Motor Details

Motor Rating 10 Kw 10.00 7.46


System Voltage V (L-L) 240 Volt 1 Ph
Supplay Frequency 50 Hz
Pole 4 No
Motor Spped 1000 Rpm
Locked Rotor Code B
Motor Demand Factor 1
Motor Service Factor 2
Motor Operating Temperature 30 C
Motor Starting Method Y-D
Motor Starting P.F 0.6
Motor Running P.F 0.8
Motor Full Load Efficiency 100 % 1
Calculation
Motor Consumed Load 10.00 Kw
Motor Starting Current 156.25 Amp
Motor Full Load Current 52.08 Amp
Syncronus Spped(Ns) 1500 Rpm
Slip 33%
Locked Rotor Current (LRA) 104.13 Amp
Motor Protection
Maximum Size of OverLoad Perotection 65.10 Amp
Standared(On Time Delay) Fuse (Max) 156.25 Amp
On Time Delay Fuse (Max) 91.15 Amp
Instantaneous Trip C.B(Max) 416.67 Amp
Inverstime C.B(Max) 130.21 Amp
Instant.Short Circuit Tripping Setting of C.B
Voltage(L-L) 440 Volt
Voltage(L-N) 230 Volt
Instantaneous Short-Circuit Triping Set 100 Amp
Accuracy 20 %
Cable Size 3cx10 6 0
Cable Material Cu
Actual Length of Cable 5 Meter

Max.Length of Cable for your Tripping setting 333 Meter


Tripping Setting of C.B OK

Selection of Circuit Fuse

Circuit Wire /Cable Size 55 mm2

Circuit Fuse Size(Max) 325 Amp

Jignesh.Parmar
jiguparmar@yhaoo.com
www.electricalnotes.wordpress.com
Dol Alu AWG
Y-D Cu mm2
Hp Auto Tra.
Kw Soft
1 Ph Freq.Conv
3 Ph 3.35
A 0 3.15
B 3.15 3.55
C 3.55 4
D 4 4.5
E 4.5 5 55
F 5 5.6
G 5.6 6.3
H 6.3 7.1
J 7.1 8
K 8 9
L 9 10
M 10 11.2
N 11.2 12.5
P 12.5 14
R 14 16
S 16 18
T 18 20
U 20 24
V 24
AWG mm2 Maximum Fuse Size(Amp)
OO 70 400
OO 55 325
1 50 250
2 35 200
4 25 125
6 16 80
8 10 50
10 6 30
12 4 20
14 2.5 15
16 1.5 7.5

You might also like