot.] 1500 [Motor speed rpm]


FM [AO scaling]

ub [Mot Voltage Boost] A16.5 [Drive out. rat. cur. A]


Pt [Mot cont. mode sel.]

Pt [Mot cont. mode sel.] H 75 [Total motor power]


uL [Motor rated freq.]

uLu [Motor rated voltage] h 85 [Total input power]


uLu [Motor rated voltage]

uL [Motor rated freq.] b 70 [PID computed ref.]


Hz Hz
(1) Fr-F Fr-F = forward direction
[Direction]
Fr-r = reverse direction
LL [Low limit frequency] d 50 [PID feedback]
Hz

MODE
UL [Upper limit freq] uE01 [Memory ver.]

MODE
FH [Max frequency] uc01 [CPU MMI ver.]

dEC [Deceleration time 1] u101 [CPU CTRL ver.]

ACC [Acceleration time 1] 0 il [Relay map]

Fr [Local mot. direction] iii [LOGIC INPUT MAP]

tYP [Parameter reset] o60.0 [Motor frequency]


Hz

FM [AO scaling] H 75 [Output power KW]

FMSL [AO funct. selection] h 80 [Input power KW]

%
FMOd [Frequency mode sel] L 70 [Drive load %]

%
CMOd [Command mode sel] c 90 [Torque current]

%
AU4 [Auto set function] q 60 [Motor torque %]

%
AU1 [Auto ramp] P100 [Motor voltage]

Submenu %
[Line voltage]
AUH Y100
[5 LAST PARAM CHANGE]

%
C 80 [Motor current]

Refer to the programming manual for comprehensive menu description


F60.0 [Speed reference]
Hz

www.schneider-electric.com 4/4 S1A53825 - 10/2010